Honeywell warrants goods of its manufacture as being free of defective materials and faulty
workmanship. Contact your local sales office for warranty information. If warranted goods are
returned to Honeywell during the period of coverage, Honeywell will repair or replace without
charge those items it finds defective. The foregoing is Buyer’s sole remedy and is in lieu of all
other warranties, expressed or implied, including those of merchantability and fitness for a
particular purpose. Specifications may change without notice. The information we supply is
believed to be accurate and reliable as of this printing. However, we assume no responsibility for
its use.
While we provide application assistance personally, through our literature and the Honeywell web
site, it is up to the customer to determine the suitability of the product in the application.
Revision E – April 5, 2000
Sensing and Control
Honeywell
11 West Spring Street
Freeport, Illinois 61032
DR4300 and Accutune II are U.S. trademarks of Honeywell
Information Mapping is a trademark of Informati on Mapping Inc.
Modbus is a trademark of Modicon, Inc.
Other brands or product names are t rademarks of their respective owners.
The following table lists those symbols used in this document to denote certain conditions.
SymbolDefinition
This CAUTION symbol on the equipment refers the user to the Product Manual for
additional information. This symbol appears next to required information in the
manual.
WARNING
PERSONAL INJURY: Risk of electrical shock. This symbol warns the user of a
potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms,
42.4 Vpeak, or 60 Vdc may be accessible. Failure to comply with these
instructions could result in death or serious injury.
Protective Earth (PE) terminal. Provided for connection of the protective earth (green
or green/yellow) supply system conductor.
Functional earth terminal. Used for non-safety purposes such as noise immunity
improvement. NOTE: This connection shall be bonded to protective earth at the
source of supply in accordance with national local electrical code requirements.
Earth Ground. Functional earth connection. NOTE: This connection shall be bonded
to Protective earth at the source of supply in accordance with national and local
electrical code requirements.
Chassis Ground. Identifies a connection to the chassis or frame of the equipment
shall be bonded to Protective Earth at the source of supply in accordance with
national and local electrical code requirements.
Table 2-8 Procedure for Power Wiring Models..........................................................................................................28
Table 2-9 Analog Input Wiring..................................................................................................................................31
Table 2-10 Digital Input Wiring.................................................................................................................................33
Table 2-11 Communication Wiring............................................................................................................................35
Table 2-12 Output Terminal Use for Output Algorithm and Option Combinations...................................................37
Table 2-14 Current Output Wiring.............................................................................................................................41
Table 2-15 Transmitter Power Out Wiring.................................................................................................................43
Table 3-1 Procedure for Configuring Model without Display....................................................................................46
Table 3-2 Configuration and Input Switch Settings for Models without Display.......................................................49
Table 3-3 Preparing the Recorder for Operation........................................................................................................66
Table 3-4 Procedure for Running the Step Test..........................................................................................................67
Table 4-8 Totalizer Function Definitions...................................................................................................................91
Table 4-9 Control Parameter Definitions....................................................................................................................94
Table 4-19 Limit Control Parameter Definitions......................................................................................................118
Table 4-20 Preparing the Recorder for Operation............................................................................... .....................120
Table 4-21 Procedure for Running the Step Test......................................................................................................121
Table 4-22 Procedure for Setting Chart Time and Applying Power.........................................................................123
Table 4-24 Procedure for Testing the Displays and Keys.........................................................................................125
Table 4-25 Procedure for Starting the Recorder.......................................................................................................126
Table 4-26 Meaning of Indicators............................................................................................................................129
Table 4-33 Procedure for Resetting Totalizer...........................................................................................................137
Table 4-34 Procedure for Starting Timer..................................................................................................................138
Table 4-35 Procedure for Resetting Limit Controller...............................................................................................139
Table 5-1 Voltage and Resistance Equivalents for 0 % and 100 % Range Values...................................................143
Table 5-2 Equipment Needed for Calibration...........................................................................................................144
Table 5-3 Disconnect the Field Wiring.....................................................................................................................145
Table 5-4 General Calibration Set Up Procedure.....................................................................................................146
Table 5-5 Set Up Wiring Procedure for Thermocouple Inputs Using a Compensated Calibrator...........................147
Table 5-6 Set Up Wiring Procedure for Thermocouple Inputs Using an Ice Bath...................................................148
Table 5-7 Set Up Wiring Procedure for Calibrating RTD Inputs.............................................................................149
Table 5-8 Set Up Wiring Procedure for Calibrating Millivolts, Volts, and Milliamps Inputs..................................150
Table 5-10 Set Up Wiring Procedure for Current Proportional Output....................................................................153
Table 5-11 Procedure for Calibrating Current Output..............................................................................................154
Table 6-1 Procedure for Replacing the Chart...........................................................................................................158
Table 6-2 Procedure for Replacing the Ink Cartridge...............................................................................................159
Figure 2-6 Mounting Flush on a Surface of Panel or Wall (Rear View).....................................................................22
Figure 2-7 Recommended Wiring Routing - Models Without CE Mark....................................................................24
Figure 2-8 Recommended Wiring Routing - Models With CE Mark.........................................................................25
Figure 2-9 Power Wiring – Models Without CE Mark...............................................................................................29
Figure 2-10 Power Wiring – Models With CE Mark..................................................................................................30
Figure 2-11 Analog Input Wiring...............................................................................................................................32
Figure 2-12 Digital Input Wiring................................................................................................................................34
Figure 2-13 Communication Wiring...........................................................................................................................36
Figure 2-15 Open Collector Output Wiring................................................................................................................40
Figure 2-16 Current Output Wiring............................................................................................................................42
Figure 2-17 Transmitter Power Out Wiring................................................................................................................44
Figure 3-1 Location of Configuration and Input Switches..........................................................................................47
Figure 3-2 Sample Chart for Single Pen Recorder...................................................................................................... 48
Figure 3-4 Typical Step Test Chart Patterns...............................................................................................................68
Figure 3-5 Setting Chart Time to Time Index.............................................................................................................69
Figure 4-3 Location of Switches and Relays..............................................................................................................82
Figure 4-5 Typical Step Test Chart Patterns.............................................................................................................122
Figure 4-6 Setting Chart Time to Time Index...........................................................................................................123
Figure 5-1 Location of the Input Connections on the Input Boards..........................................................................145
Figure 5-2 Calibration Set Up Diagram for Thermocouple Inputs Using a Compensated Calibrator......................147
Figure 5-3 Calibration Set Up Diagram for Thermocouple Inputs Using an Ice Bath ..............................................148
Figure 5-4 Calibration Set Up Diagram for RTD Inputs ..........................................................................................149
Figure 5-5 Calibration Set Up Diagram for Millivolts, Volts, and Milliamps Inputs...............................................150
Figure 5-6 Test Equipment Connections for Calibrating Current Output.................................................................153
Figure 6-1 Replacing the Chart and Ink Cartridge....................................................................................................158
Figure 9-1 Door Assembly........................................................................................................................................192
The DR4300 recorder is a one or two pen microprocessor-based circular chart recorder. The basic DR4301
(one pen) and DR4302 (two pen) recorders provide reliable, convenient pen-drawn analog traces on
preprinted 10 inch (250 mm) charts. Both the chart and the pens are driven by stepper motors controlled by
the microprocessor. Chart speed and range are configurable. The basic recorder is also available in CE
models DR4321 (one pen) and DR4322 (two pen).
In addition to generating pen-drawn chart traces, the DR4311 (one pen) and DR4312 (two pen) models
include a display and keypad. This option lets you display the real time value of the process variable for
each pen channel, as well as other values. The recorder with display and keypad is also available in CE
models DR4331 (one pen) and DR4332 (two pen).
Each pen channel has its own printed circuit assembly (PCA), allowing the channels to operate
independently.
Overview
1. Overview
CE conformity (Europe)
Indicated models of this product are in conformity with the protection requirements of the following
European Council Directives: 73/23/EEC, the Low Voltage Directive, and 89/336/EEC, the EMC
Directive. Conformity of this product with any other “CE Mark” Directive(s) shall not be assumed.
Deviation from the installation conditions specified in this manual, and the special conditions for CE
conformity in Section 2 of this manual, may invalidate this product’s conformity with the Low Voltage and
EMC Directives.
Analog inputs
The input for each pen channel can be one of any standard electrical signal: milliamp, millivolt, voltage,
RTD, or thermocouple. The input type and range are configurable. In the models having display and keypad
the range can be expanded and compressed to meet specific measurement needs. The display and keypad
also permit entry of input bias and filter values. (The input filter for the models without a display is fixed at
one second; their bias is zero.)
Digital inputs
Two digital inputs for each pen channel are available as an option. These inputs can be used to trigger the
switchover to a second control setpoint or a pre-configured constant output if an external event causes
contact closure (sets the digital input to ON). In addition, the digital inputs can be used to remotely reset the
optional totalizer or limit controller.
The Modbus communication option permits configuration of the unit and monitoring of process variables
over a standard multi-drop serial communications link.
Relay outputs for control and alarms
The models with display and keypad are available with output relays, two for each pen channel. These
relays can be wired for Normally Open (NO) and Normally Closed (NC) terminals. ON-OFF control can be
performed using one relay (relay simplex control) or two relays (relay duplex control).
Any relay not used for control is available for alarming. Two alarm setpoints can be configured for each
alarm relay. An adjustable hysteresis of 0.0 % to 100.0 % is configurable for the alarm setpoint.
Analog output for control or retransmission
Depending on the model ordered, a 4 to 20 mA current output may be available for control or
retransmission of a process variable (“auxiliary output”).
Failsafe operation
The control function can operate in automatic or manual mode. In automatic the control function works to
maintain the process variable at the setpoint entered locally by the operator. During configuration a
“failsafe” value can be specified. This value is used as the output at power up and in case of input failure
during automatic operation. (When the unit goes to failsafe, the control function goes to manual mode.)
In manual mode the operator enters the output locally. If the recorder has gone to failsafe operation, the
operator will be able to change the output value from the failsafe value specified during configuration.
Timer and totalizer options
The recorder is available with timer and totalizer options. The timer can be started locally, remotely, or by
an alarm. The unit can be configured to display elapsed time or time remaining. At the end of the timeout
period Relay 2 is energized, and remains energized until the timer is reset. The totalizer can be reset locally
or remotely; its displayed value can be scaled.
Setpoint Programming Option
The recorder is available with a Setpoint Program option. This feature allows configuration of up to four
setpoint programs using a total of twenty-four ramp and soak segments. A setpoint and time is configured
for each segment. The program can be set up to include guaranteed soak segments. A plus/minus deviation
is configured for all soak segments. Whenever the plus/minus deviation is exceeded, soak timing is frozen.
Display and keypad
In addition to process variables, the display can show output, setpoint, and deviation real time values if the
recorder is equipped with optional outputs. The upper display uses four characters to display the input
value. The lower display shows other parameters using a two- or three-character label and four- or threedigit values. In addition, status and error messages flash on the lower display when necessary.
The six keys are used to select the real time value to be displayed, and to select set up parameters and their
values during configuration. The display and keypad are behind the door, protecting them from dirt.
A supplementary external keypad is also available.
For more information about the operator interface on models having a display and keypad, see Subsection
4.2.
Configuration
The models without a display are configured with two switchbanks: one for configuration, the other for
input definition. Configuration is a simple matter of consulting a table in this manual; selecting the
appropriate combination of range, chart speed, engineering unit, and input type; then setting the switches as
shown in the table.
The display and keypad are used to configure models with these options. When the unit is in configuration
mode, set up parameters are displayed, and grouped by function. Designate site-specific values by selecting
them from a list of choices, or entering them as numeric values. The operator can be locked out from
making configuration changes.
The models with display also use a switchbank to define the type of input to be expected by the hardware.
Input parameters used by the software are configured using the display and keypad.
Overview
Self-diagnostics
All DR4300 recorders run self-diagnostics at power up and in the background during normal operation.
Problems are reported by error messages on the display when present. An LED in the models without a
display lights if the unit fails a self-diagnostic.
Construction
All DR4300 recorders are housed in a rugged molded case which can be panel-, pipe- or surface-mounted.
An acrylic-windowed, gasketed door protects internal components from harsh environments while allowing
easy access to the chart.
The model number breakdown is presented in the tables that follow. Note that not all options are available
with all recorders. Check the “Availability” column for each model. A star () in the Availability column
means unrestricted availability of the feature for that model. N/A indicates the feature is not available for
that model. A letter in the Availability column denotes restricted availability. The meaning of each letter is
provided at the bottom of this page.
The Notes referred to in the tables are also at the end of this subsection.
Model number format
The basic model number consists of a key number. Appended to this key number are characters that identify
the features in various categories. The meaning of the characters in each category is presented in a table
identified below.
Key Number Table I Table IITable III Table IV Table VTable VI
The base model numbers for the DR4300 Circular Chart Recorder are:
One Pen Recorder (Basic Recorder Without Display)DR4301
Two Pen Recorder (Basic Recorder Without Display)DR4302
One Pen Recorder (With Display) DR4311
Two Pen Recorder (With Display)DR4312
One Pen Recorder (Basic Recorder Without Display, With CE Mark)DR4321
Two Pen Recorder (Basic Recorder Without Display, With CE Mark)DR4322
One Pen Recorder (With Display, With CE Mark) DR4331
Two Pen Recorder (With Display, With CE Mark)DR4332
Restricted availability designations
d = Not available with Table I selection XX0X.
e = Not available with Table I selection XXX0.
f = Not available with Table I selection 0XXX.
g = Not available with Table I selection 0000.
h = Not available with Table I selections FXXX, XFXX, GXXX, XGXX.
j = Not available with Table I selection 0XXX.
k = Not available with Table I selection X0XX.
m = Not available with Table I selections 2XXX, 3XXX, 4XXX, 5XXX, AXXX, XXX0.
n = Not available with Table II selection SXXXX.
p = Not available with Table II selections RXXXX, SXXXX.
q = Not available with Table II selections GXXXX, BXXXX, HXXXX, CXXXX, KXXXX, LXXXX.
None0 _ _ _
2 Outputs (Alarm/On-Off Control)2 _ _ _N/AN/Add
1 PID Control with Accutune II(see Note 1)3 _ _ _N/AN/Add
1 PID Control/Setpoint Program/Timer (see Not e 1)4 _ _ _N/AN/Add
2 Outputs (Alarm 1 and Timer)5 _ _ _N/AN/Add
4 to 20 mA Retransmission Output(see Note 4)A _ _ _N/AN/Add
FM Approved Limit ControlF _ _ _N/AN/Add
FM Approved Limt Control/Timer OutputG _ _ _N/AN/Add
Pen Two
None_ 0 _ _
2 Outputs (Alarm/On-Off Control)_ 2 _ _N/AN/AN/Ae
1 PID Control with Accutune II(see Note 1) _3 _ _N/AN/AN/Ae
1 PID Control/Setpoint Program/Timer (see Not e 1)_ 4 _ _N/AN/AN/Ae
4302
4322
4311
4331
4312
4332
2 Outputs (Alarm 1 and Timer)_ 5 _ _N/AN/AN/Ae
4 to 20 mA Retransmission Output(see Note 4)_ A _ _N/AN/AN/Ae
FM Approved Limit Control_ F _ _N/AN/AN/Am
FM Approved Limt Control/Timer Output_ G _ _N/AN/AN/Am
Output Type Pen 1
None_ _ 0 _
Electromechanical Relay_ _ E _N/AN/Ajj
Solid State Relay_ _ S _N/AN/Ajj
Open Collector_ _ T _N/AN/Ajj
Output Type Pen 2
None_ _ _ 0
Electromechanical Relay_ _ _ EN/AN/AN/Ak
Solid State Relay_ _ _ SN/AN/AN/Ak
Open Collector_ _ _ TN/AN/AN/Ak
No Digital Inputs0 _ _ _
Digital Inputs(See Note 3)D _ _ _N/AN/Afg
None_ 0 _ _
No Totalizer Function_ _ 0 _
Totalizer_ _ T _N/AN/Ahh
Future_ _ _ 0
4302
4322
4311
4331
4312
4332
Model Number Table IV - PEN 2 OPTIONS
DescriptionModel No.Availability
4301
4321
No Digital Inputs0 _ _ _
Digital Inputs(See Note 3)D _ _ _N/AN/AN/Ag
None_ 0 _ _
4302
4322
4311
4331
4312
4332
No Totalizer Function_ _ 0 _
Totalizer_ _ T _N/AN/AN/Ah
Future_ _ _ 0
Model Number Table V - APPROVALS/CERTIFICATES
DescriptionModel No.Availability
4301
4321
No Approvals0 _
UL ListingU _nnnn
CSA CertificationC _nnnn
UL and CSA ApprovedB _nnnn
No Certificate_ 0
Certificate of Conformance (F3391)_ 1
Certificate of Calibration (F3399)(See Note 2)_ 2
Certificate of Conformance and Calibration
NOTE 1: PID control o ptions include current output plus two discrete outputs for alarms. If ON-OFF or
time-proportioned simplex control is used, only one discrete output is available for an alarm.
Time-proportioned duplex control requires the use of both outputs and therefore no relay outputs
are available for alarms on that pen channel. Accutune II tuning is a standard feature with PID
control options.
NOTE 2: Customer must supply the input actuation and range information for each input in the Free Form
section of the order to have the unit supplied with a Certificate of Calibration.
NOTE 3: Digital Inputs are only available when ordering outputs in Table I.
NOTE 4: 4 to 20 mA Retransmission Output includes two outputs per pen for alarms. You must specify
the type of alarm outputs required (i.e., Relay, SS Relay, Open Collector Outputs).
NOTE 5: On key numbers DR4301, DR4302, DR4321, and DR4322 the communication address is fixed;
the display assembly is required to change it. Only one DR4301 or DR4321 instrument, or only
one pen of a DR4302 or DR4322 can exist on the network, otherwise communication conflicts
will exist. Pen 1 is the default when communications is specified on these models.
NOTE 6: Recorder is supplied with one box of 30755820-001, 0 to 100 Even "starter" charts. For special
range configuration on the DR4301, DR4302, DR4321, or DR4322 Recorder, provide the Input
Type, Chart Range, Chart Speed, °C or °F, Engineering Units, Linear or Non-Linear Chart Type
when ordering.
For example: Pen 1: "J" Thermocouple, 0-375 °F, 7-Day Linear Chart
Pen 2: 4-20 mA, 0-1000, 7-Day Linear Chart
For configuration on Models DR4311, DR4312, DR4331, and DR4332, the customer must
supply completed "Configuration Worksheets" with order for units to be Factory configured.
This manual contains instructions for installation, set up, startup, operation, troubleshooting, and repair of
all recorder models listed in Subsection 1.2. The models fall into two broad categories:
• basic version without display: DR4301, DR4302, DR4321, and DR4322
• enhanced version with display: DR4311, DR4312, DR4331, and DR4332
Some sections in the manual apply to all models, while others contain information specific to one of these
two categories. Unless a section’s title refers to recorders “without display” or “with display”, the
information in the section applies to all models. To see which sections apply to your recorder, see Figure
1-1.
Installation of the DR4300 recorder consists of mounting and wiring the recorder according to the
instructions given in this section.
Read the pre-installation information below, check the model number interpretation in Section 1, and
become familiar with your model selections, then proceed with installation.
What’s in this section?
The following is a list of topics in this section.
2.1 Overview11
2.2 Mounting Considerations and Overall Dimensions15
2.3 Mounting Methods16
2.4 Wiring Prerequisites22
2.5 Input Wiring27
2.6 Output Wiring37
Installation
2. Installation
TopicSee Page
Pre-installation information
If the recorder has not been removed from its shipping carton, inspect the carton for damage and remove the
recorder. Inspect the unit for any obvious shipping damage and report any damage due to transit to the
carrier.
• Make sure a bag c ontaining mounting hardware is included in the carton with the recorder.
• Check that the model number shown on the chart plate agrees with what you have ordered.
We recommend that you review and adhere to the operating limits listed in Table 2-1 when you install your
recorder.
Table 2-1 Operating Limits and Condensed Specifications
ConditionSpecifications
AccuracySee Appendix A
Ambient Temperature0 °C to 55 °C [32 °F to 131 °F]
Relative Humidity5 % to 90 % RH at 40 °C [104 °F]
Vibration
Frequency
Acceleration
Mechanical Shock
Acceleration
Duration
Mounting Position from
Vertical
Tilted Forward
Tilted Backward
Tilted to side (±)
0 to 200 Hz
0.5 g
5 g
30 ms
5°
90°
20°
Power
Voltage (ac/dc)
Frequency (Hz)
Power Consumption20 Watts maximum
Type of ActuationsThermocouple: B, E, E (low), J, J (low), K, K (low), Ni-Ni Moly, Nicrosil-Nisil, R, S,
Minimum Input SpanRange is fully configurable within span limitation of the sensing element.
Input ImpedancemA dc: 250 ohms
Span Step Response Time7 seconds maximum
Reproducibility0.1 percent of span
100 Vac to 240 Vac
or
20 Vac/Vdc to 27 Vac/Vdc
49 Hz to 61 Hz
Solid State Relay OutputSPST solid state contacts consisting of a triac NO output.
Internally socketed.
Resistive Load:1.0 A @ 25 °C for 120 Vac or 240 Vac.
0.5 A @ 55 °C for 120 Vac or 240 Vac.
Inductive Load:50 VA @ 120 Vac or 240 Vac.
Open Collector OutputMaximum Sink Current: 20 mA
Internally powered @ 30 Vdc
Opto-isolated from all other circuits except current output, but not from each other.
Socketed jumper assembly replaces relay.
Modbus CommunicationBaud Rate: 19,200 maximum, configurable for models with display;
fixed at 9,600 for models without display
Protocol: Modbus
Length of Link: 1,219 m [4,000 ft] maximum
Link Characteristics: Two-wire, multidrop
Digital Inputs
(Supply common with
current output)
Transmitter Power24 Vdc with adjustment of ± 6 % (22.6 to 25.4)
+24 Vdc source for external dry contacts or isolated solid state contacts for either
of the two inputs.
On contact closure the recorder will respond according to how each digital input is
configured. Opening contact causes return to previous state.
2.2 Mounting Considerations and Overall Di mensions
Physical considerations
The recorder can be mounted flush in a panel or on the surface of a panel or wall using the mounting kit
supplied with the recorder. Adequate access space must be available at the back of the panel for installation
and servicing.
A kit for mounting the unit on a pipe is available (see Section 9 Parts List).
Overall dimensions
The overall dimensions and panel cutout requirements for mounting the recorder are shown in Figure 2-1.
This section provides instructions for mounting the recorder using one of the following methods:
• Flush in a panel (Subsection 2.3.2)
• Flush in a panel for recorders with NEMA4 or Heavy Duty door (Subsection 2.3.3)
• On a 2-inch pipe (Subsection 2.3.4)
[A pipe mounting kit is available (see Section 9 Parts List).]
• On the surface of a wall or panel (see Subsection 2.3.5).
Choose the method that meets your mounting requirements. Use the associated dimension drawings for
reference.
How to remove knockouts for conduits
Before you mount the recorder, remove the appropriate plugs in the bottom and/or sides of the recorder case
for wire entry via 1/2" (12.7 mm) conduits. Refer to Figure 2-2 for plug locations. To see recommended
use of conduits for various types of wiring, refer to Figure 2-7 and Figure 2-8.
Refer to Figure 2-3 and follow the procedure in Table 2-2 to make a new cutout in a panel and mount your
recorder in the cutout.
Table 2-2 Mounting Flush in a New Panel Cutout
StepAction
Installation
1
2
3
4
At the appropriate location, make a square cutout in the panel. Cutout dimensions should be
322.56 mm ± 1.52 mm x 322.56 mm ± 1.52 mm [12.7 in ± 0.060 in x 12.7 in ± 0.060 in]. See
Figure 2-3.
Orient the recorder case properly and slide it into the cutout from the front of the panel.
Support the recorder as shown in Steps 3 and 4.
Refer to Figure 2-3. From the back of the panel, attach a mounting bracket to each side of the
recorder case using a 1/4-20 x 1/2-inch hex screw for each bracket (mounting hardware
supplied with recorder). Leave the screws slightly loose so you can adjust the brackets.
While holding the recorder firmly against the panel, slide each bracket against the back of the
panel and tighten the screws.
Hex screw,
1/4-20 x
1/2 inch and
washer
21406
Figure 2-3 Mounting Flush in a New Panel Cutout (Rear View)
2.3.3 Panel Mounting Recorder with NEMA4 or Heavy Duty door
Refer to Figure 2-4 and follow the procedure in Table 2-3 to panel mount your recorder if it has a NEMA4
or Heavy Duty door.
Table 2-3 Procedure for Mounting Recorder with NEMA4 or Heavy Duty Door
StepAction
Place the panel gasket onto the rear flange of the recorder case.
1
Install four #8-32 screws on each of the three mounting brackets so the ends of the screw
2
threads are flush with the face of the bracket.
NOTE: Screw heads to be flange side of brackets.
Insert the case with gasket into the panel opening.
3
Install one left hand and one right hand bracket with 1/4 x 3/8 long bolts and lockwashers on
4
each side of the case.
NOTE: The notch on each bracket should be facing upward towards the top of the unit.
Do not tighten the hex bolts at this time.
Install the remaining right hand bracket on the top with the 1/4 x 3/4 long bolt and lockwasher.
5
Do not tighten the bolt at this time.
Place a screwdriver blade on the notch of each bracket and firmly tap so that each bracket
6
firmly mates the case with gasket to the panel.
NOTE: Keep brackets parallel to case. Tighten the three 1/4 hex bolts to hold the brackets in
place.
Start to tighten the #8-32 x 1/2 screws on the right side bracket. Alternate screws at opposite
7
ends until all four screws have a minimum of 10 lb-in of torque applied. Do the same to both
the left side and top brackets.
When completed all twelve screws should have a minimum of 10 lb-in of torque applied. This
assures the case and panel gasket are adequately sealed against the panel.