• Please read this instruction sheet thoroughly before
installation and keep this instruction sheet and the CD
shipped with the product at hand and distribute to all
users for reference.
• To ensure the safety of operators and equipment, only
qualified personnel familiar with AC motor variable
frequency drives (VFD) are allowed to do installation,
trial run and parameter settings. Always read this
instruction sheet thoroughly before using the AC motor
VFD, especially the WARNING, DANGER and
CAUTION notes. If you have any questions, please
contact your dealer.
Please read prior to installation for
safety.
The ground terminal of the VFD must be
grounded correctly. The grounding method must
comply with the laws of the country and local codes
where the VFD is to be installed.
After power has been turned off to the VFD, the VFD's
capacitors may still be holding a high voltage charge.
Do not work with the VFD while the POWER indicator
light is ON. To prevent personal injury, DO NOT touch
the internal circuits and components until the voltage
between +1 and – is less than 25VDC. Please wait at
least 5 minutes for 22kW/30hp models to discharge to
a safe voltage level. (10 minutes for 30kW/40hp
models).
The CMOS ICs on the internal circuit boards of the
VFD are sensitive to static electricity. DO NOT touch
the circuit boards with bare hands before taking antistatic measures. Never reassemble the internal
components or circuits.
If the wiring needs to be changed, please turn off the
power of the VFD before wiring. The internal DC-bus
capacitors need time to discharge; wiring changes
made before the voltage is discharged to the safe level
may cause short circuit and fire. To ensure personal
safety, only perform wiring changes after the safety
voltage level is reached.
DO NOT install the VFD in a place subjected to high
temperature, direct sunlight and inflammable materials.
See specification data in this manual for details.
Never apply power to the output terminals U/T1, V/T2,
W/T3 of the VFD.
Please stop operation immediately when a fault occurs
during operation of the VFD and motor and refer to
fault code information to reset the drive.
DO NOT use Hi-pot test for internal components. The
semi-conductors in the VFD are easily damaged by
high-voltage.
When the motor cable between the VFD and motor is
too long (see motor cable data on page 3), the layer
insulation of the motor may be damaged. Please use a
frequency inverter duty motor and add an output
reactor to prevent damage to the motor and the VFD.
The rated voltage of the VFD must be ≤ 240V for 208V
and 230V models and ≤ 480V for 460V models and the
mains supply current capacity must be ≤ 5000A RMS
(≤10000A RMS for the ≥ 30kW/40hp models).
The VFD must be placed in a clean, well-ventilated and
dry location, free from corrosive gases or liquids.
The VFD must be stored within an ambient
temperature range of –25C/-13F ~ +75C/167F and
relative humidity range of 0% to 95% without
condensation.
DO NOT place the VFD on the ground directly. It
should be stored properly. Moreover, if the surrounding
environment is humid, you should put exsiccator in the
package. To prevent condensation and frost, please
DO NOT store in an area with rapid changes in
temperature. DO NOT install the VFD in a place
subjected to direct sunlight or vibration.
If the VFD is stored for more than 3 months, the
temperature should not be higher than 30° C (86° F).
Storage longer than one year is not recommended, it
could result in the degradation of the electrolytic
capacitors.
Please turn on the power after the front cover is
installed. DO NOT operate with moist hands. Make
sure that the VFD is not under load at first. After a fault
occurs, please wait 5 seconds after a fault has been
cleared before pressing RESET key.
62-0410—042
Page 3
HONEYWELL CORE DRIVE
ENVIRONMENT FOR OPERATION, STORAGE AND
TRANSPORTATION
DO NOT expose the VFD to an improper environment, such as dust, direct sunlight, corrosive/inflammable gases,
humidity, liquid and vibration environment. The salt in the air must be less than 0.01mg/cm
2
every year.
Installation location IEC60364-1/IEC60664-1 Pollution degree 2, Indoor use only
Air PressureOperation/ Storage: 86 to 106 kPa Transportation: 70 to 106 kPa
IEC721-3-3
Environment
Pollution Level
Operation: Class 3C2; Class 3S2 Storage: Class 2C2; Class 2S2 Transportation: Class 1C2; Class 1S2
No concentrate
Conformal coated boards
If VFD is installed at altitude 0~1000m, follow normal operation restriction. If it is installed
at altitude 1000~3000m, decrease 2% of rated current or lower 0.5
o
C of temperature for
every 100m increase in altitude. Maximum altitude for Corner Grounded is 2000m.
o
(under normal installation
Package
Drop
Vibration
Impact
Operation
Position
Plenum
Rating
AltitudeOperation
Storage
Tra ns por ta tio n
ISTA procedure 1A(according to weight) IEC60068-2-31
1.0mm, peak to peak value range from 2Hz to 13.2 Hz; 0.7G~1.0G range from 13.2Hz to 55Hz; 1.0G range from 55Hz to
512 Hz. Comply with IEC 60068-2-6
IEC/EN 60068-2-27
Max. allowed offset angle ±10
position)
Compliance with UL 508C, the Standard for Power Conversion Equipments, 3rd Edition, and the Canadian Standard for
Industrial Control Equipment, C22.2-No. 14.
* HD = Heavy Duty, higher overload rating. ND = Normal Duty, Standard HVAC applications
NOTE: To prevent personal injury, please make sure that the case and wiring are installed according to this instruc-
tion. The figures in this instruction are only for reference, they may be slightly different from the one you have
but it will not affect your customer rights. The installation instruction may revise without prior notice. Please
refer to our distributors or download the updated version at http://www.customer.honeywell.com/VFD.
362-0410—04
Page 4
HONEYWELL CORE DRIVE
SPECIFICATION TABLES
Table 1. GENERAL SPECIFICATIONS
Control Method1: V/F (V/F control); 2: SVC (Sensorless Vector Control)
Starting TorqueReach up to 150% or above at 0.5Hz.
V/F Curve 4 point adjustable V/F curve and square curve
Speed Response
Ability5Hz
Torque LimitHeavy Duty: Max.170% torque current
Torque Accuracy±5%
Max. Output
Frequency (Hz)
Frequency Output
Accuracy
Output Frequency
Resolution
Overload Tolerance
Frequency Setting
Signal0~+10V, 4~20mA, 0~20mA, pulse input
Accel./Deccel. Time 0.00~600.00/0.0~6000.0 seconds
Control Characteristics
Main control
function
Fan Control
Motor ProtectionElectronic thermal relay protection
Over-current
Protection
Over-voltage
Protection
Over-temperature
ProtectionBuilt-in temperature sensor
Stall PreventionStall prevention during acceleration, decceleration and running independently
Restart After
Instantaneous
Protection Characteristics
Power FailureParameter setting up to 20 seconds
Grounding Leakage
Current Protection Leakage current is higher than 50% of rated current of the AC motor drive
International
CertificationsCE, GB 12668.3
62-0410—044
230V series: 600.00Hz (55kw and above: 400.00Hz);
460V series: 600.00Hz (90KW and above: 400.00Hz)
Digital command:±0.01%, -10C~+ 40C, Analog command: ±0.1%, 25±10C
Digital command: 0.01Hz, Analog command: max. output frequency x 0.03/60 Hz (±11 bit)
Normal duty: 120% of rated current for 1 minute
Heavy duty: 120% of rated current for 1 minute;160% of rated current for 3 seconds
Fault restartParameter copyDwellBACnet COMMMomentary power
Speed searchOver-torque
S-curve accel/
deccel
Slip compensation Torque
Smart StallPID control (with
230V series
Model HCRDA0200B1000T (20HP) and above are PWM controlled
Model HCRDA0150B1000T (15HP) and below are on/off switch controlled
460V series
Model HCRDC0200B1000T and above are PWM controlled
Model HCRDC0150B1000T (15HP) and below are on/off switch controlled
Normal Duty: Over-current protection for 240% rated current
Current clamp Normal duty: 170~175%
230: drive will stop when DC-BUS voltage exceeds 410V
460: drive will stop when DC-BUS voltage exceeds 820V
Rated Voltage/Frequency3-phase AC 380V~480V (-15%~+10%), 50/60Hz
Operating Voltage Range323~528Vac
Frequency Tolerance47~63Hz
Cooling methodNatural CoolingFan Cooling
Braking Chopper
DC choke
EMI Filter
Frame A,B,C: Built-in
Frame A, B,C: Optional
Frame A, B, C - EMI filter NOT built-in
2~9
kHz
(4KHz
2~9
kHz
(4KHz
Frame D and above:
Optional
Frame D and above: 3%
DC built-in
Frame D and above:
Optional
62-0410—046
Page 7
MINIMUM MOUNTING CLEARANCES
AA
A
A
A
A
B
B
A
A
B
A
A
C
A
A
B
A
A
D
A
A
B
A
A
2B
A
A
B
A
A
D
A
A
B
A
A
A
A
D
B
B
A
A
B
A
D
Ta*
B
A
A
C
B
B
A
A
C
B
50 mm
Ta
50 mm
Ta
50 mm
Ta
50 mm
Ta
A
A
D
Ta*
A
FRAME A, B, C
MULTIPLE DRIVES: INDEPENDENT
INSTALLATION IN HORIZONTAL
FRAME D, E
MULTIPLE DRIVES: INDEPENDENT
INSTALLATION IN HORIZONTAL
INSTALL A BARRIER BETWEEN THE
DRIVES
FRAME A, B, C
MULTIPLE DRIVES: INDEPENDENT
INSTALLATION
TA: FRAME A~E
IT IS SUGGESTED TO INSTALL A
BARRIER BETWEEN THE DRIVES.
ADJUST THE SIZE OF THE BARRIER TILL
THE TEMPERATURE OF THE FAN ON THE
INFLOW SIDE IS LOWER THAN THE
OPERATION TEMPERATURE.
(REFER TO THE RIGHT FIGURE)
OPERATION TEMPERATURE IS THE
TEMPERATURE MEASURED 50MM AWAY
FROM THE INFLOW SIDE OF THE FAN.
MINIMUM MOUNTING CLEARANCE
FRAME
A~C
A (mm/in) B (mm/in) C (mm/in)
D (mm/in)
D~F
60/1.2
100/3.3
30/0.6
50/1.7
10/0.2
0
0
-
A
B
B
A
INVERTER
INVERTER
INVERTER
INVERTER
INVERTER
INVERTER
INVERTER
INVERTER
INVERTERINVERTER
INVERTER
INVERTER
INVERTER
INVERTER
INVERTER
INVERTER
INVERTER
NOTE:
THE MOUNTING CLEARANCES SHOWN IN THE LEFT FIGURE ARE NOT FOR INSTALLING THE DRIVE IN A
CONFINED SPACE (SUCH AS CABINET OR ELECTRIC BOX). WHEN INSTALLING IN A CONFINED SPACE,
BESIDES THESE SAME MINIMUM MOUNTING CLEARANCES, IT NEEDS TO HAVE THE VENTILATION
EQUIPMENT OR AIR ONDITIONER TO KEEP THE SURROUNDING TEMPERATURE LOWER THAN THE
OPERATION TEMPERATURE.
THE FOLLOWING TABLE SHOWS HEAT DISSIPATION AND THE REQUIRED AIR VOLUME WHEN INSTALLING
A SINGLE DRIVE IN A CONFINED SPACE. WHEN INSTALLING MULTIPLE DRIVES, THE REQUIRED AIR
VOLUME SHALL BE MULTIPLIED BY THE NUMBER OF DRIVES.
REFER TO THE CHART (AIR FLOW RATE FOR COOLING) FOR VENTILATION EQUIPMENT DESIGN AND
SELECTION.
REFER TO THE CHART (POWER DISSIPATION) FOR AIR CONDITIONER DESIGN AND SELECTION.
IT IS THE MINIMUM DISTANCE REQUIRED FOR FRAME A~D. IF DRIVES ARE INSTALLED CLOSER THAN
THE MINIMUM MOUNTING CLEARANCE, THE FAN MAY NOT FUNCTION PROPERLY.
(BLUE ARROW) INFLOW
(FRAME A-E)
SINGLE DRIVE: INDEPENDENT INSTALLATION
(RED ARROW) OUTFLOW
(FRAME A-C)
PARALLEL MOUNTING IN HORIZONTAL
M31500
(Appearances shown in the following figures are only for reference)
HONEYWELL CORE DRIVE
762-0410—04
Fig. 1. Minimum Mounting Clearances.
Page 8
HONEYWELL CORE DRIVE
Table 4. Air Flow Requirements
Air flow rate for coolingPower Dissipation
Flow Rate (cfm)Flow Rate (m3/hr)
Power Dissipation (Watts)
Loss
External
Model 230Vac
Frame
External Internal Total External Internal Total
Size
(Heat
sink)
Internal Total
HCRDA0010A1000TA------403171
HCRDA0020A1000TA------6139100
HCRDA0030A1000TA14-1424-248145126
HCRDA0050A1000TA14-1424-2412757184
HCRDA0075A1000TA10-1017-1715893251
HCRDA0100B1000TB401454682492291101392
HCRDA0150B1000TB66148011224136403162565
HCRDA0200B1000TB5814739924124570157727
HCRDA0250C1000TC1661217828220302622218840
HCRDA0300C1000TC1661217828220302777197974
HCRDA0400C1000TC14612158248202688782221100
HCRDA0500D1000TD179302093045135512713111582
HCRDA0600D1000TD179302093045135515503551885
HCRDA0750E1000TE2287330138712451117624892251
HCRDA1000E1000TE2287330138712451120205742594
HCRDA1250E1000TE2467331941812454222425843026
Model 460Vac
HCRDC0010A1000TA------353267
HCRDC0020A1000TA------443175
HCRDC0030A1000TA------5843101
HCRDC0050A1000TA14-1424-249260152
HCRDC0075A1000TA10-1017-1713599234
HCRDC0100A1000TA10-1017-17165164439
HCRDC0150B1000TB40145468249227593380
HCRDC0200B1000TB66148011224136370194564
HCRDC0250B1000TB5814739924124370194564
HCRDC0300C1000TC992112016836204455358813
HCRDC0400C1000TC992112016836204609363972
HCRDC0500C1000TC12621147214362508454051250
HCRDC0600D1000TD179302093045135510564591515
HCRDC0750D1000TD179302093045135511636691832
HCRDC1000D1000TD179302093045135516396572296
HCRDC1250D1000TD186302163165136717879552742
The required airflow shown in chart is for installing single drive in a confined space.
When installing the multiple drives, the required air volume should be the required air volume for single drive multiplied
by the number of the drives.
Heat dissipation for each model is calculated by rated voltage, current and default carrier at full load, full speed, and
maximum ambient temperature
62-0410—048
Page 9
SPECIFICATIONS FOR WIRING TERMINALS
M31491
FIGURE 1
26.5 MAX.
8.2 MIN.
31 MAX.
70 MAX.
16
+0
-4
17 MAX.
65 MAX.
8.2 MIN.
28 MAX.
FIGURE 2
WIRE
HEAT
SHRINK
TUBE
RING LUG
FIGURE 3
13 MIN.
Table 5. Specifications for Wiring Terminals (refer to wiring diagram)
Use 600V, 90oC wired for UL installation for
HCRDA0400C1000T install in ambient temperature
exceeds 40oC.
4/0 AWG (107mm2)
Use the specified insulated heat shrink tubing that
complies with UL (600C, YDPU2). Must use 90oC wire
for HCRDA0600D1000T & HCRCD1250D1000T.
28 MAX.
8.2 MIN.
RING
LUG
28 MAX.
(Figure 1) The usage of ring terminals should comply
with the specifications shows in the figure.
(Figure 2) Grounding wire specification: 300MCM*2
[152 mm2*2]
Torque M8 180Kg-cm [156 lb-in.] (17.64Nm) (±10%)
(Figure 3) The figure shows the specification of
insulated heat shrink tubing that complies with UL
(600C, YDPU2)
1/0 AWG*2
2
(53.5mm
2/0 AWG*2
(67.4mm2*2)
3/0AWG*2
(85mm2*2)
M8 200kg-cm
(173 lb-in.)
(19.62Nm)
*2)
M8 200kg-cm
(173 lb-in.)
HONEYWELL CORE DRIVE
RING LUG
17 MAX.
HEAT
13 MIN.
SHRINK
48 MAX.
WIRE
TUBE
M31492
962-0410—04
Page 10
HONEYWELL CORE DRIVE
Table 6. Fuse and Non-fuse Circuit Breaker
Input Current I(A)Line FuseRecommended non-
Model 230V
Normal DutyHeavy Duty
I (A)Bussmann P/N
fuse breaker (A) **
HCRDA0010A1000T6.43.915JJN-1515
HCRDA0020A1000T9.66.420JJN-2020
HCRDA0030A1000T151230JJN-3030
HCRDA0050A1000T221640JJN-4040
HCRDA0075A1000T252050JJN-5050
HCRDA0100B1000T352860JJN-6060
HCRDA0150B1000T5036100JJN-100100
HCRDA0200B1000T6552125JJN-125125
HCRDA0250C1000T8372150JJN-150150
HCRDA0300C1000T10083200JJN-200200
HCRDA0400C1000T11699225JJN-225225
HCRDA0500D1000T146124250JJN-250250
HCRDA0600D1000T180143300JJN-300300
HCRDA0750E1000T215171400JJN-400400
HCRDA1000E1000T276206450JJN-450450
HCRDA1250E1000T322245600JJN-600600
Input current (A)Line FuseRecommended non-
Model 460V
Normal DutyHeavy Duty
I (A)Bussmann P/N
fuse breaker (A) **
HCRDC0010A1000T4.33.510JJS-105
HCRDC0020A1000T5.44.310JJS-1010
HCRDC0030A1000T7.45.915JJS-1515
HCRDC0050A1000T118.720JJS-2020
HCRDC0075A1000T1815.530JJS-3030
HCRDC0100A1000T201740JJS-4040
HCRDC0150B1000T252050JJS-5050
HCRDC0200B1000T332660JJS-6060
HCRDC0250B1000T393575JJS-7575
HCRDC0300C1000T4740100JJS-100100
HCRDC0400C1000T5847125JJS-125125
HCRDC0500C1000T7663150JJS-150150
HCRDC0600D1000T9174175JJS-175175
HCRDC0750D1000T110101250JJS-250250
HCRDC1000D1000T144114300JJS-300300
HCRDC1250D1000T180157300JJS-300300
** To comply with UL standard: Per UL 508, paragraph 45.8.4, part a:
The rated current of the breaker shall be 2~4 times of the maximum rated input current of AC motor drive.
NOTE: Fuses with specification smaller than the data in the following table are allowed
62-0410—0410
Page 11
Table 7. Dimensions for Frames A, B, C in mm [inch].
208/230Vac460VacHP Weight
HCRDA0010A1000T HCRDC0010A1000T 12.8A130
HCRDA0020A1000T HCRDC0020A1000T 22.8
HCRDA0030A1000T HCRDC0030A1000T 32.8
HCRDA0050A1000T HCRDC0050A1000T 52.8
HCRDA0075A1000T HCRDC0075A1000T 7.52.8
HCRDC0100A1000T 102.8
HCRDA0100B1000T104.6B190
HCRDA0150B1000T HCRDC0150B1000T 154.6
HCRDA0200B1000T HCRDC0200B1000T 205.6
HCRDC0250B1000T 25
HCRDA0250C1000T2510.5C250
HCRDA0300C1000T HCRDC0300C1000T 30 10.5/8.7
HCRDA0400C1000T HCRDC0400C1000T 40 10.5/8.7
HCRDC0500C1000T 509.4
Frame WHDW1H1D1*S1
(kg.)
[5.12]
[7.48]
[9.84]
D1*: Flange mounting Unit: mm [inch]
FRAME A
W
W1
CORE
250
[9.84]
[6.69]
320
[12.60]
[7.48]
400
[15.75]
[8.27]
SEE DETAIL A
170
190
210
116
[4.57]
173
[6.81]
231
[9.09]
HONEYWELL CORE DRIVE
236
45.8
D
[1.80]
77.9
[3.07]
92.9
[3.66]
6.2
[.24]
8.5
[0.33]
8.5
[0.33]
[9.29]
303
[11.93]
381
[15.00]
φ1φ2φ3
22.2
[.87]
22.2
[0.87]
22.2
[0.87]
D1
34
[1.34]
34
[1.34]
34
[1.34]
28
[1.1]
28
[1.10]
50
[1.97]
SEE DETAIL B
H
H1
CORE
1
1
3
2
SEE DETAIL B
3
DETAIL A (MOUNTING HOLE)
DETAIL B (MOUNTING HOLE)
Fig. 2. Frame A: Units in mm (inches). See also Table 7.
1162-0410—04
S1
S1
M31495
Page 12
HONEYWELL CORE DRIVE
M31497
SEE DETAIL A
SEE DETAIL B
DETAIL A (MOUNTING HOLE)
DETAIL B (MOUNTING HOLE)
S1
S1
W1
W
D1
D
H1
H
1
3
2
1
1
1
3
CORE
CORE
FRAME B
W
W1
CORE
CORE
SEE DETAIL A
H
H1
D
D1
FRAME C
SEE DETAIL B
1
3
1
2
1
3
Fig. 3. Frame B: Units in mm (inches). See also Table 7.
S1
DETAIL A (MOUNTING HOLE)
S1
DETAIL B (MOUNTING HOLE)
M31496
62-0410—0412
Fig. 4. Frame C: Units in mm (inches). See also Table 7.
Page 13
Tab le 8 . Dimensions for Frames D and E.
SEE DETAIL A
SEE DETAIL B
W1
W
D1
D
H1
H
DETAIL B
(MOUNTING HOLE)
DETAIL A
(MOUNTING HOLE)
S1
S1
1
1
3
3
2
2
M31498
CORE
CORE
208/230Vac460VacHP Weight
HCRDA0500D1000T50 35.5D330
HCRDA0600D1000T HCRDC0600D1000T 60 35.5
HCRDC0750D1000T 75 35.5
HCRDC1000D1000T 100 40.5
HCRDC1250D1000T 125 40.5
HCRDA0750E1000T
75 45.7
HCRDA1000E1000T100 46.2
HCRDA1250E1000T125 54.7
Frame WHDW1H1D1*S1
(Kg.)
[12.99]
E370
[14.57]
*D1 Flange mounting
FRAME D
688.3
[27.10]
715.8
[28.18]
275
[10.83]
300
[11.81]
285
[11.22]
335
[13.19
550
[21.65]
589
[23.19]
HONEYWELL CORE DRIVE
φ1φ2φ3
107.2
11.0
76.2
[4.22]
143.0
[5.63]
[0.43]
13.0
[0.51]
[3.00]
22.0
[0.87]
34.0
[1.34]
34.0
[1.34]
22.0
[0.87]
92.0
[3.62]
Fig. 5. Frame D: Units in mm (inches). See also Table 8.
1362-0410—04
Page 14
HONEYWELL CORE DRIVE
SEE DETAIL A
SEE DETAIL B
DETAIL B
(MOUNTING HOLE)
DETAIL A
(MOUNTING HOLE)
S3
D2
S1
S2
D1
D
W1
W
H1
H2
H3
H
M31499
1
1
2
2
2
2
3
3
CORE
CORE
FRAME E
Fig. 6. Frame E: Units in mm (inches). See also Table 8.
62-0410—0414
Page 15
KEYPAD BASICS
M31501
CORE
F1
F2
F3
F4
ESC
MENU
AUTO
HAND
STOP
RESET
FWD
REV
FWD
ENTER
ERR
COMM
RUN
RUN
REV
FWD
ENTER
ESC
MENU
Table 9. Descriptions of Keypad Functions
KeyDescriptions
This is the RUN/START command to the VFD when in Hand/Keypad control only.
HONEYWELL CORE DRIVE
RUN
STOP
RESET
It can operate the AC motor drive by the function setting and the RUN LED will be ON.
Stop Command Key. This key has the highest processing priority in any situation. Drive will
always STOP when this button is pressed.
The RESET key can be used to reset the drive after the fault occurs. For those faults that can’t
be reset by the RESET key, see the fault records after pressing MENU key for details.
This key controls the operational direction of the motor. NOT activated out of the box.
Press ENTER and go to the next submenu. If at the parameter level, press enter to modify and
press enter to save changes
ESC key function is to leave current menu and return to the last menu. It is also functioned as a
return key in the sub-menu.
Press menu to return to main menu. See main menu descriptions on following pages.
1562-0410—04
Page 16
HONEYWELL CORE DRIVE
HAND
AUTO
RUN
STOP
RESET
REV
FWD
HAND
AUTO
RIGHT and LEFT arrows to move the cursor with a numeric parameter, or to enter into and out
of menus.
UP and DOWN arrows used to change numeric parameter values, or cycle through menu
options.
Table 9. Descriptions of Keypad Functions
F1
F3
LEDDescriptions
Function Keys - will have different functions at different times as displayed on the screen. Used
F2
during Wizard Mode.
F4
Pressing the HAND key will take the VFD into Hand control, where the user can control the
motor Frequency and START and STOP.
Pressing this key will revert the VFD to remote/Automatic control from a remote speed and start
command source.
Table 10. Descriptions of LED Functions
Steady ON: operation indicator for the VFD, including DC brake, zero speed, standby, restart
after fault and speed search.
Blinking: VFD is decelerating to stop.
Steady OFF: VFD is not running.
Steady ON: VFD is stopped.
Blinking: VFD is in the standby status.
Steady OFF: VFD running.
Operation Direction LED (green: forward running, red: reverse running).
Blinking: drive is changing the operation direction.
HAND LED: When HAND LED is on (HAND mode); when HAND LED is off (AUTO mode).
AUTO LED: When AUTO LED is on (AUTO mode); when AUTO LED is off (HAND mode).
62-0410—0416
Page 17
START-UP WIZARD GUIDE
Table 11. Honeywell Commissioning Start-Up Wizard
Screen #Screen
Verbiage
1Boot
Screen
2Selection
Screen
3Select
Language
4Clock Time
and DATE
5Motor
Voltage
6Motor
Current
7Motor
FREQ
8Motor RPM Motor's rated RPM based upon Motor Name
9ACCEL
TIME
10DECEL
TIME
11, 12, 13PRESET
SPEED
1,2,3
14Analog
Input
15MIN
Frequency
16MAX
Frequency
17PRESS F4
to SAVE
ALL
Honeywell displayed for 3 secondsN/A
Choose how to interact with the VFD:
Recommendation: Press function key F4 to
start the wizard
Choose the keypad programming language
Use UP and DOWN arrows to change from
default. Press ENTER to accept change.
F1 BACK up one menu (SAME function
throughout WIZARD)
F4 Next Parameter (SAME function
throughout WIZARD)
Select the time (Military) HH:MM:SS and date
YY/MM/DD
Motor's rated voltage based upon Motor
Name Plate data
Motor's rated current in FLA, Full Load AMPs
based upon Motor Name Plate data. Do not
use motor service factor amperage for this
value.
Motor's rated frequency based upon Motor
Name Plate data
Plate data
The time required to accelerate from the
motor’s current speed reference to a new
speed reference
The time required to decelerate from the
motor’s current speed reference to a new
speed reference
Present Speed options. On digital input
closure the VFD will ignore the speed
reference from the analog input and will run at
the programmed speed.
Select the speed reference signal type. 0. 0-10V - Use AVI (Analog Voltage Input terminal)
The minimum frequency at which the motor
will operate
The maximum frequency at which the motor
will operate
Saves all parameter updates - VFD is ready
to operate
Screen DescriptionScreen options
HONEYWELL CORE DRIVE
F4: Initials the START UP WIZARD
Menu: redirects to MAIN MENU
ESC: redirects to MONITOR Screen
1. English
2. Spanish
3. Chinese
4. Portuguese
5. French
Use arrow keys to adjust. Press ENTER to save
changes, F4 to advance without changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save
changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save
changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save
changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save
changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save
changes.
Acceleration time is factory set for typical Fan and
Pump needs. Use arrow keys to adjust. Press ENTER
to save changes, F4 to advance without changes.
Decceleration time is factory set for typical Fan and
Pump needs. Use arrow keys to adjust. Press ENTER
to save changes, F4 to advance without changes.
With the use of MFI (Multifunction inputs) 1, 2, or 3 the
drive can be sent to the programmed speed on digital
input closure (Usage not required in the field). Adjust as
needed or press F4 to accept factory defaults.
1. 4-20mA - Use ACI (Analog current input terminals)
2. 2-10V - Use AVI
3. 0-20mA - Use ACI
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save
changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save
changes.
F1 will escape the user back to the Selection Screen
agai
n
F4 will save parameters and take the user to the display
screen
1762-0410—04
Page 18
HONEYWELL CORE DRIVE
Copy/Save
1.
2.
3.
Copy/Save
1.2009/05/04
2.
3.
File 1
1.Keypad->VFD
2.VFD->Keypad
3.
Quick Setup
1: V/F Mode
2: SVC Mode
3: My Mode
Keypad Lock
Press ENTER to
Lock Key
Keypad Lock
Press ESC 3sec
to UnLock Key
Displ Setup
1:Contrast
2:Back-Light
3:Text Color
MENU STRUCTURE
NOTE: This menu is accessed when the MENU button is pressed.
Start WizardRestart the Start-up Wizard: See Wizard instructions
Copy/Save1. Copy Parameters (4 parameter copies can be stored per keypad)
2. Press Enter on row 1-4, then select save to save parameters or load to upload
parameters to the connect VFD from the saved parameter list.
Fault Record1. Records the last 6 fault records
2. The first fault is the current or most recent fault
3. Select the fault code for time, date, frequency output, current, voltage, and DC Bus
Voltage at time of fault
4. Press ENTER to view a particular fault and scroll UP and DOWN to see data
Time Setup
Quick SetupQuick Settings Menu contains a list of optional parameter lists for different applications.
MY MODE, where frequency used parameters can be saved is located here.
STARTUP WIZARD parameters are also listed in this menu.
Table 12. Main Menu Structure.
Keypad LockThe keypad is locked when ENTER is pressed. When any key is pressed the following
LanguageUse the arrow key to move up and down to change the language selection
Display SetupDisplay Setup Menu allows the user to adjust the backlight time and contract. UP and
Advanced ParametersFull Parameter list setup. Refer to the Full User Manual on the accompanying CD or at
Splash ScreenSee Full User Manual for details
Main PageSee Full User Manual for details
PLC EnabledSee Full User Manual for details
Copy PLCSee Full User Manual for details
PC LinkSee Full User Manual for details or customer.honeywell.com
62-0410—0418
screen will appear.
DOWN arrows are used to adjust settings. ENTER must be pressed for changes to be
saved.
customer.honeywell.com for access
Page 19
HONEYWELL CORE DRIVE
1
2
3
1
2
3
Display error signal
Abbreviated error code
Display error description
WARNING CODES
Table 13. Warning Codes
Warning
CodeKeypad Display
CE01Comm. Error 1Modbus function code error
CE02Comm. Error 2Address of Modbus data is error
CE03Comm. Error 3Modbus data error
CE04Comm. Error 4Modbus communication error
CE10Comm. Error 10Modbus transmission time-out
CP10Keypad Time OutKeypad transmission time-out
SE1Save Error 1Keypad COPY error 1
SE2Save Error 2Keypad COPY error 2
SE3Save Error 3Keypad COPY error 3
oH1Over heat 1 warnIGBT over-heating warning
oH2Over heat 2 warnCapacity over-heating warning
PIDPID FBK ErrorPID feedback error
ANLAnalog lossACI signal error
uCUnder CurrentLow current
AUEAuto-Tune ErrorAuto tuning error
oSPDOver Speed WarnOver-speed warning
DAvEDeviation WarnOver speed deviation warning
PHLPhase Loss WarnPhase loss
ot1Over Torque 1Over torque 1
ot2Over Torque 2Over torque 2
oH3Motor Over HeatMotor over-heating
oSLOver Slip WarnOver slip
tUnAuto TuningAuto tuning processing
OPHLOutput PHL WarnOutput phase loss warning
EcidExCom ID failedDuplicate MAC ID error
ECLvExCom pwr lossLow voltage of communication card
EcttExCom Test ModeCommunication card in test mode
ECFFExCom Facty defFactory default setting error
ECiFExCom Inner errSerious internal error
EcioExCom IONet brkIO connection break off
ECEFExCom Link failEthernet Link fail
EctoExCom Inr T-outCommunication time-out for communication card and drive
ECCSExCom Inr CRCCheck sum error for Communication card and drive
ECrFExCom Rtn defCommunication card returns to default setting
ECo0ExCom MTCP overModbus TCP exceed maximum communication value
ECo1ExCom EIP overEtherNet/IP exceed maximum communication value
ECiPExCom IP failIP fail
EC3FExCom Mail failMail fail
EcbyExCom BusyCommunication card busy
1962-0410—04
Description
Page 20
HONEYWELL CORE DRIVE
FAULT CODES AND DESCRIPTIONS
Display error signal
1
2
3
1
Abbreviated error code
2
3
Display error description
NOTE: Additional details and screen shots of the error messages can be found in the full manual.
Fault
Keypad
Code
Fault Desc
ocAoc at accel Over-current during acceleration1. Short-circuit at motor output: Check for possible poor
(Output current exceeds triple rated current
during acceleration)2. Acceleration Time too short: Increase the Acceleration Time.
ocdoc at decel Over-current during decceleration1. Short-circuit at motor output: Check for possible poor
(Output current exceeds triple rated current
during decceleration.)
ocnoc at normal
SPD
ocSoc at stopHardware failure in current detectionReturn to the factory
GFF Ground fault Ground faultWhen (one of) the output terminal(s) is grounded, short circuit
occShort Circuit Short-circuit is detected between upper
ovAov at accel DC BUS over-voltage during acceleration
ovdov at decel DC BUS over-voltage during decceleration
Over-current during steady state operation1. Short-circuit at motor output: Check for possible poor
(Output current exceeds triple rated current
during constant speed.)
bridge and lower bridge of the IGBT module Return to the factory
(230V: DC 450V; 460V: DC 900V)
(230V: DC 450V; 460V: DC 900V)
Table 14. Fault Codes and Descriptions
Fault Descriptions
Corrective Actions
insulation at the output.
3. AC motor drive output power is too small: Replace the AC
motor drive with the next higher power model.
insulation at the output.
2. Decceleration Time too short: Increase the Decceleration
Time.
3. AC motor drive output power is too small: Replace the AC
motor drive with the next higher power model.
insulation at the output.
2. Sudden increase in motor loading: Check for possible motor
stall.
3. AC motor drive output power is too small: Replace the AC
motor drive with the next higher power model.
current is more than 50% of AC motor drive rated current, the
AC motor drive power module may be damaged.
NOTE: The short circuit protection is provided for AC motor
drive protection, not for protecting the user.
1. Check the wiring connections between the AC motor drive
and motor for possible short circuits, also to ground.
2. Check whether the IGBT power module is damaged.
3. Check for possible poor insulation at the output.
1. Check if the input voltage falls within the rated AC motor
drive input voltage range.
2. Check for possible voltage transients.
3. If DC BUS over-voltage due to regenerative voltage, please
increase the Decceleration Time or add an optional brake
resistor.
1. Check if the input voltage falls within the rated AC motor
drive input voltage range.
2. Check for possible voltage transients.
3. If DC BUS over-voltage due to regenerative voltage, please
increase the Decceleration Time or add an optional brake
resistor.
62-0410—0420
Page 21
HONEYWELL CORE DRIVE
NOTE: Additional details and screen shots of the error messages can be found in the full manual.
ovnov at normal
SPD
ovSov at stopHardware failure in voltage detection1. Check if the input voltage falls within the rated AC motor
LvALv at accel DC BUS voltage is less than
LvdLv at decel DC BUS voltage is less than
LvnLv at normal
SPD
LvSLv at stopDC BUS voltage is less than Pr.06-00 at stop 1. Check if the input voltage is normal
OrPPhase
lacked
oH1IGBT over
heat
oH2CAP over
heat
oH3Motor over
heat
PWR Power RST
OFFPower off
oLOver loadOverload, The AC motor drive detects
ot1Over Torque 1These two fault codes will be displayed when
ot2Over Torque
2
uCUnder
Ampere
LMIT Limit Error Limit error
DC BUS over-voltage at constant speed
(230V: DC 450V; 460V: DC 900V)
Pr.06-00 during acceleration
Pr.06-00 during decceleration
DC BUS voltage is less than
Pr.06-00 in constant speed1. Check if the input voltage is normal
Phase LossCheck Power Source Input if all 3 input phases are connected
IGBT overheating1. Ensure that the ambient temperature falls w ithin the specified
IGBT temperature exceeds protection level 2. Make sure that the ventilation holes are not obstructed.
1 to15HP: 90 oC
20 to 100HP: 100 oC4. Check the fan and clean it.
Heatsink overheating1. Ensure that the ambient temperature falls within the specified
Capacitance temperature exceeds 90oC
cause heatsink overheating.
Motor overheating1. Make sure that the motor is not obstructed.
The AC motor drive detects that the internal
temperature exceeds
Pr.06-30 (PTC level)
excessive drive output current.
output current exceeds the over-torque
detection level (Pr06-06 or Pr06-09) and
exceeds over-torque detection (Pr06-07 or
Pr06-10) and it is set to 2 or 4 in Pr06-05 or
Pr06-08.
Low current detection
Table 14. Fault Codes and Descriptions
1. Check if the input voltage falls within the rated AC motor
drive input voltage range.
2. Check for possible voltage transients.
3. If DC BUS over-voltage due to regenerative voltage, please
increase the Decceleration Time or add an optional brake
resistor.
drive input voltage range.
2. Check for possible voltage transients.
1. Check if the input voltage is normal
2. Check for possible sudden loa d
1. Check if the input voltage is normal
2. Check for possible sudden loa d
2. Check for possible sudden loa d
2. Check for possible sudden loa d
without loose contacts.
For models 40hp and above, please check if the fuse for the AC
input circuit is blown.
temperature range.
3. Remove any foreign objects from the heatsinks and check for
possible dirty heat sink fins.
5. Provide enough spacing for adequate ventilation.
temperature range.
2. Make sure heat sink is not obstructed. Check if the fan is
operating
3. Check if there is enough ventilation clearance for AC motor
drive.
2. Ensure that the ambient temperature falls within the specified
temperature range.
3. Take the next higher power AC motor drive model.
Check if the motor is overloaded, if yes, replace with next larger
drive
1. Check whether the motor is overloaded.
2. Check whether motor rated current setting (Pr.05-01) is
suitable
3. Take the next higher power AC motor drive model.
Check Pr.06-61, Pr.06-62, Pr.06-63.
2162-0410—04
Page 22
HONEYWELL CORE DRIVE
NOTE: Additional details and screen shots of the error messages can be found in the full manual.
cF1EEPROM
write Err
cF2EEPROM
read Err
cd1las sensor
Err
cd2lbs sensor
Err
cd3lcs sensor
Err
AFE PID Fbk
error
ACE ACI lossACI loss1. Check the ACI wiring
EFExternal
EF1 Emergency
bbBase block External Base Block1. When the external input terminal (B.B) is active, the AC
Pcod Password
ccod SW Code
CE1PC Err
command
CE2PC Err
address
CE3 PC Err data Illegal data valueCheck if the data value exceeds max./min. value
CE4PC slave
CE10 PC time out Modbus transmission time-out
CP10 Keypad time
dEb Dec Energy
S1S1-emergy
Fire On Fire Fire Mode
Uoc,
A, B, or C
Voc,
phase short
Woc
OPHL U, V, or W
Internal EEPROM can not be programmed. 1. Press “RESET” key to the factory setting
Internal EEPROM can not be read.1. Press “RESET” key to the factory setting
U-phase errorReboots the power. If fault code is still displayed on the keypad
V-phase errorReboots the power. If fault code is still displayed on the keypad
W-phase errorReboots the power. If fault code is still displayed on the keypad
PID loss (ACI)1. Check the wiring of the PID feedback
External Fault1. Input EF (N.O.) on external terminal is closed to GND. Output
fault
Emergency stop1. When the multi-function input terminals MI1 to MI6 are set to
stop
Password is locked.Keypad will be locked. Cycle power OFF and then ON to re-
error
ErrorSoftware code error
Illegal function codeCheck if the function code is correct (function code must be 03,
Illegal data address (00H to 254H)
Data is written to read-only address
fault
outKeypad transmission time-out
When Pr07-12 is not set to 0 and momentary
back
power off or power cut, it will display dEb
during accel./decel. stop.
stopEmergency stop for external safety
Phase A, B, or C short circuit
phase
lackedOutput phase loss (Phase U), (Phase V), (phase W)
Table 14. Fault Codes and Descriptions
2. Return to the factory.
2. Return to the factory.
please return to the factory
please return to the factory
please return to the factory
2. Check the PID parameters settings
2. Check if the ACI signal is less than 4mA
U, V, W will be turned off.
2. Give RESET command after fault has been cleared.
emergency stop, the AC motor drive stops output U, V, W and
the motor coasts to stop.
2. Press RESET after fault has been cleared.
motor drive output will be turned off.
2. Deactivate the external input terminal (B.B) to operate the AC
motor drive again.
enter the correct password. See Pr.00-07 and 00-08.