Honeywell DG T, DG NT, DG FT, DG ST Operating Instructions Manual

USA
CAN
D
03251549
USA CAN MEX
www.docuthek.com
Operating instructions
Pressure switches for gas DG..T
© 2018 Elster GmbH · Edition 09.18
Cert. version 05.18
Translation from the German
Safety
Please read and keep in a safe place
Please read through these instructions carefully before installing or operating. Following the installation, pass the instructions on to the opera­tor. This unit must be installed and commissioned in accordance with the regulations and standards in force. These instructions can also be found at www.docuthek.com.
Explanation of symbols
• , 1 , 2 , 3 ... = Action
= Instruction
Liability
We will not be held liable for damage resulting from non-observance of the instructions and non-com­pliant use.
Safety instructions
Information that is relevant for safety is indicated in the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM spare parts.
Checking the usage
Gas pressure switches DG..T for monitoring increas­ing and decreasing gas or air pressure.
DG..T, DG..FT
DG..HT, DG..NT
DG..ST NH
DG..NT and DG..HT lock off after switching. They can be unlocked using the manual reset.
This function is only guaranteed when used within the
specified limits– see page5 (Technical data). Any other use is considered as non-compliant.
Type code
Code Description
DG Gas pressure switch 6 – 500 Max. setting in mbar
F* H* N* S*
T T-product G With gold-plated contacts
-2
-4
-9 1 2 K2 T2
Red/green pilot LED for 110 to 230 V AC
N A External adjustment
* If “none”, this specification is omitted; DG..T
switches with rising pressure.
Part designations
1 Upper housing section with cover 2 Lower housing section 3 Hand wheel 4 ½" NPT conduit coupling 5 Manual reset
(DG..NT and DG..HT only)
Positive
pressure
Gas, air, flue gas, biogas
Gas, air, flue gas, biogas
, O2, air
3
Negative pressure
Air, flue gas
Air, flue gas
Switches with falling pressure
Locks off with rising pressure
Locks off with falling pressure
Switches with rising and falling pressure;
for NH
, O2 (without approval)
3
Electrical connection
via screw terminals
via screw terminals, IP65
4-pin plug, with socket, IP65
1x ¼" NPT connection
2x ¼" NPT connections
Red/green pilot LED for 24 V DC/AC
Blue pilot lamp for 120 V AC
2
1
5
3
4
USA-1
CAN
D
Type label
4
USA
Approval and type: see
DG T
type label.
CAUTION
If port 4 is at the top, IP65 will not be satisfied.
IP 65
For detailed information on the adjusting range, mean switching differential, max. inlet pressure, lock-off,
medium and switching properties, see page 5
(Technical data) and the table on page 3 (Ad-
justment).
Installation
CAUTION
Please observe the following to ensure that the DG..T is not damaged during installation and op eration:
– Continuous operation with gases containing
more than 0.1%-by-vol. H2S or ozone con­centrations exceeding 200µg/m3 accelerate the ageing of elastomer materials and reduce
the service life. – Use approved sealing material only. – Dropping the device can cause permanent dam-
age. In this event, replace the entire device and
associated modules before use. – Check max. ambient temperature – see
page5 (Technical data). – When using silicone tubes, only use silicone
tubes which have been sufficiently cured. – Vapours containing silicone can adversely affect
the functioning of electrical contacts. – Condensation or vapours containing silicone
must not be allowed to get into the housing.
At subzero temperatures, malfunctions/failures due to icing can occur.
– When installing outdoors, place the DG..T in
a roofed area and protect from direct sunlight (even IP65 version).
– Avoid strong impact on the unit.
▷ Installation position as required, preferably with
vertical diaphragm. Then the switching point p corresponds to the scale value SK set on the hand wheel. In other installation positions, the switching pointpS will change and no longer correspond to the scale valueSK set on the hand wheel. Check the switching point.
▷ The DG..T must not be in contact with masonry.
Minimum clearance 1" (25 mm).
Ensure that there is sufficient installation space. Ensure unobstructed view of the hand wheel.
1 Disconnect the system from the electrical power
supply.
2 Shut off the gas supply. 3 Ensure that the pipeline is clean.
Ports
1 or 2 for
-
4
1
2 *
positive pressure (¼" NPT)
4 for negative pressure (
Connect Free Positive pressure
1 or 2* 4
DG..T Negative pressure
4 1 or 2*
DG..T Differential pressure DG..T
1 or 2* for higher absolute pressure. 4 for lower absolute pressure.
* Port 2 only on DG..T..2 with 2x ¼” NPT connections..
CAUTION
Port 4 connects the upper diaphragm chamber
with the micro switch. Do not connect port4 to
pipes carrying gas.
▷ The pressure switches are supplied with an inte-
grated vent limiter. In the event of a diaphragm tear, the vent limiter limits the escape of gas to less than 1.0 CFH of natural gas at 2.8psi
S
(DG..6T) or 7 psi (DG..10T – DG..500T). If neces­sary, port4 (1/8" NPT) can be used to connect the venting line.
A filter pad at port4 protects the electrical contacts
in the DG..T from dirt particles in the surrounding air or in the medium.
▷ Filter pad for port4, see PartDetective.
1
/8" NPT)
ps = SK
ps =SK + 0,08 "WC ps = SK - 0,08 "WC