This document contains Honeywell proprietary information.
Information contained herein is to be used solely for the purpose
submitted, and no part of this document or its contents shall be
reproduced, published, or disclosed to a third party without the
express permission of Honeywell International Sàrl.
While this information is presented in good faith and believed to be
accurate, Honeywell disclaims the implied warranties of
merchantability and fitness for a purpose and makes no express
warranties except as may be stated in its written agreement with and
for its customer.
In no event is Honeywell liable to anyone for any direct, special, or
consequential damages. The information and specifications in this
document are subject to change without notice.
Copyright 2018 - Honeywell International Sàrl
2
Page 3
CONTENTS
Contents3
Chapter 1 - About this guide7
Chapter 2 - Overview13
Chapter 3 - ControlEdge PLC15
PLC I/O Network Topology15
Hardware Configuration of CPM22
Hardware Configuration of EPM27
Hardware Configuration of IO27
Device Replacement27
Chapter 4 - ControlEdge UOC33
Contents
UOC I/O Expansion Network Topology34
HSR Ring to 900 I/O34
Non-Redundant or Redundant Star to 900 I/O36
DLR Direct Connection to 900 I/O and EIP devices38
DLR ETAP Connection to 900 I/O and EIP Devices39
Non-Redundant Star to 900 I/O and EIP Devices41
Hardware configuration of UOC-CPM43
Hardware Configuration of UOC EPM46
Hardware configuration of I/O46
Device Replacement47
Chapter 5 - ControlEdge 900 Common Reference Information53
Installation53
Rack options53
Rack Types55
Rack installation64
Power Supply77
Environmental considerations81
Power Status Module82
3
Page 4
Contents
Expansion Processor Module82
Serial Communication Module84
ControlEdge 900 I/O87
Terminal block styles100
Terminal Block-to-Field (Signal) Wiring106
Chapter 6 - Wiring and cabling planning149
Electrical considerations149
Wiring and cabling distance guidelines153
Chapter 7 - Maintenance155
Safety considerations - PLAN AHEAD!155
Periodic checks157
Removal and Insertion Under Power (RIUP)157
Replacing the power supply158
Replacing an EPM160
Replacing an I/O module161
Spare parts and model numbers164
Chapter 8 - Diagnostics and Troubleshooting169
EPM Indicators169
Serial Communication Module Indicators171
I/O Indicators172
UIO Indicators176
Chapter 9 - Special Condition of Use and Approved Standards179
Approval Rating179
Special Condition of Use for Division 2/Zone 2 Hazardous Location
Installation179
For the United States179
For Canada180
For ATEX180
Approved Standards for Division 2/Zone 2 Hazardous Location181
US Approval Standards181
Canadian Standards181
European Standards (Zone 2)182
4
Page 5
Contents
CE LVD and EMC Compliance Standards182
UL Compliance Standards184
Appendix A - Installing RTP185
Overview of RTPs186
RTP Dimension187
Using the RTP to field wire the IOMs188
Using an RTP to field wire the UIO189
Using an RTP to field wiring the UAI191
Using Dual RTPs to field wiring the 16 Point AI196
Using an RTP to field wiring the 16 Point AC DI199
Using an RTP to field wiring the 16 Point DC DI202
Using Dual RTPs to field wiring the 32 Point DC DI204
Using an RTP to field wiring the 8 Point AC DO207
Using Dual RTPs to field wiring the 32 Point DC DO210
Using an RTP to field wiring 4 Channel Analog Output212
Using an RTP to field wiring the 8 Channel Analog Output214
Using an RTP to field wiring Relay Output217
RTP Cable wire positions, colors, and internal schematic219
Securing the RTP to the DIN rail228
5
Page 6
Contents
6
Page 7
CHAPTER
ABOUT THIS GUIDE
1
Scope
This guide describes how to set up the ControlEdge 900 platform and
install UOC or PLC.
Revision history
Revision DateDescription
ASeptember
2016
BNovember
2016
CApril 2017Update for the PLC R140 Release including:
DJune 2017Update for PLC. Adding the following items:
Initial release of document
Update for PLC R130.2 Release including:
lDelete the Self-powered 3–wire transmitter for UIO AI,
and updated Self-powered 4-wire transmitter for UIO AI.
lAdd 900RTP-H1xx RTP Cable
lAdd MOXA Unmanaged Ethernet Switch EDS-308 and
EDS-316-MM-SC.
lFive new I/O modules
lAdd new RTP and RTP Cables
lNew Terminal Blocks
lNew accessory parts
lAdd UIO wiring limitation and hardware version
comparison
lAdd RTP dimension for installing
ESeptember
2017
FNovemberUpdate for UOC network topologies
Added UOC information (for Experion R505 release)
7
Page 8
Chapter 1 - About this guide
Revision DateDescription
2017
GDecember
Update for ControlEdge PLC R150 Release including:
2017
lFive new I/O modules
lAdd new relay RTP
IJuly 2018Update DLR topologies for UOC
JNovember
Update for UOCOne Slot Rack added
2018
Update for ControlEdge PLC R151 Release including:
l8 channel Analog Output
l16 Channel DC/AC Digital Input
lQuadrature Input and Pulse Output
lSerial Communication Module
lEtherNet/IP
Intended audience
This guide is primarily intended for Honeywell field personnel who do
hardware planning, installation, operation, and maintenance for the
Honeywell ControlEdge™ 900 Controller.
Related documents
The following list identifies publications that may contain information
relevant to the information in this document.
ControlEdge PLC and ControlEdge RTU Network and Security
Planning Guide
ControlEdge EtherNet/IP User's GuideRTDOC-X548
PLC document
Set
RTDOC-X286
RTDOC-XX75
UOC Specific
Doc Name
Control Building User's GuideEPDOC-XX19
Firmware Manager User's GuideEPDOC-X404
Experion document set for deployments of
UOC
ControlEdge UOC Software Change
Notice
Control Builder Parameter References
Guides
UOC User's GuideEPDOC-X512
Control Builder Components TheoryEPDOC-XX16
EPDOC-X166
EPDOC-XX18
Introduction to ControlEdge Technology
ItemDescription
ControlEdge
PLC
ControlEdge
RTU
ControlEdge 900 controllers running the eCLR (IEC 61131-3)
execution environment with PLC software options configured with
ControlEdge Builder.
ControlEdge 2020 controllers running the eCLR (IEC 61131-3)
execution environment with RTU software options configured with
ControlEdge Builder.
9
Page 10
Chapter 1 - About this guide
ItemDescription
ControlEdge
UOC
ControlEdge 900 controllers running the Honeywell control execution
environment (CEE) configured with Experion Control Builder.
Special Terms
The following table describes the commonly used industry-wide and
Honeywell-specific terminology:
Terminology Description
AIAnalog Input
AOAnalog Output
CEEControl Execution Environment (Experion)
ControlEdge
900
ControlEdge
Builder
Control
Builder
A family of controller and I/O hardware which can be assembled to
create PLC or UOC systems.
Software configuration tool for PLC.
Experion Control Builder, configuration tool for UOC.
COTSCommercial Off the Shelf
CPMControl Processor Module (commonlyreferred to as the controller).
The ControlEdge 900 CPM, can be loaded with PLC firmware to
become the PLC or with UOC-CPM firmware to become the UOCCPM.
DCSDistributed Control System
DIDigital Input
DLRDevice Level Ring
DODigital Output
EPMExpansion Processor Module (used to connect multiple I/O racks to
the Control Processor Module)
Expansion
I/O rack
Ethernet/IPEtherNet/IP™ is a trademark protocol owned by ODVA.
I/O rack with EPM installed
10
Page 11
Chapter 1 - About this guide
Terminology Description
HMIHuman Machine Interface
HSRHigh Availability Seamless Redundancy
I/O RackControlEdge 900 form factor rack with 4, 8, or, 12 I/O slots and one
slot for non-redundant CPM or EPM.
PLCProgrammable Logic Controller
PSMPower Status Module
PSUPower Supply Unit
PWAPrinted Wiring Assembly
Redundant
ControlEdge 900 rack capable of hosting a redundant pair of CPMs.
Controller
Rack
RMRedundancy Module
RTPRemote Termination Panel
RIUPRemoval and Insertion Under Power
SCADASupervisory Control and Data Acquisition
UIO/UIOMUniversal Input/ Output (Module)
UOCUnit Operations Controller (Experion). This is a term used to refer to
the CPM when used as a controller in the Experion PKS Distributed
Control System.
11
Page 12
Chapter 1 - About this guide
12
Page 13
CHAPTER
2
OVERVIEW
Make sure all the hardware modules used in the system are installed
with the right firmware version and the engineering station has the
latest ControlEdge Builder. You can find the firmware and software
updates on http://www.honeywellprocess.com with valid credentials.
If the equipment is not used in a manner not specified by the
manufacturer, the protection provided by the equipment may be
impaired.
ControlEdge 900 hardware components can be deployed in two
distinct types of control systems.
n The ControlEdge Programmable Logic Controller (PLC)
n The ControlEdge Unit Operations Controller (UOC)
For Control Processor Module (CPM), both the UOC and PLC use it
but with different firmware loaded.
ControlEdge PLC can be deployed standalone or with a SCADA
system including Experion PKS. Within Experion, ControlEdge PLC
can also communicate in a peer relationship to the DCS controllers
such as C300 and ContorlEdge UOC.
ControlEdge UOC is a DCS controller always deployed within
Experion PKS.
This document has been divided into three major sections.
n ControlEdge PLC - contains details specific to PLC.
n ControlEdge UOC - contains details specific to UOC.
n ControlEdge 900 common reference information and other
chapters- contains details applicable to ControlEdge platform,
both PLC and UOC.
How to Use this Guide
The following table outlines the tasks involved in planning and
installing a Honeywell ControlEdge 900 Controller. The links provided
will navigate the user through those tasks.
13
Page 14
Chapter 2 - Overview
RevisionPLC SpecificUOC Specific
Check the model number of
See the section Spare parts and model numbers
the hardware components
Plan the architecture of the
system
Understand and plan the
See the section System
architectures planning
See the section System
architectures
See the section Hardware components
hardware components of the
system
Plan the wiring of the systemSee the section Wiring and cabling planning
Install the racks to house the
See the section Rack installation
system
Install and wire the I/O
See the section I/O Module installation and wiring
modules
Troubleshoot the systemSee the section Diagnostics and Troubleshooting
Remove or replace system
See the section Maintenance
components
Software configurationSee ControlEdge Builder
User’s Guide for PLC
systems.
See Control Building
User’s Guide for UOC
systems.
14
Page 15
CHAPTER
3
CONTROLEDGE PLC
Honeywell ControlEdge 900 family comprises a set of hardware and
software enabling users and OEMs to assemble a system that fits a
broad range of requirements. Any configuration can be readily
modified or expanded as requirements dictate.
This section provides the following information:
n PLC Expansion Network Topology
n Hardware Configuration of PLC-CPM
n Hardware configuration of EPM
n Hardware configuration of I/O module type
n Device Replacement
PLC I/O Network Topology
The ControlEdge PLC is configured with a non-redundant Control
Processor Module (CPM) or a redundant CPM. This section provides
details of each configuration.
ControlEdge PLC includes provisions for communication via Ethernet
with host systems such as the Honeywell Experion Human Machine
Interface (HMI) and other HMI software that support Modbus/TCP or
OPC UA protocols. The communication structure of the ControlEdge
PLC enables remote placement of input/output components, allowing
economies in cabling and wiring.
The Ethernet ports provide a layer of protection against cyber-attacks.
Multiple layers of protection are always considered good cybersecurity practice so using a firewall device configured to prevent
uncontrolled messages into the CPM is advised. The figures in this
manual assume the firewall is installed properly above the CPM's
Ethernet port(s) ETH1 and ETH2.
While the CPM has an embedded firewall, it is still recommended to
apply network firewall(s) to the control system as the application
requires.
Close all Ethernet ports into PLC-CPM except:
15
Page 16
n Modbus TCP Slave
n OPC UA Server
n HART IP
n ControlEdge Builder Controller Configuration protocol
n Privacy protocol
n SNTP (if NTP server is enabled)
n Destination DHCP for uplink
n Modbus Master and OPC UA Client that configured in the relative
function blocks
n CDA Responder
The port number can be configured in ControlEdge Builder, and see
the following table for the default port numbers.
Table 3-1: Default port numbers
Port number Port number typeDescription
41103Fixed destination portBuilder protocol
24558Fixed destination portDiscovery protocol
9050Fixed source portDiscovery protocol
123Fixed source portSNTP protocol
123Fixed destination portSNTP protocol
68Fixed destination portDHCP Client for uplink
500Fixed destination/source portIPSec for uplink (IKE ports)
4500Fixed source portIPSec for uplink(IKE ports)
55601Fixed destination portIPSec for uplink(CertMngr cleartext)
55602Fixed destination portIPSec for uplink(CertMngr encryption)
80Fixed source portIPSec for uplink (SCEP)
16
Page 17
I/O Network
In the I/O network used to connect the PLC-CPM to expansion I/O
racks via the EPM, two network topologies are supported in the
network: Ring and Star.
n Up to 144 I/O modules can be configured. Rationale: 12 racks x
12 modules per rack.
n Up to 4608, channels can be configured. Rationale: 12 racks x 12
modules per rack x 32 channels per module (applicable for certain
I/O module types only)
Figure 3-1: System architecture with non redundant PLC-CPM
17
Page 18
Figure 3-2: System architecture with redundant PLC-CPM
Physical cabling/connection of the nodes forming the ring, applicable
to the purple HSR/Ring topology on the right side of the above
illustration, must be connected as follows:
n CPM port 3 (ETH3) must be connected to CPM port 4 (ETH4) or
EPM port 2 (ETH2).
n CPM port 4 (ETH4) must be connected to CPM port 3 (ETH3) or
EPM port 1 (ETH1).
n EPM port 1 (ETH1) must be connected to EPM port 2 (ETH2) or
CPM port 4 (EHT4).
n EPM port 2 (ETH2) must be connected to EPM port 1 (ETH1) or
CPM port 3 (EHT3).
18
Page 19
Table 3-2: System component list for ControlEdge 900 PLC Hardware
Item
Component
Name
DescriptionSource
1I/O RackSystem may consist of 5 different types of
I/O racks:
l4-slot w/1 power supply
l8-slot w/1 power supply
l12-slot w/1 power supply
l8-slot w/redundant power supplies
l12-slot w/ redundant power upplies
Local I/O Rack
l1 I/O Rack
l1 CPM (for controller racks) or 1 EPM
(for I/O racks)
lUp to 4, 8 or 12 I/O modules
l1 or 2 Power Supplies
Optional second Power Supply and
Power Status Module (PSM) on 8and 12-slot I/O rack.
A Power Status Module (PSM) is
required with redundant power
supplies.
2Redundant CPM
Rack
3Expansion I/O
Rack (Optional)
l1 Redundant Controller Rack
l2 Power Supplies
l2 CPMs: Redundancy is provided by
two CPMs operating in a Redundant
Controller Rack; this rack has no I/O
modules.
l1 Filler block cover
Includes:
l1 rack
l1 Power Supply
lOptional second Power Supply and
Honeywell
Honeywell
19
Page 20
Item
Component
Name
DescriptionSource
Power Status Module (PSM) on 8and 12- slot I/O rack.
l1 Expansion Processor Module
(EPM)
lUp to 4, 8 or 12 I/O modules
lA Power Status Module (PSM) is
required with redundant power
supplies.
System may consist of 5 different types of
I/O rack:
l4-slot w/1 power supply
l8-slot w/1 power supply
l12-slot w/1 power supply
l8-slot w/redundant power supplies
4Human-Machine
Interface (HMI)
(Optional)
5Configuration
Station
6Un-managed
Ethernet
100Base-T
Switch
7Ethernet
100Base-T
l12-slot w/ redundant power upplies
PC links to Ethernet network, which
includes other HMIs, other ControlEdge
900 Controllers, and other networks
(including Internet). Typically includes HMI
operating software which includes
configuration tool from Honeywell.
HMI software
is available
from
Honeywell or
from thirdparty
supplier.
Connects from ETH1/ETH2 of the certain
CPM or network switch linking CPMs.
Configuration
software is
from
Honeywell.
(Only for Star topology) Enables
connection of the private Ethernet
100Base-T port on a CPM to the EPMs on
Expansion I/O rack. (The switch is not
required if there is no expansion I/O or
only one expansion I/O rack in the system.)
Third-party
suppliers or
Qualified
third party
devices
available
from
Honeywell
Enables inter-connection of severalThird-party
suppliers.
20
Page 21
Item
Component
Name
DescriptionSource
Switch or
Router/Firewall
8Ethernet CAT5
shielded cable
Fiber Optics
Cable
9Communications
cable
100Base-T Ethernet devices in an Ethernet
network. Devices include other
ControlEdge 900 Controller, HMIs, and
includes routers, servers, and other devices
in wider networks. Use of a properly
configured firewall provides a more robust
network limiting exposure to uncontrolled
network traffic.
Connects I/O expansion racks to CPMs
and/or to 100Base-T Ethernet switches.
The maximum length of the Ethernet cable
is 100m.
The maximum length of multi-mode fiber
optic cable depends on the specification of
network device, typically 5 Km with a MOXA
EDS-308-MM-SC. A qualified Fiber Optic
Convertor is required.
Ethernet able or Fiber Optic Cable
connects devices icn Ethernet Open
Connectivity network to SCADA
applications.
Third-party
suppliers
Third-party
suppliers
Following sections provide information about installing racks, EPM,
power supply and so on.
Table 3-3: Reference about installing racks, EPM, power supply and so on
ComponentsReference section
RacksFor information about options and types of racks, see the sections
Rack Options and Rack Types. For information about installing
Racks, see the section Rack Installation.
EPMFor information about installing EPM, see the section Expansion
Processor Module.
Power SupplyFor information about connecting to AC or DC power supply, see
the section Power Supply.
ConfigurationFor information about configuration, refer to the Software
Configuration Guide.
EnvironmentalFor information about environmental consideration to be taken
care, see the section Environmental Considerations.
21
Page 22
Hardware Configuration of CPM
Control Processor Module
A Redundant Controller Rack contains two CPMs. Either CPM can be
primary.
The CPM is shown in the following figure:
Figure 3-3: Control Processor Module
Table 3-4: CPM Components
Item Description
1Status LED indicator for the CPM. For more information, see CPM Indicators
section.
2Role LED indicator for the CPM. For more information, see CPM Indicators
section
3SD card slot: supports 32GB Class 6 / Class 10 industry standard, not hot-
swappable, maximum weight 3g (0.0066 lb, 0.1058 oz).
4Mode switch. For more information, see CPM mode switch section.
22
As indicated in this figure, CPM includes:
Page 23
Item Description
5ETH1 and ETH2 host ports to PC applications and/or other CPMs, or other
devices.
6ETH3 and ETH4 ports connect to the Ethernet ports of EPM, switch (for star
topology), or CPM.
7Ethernet LED status indicators for communications functions. For more
information, see CPM Indicators section.
CAUTION: Do not remove or insert the Ethernet connection when
the CPM is powered unless the area is known to be nonhazardous.
PLC-CPM mode switch
There are four mode switch positions on CPM: STOP, RUN, and two
REMOTE positions which are identical.
Figure 3-4: Mode switch on CPM
The switch can be rotated in a clockwise or counter-clockwise fashion
in order to engage the four switch positions. When the mode switch is
23
Page 24
in REMOTE position, the operating modes can be configured in the
Configuration tool.
For more information for the operating modes, see “Selecting
operating modes” in ControlEdge Builder User’s Guide.
ATTENTION: For redundant controller system, the position of
mode switch in primary PLC-CPM in this box determines the
system operating mode. If the mode switches on the primary
and secondary CPMs are in different positions, the system will
drop sync. Do not rotate the Mode switch when the CPM is
powered unless the area is known to be non-hazardous.
PLC-CPM Rotary Switch
PLC CPM system does not utilize the Rotary switches. They are set to
zero as indicated in the picture.
Figure 3-5: Control Processor Module
24
Page 25
PLC-CPM Indicators
The following diagram displays the location of the LED indicators on
the CPM. The following table explains the meaning of each LED state.
Figure 3-6: LED Indicators on PLC-CPM
25
Page 26
Table 3-5: LED Indications on PLC-CPM
Item LED
LED
State/Color
Description
1StatusOFFNo Power is applied to CPM.
On/GreenThe controller is working normally.
On/RedThe controller is stopped.
On/OrangeThe controller is in power-up process.
Blinking Red
The controller is running with error.
@ 1HZ
Blinking Red
@ 0.5HZ
The controller is accessible via online
communication, but no application is
loaded.
Blinking Red
IP address is in conflict.
@ 5HZ
Blink @ 1HZ /
The controller is upgrading firmware.
Green &
Orange
2RoleOFFIt is a non-redundant system or;
3, 5,
7, 9
Ethernet Port
Speed ( Upper
LED)
On/GreenThe controller is in primary role and the
system is synchronized, or;
On/OrangeThe controller is in secondary role and
the system is synchronized.
Blinking
Green @ 1HZ
Blinking
Orange @
The controller is in primary role and the
system is synchronizing.
The controller is in secondary role and
the system is synchronizing.
1HZ
Blinking
Green @
The controller is in primary role and the
system is unsynchronized.
0.5HZ
Blink Red @
0.5HZ
The controller is in secondary role and
the system is unsynchronized.
Yellow On/OffOFF for 10Base-T; ON for 100Base-TX.
26
Page 27
Item LED
LED
State/Color
Description
4, 6,
8,
10
Ethernet Port
Link/ Active (
Lower LED)
Green
On/Off/
Blinking
On for connection; Off for no
connection; and blinking for activity
Hardware Configuration of EPM
Refer to the common EPM section.
Hardware Configuration of IO
Refer to the I/O module type section.
Device Replacement
ATTENTION: If Secure Communication is enabled in the system, the relative
information of the new CPM should be updated in the IPsec configuration of the
PC installed the ControlEdge Builder and IPsec should be configured and
enabled on the new CPM. For more information, see "Chapter 9 " in the
ControlEdge PLC and ControlEdge RTU Network and Security Planning Guide.
Replacing a non-redundant or unsynchronized
primary PLC-CPM
ATTENTION: This procedure can only be performed while offprocess.
We recommend that you proceed with extreme caution
whenever replacing any component in a control system. Be
sure the system is offline or in a safe operating mode.
Component replacements may also require downloading
appropriate configuration data to the replaced component
through ControlEdge Builder.
Wear an ESD wrist strap and observe static precautions.
Before replacing a non-redundant or unsynchronized primary PLCCPM:
n It is recommended to upload and SAVE a copy of the
configuration, or ensure that a previously saved copy of the
27
Page 28
current configuration is available.
n It is recommended to bring the process to a safe and orderly
shutdown.
You will need a #2 Phillips screwdriver.
To replace a non-redundant or unsynchronized primary PLC-CPM
1. If a process is currently in operation, bring it to the safe mode, and
orderly shutdown if it is required.
2. Using an external (user-supplied) switch, disconnect the power
supply in the rack (associated with the CPM to be replaced) from
the source main power.
3. Observe where communications cables are plugged into the CPM,
and if necessary, tag them to identify their functions. Unplug all
communications cables.
4. At the top and bottom of the module, loosen the captured screws
that secure the module in the rack, and remove the CPM from the
rack. (Note that an up/down rocking motion helps with removal of
the module.)
5. Ensure that the new CPM is properly aligned with the slot guides,
insert the new CPM in the rack, and secure it in place with the
captured screws at top and bottom of the module.
6. Re-install communications cables.
7. Set the new CPM’s mode switch position to STOP (to prevent an
old/stale configuration from running and to enable firmware
update and configuration load).
8. Using the (user-supplied) switch, re-connect power supply in the
rack (associated with the new CPM) the source main power to the
rack.
9. Optional-for IPsec enable system, if Secure Communication is
enabled in the system, disable the IPsec in the PC installed the
ControlEdge Builder. See "Disable IPsec policy on PCs" in
ControlEdge PLC and ControlEdge RTU Network and Security
Guide for more information.
10. Use the ControlEdge Builder to load firmware to the new CPM to
match the version that was running in the removed CPM.
11. Use the ControlEdge Builder to download the configuration to the
new CPM.
12. Set the new CPM’s mode switch position to the desired operation
state.
13. Optional-for IPsec enable system, setup certificates and IPsec
policy in the CPM. See "Setup certificates and IPsec policy in
28
Page 29
PLC/RTU" in ControlEdge PLC and ControlEdge RTU Network and
Security Guide for more information.
14. Optional-for IPsec enable system, enable the IPsec in the PC
installed the ControlEdge Builder. See "Enable IPsec policy on
PCs" in ControlEdge PLC and ControlEdge RTU Network andSecurity Guide for more information.
Replacing a secondary PLC-CPM
ATTENTION: Replacing a secondary CPM can be performed
while on-process or off-process.
We recommend that you proceed with extreme caution
whenever replacing any component in a control system. Be
sure the system is offline or in a safe operating mode.
Component replacements may also require firmware update.
Wear an ESD wrist strap and observe static precautions
You will need a #2 Phillips screwdriver.
To replace a secondary PLC-CPM
1. [Optional] It is recommended to disable and prevent
synchronization first by issuing the redundancy disable
synchronization command from ControlEdge Builder.
2. Using an external (user-supplied) switch, disconnect the power
supply in the rack (associated with the CPM to be replaced) from
the source main power.
3. Observe where communications cables are plugged into the CPM
to be replaced, and if necessary, tag them to identify their
functions. Unplug all communications cables.
4. At the top and bottom of the module to be replaced, loosen the
captured screws that secure the module in the rack, and remove
the CPM from the rack. (Note that an up/down rocking motion
helps with removal of the module).
5. At the top and bottom of the module, loosen the captured screws
that secure the module in the rack, and remove the CPM from the
rack.
6. Ensure that the new CPM is properly aligned with the slot guides,
insert the new CPM in the rack, and secure it in place with the
captured screws at top and bottom of the module.
7. Re-install communications cables.
29
Page 30
8. Set the new CPM’s mode switch position to STOP (to enable
firmware update).
9. Using an external (user-supplied) switch, re-connect the power
supply in the rack (associated with the new CPM) to the source
main power.
10. Optional-for IPsec enable system, setup certificates and IPsec
policy in the CPM. See "Setup certificates and IPsec policy in
PLC/RTU" in ControlEdge PLC and ControlEdge RTU Network andSecurity Guide for more information.
11. Use the ControlEdge Builder to load firmware to the new CPM to
match the version that is running in the primary redundant
partner CPM.
12. Check the redundancy synchronization state by monitoring the
role LED of the primary or secondary CPM.
13. Switch the new secondary CPM’s mode switch position to match
the primary redundant partner CPM.
Replacing a primary PLC-CPM
ATTENTION: Replacing a synchronized primary CPM can be
performed while on-process or off-process.
Replacing an unsynchronized primary CPM can only be
performed off-process.
We recommend that you proceed with extreme caution
whenever replacing any component in a control system. Be
sure the system is offline or in a safe operating mode.
Component replacements may also require firmware update
and/or downloading appropriate configuration data to the
replaced component through ControlEdge Builder.
Wear an ESD wrist strap and observe static precautions.
You will need a #2 Phillips screwdriver.
Replacing an unsynchronized primary PLC-CPM
n It is recommended to first establish redundancy synchronization
between the redundant controllers (when possible) and follow the
procedure to replace a synchronized primary PLC-CPM below.
n When primary CPM on-process replacement is either not required
or not possible due to inability to synchronize the redundant
controllers, follow the off-process procedures in Replacing a non-
redundant PLC-CPM section.
30
Page 31
Replacing a synchronized primary PLC-CPM
1. [Optional] It is recommended to first transition the synchronized
primary CPM into the secondary role by issuing the redundancy
switchover command from ControlEdge Builder. This step {1}
transitions the synchronized secondary (redundant partner) CPM
into the primary role and {2} the CPM to be replaced restarts into
the secondary role.
2. Using an external (user-supplied) switch, disconnect the power
supply in the rack (associated with the CPM to be replaced) from
the source main power. If the optional switchover command was
not issued, this step transitions the synchronized secondary
(redundant partner) CPM into the primary role. and {2} the CPM to
be replaced restarts into the secondary role.
3. Observe where communications cables are plugged into the CPM
to be replaced, and if necessary, tag them to identify their
functions. Unplug all communications cables.
4. At the top and bottom of the module to be replaced, loosen the
captured screws that secure the module in the rack, and remove
the CPM from the rack. (Note that an up/down rocking motion
helps with removal of the module).
5. Ensure that the new CPM is properly aligned with the slot guides,
insert the new CPM in the rack, and secure it in place with the
captured screws at top and bottom of the module.
6. Re-install communications cables.
7. Set the new CPM’s mode switch position to STOP (to enable
firmware update).
8. Using an external (user-supplied) switch, reconnect the power
supply in the rack (associated with the new CPM) to the source
main power.
9. Optional-for IPsec enable system, setup certificates and IPsec
policy in the CPM. See "Setup certificates and IPsec policy in
PLC/RTU" in the ControlEdge PLC and ControlEdge RTU Networkand Security Guide for more information.
10. Use the ControlEdge Builder to load firmware to the new
secondary CPM to match the version that is running in the
primary redundant partner CPM.
11. Switch the new secondary CPM’s mode switch position to match
the primary redundant partner CPM.
12. Check the redundancy synchronization state by monitoring the
role LED of the secondary CPM.
31
Page 32
Following section provides information about replacing EPM, I/O
Module and Spare parts that are common to both PLC and UOC.
Table 3-6: Component Replacement Reference
Component
replacement
Reference
EPMFor information about replacing EPM, see the section EPM
device replacement.
I/O ModuleFor information about replacing I/O Module, see the section I/O
module replacement.
Spare partsFor information about replacing spare parts, see the section
Spare parts.
32
Page 33
CHAPTER
4
CONTROLEDGE UOC
ControlEdge UOC is DCS controller available with Experion. UOC
provides control for process units through level 0 I/O devices and
provides communication data access from level 1 and level 2 FTE
networks. Like other Experion DCS controllers, ControlEdge UOC
uses the Experion Control Execution Environment (CEE) as the
control engine and is configured with Experion Control Builder.
ControlEdge UOC uses many of the ControlEdge 900 platform
components. These include the following:
n CPM
n EPM (Firmware version 140 or later)
n ControlEdge 900 UIO Module
n Redundant Controller Rack
n I/O Controller Rack
n Power System
n RTP Kit
n Barrier Terminal Blocks
n Accessories (switches, jumpers, resistors)
Points to note specific to the use of the CPM as a UOC in Experion:
n SD card slot on CPM is currently not utilized and is reserved for
use in future.
n The CPM Mode switch is not utilized by UOC firmware. Honeywell
recommends that it be covered using (HW part number, if
available) after conversion of the PLC CPM into a UOC CPM.
However, the switch movement has no effect. For further
information on conversion, see UOC User’s Guide.
n Currently, of the ControlEdge 900 I/O modules described in this
document, the UOC supports only the UIOM. Support for
additional I/O card types will be extended in future releases.
This section provides information about following:
n UOC I/O Expansion Network Topology
n Hardware Configuration of UOC-CPM
33
Page 34
n Hardware configuration of EPM
n Hardware configuration of I/O module type
n Device Replacement
UOC I/O Expansion Network Topology
UOC has four Ethernet ports. Port 3 and 4 are used to connect to I/O
network, used for I/O. Table below shows UOC supported these
network topologies.
Topology TypeDescriptionSwitch Types
Topology 1HSR ring to 900 I/O.None
Topology 2Non-redundant star to 900 I/OGeneric
Topology 3Redundant star (via PRP) to 900 I/OGeneric
Topology 4DLR direct connection to 900 I/O and
EIP devices
Topology 5DLR ETAP connections 900 I/O and
EIP devices.
Topology 6Non-redundant star to 900 I/O and
EIP devices
Uplink and downlink subnets must be unique. The Downlink subnet
mask must be limited to the number of addresses expected in that
subnet.
For example, if a max of 64 addresses is expected, you could use a
mask of 255.255.255.192.
HSR Ring to 900 I/O
When connecting to ControlEdge 900 I/O only, a redundant ring
topology may be used. The ring type is HSR (High Availability
Seamless Redundancy). In this topology no third party redundancy
boxes are required. The UOC CPM connects directly, using its two
downlink Ethernet ports. Similarly, EPM modules connect directly
using their two Ethernet ports. When a UOC downlink is constructed
in this fashion, it is not possible to connect third party I/O, Devices or
PLCs. Only 900 I/O racks may be connected.
None
ETAPs for EPMs or nonDLR devices
Generic and stratix
34
When connecting CPMs and EPMs into an I/O network ring, the
numbered ports must be connected so that odd numbered ports
always connect to even numbered ports. This is shown in the
Page 35
following diagram for the case of a redundant UOC rack with two
UOC CPMs connecting to two, 4-I/O slot, non-redundant racks, each
with its own EPM. Also shown are the CPM’s connection of ETH1 to
the A, Yellow FTE network tree and ETH2 to the B, Green FTE network
tree.
Downlink I/O Network
Considerations for components that connect to a UOC’s downlink
HSR ring network are summarized in the following table.
Component
Type
ControlEdge
UOC CPM
Comments
The UOC CPM must be connected to the downlink I/O ring such that
even numbered ports always connect to odd numbered ports.
Important properties of UOC CPM communications on the downlink
network are configured on the UOC Platform Block in Control Builder.
This includes configuration of the UOC DHCP server for assigning
EPM IP addresses. It also includes setting the Downlink Network
Configuration to Ring-HSR.
ControlEdge
900 I/O
Racks with
An EPM must be connected to the downlink I/O ring such that even
numbered ports always connect to odd numbered ports. Before it is
inserted into its slot, the 100X rotary switch on the EPM board must
35
Page 36
Component
Type
EPMsbe set to indicate I/O network connectivity. This is done by setting it to
Comments
position 3. The IP address of the EPM is assigned by the UOC CPM
based on the module number set on the 10X and 1X rotary switches.
Ensure that the values within the range of 1-12 are used, as these are
the valid values. This too must be set before the EPM is inserted into
its slot.
Non-Redundant or Redundant Star to 900 I/O
When connecting to ControlEdge 900 I/O only, either a nonredundant or redundant star topology may be used. The network
redundancy type is PRP (Parallel Redundancy Protocol). In this
topology no third party redundancy boxes are required. The UOC CPM
connects directly, using its two downlink Ethernet ports. Similarly,
EPM modules connect directly using their two Ethernet ports. When a
UOC downlink is constructed in this fashion, it is not possible to
connect third party I/O, Devices or PLCs. Only 900 I/O racks may be
connected.
An example of a UOC and two 900 I/O racks on a downlink,
redundant, star network is shown in the following diagram. Also
shown are the CPM’s connection of ETH1 to the A, Yellow FTE
network tree and ETH2 to the B, Green FTE network tree.
36
Page 37
Redundant Star Network
The UOC does not support star topologies which mix redundant and
non-redundant connectivity. Downlink star networks must be set up
as exclusively redundant or exclusively non-redundant.
Considerations for components that connect to a UOC’s downlink
non-redundant or redundant star network are summarized in the
following table.
Component
Type
ControlEdge
UOC CPM
ControlEdge
900 I/O
Racks with
EPMs
Comments
Important properties of UOC CPM communications on the downlink
network are configured on the UOC Platform Block in Control Builder.
This includes configuration of the UOC DHCP server for assigning
EPM IP addresses. It also includes setting the Downlink Network
Configuration to “Non-redundant” in the case of a non-redundant star
network or “Star-PRP” in the case of a redundant star network.
Before it is inserted into its slot, the 100X rotary switch on an EPM
board must be set to indicate I/O network connectivity. For a nonredundant or redundant star network, this is done by setting it to
position 4. The IP address of the EPM is assigned by the UOC CPM
based on the module number set on the 10X and 1X rotary switches.
Ensure that the values within the range of 1-12 are used, as these are
the valid values. This too must be set before the EPM is inserted into
37
Page 38
Component
Type
Comments
its slot.
Unmanaged
Switches
900 I/O racks with EPM gateways have been qualified to
communicate with UOC through unmanaged switches. Managed
switches may not be used. For information on qualified switches see
the ControlEdge 900 Hardware and Installation Guide.
DLR Direct Connection to 900 I/O and EIP devices
DLR is layer 2 data link layer protocol that provides media
redundancy, faster network fault detection, and network fault
resolution in a ring topology. On network with only DLR devices, one
device act as an active ring supervisor and other devices form ring
nodes. DLR network contain a maximum 50 IP address nodes(This is
Honeywell specification).
DLR network should have at least one node configured as ring
supervisor. If there are multiple nodes configured as supervisor, then
the node with highest supervisor precedence value becomes active
supervisor, others will be backup Supervisors. Ring supervisor
connects to CPM through a third party devices.
The active ring supervisor cyclically sends out Beacon Frames and
Announce Frames on both ports. They are received on one port of a
ring node, processed and passed on to the next ring node via the
other port. By default the Beacon Frames are sent every 400
microseconds and the Announce Frames are sent every second.
38
An example of a DLR Ring network is shown in the following diagram
Page 39
Downlink DLR Network
DLR ETAP Connection to 900 I/O and EIP Devices
As an alternative to an HSR ring network with only ControlEdge 900
I/O, UOC can optionally be connected to an EtherNet/IP-based I/O,
device and PLC ring network through its ETH3 downlink port. Under
that configuration a UOC can communicate simultaneously with
ControlEdge 900 I/O and third party devices attached to the same
EtherNet/IP network.
One supported EtherNet/IP network topology is that of a DLR ring
which provides redundancy protection against a single network ring
fault. Installation and maintenance of a downlink EtherNet/IP network
must be done in accordance with the best practices of Ethernet
networking in general and EtherNet/IP in particular. In Experion
R510, UOCs will be directly connected to DLR network, and EPMs
must be connected to a DLR ring using redundancy boxes called
ETAPs (EtherNet/IP Taps). This requirement will be removed in a
future release.
In this topology, UOC connects directly to the ring through downlink
ports ETH3 and ETH4. EPMs connect through their ETH1 port with
ETH2 port disconnected
An example is shown in the diagram below.
DLR ETAP Connection to 900 I/O and EIP Devices
39
Page 40
Installation and maintenance practices for the UOC’s downlink
EtherNet/IP network generally follow those described in (EtherNet IPUser's Guide) for topology 2, “C300 Through EIM To EtherNet/IP”.
Additional considerations for components that connect to the
EtherNet/IP network are summarized in the following table.
Component
Type
ControlEdge
UOC CPM
ControlEdge
900 I/O
Racks with
EPMs
EtherNet/IP
TAPs (ETAPs)
Comments
The UOC CPM connects to a downlink EtherNet/IP network through
its ETH3 and ETH4 ports. Important properties of UOC CPM
communications on the downlink network are configured on the
UOC Platform Block in Control Builder. This includes configuration
of the UOC DHCP server for assigning EPM IP addresses. It also
includes Downlink Network Configuration to Non-redundant.
When 900 I/O is used, the EPM in the I/O rack serves the role of
communication gateway into the I/O rack. When an EPM is
connected to an EtherNet/IP network, its ETH1 port is connected to
the ETAP while its ETH2 port is left disconnected. Before it is inserted
into its slot, the 100x rotary switch on the EPM board must be set to
indicate the type of network connectivity in use. This is done by
setting it to position 4. The IP address of the EPM is assigned by the
UOC CPM based on the module number set on the 10X and 1x rotary
switches. These switches must also be set before the EPM is inserted
into its slot.
UOC systems use redundancy boxes called ETAPs for connectivity to
downlink DLR rings. For further information on the use of ETAPs, see
EtherNet IP User's Guide_EPDOC-X399-en-510A.pdf.
40
ControlLogix
PLC
EtherNet/IP
I/O and
Devices
UOC can communicate with Rockwell Allen Bradley ControlLogix
PLCs by passing instances of User Defined Types (UDTs). References
to ControLogix data are created in Experion Control Builder with the
aid of tag names provided by the Matrikon Allen Bradley OPC server
or by export of ControlLogix tag names from the Rockwell Allen
Bradley Studio 5000 designer tool. ControlLogix PLCs on a UOC’s
downlink EtherNet/IP network must always use static IP address
assignments. For information on the configuration of ControlLogix
communications, see EtherNet IP User's Guide_EPDOC-X399-en-510A.pdf.
UOC supports a set of EtherNet/IP devices with pre-populated CEE
block types in Experion Control Builder (CB). In addition, CB provides
the Parameter Definition Editor (PDE) tool which allows for the
integration of new EtherNet/IP I/O and devices independent of
Experion release. Although some third party EtherNet/IP devices
support IP address assignment from a network resident DHCP
server, this feature cannot be used when the EtherNet/IP network
Page 41
Component
Type
Comments
connects to UOC. All device IP addresses must be statically assigned.
For further information, see EtherNet IP User's Guide_EPDOC-X399-en-510A.pdf.
Allen Bradley
OPC Server
from
MatrikonOPC
Studio 5000
Logix
Designer
Software
The Rockwell Allen Bradley OPC Server from MatrikonOPC can be
installed on the Experion Server in systems which incorporate UOC.
The Matrikon OPC Server enables one of two methods whereby
ControlLogix tag names can be used to make UDT references in a
UOC strategy. For further information, see EtherNet IP User's Guide_EPDOC-X399-en-510A.pdf.
Studio 5000 Logix Designer Software from Rockwell Allen Bradley is
used in conjunction with UOC configurations to configure IP
addresses of Rockwell Allen Bradley EtherNet/IP devices. It can also
be used to export a file which defines ControlLogix tag names so that
they can be used in Control Builder to construct UDT data references
from UOC. For further information, see EtherNet IP User's Guide_EPDOC-X399-en-510A.pdf.
While using DLR (Device Level Ring) on Stratix 5700 Switch, DO NOT
CONNECT a DLR network to a Non-DLR port on the Switch. DLR
should be connected only to the DLR ports on the switch. Doing this
will result in the entire down link network going down. The recovery is
to only remove the DLR connection from the switch.
Non-Redundant Star to 900 I/O and EIP Devices
In addition to the DLR ring topology, the UOC can also connect to a
non-redundant star EtherNet/IP network through its ETH3 downlink
port. This allows it to communicate simultaneously with ControlEdge
900 I/O as well as EtherNet/IP-capable I/O, devices and PLCs.
Installation and maintenance of a downlink EtherNet/IP network
must be done in accordance with the best practices of Ethernet
networking in general and EtherNet/IP in particular.
In this topology, CPMs connect through their ETH3 downlink port
with ETH4 port disconnected. EPMs connect through their ETH1 port
with ETH2 port disconnected. An example is shown in the diagram
below.
41
Page 42
UOC CPM to 900 I/O and EIP Devices
Installation and maintenance practices for the UOC’s downlink
EtherNet/IP network generally follow those described in EtherNet IP
User's Guide_EPDOC-X399-en-510A.pdf for topology 2, “C300
Through EIM To EtherNet/IP”. Additional considerations for
components that connect to the EtherNet/IP network are
summarized in the following table. ControlLogix PLCs and
EtherNet/IP I/O and Devices are equivalent to those for DLR ring
networks.
42
Component
Type
ControlEdge
UOC CPM
ControlEdge
900 I/O
Racks with
Comments
The UOC CPM connects to a downlink EtherNet/IP network through
its ETH3 and ETH4port. Important properties of UOC CPM
communications on the downlink network are configured on the UOC
Platform Block in Control Builder. This includes configuration of the
UOC DHCP server for assigning EPM IP addresses. It also includes
Downlink Network Configuration to Non-redundant.
When 900 I/O is used, the EPM in the I/O rack serves the role of
communication gateway into the I/O rack. When an EPM is connected
to an EtherNet/IP network, its ETH1 port is connected to the switch
Page 43
Component
Type
EPMswhile its ETH2 port is left disconnected. Before it is inserted into its
Comments
slot, the 100x rotary switch on the EPM board must be set to indicate
the type of network connectivity in use. This is done by setting it to
position 4. The IP address of the EPM is assigned by the UOC CPM
based on the module number set on the 10X and 1x rotary switches.
These switches must also be set before the EPM is inserted into its
slot.
Unmanaged
Switches
Stratix
Switches
Table 4-1: Reference for installing racks, EPM, power supply and so on
ComponentsReference section
RacksFor information about options and types of racks, see the sections
EPMFor information about installing EPM, see the section Expansion
Power SupplyFor information about connecting to AC or DC power supply, see
900 I/O racks with EPM gateways have been qualified to
communicate with UOC through unmanaged switches. EPMs may not
be connected through managed switches.
EIP I/O, devices and PLCs may be connected to UOC through
qualified, Stratix managed switches. For further information on how to
deploy and configure Stratix switches, see EtherNet IP User's Guide_EPDOC-X399-en-510A.pdf.
Following section provides information about installing racks, EPM,
power supply and so on.
Rack Options and Rack Types. For information about installing
Racks, see the section Rack Installation.
Processor Module.
the section Power Supply.
ConfigurationFor information about configuration, refer to the Software
Configuration Guide.
EnvironmentalFor information about environmental consideration to be taken
care, see the section Environmental Considerations.
Hardware configuration of UOC-CPM
For more information refer to the UOC User’s Guide (PLC to UOC
conversion).
43
Page 44
Control Processor Module
A Redundant Controller Rack contains two CPMs. Either CPM can be
primary.
The CPM is shown in the following figure.
Figure 4-1: Control Processor Module
As indicated in this figure, CPM includes:
Table 4-2: Control Processor Module Components
Item Description
1Status LED indicator for the CPM.
2Role LED indicator for the CPM.
3SD card slot: Reserved for future use.
4Mode switch
5Ethernet port 1 (ETH1) and Ethernet port 2 (ETH2) for uplink connectivity to
an Experion FTE network. ETH1 should be connected to the FTE A (yellow) and
ETH2 should be connected to FTE B (green) networks. For more information,
see Experion documentation.
6Ethernet port 3 (ETH3) and Ethernet port 4 (ETH4) for connectivity to the
44
Page 45
Item Description
downlink network for ControlEdge 900 Expansion I/O racks or third party I/O.
Only ring network topologies are supported.
7Ethernet LED status indicators for communications functions. Refer to UOC
User’s guide for detailed information.
CAUTION: Do not remove or insert the Ethernet connection when
the CPM is powered unless the installation is in a hazardous area.
UOC-CPM mode switch
Although the Mode switch is used when the CPM is programmed as
PLC, it is not used when programmed as UOC.
Figure 4-2: UOC-CPM Rotary Switch
The FTE Device Index uniquely identifies the controller on the FTE
Network. The FTE Device Index is configured in two places. First, the
CPM rotary switches are used to set the FTE device index of the UOC.
Second, Experion PKS Control Builder is used to configure the FTE
Device Index in the UOC Platform Function Block.
Control Builder enforces the following:
n The primary controller (of a redundant controller pair) always
configured with an odd numbered Device Index.
n A non-redundant controller is only configured with an odd
numbered Device Index.
45
Page 46
n The secondary controller of a redundant controller pair is
configured with the even Device Index that is consecutive with its
primary partner’s Device Index (i.e. primary controller Device Index
plus 1)
Set the Device Index (FTE DEVICE INDEX) by turning the three rotary
decimal switches (range 001 to 509). The leftmost switch on top is
used for setting the hundreds digit, the right switch on top is used for
setting the tens digit, and the bottom switch sets the ones digit.
Example: For a redundant pair, the primary and secondary indexes
respectively could be 001, 002; 111, 112; 507, 508 and so on. In a
non-redundant setup, the index could be: 001 or 111 or 507 and so
on.
Failure to replicate the UOC Device Control Index according to their
Control Builder configured Device Indexes will lead to failure in
establishing Control Builder - controller communication thereby
preventing configuration load.
For in-rack redundancy, the left controller is recommended to be
configured as the odd device index and the right controller as the
event device index (of the consecutive device index pair).
Redundancy communication between a pair of redundant UOC is not
possible if their device indices are not set to a consecutive odd/even
pair.
UOC-CPM Indicators
For detailed information on UOC CPM firmware, on how to convert a
PLC CPM into a UOC CPM and on the behaviors of UOC CPM LEDs,
refer to the UOC User’s Guide.
Hardware Configuration of UOC EPM
Refer to the common EPM section.
Hardware configuration of I/O
Installation and Wiring
46
Currently, only the ControlEdge 900 UIO is supported. Refer to the
I/O Installation & Wiring section.
Page 47
Modules Types
Currently, only the ControlEdge 900 UIOM is supported. Refer to the
I/O module type section.
Device Replacement
CAUTION: Explosion hazard. Removal and Insertion Under Power
is not supported in Division 2/ Zone 2. CPM and/or EPM removal
under power is not supported. The up/down rocking motion
required to remove the module causes intermittent
communications to other modules resident in the same rack. It is
recommended that before removing an active CPM or EPM, the
user first disconnects the power supply in the rack (associated
with the CPM or EPM to be removed) from the source main
power.
Replacing a non-redundant or unsynchronized
primary UOC-CPM
ATTENTION: This procedure can only be performed while offprocess.
We recommend that you proceed with extreme caution
whenever replacing any component in a control system. Be
sure the system is offline or in a safe operating mode.
Component replacements may also require downloading
appropriate configuration data to the replaced component
through Control Builder.
Wear an ESD wrist strap and observe static precautions.
Before replacing a non-redundant or unsynchronized primary UOCCPM:
n Make sure all UOC configuration data and operator commands
are up to date within saved checkpoints or uploaded Control
Builder data. If not, save checkpoint, upload to Control Builder or
both.
n It is recommended to bring the process to a safe and orderly
shutdown.
You will need a #2 Phillips screwdriver.
47
Page 48
To replace a non-redundant or unsynchronized primary CPM:
1. If a process is currently in operation, bring it to the safe mode, and
orderly shutdown if it is required.
2. Using an external (user-supplied) switch, disconnect the power
supply in the rack from the source main power.
3. Observe where communications cables are plugged into the CPM
to be replaced, and if necessary, tag them to identify their
functions. Unplug all communications cables.
4. At the top and bottom of the module to be replaced, loosen the
captured screws that secure the module in the rack (associated
with the CPM to be replaced), and remove the CPM from the rack.
(Note that an up/down rocking motion helps with removal of the
module).
5. Configure the new UOC/CPM rotary device index switches to
match the old UOC/CPM rotary device index switches on the
removed module.
6. Ensure that the new CPM is properly aligned with the slot guides,
insert the new CPM in the rack, and secure it in place with the
captured screws at top and bottom of the module.
7. Re-install communications cables.
8. Using an external (user-supplied) switch, re-connect the power
supply in the rack (associated with the new CPM) to the source
main power.
9. Use the Firmware Manager to load firmware to the new CPM to
match the version that was running in the removed module.
10. Use the Control Builder to load the configuration to the new CPM.
48
Replacing a secondary UOC-CPM
ATTENTION: Replacing a secondary CPM can be performed
while on-process or off-process.
We recommend that you proceed with extreme caution
whenever replacing any component in a control system. Be
sure the system is offline or in a safe operating mode.
Component replacements may also require firmware update.
Wear an ESD wrist strap and observe static precautions.
You will need a #2 Phillips screwdriver.
To replace a secondary UOC-CPM:
Page 49
1. [Optional] It is recommended to disable and prevent
synchronization first by issuing the redundancy disable
synchronization command from Control Builder.
2. Using an external (user-supplied) switch, disconnect the power
supply in the rack (associated with the CPM to be replaced) from
the source main power.
3. Observe where communications cables are plugged into the CPM
to be replaced, and if necessary, tag them to identify their
functions. Unplug all communications cables.
4. At the top and bottom of the module to be replaced, loosen the
captured screws that secure the module in the rack, and remove
the CPM from the rack. (Note that an up/down rocking motion
helps with removal of the module).
5. Configure the new CPM rotary device index switches to match the
rotary device index switches on the removed module.
6. Ensure that the new CPM is properly aligned with the slot guides,
insert the new CPM in the rack, and secure it in place with the
captured screws at top and bottom of the module.
7. Re-install communications cables.
8. Using an external (user-supplied) switch, re-connect the power
supply in the rack (associated with the new CPM) to the source
main power.
9. Use the Firmware Manager to load firmware to the new CPM to
match the version that is running in the primary redundant
partner CPM.
10. Check the redundancy synchronization state by monitoring the
role LED of the primary or secondary CPM.
Replacing a primary UOC-CPM
ATTENTION: Replacing a synchronized primary CPM can be
performed while on-process or off-process.
Replacing an unsynchronized primary CPM can only be
performed off-process.
We recommend that you proceed with extreme caution
whenever replacing any component in a control system. Be
sure the system is offline or in a safe operating mode.
Component replacements may also require firmware update
and/or downloading appropriate configuration data to the
49
Page 50
replaced component through Control Builder. Wear an ESD
wrist strap and observe static precautions.
You will need a #2 Phillips screwdriver.
To replace an unsynchronized primary UOC-CPM:
n It is recommended to first establish redundancy synchronization
between the redundant controllers (when possible) and follow the
procedure to replace a synchronized primary UOC-CPM below.
n When primary CPM on-process replacement is either not required
or not possible due to inability to synchronize the redundant
controllers, follow the off-process procedures in Replacing a nonredundant UOC-CPM section.
To replace a synchronized primary UOC-CPM:
1. [Optional] It is recommended to first transition the synchronized
primary CPM into the secondary role by issuing the redundancy
switchover command from Control Builder. This step {1}
transitions the synchronized secondary (redundant partner) CPM
into the primary role and {2} the CPM to be replaced restarts into
the secondary role.
2. Using an external (user-supplied) switch, disconnect the power
supply in the rack (associated with the CPM to be replaced) from
the source main power. If the optional switchover command was
not issued, this step {1} transitions the synchronized secondary
(redundant partner) CPM into the primary role and {2} the CPM to
be replaced restarts into the secondary role.
3. Observe where communications cables are plugged into the CPM
to be replaced, and if necessary, tag them to identify their
functions. Unplug all communications cables.
4. At the top and bottom of the module to be replaced, loosen the
captured screws that secure the module in the rack, and remove
the CPM from the rack. (Note that an up/down rocking motion
helps with removal of the module).
5. Configure the new CPM rotary device index switches to match the
old CPM rotary device index switches
6. Ensure that the new CPM is properly aligned with the slot guides,
insert the new CPM in the rack, and secure it in place with the
captured screws at top and bottom of the module.
7. Re-install communcation cables.
8. Using an external (user-supplied) switch, reconnect the power
supply in the rack (associated with the new CPM) to the source
main power.
50
Page 51
9. Use the Firmware Manager to laod firmware to the new CPM to
match the version that is running in the primary redundant
partner CPM.
10. Check the redundancy synchronization state by monitoring the
role LED of the primary or secondary CPM.
To replace an unsynchronized primary CPM,:
Refer to Replacing a non-redundant UOC-CPM section for this
information.
Following section provides information about replacing EPM, I/O
Module and Spare parts that are common to both PLC and UOC.
Table 4-3: Reference for replacing EPM, I/O Module and Spare parts that are common
to both PLC and UOC
Component
replacement
Reference
EPMFor information about replacing EPM, see the section EPM
device replacement.
I/O ModuleFor information about replacing I/O Module, see the section I/O
module replacement.
Spare partsFor information about replacing spare parts, see the section
Spare parts.
51
Page 52
52
Page 53
CHAPTER
CONTROLEDGE 900 COMMON REFERENCE
5
INFORMATION
This section is applicable to both UOC and PLC systems and provides
the following information:
n Installation
n Wiring and cabling planning
n Maintenance
n Diagnostics and Troubleshooting
n Special Condition of Use and Approved Standards
Installation
The topics covered in this chapter are:
n See "Rack options" below for more information.
n See "Rack Types" on page55 for more information.
n See "Rack installation" on page64 for more information.
n See "Power Supply" on page77 for more information.
n See "Environmental considerations" on page81 for more
n See "ControlEdge 900 I/O " on page87 for more information.
n See "Terminal block styles" on page100 for more information.
n See "Terminal Block-to-Field (Signal) Wiring" on page106 for
information.
more information.
Rack options
I/O racks are available in 4-slot, 8-slot, and 12-slot versions and can
be utilized to house either a controller and I/O or as an I/O expansion
rack containing EPM and I/O.
Both 8-slot I/O rack and 12-slot I/O rack have two types of racks:
53
Page 54
n 8-slot or 12-slot I/O rack with non-redundant power supply
n 8-slot or 12-slot I/O rack with redundant power supply
A Power Status Module is required if the I/O rack with redundant
power supply is used.
Figure 5-1: Rack Options
54
Additionally, to eliminate single point of failure, you can also use the
dual rack redundancy solution.
As part of this solution you have two single slot racks deployed
separately in different areas. The distance between the two racks can
be 100 meters if you use a Cat6 shielded cable. Each one slot rack
hosts a power supply, a controller module, and a redundancy module
(Redundancy +Module (RM) is being introduced as part of the dual
rack redundancy solution). Another one slot rack with the same
modules is deployed at a different location. The connection between
the two racks is established using a specific Ethernet LAN cable.
Ethernet ports are present in both the Redundancy Modules (RM).
Page 55
You can also use two Fiber Optics modules between the Redundancy
Modules to extend the distance to 500m (Multi-mode Transmission
Distance) or 10Km (Single-mode Transmission Distance).
Rack Types
ControlEdge 900 Controller supports the following types of racks:
n Redundant Controller Rack
n Non- redundant Rack, containing 4, 8 or 12 I/O slots (Containing
n Single Controller Rack - Currently this option is supported only for
I/O slot numbers are assigned from left to right from 1 to n, where n
represents the maximum number of slots:
1 CPM or EPM and 4, 8, or, 12 I/O slots) – There are 3 types of I/O
racks.
Redundant Controller Rack is shown in the following figure.
Figure 5-3: Redundant Controller Rack Components
As indicated in Redundant Controller Rack Components section, the
Redundant Controller Rack includes:
ItemDescription
1Redundant Controller Rack
2Redundant Switchover Module Slot Filler
3Two CPMs (Redundant Primary and Secondary)
4Two Power Supplies
58
Page 59
One Slot Rack
59
Page 60
I/O rack
I/O rack can include a topology with; either a non-redundant power
supply or with redundant power supplies, accommodate a CPM or an
EPM, and additional input/output modules. The I/O rack inserted with
an EPM enables I/O modules to be located close to the field devices
and remote from the CPM.
Figure 5-4: I/O rack with non-redundant power supply
Figure 5-5: I/O rack with redundant power supplies
As indicated in I/O rack with non-redundant power supply section and
I/O rack with redundant power supplies section, the I/O rack includes:
60
Page 61
Table 5-1: I/O Rack Componets
Item Description
1Rack, available in 4-, 8- or 12-slot versions
2Power Supply
3CPM or EPM with Security Cover
4Grounding bars (for I/O wiring; optional; required for safety applications)
5Input/Output modules
6I/O Terminal Blocks
7Power Status Module (PSM) (required if using redundant power supply)
Rack orientation and mounting
Racks must be mounted horizontally and must never be mounted
with the backplane flat on a horizontal panel or tabletop. This allows
airflow and ventilation through the racks. The Environmental
specifications provided in this guide apply only when using the
recommended mounting configuration.
Rack dimensions, including overall dimensions and patterns for
drilling holes for mounting, are provided in Rack dimensions section
and Rack orientation and mounting section.
Figure 5-6: Rack dimensions
61
Page 62
Figure 5-7: Rack dimensions with redundant power supply
62
Page 63
Table 5-2: Rack size
I/O Slot OptionHeight Width Depth Comments
4-slot5.4"10.5"6.0"Rear mounting plate extends
height to 6.9” (175mm)
8-slot5.4"16.5"6.0"
8-slot with redundant
5.4"20.9"6.0"
power supply
12-slot5.4"22.5"6.0"
12-slot with redundant
5.4"26.9"6.0"
power supply
Redundant Controller
5.4"10.3"6.0"
Rack
1-slot5.4"5.9"6.0"
Recommended vertical spacing of racks, which is required for rack
ventilation and for routing wires, is shown in Vertical spacing of racks
(all models).
Figure 5-8: Vertical spacing of racks (all models)
63
Page 64
Rack installation
This section contains procedures for installing the racks. It is
recommended that the information in this section be reviewed before
beginning the installation to help to prevent errors and promote
efficiency.
Pre-requisites
Before the installation of the racks and modules, check that the
required tools and equipment’s are prepared. The dimension and
spacing details in the Rack orientation and mounting section should
also be checked.
Small/medium flat-tip or #2
Phillips or 3/16 inch slotted
screwdriver
Large (long blade)For use as I/O Module extractor
#10 or M4 screws, and with drillbit extender
Vacuum cleaner, brushFor use during and after drilling
Pen, ball-point or felt-tip, for
entering data on labels for I/O
modules)
For Barrier style Terminal blocks;
also for captured screws in
Terminal Blocks
For rack mounting
operations
For entering data on labels for I/O
modules
Multi-Meter (Volt/Ohms/Amps)For safety checks and for
equipment test
Soldering pencil or gun (for
attaching filter capacitors to I/O
wiring shields)
For attaching filter capacitors on
I/O wiring shields
Preparing the installation site
Table 5-4: Site and equipment preparation
Step Procedure
1Racks (4-, 8- and 12-slot)Mount racks section.
2Install (or verify correct installation of) enclosures for
CPM and ancillary equipment:
For more
information, see
Mount racks section
Installing I/O
65
Page 66
Step Procedure
For more
information, see
3
Install (or verify correct installation of):
lExternal disconnect switches
lFuses at the power source associated with input
sensor or output devices for I/O modules
4Arrange and organize items to be installed at or near
enclosures.
Mount racks
ATTENTION: Never mount racks vertically, or with the backplane
horizontal, or upside down.
Figure 5-9: Incorrect rack mounting direction
Installing I/O
modules section
66
CAUTION: Mark hole locations then either remove or cover any
equipment below to ensure metal chips generated from drilling /
tapping do not migrate causing electrical hazard or damage.
1. Mount the Rack in the enclosure by completing these steps:
a. Using the diagrams below as a guide, mark the locations for the
top holes in the rack.
Page 67
Dimensions and drill patterns are shown here:
b. Drill and tap for # 10 (or M4) screws.
c. Start the mounting screws (supplied by the user) in the drilled
holes.
d. Hang the Rack on the screws at the top.
e. Mark the locations for the bottom screws.
f. Drill and tap for # 10 (or M4) screws.
g. Remove the rack from the enclosure.
2. Aluminum grounding bars for the I/O module wiring are optional.
They can be mounted at the top, at the bottom, or at the top and
bottom of the rack, as indicated below. If grounding bars are
67
Page 68
included, attach them with two M3 screws (supplied with
grounding bars in plastic bag), as shown below.
ATTENTION: The plastic bag also includes four M4 screws
for attaching the grounding wire lugs, which are attached
later. Attach the M4 screws loosely to the grounding bars
for safe keeping.
3. Hang the rack in the enclosure on the top screws, as shown below.
Install the mounting screws in the bottom of the rack, then tighten
all screws.
CAUTION: Postpone this step until all components have
been installed in the rack.
68
Page 69
4. Repeat for each rack in the system.
Module Insertion
When inserting a module, carefully align the card with the rack. Press
the module to ensure that the backplane connector is fully inserted.
Secure the module to the rack using the top and bottom screws.
Ensure that the screws are properly secured.
Assembling the Redundant Controller Rack
To assemble the Redundant Controller Rack assembly:
69
Page 70
1. Carefully place the Power Supplies in the slots in the Rack.
2. Make sure that the connector at the back seats properly. Insert a
flat blade in the slots at the top and bottom of the power supply
cover while pulling backward to open the cover.
3. Fasten the screws (located in the face of the power supply) into
the tabs at the top and bottom of the rack. Set the Torque to 0.4 -
0.5 N.m (3.5 - 4.4 Lb-In). See the following figure for power supply
mounting details.
70
Page 71
ATTENTION: It is recommended each power supply should
be powered from a separate power source and a power
switch should be installed to allow for servicing of each
Processor/Supply separately.
4. Ensure that wiring to the Power Supply is disconnected from the
site source, and then connect the AC or DC wiring to the power
supply as shown below.
CAUTION:
Hazardous Voltage
Ensure that wiring to the Power Supply is disconnected
from the site AC source before installing wiring.
Do not remove Yellow/Green wire from grounding stud on
the power supply.
Do not connect PE Ground (Green) Wire directly to terminal
on Power Supply.
Failure to comply with these instructions could result in
death or serious injury.
71
Page 72
ATTENTION: The Yellow/Green wire is supplied with the
power supply. The nuts (w/star washers) for the grounding
stud are on the stud. For AC power supply use 3.0A, slowblow for 115V AC operation for each line; 2.5A, slow-blow
for 230V AC operation. For DC power supply use 7.0A slowblow. Do not apply AC voltages of any kind to DC power
supply to avoid the DC power supply being destroyed and
vise-versa.
Apply power. For AC power supply only, test voltages at the test
points provided on the face of the Power Supply.
72
ATTENTION: Test-points are electrically connected to the
backplane of the rack, and voltage is measured at the
backplane. Therefore, if the power supply is not properly
seated in the backplane connectors, no voltage will be
measured at the test points.
5. Carefully place the CPMs in the rack, adjacent to the Power
Supplies. Fasten them in place with captured screws at top and
bottom. Torque to 0.4 - 0.5 N.m (3.5 - 4.4 Lb- In).
Page 73
CAUTION: Ensure that AC power to the rack is disconnected.
Insert the Filler plate in the middle slot and attach with
screws at top and bottom.
6. Insert the Filler block cover in the middle slot and attach with
screws at top and bottom.
Assembling I/O rack
To assemble the I/O rack assembly:
1. Insert the power supply into left-most slot of the main I/O rack as
shown in the figure below. See Assembling the Redundant
Controller Rack section.
If the redundant power is used, the I/O rack will contain a second
smaller compartment, as shown in item 1 in the following figure.
Insert the first power supply in the larger compartment as shown, to
the immediate right of the plate dividing the two compartments.
2. If the redundant power is used, the I/O rack will contain a second
smaller compartment, this is where the secondary redundant
power supply is housed, as shown as item 1.
3. Insert the PSM between the two power supplies. Fasten it in place
with screws at top and bottom.
73
Page 74
4. Install EPM or CPM as required.
l Install EPM:
a. Set the EPM address and network topology for the I/O rack
using the rotary switches, as shown below.
TIP: Set the 10x and 1x switches to the two digit
address ranging from 01 to 99. The lower switch (10x)
is used to set the tens digit and the upper switch (1x)
sets the ones digit. A small slotted screwdriver works
well; avoid pencils. Set the network topology using the
100x switch. 3 is for Ring network topology and 4 is for
Star network topology.
74
b. Insert EPM to the right of the power supply, and secure it in
place with the two captured screws in the faceplate, as shown
below.
Page 75
c. Insert the Ethernet cables, and mount the security cover for
the EMP.
75
Page 76
d. Optional, mount a wire security seal. The user should get a
wire security seal themselves.
76
Page 77
l Install CPM: insert CPM to the right of the power supply, and
secure it in place with the two captured screws in the faceplate.
Set the mode switch, insert the SD card and the Ethernet
cables, and mount the security cover for the EMP. Optional,
mount a diameter 0.6 mm wire security seal. Themselves.
5. Repeat steps 1 through 4 for each I/O rack.
I/O modules are ready to be installed. See Installing I/O modules
section.
ATTENTION: Install a serial communication module in any
I/O slot and secure it in place with the two captured screws
in the faceplate. Up to six serial communication modules
can be added under one CPM.
Power Supply
Both AC power supply and DC power supply can be used in
Redundant Controller Rack, I/O rack and Expansion I/O rack.
77
Page 78
Figure 5-10: AC Power Supply
Figure 5-11: DC Power Supply
78
As indicated in the figures, the power supplies include:
Page 79
Table 5-5: Power Supply Components
Item Description
1Voltage test points
2AC/DC Input terminal block
3Wiring label
4Grounding lug (Reference; lug is not part of power supply; it is mounted to
bottom of rack.)
Table 5-6: Specification of power supplies
ItemAC power supplyDC power supply
Input voltage100-240 V AC24 V DC
Input voltage range90 to 264 V AC21 to 29 V DC
Output voltage5 V DC and 24 V DC5 V DC and 24 V DC
Input rating130 VA72.5 Watt
Output rating58 Watt58 Watt
Each power supply includes a non-field-replaceable internal fuse to
protect the supply under certain conditions. (External circuit breaker
must be added on both phases of L-N or L-L by the user for Division 2
and Zone 2, the circuit breaker is used for controlling power ON/OFF.)
Power consumption calculation for rack power supply
The following table outlines how to calculate power consumption for
a rack power supply. The wattage rating is 60W.
Table 5-7: Power consumption calculation for rack power supply
Module
CPM( )750mA0mA( )( 0 )
A: Enter
Quantity
B: Max
Current
@ 5V
C: Max
Current
@ 24V
D:
Calculate
5V current
(D = A * B)
E:
Calculate
24V
current (E
= A * C)
79
Page 80
E:
Calculate
24V
current (E
= A * C)
Module
A: Enter
Quantity
B: Max
Current
@ 5V
C: Max
Current
@ 24V
D:
Calculate
5V current
(D = A * B)
EPM( )500mA0mA( )( 0 )
PSM( )22 mA0 mA( )( 0 )
UIO( )380
0 mA*( )( 0 )
mA
UAI( )40 mA25 mA( )( )
DIM, 120/240 VAC, 16
Channel
DIM, AC/DC, 16 Channel( )130
( )130
mA
0 mA( )( 0 )
0 mA( )( 0 )
mA
DIM, 24 VDC, 32 Channel( )130
0 mA( )( 0 )
mA
DOM, 120/240 VAC, 8
Channel
DOM, 24 VDC, 32 Channel( )235
( )220
mA
0 mA( )( 0 )
0 mA( )( 0 )
mA
Relay Output, 8 Channel( )110
mA
AOM, 4 Channel
( )40 mA200
100
mA
( )( )
( )( )
mA
80
AOM, 8 Channel( )225
mA
350
mA
( )( )
HLAI, 16 Channel( )75 mA50 mA( )( )
DIM, Contact type, 16
Channel
Pulse/Frequency/Quadrature( )110
Serial Comm Module( )400
( )130
mA
mA
40 mA( )( )
250
( )( )
mA
0 mA( )(0)
mA
Redundancy Module( )1 mA0 mA( )(0)
Page 81
Module
A: Enter
Quantity
B: Max
Current
@ 5V
C: Max
Current
@ 24V
D:
Calculate
5V current
(D = A * B)
E:
Calculate
24V
current (E
= A * C)
Total mA
@ 5V - ( )
* The field device is powered by external 24 V power supply. For more information,
see Universal Input/Output Module on section.
Total mA @
24V - ( )
Environmental considerations
The product is only used indoors. The CPM must be mounted in
suitable equipment enclosures. That is, all components such as the
Redundant Controller Rack and I/O rack manufactured by Honeywell
must be mounted in approved furniture designed for industrial
applications.
Consideration should be given to the installation so that the potential
for the build-up of static electricity is minimized or eliminated.
Table 5-8: Environmental specifications
ItemDescription
Operating temperature0 to 60 °C
Storage and transportation
temperature
Ambient Relative Humidity5% to 95% relative humidity (non-condensing)
Vibration (Operative)IEC 60068-2-6 Sinusoidal (5 to 8.4 Hz) 3.5mm /
Shock (Operative)Half-sine, 15g peak / 11 ms duration, 6 directions
Protection against corrosive
atmospheres (for offshore
installations)
Altitude2000 meters
-40 to 85 °C
(8.4 to 150 Hz) 1.0 g; 1 octave/min, 10 cycles per
axis, 3 axes.
ANSI/ISA S71.04 Class G3
81
Page 82
Power Status Module
The Power Status Module (PSM), shown in the following figure, sits
between redundant power supplies on the I/O rack. It is a status
module for both power supplies and indicates which are powered, PS1 (left) or PS-2 (right) or both (typical).
When the status indicator for either or both of the power supplies is
lit, it is reporting that the status of the associated power supply is
good and that the outputs are within specified limits. When the status
is off, either the power supply is off or the voltages are out of
tolerance.
Figure 5-12: Power Status Module
Expansion Processor Module
EPM is shown in the following figure.
Figure 5-13: Expansion Processor Module
82
Page 83
It is installed in the expansion I/O rack and provides the link between
the CPM and remote I/O modules. Features at the front of the module
include:
Table 5-9: Expansion Processor Module Components
Item Description
1Status LED indicator for EPM functions. For more information, see EPM
Indicators section.
2Role LED indicator for EPM functions. For more information, see EPM
Indicators section.
3Ethernet 10/100 Base-T Ports; connect to the ports on other EPMs, CPM, or a
switch that connects to the CPM (for star topology).
4Ethernet LED status indicators for communications functions. For more
information, see EPM Indicators section.
CAUTION: Do not remove or insert the Ethernet connection when
the EPM is powered unless the area is known to be nonhazardous.
83
Page 84
Serial Communication Module
The rack-slot based serial communication module is used to
communicate to serial based controllers. The module can be used to
communicate to Modbus RTU Slave, Modbus RTU Master, Modbus
ASCII Slave, Modbus ASCII Master and user defined protocol type
devices. It contains one Multi-SPI at 4MBps of maximum
communication code rate. Also it supports short circuit protection
and over voltage protection. The galvanic isolation is 2000 VDC.
There are two DB9 connectors for RS232 and a dual-row terminal
connector for RS485 shown in the following figure.
As indicated in this figure, Serial Communication Module includes:
Table 5-10: Serial Communication Module Components
Item Description
1Module Status LED indicator for the Serial Communication Module. See
"Serial Communication Module Indicators" on page1 for more information.
2RS232 LED indicator for the Serial Communication Module. See "Serial
Communication Module Indicators" on page171 for more information.
3RS232 Ports (two)
4RS485 LED indicators for the Serial Communication Module. See "Serial
84
Page 85
Item Description
Communication Module Indicators" on page1 for more information.
5RS485 Ports (two)
CAUTION:Do not remove or insert the serial communication
connection when the Serial Communication Module is powered
unless the area is known to be non-hazardous.
Table 5-11: RS485 Pin definition
PinTypeDescription
T-OutputRS485 terminal resister
T+OutputRS485 terminal resister
AInput/outputRS485 A line (+)
BInput/outputRS485 B line (-)
Typically, short T+ and T-, and a 120-ohm resistor is activated between
A and B to revent signal reflections potentially interfering with
communications.
Table 5-12: RS232 Pin definition
85
Page 86
FigurePinDefinitionTypeDescription
1DCDInputDate carrier detect
2RXInputReceive data
3TXOutputTransimit data
4DTRInputData terminal ready
5GND_ISO1InputIsolated ground
6DSRInputData set ready
7RTSOutputRequest to send
8CTSInputClear to send
Male DB9
9RIInputRing Input
Application cable:
n RS232 port connect to Male DB9 connector:
As below figure shows, cable require Female-Female cross
connection:
86
n RS232 port connect to Female DB9 connector:
As below figure shows, cable require Female-Male direct
connection:
Page 87
The application cables are not supplied by Honeywell, and you
could prepare them by yourself.
ControlEdge 900 I/O
The configuration and operation of the I/O expansion network is
automatic, it is entirely under control of built-in private software that
resides in the CPM and in each EPM included in the ControlEdge 900
Controller system. The controller examines the control strategy stored
in its memory, verifies that the physical configuration (Rack Numbers
and I/O Module type- by Module Number) matches the stored control
strategy, and establishes communication with each of the I/O
modules in each of the I/O rack.
CAUTION: The ControlEdge 900 Controller I/O expansion
network is a private network and the switch used for the
interconnection of the CPM and EPMs must not be connected to
any other LAN or WAN. Likewise, no devices other than the
ControlEdge 900 Controller components should be connected to
the switch. Failure to comply will cause communication failures
on the I/O expansion network causing I/O modules to go in and
out of their failsafe settings.
Placing I/O modules in the racks
Each I/O module is placed in an I/O slot in a rack.
87
Page 88
Each slot in a rack includes a set of guides that locate the circuit
board in the rack, and a pin socket in the backplane that receives the
associated pin plug at the back of the I/O module.
At the front of each I/O module, a pin plug receives the associated
socket on the back of a terminal block. When the I/O module is
inserted into the rack and the terminal block is placed on the circuit
board, two captured screws in the terminal block are fastened to
metal tabs on the rack.
Figure 5-14: I/O module installation
88
CAUTION:
l Do not use an input/output terminal block if the terminal block
is damaged, if the door is missing, or if one or both mounting
screws are missing.
l Always tighten both terminal block screws to proper torque
settings before applying field power to the module. Torque to
0.4 - 0.5 Nm (3.5 - 4.4 Lb-In).
l Do not apply energized (“live”) field wiring to an input/output
module that is not installed in one of the racks in the system.
l Do not operate the module without a Protective Earth
connection on the rack.
Failure to comply with these instructions could result in death or
serious injury.
Page 89
I/O Module Specification
ControlEdge PLC supports various input/output modules. This
section provides technical information to configure ControlEdge PLC
IO Modules. The following IO modules are included:
n Universal Input/output module, 16 channel
n Universal AI – RTD,TC,V 8 Channel
n Analog Input High Level, 16 Channel
n Analog Output, 4 Channel
n Analog Output, 8 Channel
n Digital Input 120/240 VAC, 16 Channel
n Digital Input 24 VDC, 32 Channel
n Digital Input Contact, 16 Channel
n Digital Input 120/240 VAC, 125 VDC (16 Channel Isolated)
n Digital Output 120/240 VAC, 16 Channel
n Digital Output 24 VDC, 32 Channel
n Digital Relay Output, 8 Channel
n Pulse/Frequency/Quadrature, 4 Channel
See ControlEdge PLC Specification for details.
Universal Input/Output Module
The maximum current of the Universal Input/Output Module (UIO)
field side is 4.2 A.
One UIO module provides a 20-terminal block with 16 channels, and
it can be connected with two external 24 V DC power supplies. At least
one power supply must be connected.
See UIO module wiring section.
UIO module supports:
n 16 Channel, each channel can be configured for AI, AO, DI & DO
l Analog Input (AI), 0-20 mA
l Analog Input (AI) with open wire detection, 4-20 mA
l Analog Output (AO), 4-20 mA, See Field wiring for Analog
Output section for channel restrictions on the same UIO
module.
l Digital Input (DI) with line monitoring
l Digital Output (DO) with short circuit protection
89
Page 90
l Reverse polarity protection is limited to max of Field Supply
Voltage.
l Module I/O configuration and maximum power delivery by
I/Os, depends on number of channels, configuration Type and
the environment.
n 20 pin EURO style terminal block
n 20 position Barrier style terminal block
n HART Support (AI and AO)
n RTP support. See "Installing RTP" on page185 for more
information.
Figure 5-15: UIO module terminal block
90
Page 91
Universal Analog Input Module (UAI)
One UAI module provides a 20-terminal block with 8 channels, it
supports inputs mixed on a module. Each channel can be configured
as
n mV, V, mA
n T/C
n RTD
n Ohms
n Input impedance: 10 megohm for T/C and mV inputs; >1 megohm
for volts and 250 ohms for mA inputs;
n Isolation: 400 V DC for Channel to channel isolation and 1000 V
DC for channel to rack isolation;
n Noise Rejection
n Series Mode >60 dB
n Common Mode >130 dB at 120 V AC;
n A/D resolution: 15 Bits
n Update rate: 500 ms (Analog to Digital Converter per module)
n Power Supply Loading: 5 V: 40 mA maximum and 24 V: 25 mA
maximum
n 20 pin EURO style terminal block
n RTP support, but TC signal not support RTP solution. For more
information, see Using an RTP to field wiring the UAI section.
Digital Input Module (16 channels) - AC Voltage Type
The DI AC Voltage type module is a sinking type module and provides
a 20-terminal block with 16 channels. Its input voltage range is from
80V AC to 264 V AC.
DI AC Voltage type module supports:
n Isolation: Galvanic ally isolated in 2 groups of 8 channel to chassis
n ON Voltage Level: 75 V AC
n OFF Voltage Level: 20 V AC
n Input Impedance: 48 K ohms nominal
n Input Current: 1 mA nominal 120V AC, 60 Hz and 2 mA nominal
230 V AC, 50 Hz
n Minimum ON Current: 0.3 mA
n Maximum OFF Current: 0.2 mA
91
Page 92
n OFF to ON Response Time: 4 ms maximum with 1.5 lines cycle
maximum
n ON to OFF Response Time: 4 ms maximum with 2 lines cycle
maximum
n Power Supply Loading: 5 V: 130 mA max and 24 V: 0 mA
n RTP support. For more information, see Using an RTP to field
wiring the 16 Point AC DI section.
Digital Input Module (32 channels) - DC Voltage Type
The Digital Input Module-DC Voltage Type is sinking type module with
below features:
n Channel Density: 32 Channels with two groups of input, each with
a pair of terminals of connection to common
n Input voltage range: 10 V DC to 32 V DC.
n Isolation: Galvanic ally isolated in 2 groups of 16 points to rack (30
V DC maximum)
n ON Voltage Level: 9.5 V DC minimum
n OFF Voltage Level: 3.5 V DC maximum
n Minimum ON Current: 1.0 mA
n Maximum OFF Current: 0.7 mA
n OFF to ON Response Time: 5 ms maximum
n ON to OFF Response Time: 5 ms maximum
n Power Supply Loading: 5 V: 215 mA maximum and 24 V: 0 mA
n 20 pin EURO style terminal block
n RTP support, 2 RTP are needed for each module. For more
information, see Using Dual RTPs to field wiring the 32 Point DC
DI section.
n Channel 1, Channel 2, Channel 7 and Channel 8 are form C type,
provide both NO and NC contact
n Channel 3 ~ Channel 6 are form A type, provide NO contact.
n Input Voltage: 120/240 V AC or 30 VDC
n Output Device: Electromechanical relay; Specified relay life:
1000000 cycles
Page 93
n Current Rating:
l 4 A at 240 VAC or 30 VDC resistive load;
l 0.5 A at 240 VAC or 30 VDC incandescent lamp load
n OFF to ON response time: 11 ms Max
n ON to OFF response time: 8 ms Max
n Maximum Leakage Current: 1 mA @ 350 VDC
n Power Supply Loading: 5V- 110mA maximum; 24V-100mA
maximum
n Galvanic Isolation:
l Relay output contact to relay output contact
l Relay output contact to logic
Pulse Input/Frequency Input Module (4 Channels)
The 4 Channel Pulse/Frequency/Quadrature Module provides four
different functionalities in the form of Pulse Input, Frequency
measurement, Quadrature encoder input and Pulse Output. Each of
the 4 channels can be configured for any one of these four
functionalities; with the exception that quadrature encoder input (A
and B pulses) can be applied to only Channels 1 and 2 respectively.
When configured for quadrature, Channels 3 and 4 will still be
available for use.
The Pulse Output functionality uses the digital output available on the
module for outputting pulses. 4 Digital Outputs, Open collector, 5 to
24 V DC, 30 mA max used for fast signaling.
Pulse Input Type supports:
n Input Voltage: 0 V DC to 24 V DC
n ON Voltage Level: 3.0 V DC minimum
n OFF Voltage Level: 1.0 V DC maximum
n Input Impedance: 25K ohm
n Frequency: 10 KHz maximum
n Minimum Pulse Width: 3 μsec
n Pulse Counter: 32 bits
n Digital Output:
l If preset action ON, output turns ON for 1 second.
l If preset action OFF, output latches ON, and remains ON until
counter reset command.
Pulse Output supports:
93
Page 94
n Channel Used: Any one of the channels can be used for Pulse
Output. However, the use of a particular channel for outputting
pulses will render the particular input channel unusable for either
of pulse, frequency or quadrature input.
n Digital Output Type: Open Collector, 5 to 24V, 30 mA max
n Frequency Range: 25 Hz – 10 KHz
n Duty cycle: Always 50%
n Pulse Output Duration: Selectable CONTINUOUS or NUMBERED
PULSES.
Frequency Input supports:
n Input Voltage: 0 V DC to 24V DC
n ON Voltage Level: 3.0 V DC minimum
n OFF Voltage Level: 1.0 V DC maximum
n Input Impedance: 25K ohm
n Frequency: 10 Hz to 100 KHz
n Minimum Pulse Width: 500 μsec (10 Hz to 500 Hz) ; 50 μsec (10 Hz
to 5 KHz) ; 2.5 μsec (10 Hz to 100 KHz)
l The input signal will be rejected if it is below a selected pulse
width.
l The input signal whose pulse width is above the selected pulse
width must be within the frequency range specified, otherwise a
invalid value (NAN) will be shown and a fail-to-convert error
occurs.
94
n Digital Output ON if input frequency out of range, else OFF
Quadrature Input Supports:
n Channel Used: Only channel 1 and 2 can be used for quadrature
pulses A and B respectively. Index pulse is provided in addition.
n Input Voltage Range: Differential: -6 VDC to +6 VDC; Single-ended:
0 VDC to 24 VDC
n ON Voltage Level: Differential: 0.2 VDC minimum; Single-ended:
3.0 VDC minimum
n OFF Voltage Level: Differential: -0.2 VDC maximum; Single-ended:
1 VDC maximum
n Common Mode Voltage: +/- 12VDC
n Input Sensitivity: +/- 200mV
n Hysteresis: +/- 50mV
n Module powered encoder: 5V DC, 0.50A
n Frequency: 200 KHz maximum
Page 95
n Minimum Pulse Width: 2.25 μsec
n Quadrature Counter: 32 bits signed
n Quadrature Modes: For variable resolution there are three count
modes for the Pulse/Quadrature input: X1: rising edges of signal A
are counted (increment); falling edges of signal A (decrement) X2:
rising and falling edges of signal A are counted X4: rising and
falling edges of signals A and B are counted
n Quadrature LEDs: Two LEDs indicate UP and DOWN direction of
counting.
Analog Output Module (4 Channels)
n 4 channel 0-21.8 mA, range selectable analog output
n Load resistance: 750 ohms maximum
n Accuracy: 0.1% full scale
n D/A resolution: 12 Bitsat reference conditions
n Modules per rack: 10 max, up to 12 with product ambient
temperature de-rating. See the figure below:
Figure 5-16: De-rating of AO modules
n Update rate: 500 ms
n Minimum current sensing: >3.5 mA per output
n Isolation:
l 500V DC channel to channel
l 600V DC isolation from logic
n Output Verification: Readback to controller that indicates output
current flowing.
n D/A resolution: 12 bits
95
Page 96
n Configurable failsafe behavior between failsafe value and hold last
value.
n Failsafe Value: A user-configurable failsafe value to allow
predictable in the event of communication between the module
and the controller is interrupted or controller exception stop.
n Hold Last value: AO channel hold last value when module is in
failsafe state.
n Minimum settable failsafe value is EU Ex Low.
n AO channel of a module be in failsafe will output 0mA when the
failsafe value is set as EU Ex Low, and open wire or EU Ex Low
error will not be triggered in this case.
Analog Output Module (8 Channels)
The Analog Output module provides eight 0 to 21.0 mA outputs .
Outputs are isolated in groups of four with no isolation between
outputs in a group. All points are isolated from controller logic.
A green blinking status LED on the module indicates when the
module is being scanned. A red status LED when module or channel
diagnostics exist. A user specified failsafe value is supported to allow
predictable operation in the event communication between the
module and the controller is interrupted. Outputs are updated
synchronous with control execution.
n Outputs per module: 8, isolated in 2 groups of 4 outputs (1-4, 5-8)
n Current: 0 to 21.0 mA, selectable options: 0-20 mA and 4-20 mA
n Load resistance: 750 ohms max
n Galvanic Isolation: 500VDC group to group. Groups 1-4, 5-8
n Galvanic Isolation from logic: 500 VDC
n Accuracy: 0.1% full scale at reference conditions
n Modules per rack: 4 max when powered from internal 24V
backplane power
n Minimum current sensing: >0.5mA per output
n Output Verification: Feedback to controller to indicate output
current is flowing.
n D/A Resolution: 13+ bits (1 part in 13332)
n Power Supply Loading: 5V; 225 mA max 24V; 350 mA max
n Terminal Block: 36 Position – Euro style, (Model 900TCK-0001)
A DIP switch on the module selects the use of 24V from Rack PS
(internal) power or external loop power via a separate 24V DC power
source. The as-shipped (default) switch setting is external power.
96
Page 97
ATTENTION: When the DIP switch is set to be off , while the
external power is down, the open wire detection is not available.
n External Power Source requirement: Vin:18 to 36 VDC
n Current: 350 mA per module
Digital Input Module-AC DC Voltage type
The AC/DC Input Module provides 16 individually isolated, inputs that
are powered externally. Two terminals are provided for each circuit.
AC or DC power applied between the input terminals cause the inputs
to turn On.
There is a green LED state indicator for each channel on the module
to indicate when a digital input is ON. A green blinking status LED on
the module indicates when the module is being scanned. A red status
LED when module diagnostics exist. Logic in the controller allows the
state to be inverted when necessary. Requires Euro style 36-terminal
terminal block.
*Nominal times excluding controllers scan time and excluding
transmission time from module to rack. DC application must include
controller line filter setting of 50/60 Hz.
Figure 5-17: Active input De-rating table for AC/DC DI
High Level Analog Input Module (16 Channels)
16 user-configurable channel, each channel can be configured as
below type: 0-20 mA;4-20 mA;0-1 V;0-2 V;0-5 V;0-10 V;-1-1
V;-2-2 V;-5-5 V; -10-10 V
97
Page 98
n Input Impedance : >1 megohm for volts and 250 ohms for mA
inputs
n Galvanic Input Isolation:
l 400 VDC point to point, solid state switching;
l 1K VDC to logic.
n Noise Rejection:
l Series Mode >31dB
l Common Mode >90dB at 120VAC
n Over-range limit: +/- 10% for linear ranges
n Accuracy:
Factory configured accuracy = ± 0.1 % of range with below
Reference condition:
Temperature = 25 °C ± 3 °C (77 °F ± 5 °F)
Humidity = 45 % to 55 % RH non-condensing
Line voltage = Nominal ± 1 %
Source resistance = 0 ohm
Series mode and common mode = 0 V
Frequency = Nominal ± 1 %
n Temp. Effect on Accuracy: ±0.01% of full scale per degree Celsius
maximum
n A/D Converter: One per module
n A/D resolution: ±15Bits
n Update rate: 100ms (Analog to Digital Converter per module)
n Long term Stability: 0.1% per year
n Channel Configuration Data : Stored in non-volatile memory.
n Power supply loading: 5V ; 75mA max 24V ; 50mA max
Digital Input Module-Contact Type (16 Channel)
16 channel Contact Type:
n Inputs per module: 16 (single-ended)
n Voltage supplied: 15 V DC nominal
n Maximum Contact Resistance: 1000 ohms
98
Page 99
n Update Rate: 6 ms Maximum
n Switching current: 2.6mA norminal
n Galvanic Isolation: Between Field wiring (input or output) and
Module
n Power supply Loading:
l 5 V; 130 mA maximum
l 24v; 40 mA maximum
Digital Output Module (8 Channels) - AC Voltage
Type
DO AC Voltage type module supports:
l Channel Density: 8 Channels
l Output Type: Triac (Zero switching voltage)
l Input voltage range: 85 V AC to 240 V AC.
l Isolation: Galvanic ally isolated per Channel to channel and
channel to rack.
l Transient Overload Voltage Protection
l Maximum Load Current: 2 A per channel and 8 A max. per module
(Resistive load)
l OFF to ON Response Time*: 3 ms + 0.5 line cycle max
l ON to OFF Response Time*: 3 ms + 0.5 line cycle max
l Power Supply Loading: 5 V: 220 mA max and 24V: 0 mA
l Per channel Field-replaceable fuse support
l 20 pin EURO style terminal block
l RTP support. For more information, see Using an RTP to field
wiring the 8 Point AC DO section.
TIP:
*Excluding controllers scan time and excluding transmission
time from module to rack.
Digital Output Module (32 Channels) - DC Voltage
Type
The Digital Output Module – DC Voltage Type is current sourcing type
module.
DO DC Voltage type module supports:
99
Page 100
l Channel Density: 32 Channels
l Input voltage range: 10.5 V DC to 32V DC.
l Isolation: Galvanic ally isolated in 2 groups of 16 channel to rack
l Overload Current Protection: Active Current Limiting is integrated
into the output driver as 4 groups of 8 channels each. Power
cycling is not required to reset the module after a fault condition.
l Short Circuit: Whole group of 8 output channels will be switched
off if short circuit happens in any channel of the group. Power
cycling is not required to reset the module.
l Maximum Load Current:
o
0.5 A per channel;
o
6 A maximum per channel group ;
o
12 A maximum per module;
o
Resistive load 0.25 A per point incandescent lamp load (5 mH
maximum)
o
OFF to ON Response Time*: 6 ms
o
ON to OFF Response Time*: 6 ms
o
Power Supply Loading: 5 V: 235 mA max and 24V: 0 mA
o
20 pin EURO style terminal block
o
RTP support, 2 RTP are needed for each module. For more
information, see Using Dual RTPs to field wiring the 32 Point DC
DO section.
TIP:
*Excluding controllers scan time and excluding
transmission time from module to rack.
Terminal block styles
The terminal block is available in the barrier style, shown below at left
below, and the Euro style, shown at right. Not shown: a Euro style with
36 connections is also available for certain high capacity modules.
Figure 5-18: Terminal block Euro styles
100
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.