Honeywell CLIOL822A, CLIOL823A, CLIOLR822A, CLIOL821A, CLIOL824A Product Data

...
LonWorks Bus I/O Modules Product Data
FEATURES
Plug-and-play functionality for easy maintenance. Pluggable L
without rewiring. Further, the separate installation of terminal sockets and electronic modules lower risk of damage and theft in the construction phase.
Fast wiring with state-of-the-art push-in terminals (screw-
GENERAL
The CentraLine LONWORKS Bus I/O Modules communicate via the L These pluggable CentraLine L consist of a terminal socket and a removable electronic module, allowing the socket to be mounted and wired before the electronic module is installed. All such electronic modules can be swapped out without disrupting the power and bus connections: Simply unplug the “old” and insert the “new” module.
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet. Disconnect the power supply before you start to install
Do not reconnect the power supply until you have
Unused terminals must be closed (by completely
ONWORKS Bus I/O modules
WARNING
the control system. More than one disconnect switch may be required to de-energize the system.
completed the installation.
screwing in the terminal screws), thus preventing the accidental touching of “live” parts.
type terminals also available) and bridge connectors.
Wide range of sensors supported (NTC20kΩ, NTC10kΩ,
PT1000-1/-2, Johnson A99 PTC, NI1000TK5000, PT3000, Balco500, 0/2…10 V, 0/4…20 mA).
Binary input LEDs of the CentraLine L
Modules can be configured for status display (off / yellow) or alarm display (green / red) per channel.
Configurable safety position for outputs, in case of loss of
communication with the controller.
Max. wiring flexibility due to optional accessories like
auxiliary terminals and cross-connectors.
Can be mounted in small installation housings Flexible mix of L
your application requirements.
ONWORKS Bus I/O modules can be exchanged
ONWORKS Bus I/O
ONWORKS Bus I/O modules covering all
Software updates, configuration, and commissioning are all done automatically by the controller for all L Modules.
ONWORKS Bus I/O Modules may be used with any CPU
The L supporting L EAGLE, etc.).
Copyright © 2019 Honeywell GmbH ● All Rights Reserved EN0Z-0980GE51 R0119
ONWORKS Bus communication (e.g., the LION,
ONWORKS Bus I/O
LONWORKS BUS I/O MODULES – PRODUCT DATA
X
X
X
X
OVERVIEW
pluggable
ANALOG INPUT
pluggable
ANALOG OUTPUT
BINARY INPUT
pluggable
pluggable
RELAY OUTPUT
LonWorks
CLIOLR822A
CLIOLR824A
BUS MODULES
CLIOL821A
CONTROLLER
Fig. 1. Overview of CentraLine LonWorks Bus I/O Modules
Table 1. Overview of CentraLine LonWorks Bus I/O Modules
order number description
LonWorks Bus I/O Modules
L
CLIOL821A CLIOL822A CLIOLR822A CLIOL823A CLIOL824A CLIOLR824A
ONWORKS Bus Bus Analog Input Module (with 8 analog inputs)
L
ONWORKS Bus Bus Analog Output Module (with 8 analog outputs)
L
ONWORKS Bus Bus Analog Output Module (with 8 analog outputs and manual overrides)
L
ONWORKS Bus Bus Binary Input Module (with 12 binary inputs)
L
ONWORKS Bus Bus Relay Output Module (with 6 relay outputs)
L
ONWORKS Bus Bus Relay Output Module (with 6 relay outputs and manual overrides)
Terminal Sockets
XS821-22 XSU821-22 XS823 XSU823 XS824-25 XSU824-25
Push-in terminal socket for AI/AO modules (incl. bridge connector, swivel label) Screw-type terminal socket for AI/AO modules (incl. bridge connector, swivel label) Push-in terminal socket for BI modules (incl. bridge connector, swivel label) Screw-type terminal socket for BI modules (incl. bridge connector, swivel label) Push-in terminal socket for relay/floating output modules (incl. bridge connector, cross connector, swivel label) Screw-type terminal socket for relay/floating output modules (incl. bridge connector, cross connector, swivel label)
Table 2. Overview of auxiliary parts and spare parts
CLIOL822A CLIOL823A
XS821-22
XSU821-22
CLIOL824A
S823
SU823
order number description
XS814
Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block includes two groups with seven internally-connected push-in terminals.
XS815
20 Cross-Connectors for connection of six relay commons. One Cross-Connector is included in the Terminal Socket package.
XS816
10 Bridge Connectors. One Bridge Connector is included in the Terminal Socket package.
LonWorks Bus
S824-25
SU824-25
XAL10
10 Swivel Labels Holders (for attaching the application-specific label printed with CARE / COACH AX / COACH NX). One Swivel Label Holder is included in each Terminal Socket package. NOTE: Phased out.
NOTE: The inputs and outputs of all CentraLine analog and binary I/O modules are protected against short circuit,
EN0Z-0980GE51 R0119
24 VAC +20%, and 40 VDC. In the case of the relay outputs of other CentraLine I/O modules (i.e., relay output modules, floating output modules, and mixed I/O modules), appropriate fusing must be provided to ensure that permissible load currents are not exceeded. See also sub-section "Features" in section "Relay Output Modules" on pg. 14.
2
LONWORKS BUS I/O MODULES – PRODUCT DATA
Table 3. Pluggable LonWorks Bus I/O Module specifications
Module
no. of I/Os 8 analog inputs 8 analog outputs 12 binary inputs
characteristics Linear Graph, 0...10 VDC with pull-
CLIOL821A CLIOL822A, CLIOLR822A CLIOL823A CLIOL824A, CLIOLR824A
up, 0(2)…10 VDC without pull-up NTC20kΩ (-50…+150 °C, default) NTC10kΩ (-30…+100 °C) PT
1000-1
PT
1000-2
Johnson A99 PTC (-40…+120 °C)
NI1000TK5000 (-30…+130 °C)
PT
3000
BALCO Also configurable as: binary inputs Linear graph (0…10 V with pull-up)
Features:
16-bit resolution configurable offset per input auxiliary voltage: 10 VDC, I
5 mA
Analog Input Analog Output Binary Input Relay Output
6 relay outputs
relay outputs (default)
Features:
Changeover relays Voltage: 19…250 VAC,
1…29 VDC, P>50 mW
max. total current: 12 A current per relay: N.O.: 4(4) A
(AC) or 4(1) A (DC), N.C.: 2(1) A (AC) or 4(1) A (DC)
Safety position (remain, 0%,
100%)
yellow LED per output
Version with manual override (R):
1 switch per output auto feedback signal (mode +
value)
blinking in manual override
position
(-50…150 °C) (0…400 °C)
(-50…150 °C)
(-30…120 °C)
500
max
0…11 VDC / 1 mA Also configurable as: floating outputs or binary outputs (0 V / 10 V)
Features:
8-bit resolution (default) Safety position (remain, 0%,
50%, 100%)
red LED per output light intensity follows output
level in auto
Version with manual override (R):
1 potentiometer per output auto feedback signal (mode
=
+ value)
blinking in manual override
position
requiring a gold contact or open collector static binary input, (default: dry contact) Also configurable as: totalizers (20 Hz)
Features:
1 LED per input Color mode can be
set per input to OFF/yellow or green/red using CARE / COACH AX / COACH NX
ON: < 1.6 kΩ to GND
or < 2.5 V to GND, OFF: > 90 kΩ to GND or > 4 V to GND
Manual Overrides as per EN ISO 16484-2:2004
The manual override switches and potentiometers of the output modules support direct operation as per EN ISO 16484­2:2004, section 5.4.3 "Local Priority Override/Indicating Units." Specifically, the positions of the manual override switches and potentiometers directly control the outputs – independently of the controller and HMI. When a manual override switch or potentiometer is not in its default position ("auto"), the corresponding output LED will blink continuously, and the output module will send a feedback signal with the status "manual override" and the given override position to the controller (which will then also store this information in its alarm memory).
NOTE: When updating the firmware of output modules, their outputs are turned OFF – regardless of the position of their
manual override switches and/or potentiometers.
3
EN0Z-0980GE51 R0119
LONWORKS BUS I/O MODULES – PRODUCT DATA
GENERAL FEATURES
3
1
1:ABCDFERTAQWESDERT1
2:ABCDFERTAQWESDERT2
3:ABCDFERTAQWESDERT3
4:ABCDFERTAQWESDERT4 5:ABCDFERTAQWESDERT5
6:ABCDFERTAQWESDERT6
PRESS
S1 S2
71 COM a
72 COM b
73 24V
~
74 24V0
~
12345678
21
22 1 234
AUX
GND GND
9
10 11 12 13 14 15 16 17 18 25 26
4
3
2
1
0
F
E
D
5678
5
6
7
8
9
A
B
C
Honeywell
!
AI/AOV
7:ABCDFERTAQWESDERT7
8:ABCDFERTAQWESDERT8
PRESS
1 234 5 6 7 8 9 10 11 12
5678910
1234
BI
GND
13 14 15 16 17 18 19 20 21 22 23 24 25 26
5
S1 S2
71 COM a
3
2
1
0
F
72 COM b
E
D
~
73 24V
74 24V0
~
1
2
AAA
21
31
11
22
32
12
23
33
13
14 4424 5434 64 25
4
5
6
7
8
9
A
B
C
3
PRESS
Honeywell
0
AUTO
!
41
51
42
52
43
53
100
AAAAAAAA
616261
62
AUX
6363
GND GND
S1 S2
4
5
3
6
2
7
1
8
0
9
F
A
E
B
C
D
PRESS
5678
1234
5678
21
22 1 234
9
10 11 12 13 14 15 16 17 18 25 26
AI/AOV
PRESS
Honeywell
0
100
AUTO
!
S1 S2
PRESS
1234
21
31
11
22
32
12
23
33
13
14 4424 5434 64 25
6 7
Fig. 2. LonWorks Bus I/O Modules on DIN rails
Legend
1 Controller (e.g., LION, EAGLE, HAWK, etc.) 2 Cable (power, L
L
ONWORKS Bus I/O Modules
ONWORKS) connection from controller to
3 Swivel label holder 4 Cable connection between L
ONWORKS Bus I/O Modules
on separate DIN rails
5 Bridge connectors between L
on same DIN rail
6 Stopper (from 3
rd
-party supplier)
ONWORKS Bus I/O Modules
7 Auxiliary terminal packages
LEDs
Each CentraLine LONWORKS Bus I/O Module is equipped with:
one green power LED one yellow service LED
Overvoltage Protection
The inputs and outputs of all CentraLine analog and binary I/O modules are protected against short circuit, 24 VAC +20%, and 40 VDC. In the case of the relay outputs of other CentraLine I/O modules (i.e., relay output modules, floating output modules, and mixed I/O modules), appropriate fusing must be provided to ensure that permissible load currents are not exceeded. See also sub-section "Features" in section "Relay Output Modules" on pg. 14.
Service LED
Each LONWORKS Bus I/O Module is equipped with a yellow service LED (status: yellow/OFF) for easy diagnosis of failures.
LonWorks Service Button
Each LONWORKS Bus I/O Module is equipped with a L
ONWORKS service button.
Microprocessors
Each LONWORKS I/O Module is equipped with an FTT-10A transceiver (link power-compatible) and can thus be used with any L
ONWORKS controller.
42
Honeywell
!
11 12
71 COM a
4
5
3
6
2
7
1
8
0
9
F
A
72 COM b
E
B
C
D
~
73 24V
74 24V0
~
Honeywell
56
--1
--0
--AUTO
!
41
51
616261
42
52
62
43
53
6363
In addition to the main microprocessor, the L I/O Modules also have their own Neuron chip (3120).
System Constraints
Max. no. of I/O modules (any combination) per controller
Max. no. of I/O modules per row
Max. current (F1)
Max. current (F2)
Max. current (F3)
Max. row length
Max. distance between rows
Min. cross-section of GND (terminal 9) (protected by F2)
Table 4. System constraints
depends upon controller type
ONWORKS Bus
10
4 A
12 A
12 A
3 m
40 m
2
1.5 mm
EN0Z-0980GE51 R0119
4
Analog Input Module
V
V
LONWORKS BUS I/O MODULES – PRODUCT DATA
1
3
2
Fig. 3. CLIOL821A LonWorks Bus AI Module (shown with
Legend
1 LONWORKS service button S1 2 Service LED 3 Power LED NOTE: The hex switch S2 (located next to the L
The CentraLine L analog inputs, is installed with the XS821-22 or XSU821-22 Terminal Socket.
service S1) has no function in combination with a L
ONWORKS Bus I/O module. It is used with Panel
Bus I/O modules, only.
Fig. 4. Analog input low impedance (input circuit for
PT1000, Johnson A99 PTC, Balco500, PT3000,
NI1000TK5000, slow binary input)
terminal socket)
ONWORKS
ONWORKS Bus Analog Input Module, with 8
10 VDC
24.9 kOHM
AI
RTD
GND
AI
V
i
199.9 kOHM
10 VDC
24.9 kOHM
AI
GND
199.9 kOHM
(8.9 VDC IF CONNECTION INTERRUPTED)
V
i
Fig. 6. Analog input impedance setpoint (input circuit for
NTC10kΩ, NTC20kΩ, wall module setpoint)
COM
71
A
COM
72
B
24
73 77
V~ 24
74
V~0
V
AUX
V
AUX
21
22101
GND GND GND GND GND GND GND GND GND GND
9
AI1 AI2
11
12
AI3
AI5 AI6
AI4
3
13
5156167178
4
14
2
AI8
AI7
18 25 26
Fig. 7. CentraLine LonWorks Bus Analog Input Module
(schematic)
Features
0…10 VDC, 2…10 VDC without pull-up 0…10 VDC with pull-up (linear graph, e.g., used for wall
module connection)
0/4…20 mA, needs 499 Ω resistor in parallel NTC20kΩ (-50…+150 °C, default) NTC10kΩ (-30…+100 °C) PT1000-1 (-50…+150 °C) PT1000-2 (0…+400 °C) NI1000TK5000 (-30…+130 °C) PT3000 (-50…+150 °C) BALCO500 (-30…+120 °C) Binary input 16-bit resolution Configurable offset per input Auxiliary voltage: 10 VDC, I Sensor failure detection
MAX
= 5 mA
COM
COM
24
24
75
A
76
B
~
78
~0
GND
Fig. 5. Analog input high impedance (input circuit for
voltage input for active sensors)
5
EN0Z-0980GE51 R0119
LONWORKS BUS I/O MODULES – PRODUCT DATA
A
AI5AI6AI7A
V
V
CLIOL821A ANALOG INPUT MODULE
COM
71 71
A
COM
72 72
B
24
73 7377
V~ 24
74
V~0
V
AUXVAUX
21
22
GND GNDGND GNDGNDGNDGNDGND GND GND GNDGND
9 925
10 1026
OPT. AUX. TERMINAL MODULE XS814
A1 A2A3A4
AI1 AI2
1
2
11
12
AI3
3
13
A5 A6
AI4
4
14
5
15616
7 B1 B
7178
18
COM
75
A
COM
76
B
24 V~
24
78
~0
I8
74
COM
A
COM
B
24 V~
24
~0
CLIOL...
SHIELD INTERNALLY CONNECTED TO DIN RAIL
LEGEND:
THIN LINES
THICK LINES
DASHED LINES
EXTERNAL
GROUND
REQUIRED TO
POWER
EXTERNAL
DEVICES
(24 VAC)
F1
F2
3 3
2 2
ACTIVE SENSOR 1: 24V POWER 2: 0...10 VDC SIGNAL 3: GND (24V 0)~~
F1
F2
MAX. 4 A
MAX. 12 A
MIN. 0.75 mm
MIN. 1.5 mm
SELECTED INTERNAL CONNECTIONS
Fig. 8. CLIOL821A LonWorks Bus AI Module, wiring example 1: Active sensor and potentiometer
1 1
AUX. VOLTAGE + POT. 1: SIGNAL 2: GND 3: 10 VDC AUX.
2
2
EN0Z-0980GE51 R0119
6
Loading...