Honeywell CLIOL822A, CLIOL823A, CLIOLR822A, CLIOL821A, CLIOL824A, CLIOLR824A Product Data
Specifications and Main Features
Frequently Asked Questions
User Manual
LonWorks Bus I/O Modules Product Data
FEATURES
Plug-and-play functionality for easy maintenance.
Pluggable L
without rewiring. Further, the separate installation of
terminal sockets and electronic modules lower risk of
damage and theft in the construction phase.
Fast wiring with state-of-the-art push-in terminals (screw-
GENERAL
The CentraLine LONWORKS Bus I/O Modules communicate
via the L
These pluggable CentraLine L
consist of a terminal socket and a removable electronic
module, allowing the socket to be mounted and wired before
the electronic module is installed. All such electronic modules
can be swapped out without disrupting the power and bus
connections: Simply unplug the “old” and insert the “new”
module.
Risk of electric shock or equipment damage!
► Do not touch any live parts in the cabinet.
► Disconnect the power supply before you start to install
► Do not reconnect the power supply until you have
► Unused terminals must be closed (by completely
ONWORKS Bus.
ONWORKS Bus I/O modules
WARNING
the control system. More than one disconnect switch may
be required to de-energize the system.
completed the installation.
screwing in the terminal screws), thus preventing the
accidental touching of “live” parts.
type terminals also available) and bridge connectors.
Wide range of sensors supported (NTC20kΩ, NTC10kΩ,
Push-in terminal socket for AI/AO modules (incl. bridge connector, swivel label)
Screw-type terminal socket for AI/AO modules (incl. bridge connector, swivel label)
Push-in terminal socket for BI modules (incl. bridge connector, swivel label)
Screw-type terminal socket for BI modules (incl. bridge connector, swivel label)
Push-in terminal socket for relay/floating output modules (incl. bridge connector, cross connector, swivel label)
Screw-type terminal socket for relay/floating output modules (incl. bridge connector, cross connector, swivel label)
Table 2. Overview of auxiliary parts and spare parts
CLIOL822ACLIOL823A
XS821-22
XSU821-22
CLIOL824A
S823
SU823
order number description
XS814
Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block includes two
groups with seven internally-connected push-in terminals.
XS815
20 Cross-Connectors for connection of six relay commons. One Cross-Connector is included in the
Terminal Socket package.
XS816
10 Bridge Connectors. One Bridge Connector is included in the Terminal Socket package.
LonWorks Bus
S824-25
SU824-25
XAL10
10 Swivel Labels Holders (for attaching the application-specific label printed with CARE / COACH AX /
COACH NX). One Swivel Label Holder is included in each Terminal Socket package. NOTE: Phased
out.
NOTE: The inputs and outputs of all CentraLine analog and binary I/O modules are protected against short circuit,
EN0Z-0980GE51 R0119
24 VAC +20%, and 40 VDC.
In the case of the relay outputs of other CentraLine I/O modules (i.e., relay output modules, floating output
modules, and mixed I/O modules), appropriate fusing must be provided to ensure that permissible load currents
are not exceeded. See also sub-section "Features" in section "Relay Output Modules" on pg. 14.
2
LONWORKS BUS I/O MODULES – PRODUCT DATA
Table 3. Pluggable LonWorks Bus I/O Module specifications
Module
no. of I/Os 8 analog inputs 8 analog outputs 12 binary inputs
characteristics Linear Graph, 0...10 VDC with pull-
up, 0(2)…10 VDC without pull-up
NTC20kΩ (-50…+150 °C, default)
NTC10kΩ (-30…+100 °C)
PT
1000-1
PT
1000-2
Johnson A99 PTC (-40…+120 °C)
NI1000TK5000 (-30…+130 °C)
PT
3000
BALCO
Also configurable as:
binary inputs
Linear graph (0…10 V with pull-up)
Features:
16-bit resolution
configurable offset per input
auxiliary voltage: 10 VDC, I
5 mA
Analog Input Analog Output Binary Input Relay Output
6 relay outputs
relay outputs (default)
Features:
Changeover relays
Voltage: 19…250 VAC,
1…29 VDC, P>50 mW
max. total current: 12 A
current per relay: N.O.: 4(4) A
(AC) or 4(1) A (DC),
N.C.: 2(1) A (AC) or 4(1) A
(DC)
Safety position (remain, 0%,
100%)
yellow LED per output
Version with manual override
(R):
1 switch per output
auto feedback signal (mode +
value)
blinking in manual override
position
(-50…150 °C)
(0…400 °C)
(-50…150 °C)
(-30…120 °C)
500
max
0…11 VDC / 1 mA
Also configurable as: floating
outputs or binary outputs (0 V
/ 10 V)
Features:
8-bit resolution (default)
Safety position (remain, 0%,
50%, 100%)
red LED per output
light intensity follows output
level in auto
Version with manual
override (R):
1 potentiometer per output
auto feedback signal (mode
=
+ value)
blinking in manual override
position
requiring a gold contact
or open collector
static binary input,
(default: dry contact)
Also configurable as:
totalizers (20 Hz)
Features:
1 LED per input
Color mode can be
set per input to
OFF/yellow or
green/red using
CARE / COACH AX /
COACH NX
ON: < 1.6 kΩ to GND
or < 2.5 V to GND,
OFF: > 90 kΩ to
GND or > 4 V to
GND
Manual Overrides as per EN ISO 16484-2:2004
The manual override switches and potentiometers of the output modules support direct operation as per EN ISO 164842:2004, section 5.4.3 "Local Priority Override/Indicating Units."
Specifically, the positions of the manual override switches and potentiometers directly control the outputs – independently
of the controller and HMI. When a manual override switch or potentiometer is not in its default position ("auto"), the
corresponding output LED will blink continuously, and the output module will send a feedback signal with the status
"manual override" and the given override position to the controller (which will then also store this information in its alarm
memory).
NOTE: When updating the firmware of output modules, their outputs are turned OFF – regardless of the position of their
3 Swivel label holder
4 Cable connection between L
ONWORKS Bus I/O Modules
on separate DIN rails
5 Bridge connectors between L
on same DIN rail
6 Stopper (from 3
rd
-party supplier)
ONWORKS Bus I/O Modules
7 Auxiliary terminal packages
LEDs
Each CentraLine LONWORKS Bus I/O Module is equipped
with:
one green power LED
one yellow service LED
Overvoltage Protection
The inputs and outputs of all CentraLine analog and binary
I/O modules are protected against short circuit, 24 VAC
+20%, and 40 VDC.
In the case of the relay outputs of other CentraLine I/O
modules (i.e., relay output modules, floating output modules,
and mixed I/O modules), appropriate fusing must be provided
to ensure that permissible load currents are not exceeded.
See also sub-section "Features" in section "Relay Output
Modules" on pg. 14.
Service LED
Each LONWORKS Bus I/O Module is equipped with a yellow
service LED (status: yellow/OFF) for easy diagnosis of
failures.
LonWorks Service Button
Each LONWORKS Bus I/O Module is equipped with a
L
ONWORKS service button.
Microprocessors
Each LONWORKS I/O Module is equipped with an FTT-10A
transceiver (link power-compatible) and can thus be used with
any L
ONWORKS controller.
42
Honeywell
!
11 12
71 COM a
4
5
3
6
2
7
1
8
0
9
F
A
72 COM b
E
B
C
D
~
73 24V
74 24V0
~
Honeywell
56
--1
--0
--AUTO
!
41
51
616261
42
52
62
43
53
6363
In addition to the main microprocessor, the L
I/O Modules also have their own Neuron chip (3120).
System Constraints
Max. no. of I/O modules (any
combination) per controller
Max. no. of I/O modules per row
Max. current (F1)
Max. current (F2)
Max. current (F3)
Max. row length
Max. distance between rows
Min. cross-section of GND
(terminal 9) (protected by F2)
Table 4. System constraints
depends upon
controller type
ONWORKS Bus
10
4 A
12 A
12 A
3 m
40 m
2
1.5 mm
EN0Z-0980GE51 R0119
4
Analog Input Module
V
V
LONWORKS BUS I/O MODULES – PRODUCT DATA
1
3
2
Fig. 3. CLIOL821A LonWorks Bus AI Module (shown with
Legend
1 LONWORKS service button S1
2 Service LED
3 Power LED
NOTE: The hex switch S2 (located next to the L
The CentraLine L
analog inputs, is installed with the XS821-22 or XSU821-22
Terminal Socket.
service S1) has no function in combination with a
L
ONWORKS Bus I/O module. It is used with Panel
Bus I/O modules, only.
Fig. 4. Analog input low impedance (input circuit for
PT1000, Johnson A99 PTC, Balco500, PT3000,
NI1000TK5000, slow binary input)
terminal socket)
ONWORKS
ONWORKS Bus Analog Input Module, with 8
10 VDC
24.9 kOHM
AI
RTD
GND
AI
V
i
199.9 kOHM
10 VDC
24.9 kOHM
AI
GND
199.9 kOHM
(8.9 VDC IF
CONNECTION
INTERRUPTED)
V
i
Fig. 6. Analog input impedance setpoint (input circuit for
NTC10kΩ, NTC20kΩ, wall module setpoint)
COM
71
A
COM
72
B
24
7377
V~
24
74
V~0
V
AUX
V
AUX
21
22101
GND GNDGND GND GND GND GND GND GND GND
9
AI1 AI2
11
12
AI3
AI5 AI6
AI4
3
13
5156167178
4
14
2
AI8
AI7
1825 26
Fig. 7. CentraLine LonWorks Bus Analog Input Module
(schematic)
Features
0…10 VDC, 2…10 VDC without pull-up
0…10 VDC with pull-up (linear graph, e.g., used for wall