DPTM52-5002
2-WIRE DIFFERENTIAL PRESSURE TRANSMITTERS
CURRENT OUTPUT
SPECIFICATION DATA & MOUNTING INSTRUCTIONS
FEATURES
• Monitoring gaseous, non-aggressive media
• Piezo-resistive pressure transducer
• Up to 40 kPa (60 kPa) overload capacity
• Rugged design; protection class IP54
• Easy installation and wiring connection
• Measurement range adjustable by jumper
• Response time adjustable by jumper
• Re-zeroing possible by pushbutton
NOTE: These sensors are not suitable for use in
installations under periodic inspection by the U.S.
Food and Drug Administration.
GENERAL
The differential pressure transmitters of the DPTM series are
used for measuring differential pressure, positive pressure,
and vacuum. The transmitters are suitable for:
• air-conditioning,
• building automation,
• environmental protection,
• valve and flap control,
• filter and blower monitoring,
• fluid and level monitoring, and
• control of air flows.
Models
order no.
DPTM52 -50...0...+50 Pa1) n.a. 20 kPa 40 kPa
DPTM112 -100...0...+100 Pa1 n.a. 20 kPa 40 kPa
DPTM552 -500...0...+500 Pa1) n.a. 20 kPa 40 kPa
DPTM1102 -1 kPa...0...+ 1 kPa2) n.a. 40 kPa 70 kPa
DPTM102 0...100 Pa1) 0...250 Pa 20 kPa 40 kPa
DPTM252 0...250 Pa1) 0...500 Pa 20 kPa 40 kPa
DPTM502 0...500 Pa1) 0...1 kPa 20 kPa 40 kPa
DPTM1002 0...1 kPa2) 0...2.5 kPa 40 kPa 70 kPa
DPTM5002 0...5 kPa3) 0...10 kPa 60 kPa 120 kPa
1)
Temperature error at 0…50 °C ≤ ± 5% of FS
2)
Temperature error at 0…50 °C ≤ ± 2.5% of FS
3)
Temperature error at 0…50 °C ≤ ± 1% of FS
pressure range
1
(pre-set)
2
overload
capacity
bursting
pressure
SPECIFICATION
Supply voltage 16...32 Vdc
Output signal 4...20 mA, two-wire
Pressure medium Air + non-aggressive gases
Working temperature 0...50 °C
Linearity and hysteresis error ≤ ± 1.0% of FS
Temperature error see "Models"
Storage temperature -10...+70 °C
Humidity 0...95% rh, non-condensing
Repetition accuracy ≤ ± 0.2% of FS
Response time 1 s (switchable to 100 ms)
Process connection 6 mm hose pipe
Electrical connection Screw terminal block for wire
up to 1.5 mm²
Housing material ABS and POM
Cable entry M20x1.5 (polyamide)
Protection class IP54 as per EN60529
EMV EN60770, EN61326
Weight approx. 130 g
FUNCTION
DPTM52-5002 Two-Wire Differential Pressure Transmitters
are equipped with an integrated piezo-resistive pressure
transducer. The pressure to be measured is applied to and
thus deflects a thin membrane made of mono-silicon. The
membrane's semiconductor resistors (arranged to simultaneously compensate for the temperature response) detect
this deflection and generate an electrical output signal. The
output signal is converted into a 4…20 mA analog signal
® U.S. Registered Trademark EN0B-0467GE51 R1007
Copyright © 2007 Honeywell Inc. • All rights reserved
DPTM52-5002 TWO-WIRE DIFFERENTIAL PRESSURE TRANSMITTERS
which changes (within the specified error limits) in proportion
to the applied pressure.
NOTE: The devices are factory pre-set to pressure range 1
This can be changed (except for +/- models) to
pressure range 2 by removing the corresponding
jumper (see Fig. 3).
NOTE: The devices are factory pre-set to a response time
of 1 second. This can be changed to 100 ms by
removing the corresponding jumper (see Fig. 3).
ACCESSORIES
DPSK: Included in delivery. Duct Kit, incl. 2 m of silicone
hose and two joining pipes
DPSL: Ordered separately. L-shaped mounting brackets
with screws.
DIMENSIONS
4.5
8.5
IP 54
WIRING
Range:
high
low
Response:
fastmAslow
Mode:
Output:
V
Jumper yes
Jumper no
Differential Pressure Transmitter
2341
REZEROING:
Remove tubes and push
button approx. 5 sec.
1000
PRESSURE RANGE
jumper inserted = pressure range 1
jumper removed = pressure range 2
RESPONSE TIME
umper inserted = 1 sec
umper removed 100 msec=
NALOG OUTPUT (4...20 mA)
jumper without function
LOAD
P2 (LOW PRESSURE)
P1 (HIGH PRESSURE)
STORAGE POSITION FOR JUMPERS
Fig. 3. Wiring details
NOT USED
1
16...32Vdc
2
4...20 mA
3
DO NOT USE!
4
DO NOT USE!
Fig. 1. Dimensions (in mm)
MOUNTING
800
OHMS)
600
400
E LO
200
0
RESISTI
32 34302826242220181614
SUPPLY VOLTAGE (Vdc)
Fig. 4. Permissible load vs. supply voltage
Fig. 2. Mounting
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative:
Fema Controls
Honeywell GmbH
P.O. Box 1254
71099 Schönaich
Germany
phone: (49) 7031-637-02
fax: (49) 7031-637-850
http://www.honeywell.de/fema
Subject to change without notice.
EN0B-0467GE51 R1007