Honeywell DT-6360STC Installation Instructions Manual

Model DT-6360STC
Ceiling Mount Motion Sensor
INSTALLATION INSTRUCTIONS
MOUNTING LOCATION
The DUAL TEC® 6360STC motion sensor provides maximum coverage when mounted on ceilings from 8' (2.4 m) to 16' (4.8 m) high. Refer to the passive infrared (PIR) mirror assembly to use at different ceiling heights.
Choose a mounting location in the center of the protected area. The protected area should be free of objects that might prevent the PIR sensor from detecting an intruder: large pieces of furniture, room dividers, etc.
Remember, infrared energy cannot penetrate solid objects. If the PIR detector is blocked, the DT-6360STC will not trigger an alarm.
Note: If you plan to use the DT-6360STC's tamper switches, read the
MOUNTING PROCEDURE
To remove the front cover, orient the DT-6360STC so that one of the sides with the small rectangular slot in the center is visible. Using a small flathead screwdriver, gently push down on the slot while separating the housing parts. Set the front cover aside.
Remove the printed circuit board (PCB) by depressing one of the retaining brackets at its sides. Use the microwave antenna to carefully pull the PCB out.
Surface Mounting
If mounting the DT-6360STC directly on a ceiling, use the back cover as a template to mark holes for the mounting screws and wiring. Drill the holes. Then pull several inches of wiring from the ceiling through the center hole in the back housing.
Attach the back housing to the ceiling with the mounting screws.
Recommended mounting screws: #6 (M3.5) pan head.
Note: If surface wiring, use the knockout hole on the side of the
housing.
System Set-up section to determine which
Tamper Installation section on page 1.
To flush mount the unit, cut a 5.5" x 5.5" (14 cm x 14 cm) hole in the ceiling. Insert the recess bucket into the hole, using it as a template to mark drill holes for the four mounting screws. Remove the bucket and drill the screw holes.
If using the retainer ring, place it through, then directly over, the hole in the ceiling tile. Make sure to orient the retainer ring and recess bucket as shown in Figure 1.
Next, attach the back housing of the DT-6360STC to the inside of the recess bucket, using the same screw holes and screws used for surface mounting [#6 (M3.5) pan head]. Pull several inches of wiring from the ceiling through the center hole in the recess bucket and DT-6360STC back housing.
Insert the recess bucket into the hole in the ceiling, securing it to the ceiling (and retainer bracket) with four mounting screws.
RETAINER RING
CEILING
Figure 1 DT-6360STC Flush Mounting Kit
RECESS BUCKET
DT-6360STC
Tamper Installation
The DT-6360STC is equipped with two tamper switches: a cover tamper and ceiling tamper. When the tamper switches are used, removing the cover from the sensor will activate the cover tamper; removing the sensor from the ceiling will activate the ceiling tamper. Both tamper switches are normally closed (NC) and internally wired in series.
The cover tamper switch can be used without the ceiling tamper and requires no modifications to the DT-6360STC housing.
To use the ceiling tamper, remove the square knockout in the rear housing (directly behind the ceiling tamper switch), then install a screw* in the ceiling. Leave enough of the screw protruding to depress the tamper switch. Refer to Figure 2.
If the installation is recessed, remove the knockout from the rear housing, drill a screw hole (behind the knockout) in the recess bucket, then install the screw* in the recess bucket. Leave enough of the screw protruding to depress the tamper switch. Refer to Figure 2.
Figure 2
*Note: #6 (M3.5) pan head is recommended.
KNOCKOUT
LATCH
REAR HOUSING
Cover and Ceiling Tamper Switches
KEYHOLE
IMPORTANT: To ensure insects do not get inside the DT­6360STC housing, make sure to seal all holes. (Recommended sealant: silicone RTV.)
Flush Mounting
The DT-6360STC is shipped with a special kit for flush mount­ing. The kit contains a recess "bucket" and retainer ring. The retainer ring is only needed when flush mounting the unit in ceiling tile. Removing the tile from the ceiling (if possible) will make the installation process easier.
- 1 -
SURFACE MOUNT
Screw to depress tamper
CEILING
DT-6360STC
CEILING
Screw to depress tamper
PIN FOR PCB
FLUSH MOUNT
DT-6360STC inside recess bucket
Removing Front Cover After Installation (flush mount)
After installing and walk-testing the DT-6360STC flush mount, you may need to make adjustments. Use a screwdriver to reopen the front cover.
Insert the screwdriver as far as it will go in the grooves inside the recess bucket. Gently press outward to release the latches holding the front cover in place.
SYSTEM TESTING
DT-6360STC sensors are equipped with two diagnostic LEDs: green for PIR and yellow for microwave. The red LED is used to indicate an alarm condition.
Apply power to the sensor and wait until self-test is completed (90 seconds). Begin walk-testing after all three LEDs have gone out.
WIRING
Observing the proper polarity, wire the sensor as shown below (use 22 to 14 AWG).
OPEN COLLECTOR TROUBLE OUTPUT
Vce .3V max @ 50 mA. 1K series protection resistor.
Figure 3 Wiring Diagram
1
The Trouble Output is activated when a self-test failure or an INFORMER® condition occurs. Refer to THE INFORMER CIRCUIT and the TROUBLESHOOTING sections.
2
EOL = End-of-Line (spare) terminal.
Note: Do not leave excess wire inside the unit. Push as much wire as possible into the ceiling when returning the PCB to its housing.
Note: For proper wiring methods, refer to National Electrical Code NFPA
70.
Note: Reverse polarity will not damage the unit.
ALARM RELAY
1
EOL
TAMPER SWITCH
Normally Closed (NC) with cover on 25 mA, 30 VDC.
TBL
125 mA, 25 VDC. 22 ohm
series protection resistor.
122
NC COM
CMD
REMOTE LED ENABLE or COMMAND INPUT
(Self-Test Initiate) Active Low 0 to 1.5 V Inactive High 6 to V+ Input Impedance 110 Kohms (minimum).
EOL
NO
V-
V+
POWER
At 12 VDC, typically 40 mA; maximum 50 mA
SYSTEM SET-UP
Changing the PIR Mirror Assembly
The DT-6360STC package contains two PIR mirror assemblies: one for ceilings from 8' (2.4m) to 11' (3.3m) high, another for ceilings from 12' (3.65m) to 16' (4.8m) high. The unit is shipped with the 8'- 11' (2.4m-3.3m) mirror installed.
To change the mirror assembly, remove the front cover and turn it over. Next, remove the protective cap and existing mirror assembly by depressing the four retaining latches at their sides. Store (or discard) the existing mirror and install the new one. Snap the protective cap back into place, then replace the front cover.
PIR Masking
To eliminate specific PIR zones from the pattern, mask corre­sponding segments on the PIR mirror with the adhesive-backed masking tape provided. Remember, segments to be masked will be on the side of the mirror OPPOSITE the unwanted zones. See Figure 4.
Once the tape has been applied, walk-test the sensor to ensure that the correct mirror segments have been masked.
PIR MASKING MATERIAL PLACED HERE
MICROWAVE RANGE THUMBWHEEL R32 (set to
INSTALLER INITIATED SELF-TEST MOMENTARY SHORT
INSTALL JUMPER W3 TO DISABLE TROUBLE OUTPUT WHEN AN INFORMER CONDITION OCCURS (jumper is
factory installed)
REMOTE LED ENABLE or COMMAND INPUT
Jumper W4 installed:
CMD terminal func­tions as Remote LED En­able.
Jumper W4 removed:
CMD terminal func­tions as Command In­put.
(Set to Command Input at factory)
Red - During normal operation LED illuminates when an ALARM condition is triggered.*
Yellow - During normal operation LED flashes ON when a MICROWAVE event is detected.*
Green - During normal operation LED flashes ON when a PIR event is detected.* (PIR Zone Finder)
* If Self-Test fails or an INFORMER condition occurs, LEDs indicates nature of problem (see Tables 1,2 & 3)
maximum at factory)
MAX
R32
W3
W4
TAMPER SWITCH
ALARM & DIAGNOSTIC LEDs:
TOP
W1
BOTTOM
Figure 5 DT-6360STC PCB
PLACE JUMPER W1 TO DETERMINE PIR SENSITIVITY
(jumper set to normal at factory; see page 3)
REMOVE JUMPER W2 TO DISABLE DIAGNOSTIC LEDS AND ALARM LED
W2
(jumper is factory installed)
RED YELLOW
GREEN
Microwave Range Adjustment
DT-6360STC sensors are equipped with a microwave range thumbwheel (R32) for range adjustment. (Refer to Figure 5.) Set the range at MINIMUM by turning the thumbwheel all the way to the left.
As you perform the walk-test, gradually turn the thumbwheel to the right to increase the microwave sensitivity until the desired ranged is obtained.
Walk-test
Walk across the protected area at the ranges to be covered. Two to four normal steps make the diagnostic LEDs light, and the red LED should indicate an alarm condition. When there is no motion in the protected area, all three LEDs should be off.
COMMAND INPUT / REMOTE LED ENABLE
Position W4 determines what function the Command Input (CMD) terminal will provide.
Installing a jumper at position W4 makes the CMD terminal function as a Remote LED Enable terminal. If the signal to the Remote LED Enable terminal is low, the LEDs are enabled. If the signal to the terminal is high, the LEDs are disabled. However, if a self-test error occurs, the LEDs will light regardless of the state of the signal.
WILL BLOCK ZONES HITTING HERE
Figure 4 Masking the PIR Mirrors
The CMD terminal functions as a Command Input terminal when the jumper is removed from position W4. A momentary low signal to the terminal (at least .5 seconds) will initiate the self­test.
LED DISABLE (Local)
To disable the diagnostic LEDs and alarm LED, remove the jumper from position W2 on the PCB. (See Figure 5.)
- 2 -
Loading...
+ 4 hidden pages