All rights reserved. This manual or portions thereof may not be reporduced
in any form without permission of Honeywell Inc.
Library of Congress Catalog Card Number: 97-77856
Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis MN 55408-0524
Honeywell Latin American Region
480 Sawgrass Corporate Parkway
Suite 200
Sunrise FL 33325
Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
M2H 3N7
Honeywell Europe S.A.
3 Avenue du Bourget
1140 Brussels
Belgium
Printed in USA
ii
Honeywell Asia Pacific Inc.
Room 3213-3225
Sun Hung Kai Centre
No. 30 Harbour Road
Wanchai
Hong Kong
ENGINEERING MANUAL OF AUTOMATIC CONTROL
FOREWORD
The Minneapolis Honeywell Regulator Company published the first edition of the Engineering Manual of
Automatic Control in l934. The manual quickly became the standard textbook for the commercial building
controls industry. Subsequent editions ha ve enjoyed ev en greater success in colleges, univ ersities, and contractor
and consulting engineering offices throughout the world.
Since the original 1934 edition, the building control industry has experienced dramatic change and made
tremendous advances in equipment, system design, and application. In this edition, microprocessor controls are
shown in most of the control applications rather than pneumatic, electric, or electronic to reflect the trends in
industry today. Consideration of configuration, functionality, and integration plays a significant role in the
design of building control systems.
Through the years Honeywell has been dedicated to assisting consulting engineers and architects in the
application of automatic controls to heating, ventilating, and air conditioning systems. This manual is an outgro wth
of that dedication. Our end user customers, the building owners and operators, will ultimately benef it from the
efficiently designed systems resulting from the contents of this manual.
All of this manual’s original sections have been updated and enhanced to include the latest developments in
control technology and use the International System of Units (SI). A ne w section has been added on indoor air
quality and information on district heating has been added to the Chiller, Boiler, and Distribution System
Control Applications Section.
This third SI edition of the Engineering Manual of Automatic Control is our contribution to ensure that we
continue to satisfy our customer’s requirements. The contr ib utions and encouragement receiv ed from pre vious
users are gratefully acknowledged. Further suggestions will be most welcome.
Minneapolis, Minnesota
December, 1997
KEVIN GILLIGAN
President, H&BC Solutions and Services
ENGINEERING MANUAL OF AUTOMATIC CONTROL
iii
iv
ENGINEERING MANUAL OF AUTOMATIC CONTROL
PREFACE
The purpose of this manual is to provide the reader with a fundamental understanding of controls and how
they are applied to the many parts of heating, ventilating, and air conditioning systems in commer cial buildings.
Many aspects of control are presented including air handling units, terminal units, chillers, boilers, building
airflow , water and steam distribution systems, smoke management, and indoor air quality . Control fundamentals,
theory, and types of controls provide background for application of controls to heating, ventilating, and air
conditioning systems. Discussions of pneumatic, electric, electronic, and digital controls illustrate that applications
may use one or more of several different control methods. Eng ineering data such as equipment sizing, use of
psychrometric charts, and conversion formulas supplement and support the control information. To enhance
understanding, definitions of terms are provided within individual sections.
Building management systems have ev olved into a major consideration for the control engineer when evaluating
a total heating, ventilating, and air conditioning system design. In response to this consideration, the basics of
building management systems configuration are presented.
The control recommendations in this manual are general in nature and are not the basis for any specific job or
installation. Control systems are furnished according to the plans and specifications prepared by the control
engineer. In many instances there is more than one control solution. Professional expertise and judgment are
required for the design of a control system. This manual is not a substitute for such expertise and judgment.
Always consult a licensed engineer for advice on designing control systems.
It is hoped that the scope of information in this manual will provide the readers with the tools to expand their
knowledge base and help develop sound approaches to automatic control.
Characteristics and Attributes of Control Methods..............................................................................35
4
ENGINEERING MANUAL OF AUTOMATIC CONTROL
INTRODUCTION
CONTROL FUNDAMENTALS
This section describes heating, ventilating, and air
conditioning (HV A C) systems and discusses characteristics and
components of automatic control systems. Cross-references are
made to sections that provide more detailed information.
A correctly designed HVAC control system can provide a
comfortable environment for occupants, optimize energy cost
and consumption, improve employee productivity, facilitate
efficient manufacturing, control smoke in the event of a fire,
and support the operation of computer and telecommunications
equipment. Controls are essential to the proper operation of
the system and should be considered as early in the design
process as possible.
Properly applied automatic controls ensure that a correctly
designed HVAC system will maintain a comfortable
environment and perform economically under a wide range of
operating conditions. Automatic controls regulate HVA C system
output in response to varying indoor and outdoor conditions to
maintain general comfort conditions in office areas and provide
narrow temperature and humidity limits where required in
production areas for product quality.
DEFINITIONS
Automatic controls can optimize HVAC system operation.
They can adjust temperatures and pressures automatically to
reduce demand when spaces are unoccupied and regulate
heating and cooling to provide comfort conditions while limiting
energy usage. Limit controls ensure safe operation of HVAC
system equipment and prevent injury to personnel and damage
to the system. Examples of limit controls are low-limit
temperature controllers which help prevent water coils or heat
exchangers from freezing and flow sensors for safe operation
of some equipment (e.g., chillers). In the event of a fire,
controlled air distribution can provide smoke-free evacuation
passages, and smoke detection in ducts can close dampers to
prevent the spread of smoke and toxic gases.
HVAC control systems can also be integra ted with security
access control systems, fire alarm systems, lighting control
systems, and building and facility management systems to
further optimize building comfort, safety, and efficiency.
The following terms are used in this manual. Figure 1 at the
end of this list illustrates a typical control loop with the
components identified using terms from this list.
Analog: Continuousl y variable (e.g., a faucet controlling water
from off to full flow).
Automatic contr ol system: A system that reacts to a change or
imbalance in the variable it controls by adjusting other
variables to restore the system to the desired balance.
Algorithm: A calculation method that produces a control output
by operating on an error signal or a time series of error
signals.
Compensation control: A process of automatically adjusting
the setpoint of a given controller to compensate for
changes in a second measured variable (e.g., outdoor
air temperature). For example, the hot deck setpoint
is normally reset upward as the outdoor air temperature
decreases. Also called “reset control”.
Control agent: The medium in which the manipulated variable
exists. In a steam heating system, the control agent is
the steam and the manipulated variable is the flow of
the steam.
Control point: The actual value of the controlled variable
(setpoint plus or minus offset).
Controlled medium: The medium in which the controlled
variable exists. In a space temperature control system,
the controlled variable is the space temperature and
the controlled medium is the air within the space.
Controlled V ariable: The quantity or condition that is measured
and controlled.
Controller: A device that senses changes in the controlled
variable (or receiv es input from a r emote sensor) and
derives the proper correction output.
Corrective action: Control action that results in a change of
the manipulated variable. Initiated when the controlled
variable deviates from setpoint.
Cycle: One complete e xecution of a repeatable process. In basic
heating operation, a cycle comprises one on period
and one off period in a two-position control system.
Cycling: A periodic change in the controlled v ariable from one
value to another. Out-of-control analog cycling is
called “hunting”. T oo frequent on-off c ycling is called
“short cycling”. Short cycling can harm electric
motors, fans, and compressors.
Cycling rate: The number of cycles completed per time unit,
typically cycles per hour for a heating or cooling system.
The inverse of the length of the period of the c ycle.
ENGINEERING MANUAL OF AUTOMATIC CONTROL
5
CONTROL FUNDAMENTALS
Deadband: A range of the controlled variable in which no
corrective action is taken by the controlled system and
no energy is used. See also “zero energy band”.
Deviation: The difference between the setpoint and the value
of the controlled variable at any moment. Also called
“offset”.
DDC: Direct Digital Control. See also Digital and Digital
control.
Digital: A series of on and off pulses arranged to convey
information. Morse code is an early example.
Processors (computers) operate using digital language.
Digital control: A control loop in which a microprocessor-
based controller directly controls equipment based on
sensor inputs and setpoint parameters. The
programmed control sequence determines the output
to the equipment.
Droop: A sustained deviation between the control point and
the setpoint in a two-position control system caused
by a change in the heating or cooling load.
A control algorithm that enhances the standard PID
algorithm by allowing the designer to enter a startup
output value and error ramp duration in addition to
the gains and setpoints. These additional parameters
are configured so that at startup the PID output varies
smoothly to the control point with negligible overshoot
or undershoot.
Electric control: A control circuit that operates on line or low
voltage and uses a mechanical means, such as a
temperature-sensitive bimetal or bellows, to perf orm
control functions, such as actuating a switch or
positioning a potentiometer. T he controller signal usually
operates or positions an electric actuator or may switch
an electrical load directly or through a relay.
Electronic control: A control circuit that operates on low
voltage and uses solid-state components to amplify
input signals and perform control functions, such as
operating a relay or providing an output signal to
position an actuator. The controller usually furnishes
fixed control routines based on the logic of the solidstate components.
Final control element: A device such as a valve or damper
that acts to change the value of the manipulated
variable. Positioned by an actuator.
Hunting: See Cycling.
Load: In a heating or cooling system, the heat transfer that the
system will be called upon to provide. Also, the work
that the system must perform.
Manipulated variable: The quantity or condition regulated
by the automatic control system to cause the desired
change in the controlled variable.
Measured variable: A variable that is measured and may be
controlled (e.g., discharge air is measured and
controlled, outdoor air is only measured).
Microprocessor -based control: A control circuit that operates
on low voltage and uses a microprocessor to perform
logic and control functions, such as operating a relay
or providing an output signal to position an actuator.
Electronic devices are primarily used as sensors. The
controller often furnishes flexible DDC and energy
management control routines.
Modulating: An action that adjusts by minute increments and
decrements.
Offset: A sustained deviation between the control point and
the setpoint of a proportional control system under
stable operating conditions.
On/off control: A simple two-position control system in which
the device being controlled is either full on or full off
with no intermediate operating positions available.
Also called “two-position control”.
Pneumatic control: A control circuit that operates on air
pressure and uses a mechanical means, such as a
temperature-sensitive bimetal or bellows, to perform
control functions, such as actuating a nozzle and
flapper or a switching relay. The controller output
usually operates or positions a pneumatic actuator,
although relays and switches are often in the circuit.
Process: A gener al term that describes a change in a measurable
variable (e.g., the mixing of return and outdoor air
streams in a mixed-air control loop and heat transfer
between cold water and hot air in a cooling coil).
Usually considered separately from the sensing
element, control element, and controller.
Proportional band: In a proportional controller, the control
point range through which the controlled variable must
pass to move the final control element through its full
operationg range. Expressed in percent of primary
sensor span. Commonly used equivalents are
“throttling range” and “modulating range”, usually
expressed in a quantity of Engineering units (degrees
of temperature).
Lag: A delay in the effect of a changed condition at one point in
the system, or some other condition to which it is related.
Also, the delay in response of the sensing element of a
control due to the time required for the sensing element
to sense a change in the sensed variable.
Proportional control: A control algorithm or method in which
the final control element moves to a position
proportional to the deviation of the value of the
controlled variable from the setpoint.
6
ENGINEERING MANUAL OF AUTOMATIC CONTROL
CONTROL FUNDAMENTALS
Proportional-Integral (PI) control: A control algorithm that
combines the proportional (proportional response) and
integral (reset response) control algorithms. Reset
response tends to correct the offset resulting from
proportional control. Also called “proportional-plusreset” or “two-mode” control.
Proportional-Integral-Derivative (PID) control: A control
algorithm that enhances the PI control algorithm by
adding a component that is proportional to the rate of
change (derivative) of the deviation of the controlled
variable. Compensates for system dynamics and
allows faster control response. Also called “threemode” or “rate-reset” control.
Reset Control: See Compensation Control.
Sensing element: A device or component that measures the
value of a variable.
Setpoint: The value at which the controller is set (e.g., the
desired room temperature set on a thermostat). The
desired control point.
Short cycling: See Cycling.
Step control: Control method in which a multiple-switch
assembly sequentially switches equipment (e.g.,
electric heat, multiple chillers) as the controller input
varies through the proportional band. Step controllers
may be actuator driven, electronic, or directly activ ated
by the sensed medium (e.g., pressure, temperature).
Throttling range: In a proportional controller, the control point
range through which the controlled variable must pass
to move the final control element through its full
operating range. Expressed in values of the controlled
variable (e.g., Kelvins or degrees Celsius, percent
relative humidity, kilopascals). Also called
“proportional band”. In a proportional room
thermostat, the temperature change required to drive
the manipulated variable from full off to full on.
Time constant: The time required for a dynamic component,
such as a sensor, or a control system to reach 63.2
percent of the total response to an instantaneous (or
“step”) change to its input. Typically used to judge
the responsiveness of the component or system.
Two-position control: See on/off control.
Zero energy band: An energy conservation technique that
allows temperatures to float between selected settings,
thereby preventing the consumption of heating or
cooling energy while the temperature is in this range.
Zoning: The practice of dividing a building into sections for
heating and cooling control so that one controller is
sufficient to determine the heating and cooling
requirements for the section.
MEASURED
VARIABLE
OUTDOOR
AIR
-2
OUTDOOR
AIR
CONTROLLED
MEASURED
VARIABLE
HOT WATER
RETURN
TEMPERATURE
MEDIUM
RESET SCHEDULE
15
-15
OA
CONTROLLED
VARIABLE
HOT WATER
SUPPLY
64
AUTO
55
90
HW
SETPOINT
CONTROL
POINT
HOT WATER
SUPPLY
TEMPERATURE
71
Fig. 1. Typical Control Loop.
70
SETPOINT
INPUT
PERCENT
OPEN
VALVE
SETPOINT
OUTPUT
41
FLOW
ALGORITHM IN
CONTROLLER
FINAL CONTROL
ELEMENT
STEAM
CONTROL
AGENT
MANIPULATED
VARIABLE
M15127
ENGINEERING MANUAL OF AUTOMATIC CONTROL
7
CONTROL FUNDAMENTALS
HVAC SYSTEM CHARACTERISTICS
GENERAL
An HVAC system is designed according to capacity
requirements, an acceptable combination of first cost and operating
costs, system reliability, and available equipment space.
DAMPER
AIR
FILTER
COOLING
COIL
FAN
COOLING
TOWER
Figure 2 shows how an HVAC system may be distributed in
a small commercial building. The system control panel, boilers,
motors, pumps, and chillers are often located on the lower lev el.
The cooling tower is typically located on the roof. Throughout
the building are ductwork, fans, dampers, coils, air filters,
heating units, and variable air volume (VAV) units and dif fusers.
Larger buildings often hav e separate systems for groups of floors
or areas of the building.
DUCTWORK
HEATING
UNIT
VAV BOX
DIFFUSER
CHILLER
PUMP
Fig. 2. Typical HVAC System in a Small Building.
The control system for a commercial building comprises
many control loops and can be divided into central system and
local- or zone-control loops. For maximum comfort and
efficiency, all control loops should be tied together to share
information and system commands using a building
management system. Refer to the Building Management System
Fundamentals section of this manual.
BOILER
CONTROL
PANEL
M10506
The basic control loops in a central air handling system can
be classified as shown in Table 1.
Depending on the system, other controls may be required
for optimum performance. Local or zone controls depend on
the type of terminal units used.
8
ENGINEERING MANUAL OF AUTOMATIC CONTROL
CONTROL FUNDAMENTALS
Table 1. Functions of Central HVAC Control Loops.
Control
LoopClassificationDescription
VentilationBasicCoordinates operation of the outdoor, return, and exhaust air dampers to maintain
BetterMeasures and controls the volume of outdoor air to provide the proper mix of
CoolingChiller controlMaintains chiller discharge water at preset temperature or resets temperature
Cooling tower
control
Water coil controlAdjusts chilled water flow to maintain temperature.
Direct expansion
(DX) system control
FanBasicTurns on supply and return fans during occupied periods and cycles them as
BetterAdjusts fan volumes to maintain proper duct and space pressures. Reduces system
HeatingCoil controlAdjusts water or steam flow or electric heat to maintain temperature.
Boiler controlOperates burner to maintain proper discharge steam pressure or water temperature.
the proper amount of ventilation air. Low-temperature protection is often required.
outdoor and return air under varying indoor conditions (essential in variable air
volume systems). Low-temperature protection may be required.
according to demand.
Controls cooling tower fans to provide the coolest water practical under existing
wet bulb temperature conditions.
Cycles compressor or DX coil solenoid valves to maintain temperature. If
compressor is unloading type, cylinders are unloaded as required to maintain
temperature.
required during unoccupied periods.
operating cost and improves performance (essential for variable air volume systems).
For maximum efficiency in a hot water system, water temperature should be reset as
a function of demand or outdoor temperature.
HEATING
GENERAL
Building heat loss occurs mainly through transmission,
infiltration/exfiltration, and ventilation (Fig. 3).
TRANSMISSION
VENTILATIONDUCT
EXFILTRATION
DOOR
Fig. 3. Heat Loss from a Building.
The heating capacity required for a building depends on the
design temperature, the quantity of outdoor air used, and the
physical activity of the occupants. Prevailing winds affect the
rate of heat loss and the degree of infiltration. The heating
system must be sized to heat the building at the coldest outdoor
temperature the building is likely to experience (outdoor design
temperature).
ROOF
20°C
-7°C
WINDOW
PREVAILING
WINDS
INFILTRATION
C3971
Transmission is the process by which energ y enters or leaves
a space through exterior surfaces. The rate of energy
transmission is calculated by subtracting the outdoor
temperature from the indoor temperature and multiplying the
result by the heat transfer coefficient of the surface materials.
The rate of transmission varies with the thickness and
construction of the exterior surfaces but is calculated the same
way for all exterior surfaces:
Energy Transmission per
Unit Area and Unit Time = (TIN - T
OUT
) x HTC
Where:
TIN= indoor temperature
T
= outdoor temperature
OUT
HTC = heat transfer coefficient
HTC
=
Unit Time x Unit Area x Unit Temperature
joule
ENGINEERING MANUAL OF AUTOMATIC CONTROL
9
CONTROL FUNDAMENTALS
Infiltration is the process by which outdoor air enters a
building through walls, cracks around doors and windows, and
open doors due to the difference between indoor and outdoor
air pressures. The pressure differential is the result of
temperature difference and air intake or exhaust caused by f an
operation. Heat loss due to infiltration is a function of
temperature difference and volume of air moved. Exfiltration
is the process by which air leaves a building (e.g., through walls
and cracks around doors and windows) and carries heat with it.
Infiltration and exfiltration can occur at the same time.
Ventilation brings in fresh outdoor air that may require
heating. As with heat loss from inf iltration and exfiltration, heat
loss from ventilation is a function of the temperature difference
and the volume of air brought into the building or exhausted.
HEATING EQUIPMENT
Selecting the proper heating equipment depends on many
factors, including cost and availability of fuels, building size
and use, climate, and initial and operating cost trade-offs.
Primary sources of heat include gas, oil, wood, coal, electrical,
and solar energy . Sometimes a combination of sources is most
economical. Boilers are typically fueled by gas and may have
the option of switching to oil during periods of high demand.
Solar heat can be used as an alternate or supplementary source
with any type of fuel.
STEAM OR
HOT WATER
SUPPL Y
FAN
COIL
UNIT HEATER
STEAM TRAP
(IF STEAM SUPPLY)
CONDENSA TE
OR HOT WATER
RETURN
Fig. 5. Typical Unit Heater.
GRID PANEL
SERPENTINE PANEL
C2703
HOT WATER
SUPPL Y
HOT WATER
RETURN
HOT WATER
SUPPL Y
HOT WATER
RETURN
C2704
Figure 4 shows an air handling system with a hot water coil.
A similar control scheme would apply to a steam coil. If steam
or hot water is chosen to distribute the heat energy, highefficiency boilers may be used to reduce life-c ycle cost. Water
generally is used more often than steam to transmit heat energy
from the boiler to the coils or terminal units, because water
requires fewer safety measures and is typically more eff icient,
especially in mild climates.
THERMOSTAT
HOT WATER
SUPPLY
FAN
VALVE
HOT WATER
RETURN
DISCHARGE
AIR
C2702
Fig. 4. System Using Heating Coil.
An air handling system provides heat by moving an air stream
across a coil containing a heating medium, across an electric
heating coil, or through a furnace. Unit heaters (Fig. 5) are
typically used in shops, storage areas, stairwells, and docks.
Panel heaters (Fig. 6) are typically used for heating floors and
are usually installed in a slab or floor structure, but may be
installed in a wall or ceiling.
Fig. 6. Panel Heaters.
Unit ventilators (Fig. 7) are used in classrooms and may
include both a heating and a cooling coil. Convection heaters
(Fig. 8) are used for perimeter heating and in entries and
corridors. Infrared heaters (Fig. 9) are typically used for spot
heating in large areas (e.g., aircraft hangers, stadiums).
FAN
DISCHARGE
AIR
COOLING
COIL
RETURN
AIR
C3035
WALL
OUTDOOR
AIR
HEATING
COIL
DRAIN PAN
MIXING
DAMPERS
Fig. 7. Unit Ventilator.
10
ENGINEERING MANUAL OF AUTOMATIC CONTROL
CONTROL FUNDAMENTALS
FINNED TUBE
WARM AIR
RETURN AIR
SUPPLY
RETURN
FLOOR
TO OTHER
HEATING UNITS
FROM OTHER
HEATING UNITS
C2705
Fig. 8. Convection Heater.
REFLECTOR
INFRARED
SOURCE
RADIANT HEAT
C2706
Fig. 9. Infrared Heater.
In mild climates, heat can be provided by a coil in the central
air handling system or by a heat pump. Heat pumps have the
advantage of switching between heating and cooling modes as
required. Rooftop units provide packaged heating and cooling.
Heating in a rooftop unit is usually by a gas- or oil-fired furnace
or an electric heat coil. Steam and hot water coils are available
as well. Perimeter heat is often required in colder climates,
particularly under large windows.
A heat pump uses standard refrigeration components and a
reversing valv e to pro vide both heating and cooling within the
same unit. In the heating mode, the flow of refrigerant through
the coils is reversed to deliver heat from a heat source to the
conditioned space. When a heat pump is used to exchange heat
from the interior of a building to the perimeter, no additional
heat source is needed.
A heat-recovery system is often used in buildings where a
significant quantity of outdoor air is used. Several types of heatrecovery systems are av ailable including heat pumps, runaround
systems, rotary heat exchangers, and heat pipes.
In a runaround system, coils are installed in the outdoor air
supply duct and the exhaust air duct. A pump circulates the
medium (water or glycol) between the coils so that medium heated
by the exhaust air preheats the outdoor air entering the system.
A rotary heat exchanger is a large wheel filled with metal
mesh. One half of the wheel is in the outdoor air intake and the
other half, in the exhaust air duct. As the wheel r otates, the
metal mesh absorbs heat from the exhaust air and dissipates it
in the intake air.
A heat pipe is a long, sealed, finned tube charged with a
refrigerant. The tube is tilted slightly with one end in the outdoor
air intake and the other end in the exhaust air. In a heating
application, the refrigerant vaporizes at the lower end in the
warm exhaust air , and the vapor rises toward the higher end in
the cool outdoor air, where it gi v es up the heat of v aporization
and condenses. A wick carries the liquid refrigerant back to the
warm end, where the cycle repeats. A heat pipe requires no
energy input. For cooling, the process is rev ersed by tilting the
pipe the other way.
Controls may be pneumatic, electric, electronic, digital, or a
combination. Satisfactory control can be achieved using
independent control loops on each system. Maximum operating
efficiency and comfort levels can be achieved with a control
system which adjusts the central system operation to the
demands of the zones. Such a system can save enough in
operating costs to pay for itself in a short time.
Controls for the air handling system and zones are specifically
designed for a building by the architect, engineer, or team who
designs the building. The controls are usually installed at the job
site. T erminal unit controls are typically factory installed. Boilers,
heat pumps, and rooftop units are usually sold with a factoryinstalled control package specifically designed for that unit.
COOLING
GENERAL
Both sensible and latent heat contribute to the cooling load
of a building. Heat gain is sensible when heat is added to the
conditioned space. Heat gain is latent when moisture is added
to the space (e.g., by vapor emitted by occupants and other
sources). To maintain a constant humidity ratio in the space,
water vapor must be removed at a rate equal to its rate of addition
into the space.
Conduction is the process by which heat moves between
adjoining spaces with unequal space temperatures. Heat may
move through exterior walls and the roof, or through floors,
walls, or ceilings. Solar radiation heats surfaces which then
transfer the heat to the surrounding air. Internal heat gain is
generated by occupants, lighting, and equipment. Warm air
entering a building by infiltration and through ventilation also
contributes to heat gain.
Building orientation, interior and exterior shading, the angle
of the sun, and prevailing winds af fect the amount of solar heat
gain, which can be a major source of heat. Solar heat received
through windows causes immediate heat gain. Areas with large
windows may experience more solar gain in winter than in
summer. Building surf aces absorb solar energy , become heated,
and transfer the heat to interior air. The amount of change in
temperature through each layer of a composite surface depends
on the resistance to heat flow and thickness of each material.
Occupants, lighting, equipment, and outdoor air ventilation
and infiltration requirements contribute to internal heat gain.
For example, an adult sitting at a desk produces about 117 watts.
Incandescent lighting produces more heat than fluorescent
lighting. Copiers, computers, and other office machines also
contribute significantly to internal heat gain.
ENGINEERING MANUAL OF AUTOMATIC CONTROL
11
CONTROL FUNDAMENTALS
COOLING EQUIPMENT
An air handling system cools by moving air across a coil
containing a cooling medium (e.g., chilled water or a
refrigerant). Figures 10 and 11 show air handling systems that
use a chilled water coil and a refrigeration evaporator (direct
expansion) coil, respectively. Chilled water control is usually
proportional, whereas control of an evaporator coil is twoposition. In direct expansion systems having more than one
coil, a thermostat controls a solenoid valve for each coil and
the compressor is cycled by a refrigerant pressure control. This
type of system is called a “pump down” system. Pump down
may be used for systems having only one coil, but more often
the compressor is controlled directly by the thermostat.
CHILLED
WATER
SUPPLY
TEMPERATURE
CONTROLLER
CONTROL
VALVE
CHILLED
WATER
COIL
SENSOR
CHILLED
WATER
RETURN
COOL AIR
C2707-2
Fig. 10. System Using Cooling Coil.
Compressors for chilled water systems are usually centrifugal,
reciprocating, or screw type. The capacities of centr ifugal and
screw-type compressors can be controlled by varying the
volume of refrigerant or controlling the compressor speed. DX
system compressors are usually reciprocating and, in some
systems, capacity can be controlled by unloading cylinders.
Absorption refrigeration systems, which use heat energy directly
to produce chilled water, are sometimes used for large chilled
water systems.
While heat pumps are usually direct expansion, a large heat
pump may be in the form of a chiller. Air is typically the heat
source and heat sink unless a large water reservoir (e.g., ground
water) is available.
Initial and operating costs are prime factors in selecting
cooling equipment. DX systems can be less expensive than
chillers. However, because a DX system is inherently twoposition (on/off), it cannot control temperature with the accuracy
of a chilled water system. Low-temperature control is essential
in a DX system used with a variable air volume system.
For more information control of various system equipment,
refer to the following sections of this manual:
— Chiller, Boiler, and Distribution System
Control Applications.
— Air Handling System Control Applications.
— Individual Room Control Applications.
TEMPERA TURE
CONTROLLER
EVAPORATOR
COIL
SOLENOID
VALVE
D
X
COOL AIR
SENSOR
REFRIGERANT
LIQUID
REFRIGERANT
GAS
C2708-1
Fig. 11. System Using Evaporator
(Direct Expansion) Coil.
Two basic types of cooling systems are available: chillers,
typically used in larger systems, and direct expansion (DX)
coils, typically used in smaller systems. In a chiller, the
refrigeration system cools water which is then pumped to coils
in the central air handling system or to the coils of fan coil
units, a zone system, or other type of cooling system. In a DX
system, the DX coil of the refrigeration system is located in
the duct of the air handling system. Condenser cooling for
chillers may be air or water (using a cooling tower), while DX
systems are typically air cooled. Because water cooling is more
efficient than air cooling, large chillers ar e always water cooled.
DEHUMIDIFICATION
Air that is too humid can cause problems such as condensation
and physical discomfort. Dehumidification methods circulate
moist air through cooling coils or sorption units.
Dehumidification is required only during the cooling season.
In those applications, the cooling system can be designed to
provide dehumidification as well as cooling.
For dehumidification, a cooling coil must have a capacity
and surface temperature sufficient to cool the air belo w its dew
point. Cooling the air condenses water, which is then collected
and drained away. When humidity is critical and the cooling
system is used for dehumidification, the dehumidified air may
be reheated to maintain the desired space temperature.
When cooling coils cannot reduce moisture content
sufficiently, sorption units are installed. A sorption unit uses
either a rotating granular bed of silica gel, activated alumina or
hygroscopic salts (Fig. 12), or a spray of lithium chloride brine
or glycol solution. In both types, the sorbent material absorbs
moisture from the air and then the saturated sorbent material
passes through a separate section of the unit that applies heat
to remove moisture. The sorbent material gi v es up moisture to
a stream of “scavenger” air , which is then exhausted. Scavenger
air is often exhaust air or could be outdoor air.
12
ENGINEERING MANUAL OF AUTOMATIC CONTROL
CONTROL FUNDAMENTALS
HUMID
ROTATING
GRANULAR
BED
SORPTION
UNIT
AIR
DRY AIR
HUMID AIR
EXHAUST
HEATING
COIL
SCAVENGER
AIR
C2709
Fig. 12. Granular Bed Sorption Unit.
Sprayed cooling coils (Fig. 13) are often used for space humidity
control to increase the dehumidifier eff iciency and to provide yearround humidity control (winter humidification also).
MOISTURE
COOLING
COIL
ELIMINATORS
SPRAY
PUMP
M10511
Fig. 13. Sprayed Coil Dehumidifier.
For more information on dehumidification, refer to the
following sections of this manual:
— Psychrometric Chart Fundamentals.
— Air Handling System Control Applications.
VENTILATION
Ventilation introduces outdoor air to replenish the oxygen
supply and rid building spaces of odors and toxic gases.
Ventilation can also be used to pressurize a building to reduce
infiltration. While ventila tion is required in nearly all buildings,
the design of a ventilation system must consider the cost of
heating and cooling the ventilation air. Ventilation air must be
kept at the minimum required level except when used f or free
cooling (refer to ASHRAE Standard 62, Ventilation for
Acceptable Indoor Air Quality).
To ensure high-quality ventilation air and minimize the
amount required, the outdoor air intakes must be located to
avoid building exhausts, vehicle emissions, and other sources
of pollutants. Indoor exhaust systems should collect odors or
contaminants at their source. The amount of ventilation a
building requires may be reduced with air washers, high
efficiency f ilters, absorption chemicals (e.g., activ ated charcoal),
or odor modification systems.
Ventilation requirements vary according to the number of
occupants and the intended use of the space. For a breakdown
of types of spaces, occupancy levels, and required v entilation,
refer to ASHRAE Standard 62.
Figure 14 shows a ventilation system that supplies 100 percent
outdoor air. This type of ventilation system is typically used
where odors or contaminants originate in the conditioned space
(e.g., a laboratory where exhaust hoods and fans remove fumes).
Such applications require make-up air that is conditioned to
provide an acceptable environment.
EXHAUST
HUMIDIFICATION
Low humidity can cause problems such as respiratory
discomfort and static electricity. Humidifiers can humidify a
space either directly or through an air handling system. For
satisfactory environmental conditions, the relati ve humidity of
the air should be 30 to 60 percent. In critical areas where
explosive gases are present, 50 percent minimum is
recommended. Humidification is usually required only during
the heating season except in extremely dry climates.
Humidifiers in air handling systems typically inject steam
directly into the air stream (steam injection), spray atomized
water into the air stream (atomizing), or evaporate heated w ater
from a pan in the duct into the air stream passing through the
duct (pan humidification). Other types of humidifiers are a water
spray and sprayed coil. In spray systems, the water can be heated
for better vaporization or cooled for dehumidification.
For more information on humidification, refer to the following
sections of this manual:
— Psychrometric Chart Fundamentals.
— Air Handling System Control Applications.
SUPPLY
FAN
RETURN
AIR
MAKE-UP
AIR
SPACE
C2711
TO
OUTDOORS
OUTDOOR
AIR
SUPPLY
FILTER
EXHAUST
FAN
COIL
Fig. 14. Ventilation System Using
100 Percent Outdoor Air.
In many applications, energy costs make 100 percent outdoor
air constant volume systems uneconomical. For that reason,
other means of controlling internal contaminants are available,
such as variable volume fume hood controls, space
pressurization controls, and air cleaning systems.
A ventilation system that uses return air (Fig. 15) is more
common than the 100 percent outdoor air system. The returnair ventilation system recirculates most of the return air from
the system and adds outdoor air for ventilation. The return-air
system may have a separate fan to overcome duct pressure
ENGINEERING MANUAL OF AUTOMATIC CONTROL
13
CONTROL FUNDAMENTALS
losses. The exhaust-air system may be incorporated into the air
conditioning unit, or it may be a separate remote exhaust. Supply
air is heated or cooled, humidified or dehumidified, and
discharged into the space.
DAMPERRETURN FAN
EXHAUST
AIR
RETURN
AIR
FILTER COILSUPPLY FAN
MIXED
AIR
SUPPLY
AIR
C2712
OUTDOOR
AIR
DAMPERS
Fig. 15. Ventilation System Using Return Air.
Ventilation systems as shown in Figures 14 and 15 should
provide an acceptable indoor air quality , utilize outdoor air for
cooling (or to supplement cooling) when possible, and maintain
proper building pressurization.
For more information on ventilation, refer to the following
sections of this manual:
— Indoor Air Quality Fundamentals.
— Air Handling System Control Applications.
— Building Airflow System Control Applications.
FILTRATION
Air filtration is an important part of the central air handling
system and is usually considered part of the ventilation system.
Two basic types of filters are available: mechanical filters and
electrostatic precipitation filters (also called electronic air
cleaners). Mechanical filters are subdivided into standard and
high efficiency.
PLEATED FILTER
Filters are selected according to the degree of cleanliness
required, the amount and size of particles to be removed, and
acceptable maintenance requirements. High-efficiency
particulate air (HEP A) mechanical filters (Fig. 16) do not release
the collected particles and therefore can be used for clean rooms
and areas where toxic particles are released. HEPA filters
significantly increase system pressure drop, which must be
considered when selecting the fan. Figure 17 shows other
mechanical filters.
CELL
AIR FLOW
PLEATED PAPER
C2713
Fig. 16. HEPA Filter.
BAG FILTER
Fig. 17. Mechanical Filters.
Other types of mechanical filters include strainers, viscous
coated filters, and diffusion f ilters. Straining removes particles
that are larger than the spaces in the mesh of a metal filter and
are often used as prefilters for electrostatic filters. In viscous
coated filters, the particles passing through the filter fibers
collide with the fibers and are held on the fiber surface. Dif fusion
removes fine particles by using the turbulence present in the
air stream to drive particles to the fibers of the filter surface.
An electrostatic filter (Fig. 18) provides a low pressure drop
but often requires a mechanical prefilter to collect lar ge particles
and a mechanical after-filter to collect agglomerated particles
that may be blown off the electrostatic filter. An electrostatic
filter electrically charges particles passing through an ionizing
field and collects the charged particles on plates with an opposite
electrical charge. The plates may be coated with an adhesive.
14
ENGINEERING MANUAL OF AUTOMATIC CONTROL
CONTROL FUNDAMENTALS
–
PATH
OF
IONS
WIRES
AT HIGH
POSITIVE
POTENTIAL
SOURCE: 1996 ASHRAE SYSTEMS AND EQUIPMENT HANDBOOK
AIRFLOW
AIRFLOW
POSITIVELY CHARGED
PARTICLES
Fig. 18. Electrostatic Filter.
CONTROL SYSTEM CHARACTERISTICS
Automatic controls are used wherever a variable condition
must be controlled. In HVAC systems, the most commonly
controlled conditions are pressure, temperature, humidity, and
rate of flow. Applications of automatic control systems range
from simple residential temperature regulation to precision
control of industrial processes.
CONTROLLED VARIABLES
The sensor can be separate from or part of the controller and
is located in the controlled medium. The sensor measures the
value of the controlled variable and sends the resulting signal
to the controller. The controller receives the sensor signal,
compares it to the desired value, or setpoint, and generates a
correction signal to direct the operation of the controlled device.
The controlled device varies the control agent to regulate the
output of the control equipment that produces the desired
condition.
+
ALTERNATE
PLATES
–
GROUNDED
+
–
INTERMEDIATE
PLATES
+
CHARGED
TO HIGH
POSITIVE
–
POTENTIAL
+
THEORETICAL
PATHS OF
–
CHARGES DUST
PARTICLES
C2714
Automatic control requires a system in which a controllable
variable exists. An automatic control system controls the
variable by manipulating a second variable. The second v ariable,
called the manipulated variable, causes the necessary changes
in the controlled variable.
In a room heated by air moving through a hot water coil, for
example, the thermostat measures the temperature (controlled
variable) of the room air (controlled medium) at a specified
location. As the room cools, the thermostat operates a valve
that regulates the flow (manipulated variable) of hot water
(control agent) through the coil. In this way, the coil furnishes
heat to warm the room air.
CONTROL LOOP
In an air conditioning system, the controlled variable is
maintained by varying the output of the mechanical equipment
by means of an automatic control loop. A control loop consists
of an input sensing element, such as a temperature sensor; a
controller that processes the input signal and produces an output
signal; and a final control element, such as a valve, that operates
according to the output signal.
HVAC applications use two types of control loops: open and
closed. An open-loop system assumes a fixed relationship
between a controlled condition and an external condition. An
example of open-loop control would be the control of perimeter
radiation heating based on an input from an outdoor air
temperature sensor. A circulating pump and boiler are energized
when an outdoor air temperature drops to a specified setting,
and the water temperature or flow is proportionally controlled
as a function of the outdoor temperature. An open-loop system
does not take into account changing space conditions from
internal heat gains, infiltration/exfiltration, solar gain, or other
changing variables in the building. Open-loop control alone
does not provide close control and may result in underheating
or overheating. For this reason, open-loop systems are not
common in residential or commercial applications.
A closed-loop system relies on measurement of the controlled
variable to vary the controller output. Figure 19 sho ws a block
diagram of a closed-loop system. An example of closed-loop
control would be the temperature of discharge air in a duct
determining the flow of hot water to the heating coils to maintain
the discharge temperature at a controller setpoint.
ENGINEERING MANUAL OF AUTOMATIC CONTROL
15
CONTROL FUNDAMENTALS
SETPOINT
FEEDBACK
SENSING
ELEMENT
CONTROLLER
CORRECTIVE
SIGNAL
FINAL CONTROL
ELEMENT
MANIPULATED
VARIABLE
PROCESS
CONTROLLED
VARIABLE
SECONDARY
INPUT
DISTURBANCES
C2072
Fig. 19. Feedback in a Closed-Loop System.
In this example, the sensing element measures the discharge
air temperature and sends a feedback signal to the controller.
The controller compares the feedback signal to the setpoint.
Based on the difference, or deviation, the controller issues a
corrective signal to a valve, which regulates the flow of hot
water to meet the process demand. Changes in the controlled
variable thus reflect the demand. The sensing element continues
to measure changes in the discharge air temperature and feeds
the new condition back into the controller for continuous
comparison and correction.
Automatic control systems use feedback to reduce the
magnitude of the deviation and produce system stability as
described above. A secondary input, such as the input from an
outdoor air compensation sensor, can provide information about
disturbances that affect the controlled variable. Using an input in
addition to the controlled variable enables the controller to
anticipate the effect of the disturbance and compensate for it, thus
reducing the impact of disturbances on the controlled variable.
CONTROL METHODS
GENERAL
An automatic control system is classified by the type of
energy transmission and the type of control signal (analog or
digital) it uses to perform its functions.
Self-powered systems are a comparatively minor but still
important type of control. These systems use the power of the
measured variable to induce the necessary corrective action.
For example, temperature changes at a sensor cause pressure
or volume changes that are applied directly to the diaphragm
or bellows in the valve or damper actuator.
Many complete control systems use a combination of the
above categories. An example of a combined system is the
control system for an air handler that includes electric on/off
control of the fan and pneumatic control for the heating and
cooling coils.
Various control methods are described in the following
sections of this manual:
— Pneumatic Control Fundamentals.
— Electric Control Fundamentals.
— Electronic Control Fundamentals.
— Microprocessor-Based/DDC Fundamental.
See CHARACTERISTICS AND ATTRIBUTES OF
CONTROL METHODS.
ANALOG AND DIGITAL CONTROL
Traditionally , analog de vices have performed HVA C control.
A typical analog HVAC controller is the pneumatic type which
receives and acts upon data continuously. In a pneumatic
controller, the sensor sends the controller a continuous
pneumatic signal, the pressure of which is proportional to the
value of the variable being measured. The controller compares
the air pressure sent by the sensor to the desired value of air
pressure as determined by the setpoint and sends out a control
signal based on the comparison.
The digital controller receives electronic signals from sensors,
converts the electronic signals to dig ital pulses (values), and
performs mathematical operations on these values. The
controller reconverts the output value to a signal to operate an
actuator. The controller samples digital data at set time intervals,
rather than reading it continually . The sampling method is called
discrete control signaling. If the sampling interval for the digital
controller is chosen properly, discrete output changes pr ovide
even and uninterrupted control performance.
The most common forms of energy for automatic control
systems are electricity and compressed air. Systems may
comprise one or both forms of energy.
Systems that use electrical energy are electromechanical,
electronic, or microprocessor controlled. Pneumatic control
systems use varying air pressure from the sensor as input to a
controller, which in turn produces a pneumatic output signal to
a final control element. Pneumatic, electromechanical, and
electronic systems perform limited, predetermined control
functions and sequences. Microprocessor-based controllers use
digital control for a wide variety of control sequences.
Figure 20 compares analog and digital control signals. The
digital controller periodically updates the process as a function
of a set of measured control variables and a giv en set of control
algorithms. The controller works out the entire computation,
including the control algorithm, and sends a signal to an actuator.
In many of the larger commercial control systems, an electronicpneumatic transducer conver ts the electric output to a v ariable
pressure output for pneumatic actuation of the final control
element.
16
ENGINEERING MANUAL OF AUTOMATIC CONTROL
CONTROL FUNDAMENTALS
ANALOG CONTROL SIGNAL
OPEN
FINAL
CONTROL
ELEMENT
POSITION
CLOSED
OPEN
FINAL
CONTROL
ELEMENT
POSITION
CLOSED
DIGITAL CONTROL SIGNAL
TIME
TIME
C2080
Fig. 20. Comparison of Analog
and Digital Control Signals.
CONTROL MODES
Control systems use different control modes to accomplish
their purposes. Control modes in commercial applications
include two-position, step, and floating control; proportional,
proportional-integral, and proportional-integral-derivative
control; and adaptive control.
An example of differential gap would be in a cooling system
in which the controller is set to open a cooling valve when the
space temperature reaches 26°C, and to close the valve when
the temperature drops to 25°C. The difference between the two
temperatures (1°C or 1 Kelvin) is the differential gap. The
controlled variable fluctuates between the two temperatures.
Basic two-position control works well for many applications.
For close temperature control, however, the cycling must be
accelerated or timed.
Basic Tw o-Position Control
In basic two-position control, the controller and the final
control element interact without modification from a mechanical
or thermal source. The result is cyclical operation of the
controlled equipment and a condition in which the controlled
variable cycles back and forth between two v alues (the on and
off points) and is influenced by the lag in the system. The
controller cannot change the position of the final control element
until the controlled variable reaches one or the other of the two
limits of the differential. For that reason, the dif ferential is the
minimum possible swing of the controlled variable. Figure 21
shows a typical heating system cycling pattern.
TEMPERATURE
(°C)
23.5
OVERSHOOT
CONDTION
DIAL SETTING
DIFFERENTIAL
OFF
ON
23
22.5
22
21.5
21
TWO-POSITION CONTROL
General
In two-position control, the final control element occupies
one of two possible positions except for the brief period when
it is passing from one position to the other. T wo-position control
is used in simple HV A C systems to start and stop electric motors
on unit heaters, fan coil units, and refrigeration machines, to
open water sprays for humidification, and to energize and
deenergize electric strip heaters.
In two-position control, two values of the controlled variab le
(usually equated with on and off) determine the position of the
final control element. Between these values is a zone called the
“differential gap” or “differential” in which the controller cannot
initiate an action of the final control element. As the controlled
variable reaches one of the two values, the final control element
assumes the position that corresponds to the demands of the
controller, and remains there until the controlled variable
changes to the other value. The final control element mo v es to
the other position and remains there until the controlled variable
returns to the other limit.
20.5
20
TIME
UNDERSHOOT
CONDTION
C3972
Fig. 21. Typical Operation of Basic Two-Position Control.
The overshoot and undershoot conditions shown in Figure
21 are caused by the lag in the system. When the heating system
is energized, it builds up heat which moves into the space to
warm the air, the contents of the space, and the thermostat. By
the time the thermostat temperature reaches the off point (e.g.,
22°C), the room air is already warmer than that temperature.
When the thermostat shuts off the heat, the heating system
dissipates its stored heat to heat the space even more, causing
overshoot. Undershoot is the same process in reverse.
In basic two-position control, the presence of lag causes the
controller to correct a condition that has already passed rather
than one that is taking place or is about to take place. Consequently ,
basic two-position control is best used in systems with minimal
total system lag (including transfer, measuring, and f inal control
element lags) and where close control is not required.
ENGINEERING MANUAL OF AUTOMATIC CONTROL
17
CONTROL FUNDAMENTALS
Figure 22 shows a sample control loop for basic two-position
control: a thermostat turning a furnace burner on or off in
response to space temperature. Because the thermostat cannot
catch up with fluctuations in temperature, overshoot and
undershoot enable the temperature to vary, sometimes
considerably. Certain industrial processes and auxiliary
processes in air conditioning have small system lags and can
use two-position control satisfactorily.
THERMOST AT
FURNACE
SOLENOID
GAS VALVE
C2715
Fig. 22. Basic Two-Position Control Loop.
Timed Tw o-Position Control
GENERAL
The ideal method of controlling the temperature in a space is
to replace lost heat or displace gained heat in exactly the amount
needed. With basic two-position control, such exact operation
is impossible because the heating or cooling system is either
full on or full off and the delivery at any specific instant is
either too much or too little. Timed two-position control,
however, anticipates requirements and delivers measured
quantities of heating or cooling on a percentage on-time basis
to reduce control point fluctuations. The timing is accomplished
by a heat anticipator in electric controls and by a timer in
electronic and digital controls.
In timed two-position control, the basic interaction between
the controller and the final control element is the same as for
basic two-position control. However, the controller responds
to gradual changes in the average value of the controlled v ariable
rather than to cyclical fluctuations.
Overshoot and undershoot are reduced or eliminated because
the heat anticipation or time proportioning feature results in a
faster cycling rate of the mechanical equipment. The result is
closer control of the variable than is possible in basic twoposition control (Fig. 23).
BASIC TWO-POSITION CONTROL
OVERSHOOT
CONDITION
DIAL SETTING
UNDERSHOOT
CONDITION
TIME
TIMED TWO-POSITION CONTROL
TIME
DIFFERENTIAL
CONTROL
POINT
C3973
TEMPERATURE
(°C)
OFF
ON
TEMPERATURE
(°C)
OFF
ON
23.5
23
22.5
22
21.5
21
20.5
20
23.5
23
22.5
22
21.5
21
20.5
20
Fig. 23. Comparison of Basic Two-Position
and Timed Two-Position Control.
HEAT ANTICIPATION
In electromechanical control, timed two-position control can
be achieved by adding a heat anticipator to a bimetal sensing
element. In a heating system, the heat anticipator is connected
so that it energizes whenev er the bimetal element calls for heat.
On a drop in temperature, the sensing element acts to turn on
both the heating system and the heat anticipator. The heat
anticipator heats the bimetal element to its off point early and
deenergizes the heating system and the heat anticipator . As the
ambient temperature falls, the time required for the bimetal
element to heat to the off point increases, and the cooling time
decreases. Thus, the heat anticipator automatically changes the
ratio of on time to off time as a function of ambient temperature.
18
ENGINEERING MANUAL OF AUTOMATIC CONTROL
CONTROL FUNDAMENTALS
22.5
22
21.5
0
0.1
1
DROOP (°C)
CONTROL POINT (°C)
DESIGN
TEMPERATURE
OUTDOOR AIR
TEMPERATURE
0%
100%
LOAD
C3974
NO LOAD
TEMPERATURE
Because the heat is supplied to the sensor only, the heat
anticipation feature lowers the control point as the heat requirement
increases. The lowered control point, called “droop”, maintains a
lower temperature at design conditions and is discussed more
thoroughly in the following paragraphs. Energizing the heater
during thermostat off periods accomplishes anticipating action in
cooling thermostats. In either case, the percentage on-time varies
in proportion to the system load.
TIME PROPORTIONING
Time proportioning control provides more effective twoposition control than heat anticipation control and is available
with some electromechanical thermostats and in electronic and
Fig. 25. Relationship between Control Point,
Droop, and Load (Heating Control).
microprocessor-based controllers. Heat is introduced into the
space using on/off cycles based on the actual heat load on the
building and programmable time cycle settings. This method
reduces large temperature swings caused by a large total lag
and achieves a more even flow of heat.
Time proportioning control of two-position loads is
recommended for applications such as single-zone systems that
require two-position control of heating and/or cooling (e.g., a
gas-fired rooftop unit with direct-expansion cooling). Time
proportioning control is also recommended for electric heat
In electromechanical thermostats, the cycle rate is adjustable
by adjusting the heater. In electronic and digital systems, the
total cycle time and the minimum on and off times of the
controller are programmable. The total cycle time setting is
control, particularly for baseboard electric heat. With time
proportioning control, care must be used to avoid cycling the
controlled equipment more frequently than recommended by
the equipment manufacturer.
determined primarily by the lag of the system under control. If
the total cycle time setting is changed (e.g., from 10 minutes to
20 minutes), the resulting on/off times change accordingly (e.g.,
STEP CONTROL
from 7.5 minutes on/2.5 minutes off to 15 minutes on/5 minutes
off), but their ratio stays the same for a given load.
The cycle time in Figure 24 is set at ten minutes. At a 50
percent load condition, the controller, operating at setpoint,
produces a 5 minute on/5 minute off cycle. At a 75 percent
load condition, the on time increases to 7.5 minutes, the off
time decreases to 2.5 minutes, and the opposite cycle ratio
occurs at 25 percent load. All load conditions maintain the preset
10-minute total cycle.
10
ON
OFF
C2090
SELECTED
CYCLE TIME
(MINUTES)
7.5
5
2.5
0
1007550250
LOAD (%)
Fig. 24. Time Proportioning Control.
Because the controller responds to average temperature or
humidity , it does not w ait for a cyc lic change in the controlled
variable before signaling correcti ve action. Thus control system
lags have no significant effect.
Droop in heating control is a lowering of the control point as
the load on the system increases. In cooling control, droop is a
Step controllers operate switches or relays in sequence to
enable or disable multiple outputs, or stages, of two-position
devices such as electric heaters or reciprocating refrigeration
compressors. Step control uses an analog signal to attempt to
obtain an analog output from equipment that is typically either
on or off. Figures 26 and 27 show that the stages may be
arranged to operate with or without overlap of the operating
(on/off) differentials. In either case, the typical two-position
differentials still exist but the total output is proportioned.
THROTTLING RANGE
DIFFERENTIAL
ONOFF
STAGES
5
4
3
2
1
ONOFF
23
ONOFF
SPACE TEMPERATURE (°C)
ONOFF
LOAD
ONOFF
22
100%0%
C3981
Fig. 26. Electric Heat Stages.
raising of the control point. In digital control systems, droop is
adjustable and can be set as low as one degree or even less.
Figure 25 shows the relationship of droop to load.
ENGINEERING MANUAL OF AUTOMATIC CONTROL
19
CONTROL FUNDAMENTALS
THROTTLING RANGE
STAGES
DIFFERENTIAL
4
3
2
OFF
1
22
SPACE TEMPERATURE (°C)
0%
23
SETPOINT
LOAD
ON
ONOFF
ONOFF
ONOFF
24
100%
C3982
Fig. 27. Staged Reciprocating Chiller Control.
Figure 28 shows step control of sequenced DX coils and electric
heat. On a rise in temperature through the throttling range at the
thermostat, the heating stages sequence off. On a further rise after
a deadband, the cooling stages turn on in sequence.
SPACE OR
ACTUATOR
6
5
4
3
2
1
STEP
CONTROLLER
FAN
STAGE NUMBERS
SOLENOID
VALVES
D
X
DIRECT EXPANSION
COILS
RETURN AIR
THERMOSTAT
D
X
MULTISTAGE
ELECTRIC HEAT
DISCHARGE
AIR
C2716
full on, the modulating stage returns to zero, and the sequence
repeats until all stages required to meet the load condition are on.
On a decrease in load, the process reverses.
With microprocessor controls, step control is usually done
with multiple, digital, on-off outputs since software allows
easily adjustable on-to-off per stage and interstage differentials
as well as no-load and time delayed startup and minimum on
and off adjustments.
FLOATING CONTROL
Floating control is a variation of two-position control and is
often called “three-position control”. Floating control is not a
common control mode, but is av ailable in most microprocessorbased control systems.
Floating control requires a slow-moving actuator and a fastresponding sensor selected according to the rate of response in
the controlled system. If the actuator should move too slowly,
the controlled system would not be able to keep pace with
sudden changes; if the actuator should move too quickly, twoposition control would result.
Floating control keeps the control point near the setpoint at
any load level, and can only be used on systems with minimal
lag between the controlled medium and the control sensor.
Floating control is used primarily for discharge control systems
where the sensor is immediately downstream from the coil,
damper, or device that it controls. An example of floating control
is the regulation of static pressure in a duct (Fig. 29).
FLOATING
STATIC
PRESSURE
CONTROLLER
ACTUATOR
REFERENCE
PRESSURE
PICK-UP
AIRFLOW
STATIC
PRESSURE
PICK-UP
Fig. 28. Step Control with Sequenced
DX Coils and Electric Heat.
A variation of step control used to control electric heat is
step-plus-proportional control, which provides a smooth
transition between stages. This control mode requires one of
the stages to be a proportional modulating output and the others,
two-position. For most efficient operation, the proportional
modulating stage should have at least the same capacity as one
two-position stage.
Starting from no load, as the load on the equipment increases,
the modulating stage proportions its load until it reaches full output.
Then, the first two-position stage comes full on and the modulating
stage drops to zero output and begins to proportion its output
again to match the increasing load. When the modulating stage
again reaches full output, the second two-position stage comes
DAMPER
C2717
Fig. 29. Floating Static Pressure Control.
In a typical application, the control point moves in and out
of the deadband, crossing the switch differential (Fig. 30). A
drop in static pressure below the controller setpoint causes the
actuator to drive the damper toward open. The narrow
differential of the controller stops the actuator after it has moved
a short distance. The damper remains in this position until the
static pressure further decreases, causing the actuator to drive
the damper further open. On a rise in static pressure above the
setpoint, the reverse occurs. Thus, the control point can float
between open and closed limits and the actuator does not move.
When the control point moves out of the deadband, the
controller moves the actuator toward open or closed until the
control point moves into the deadband again.
20
ENGINEERING MANUAL OF AUTOMATIC CONTROL
Loading...
+ 482 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.