Honeywell ALL-SPEC Installation Instructions Manual

ALL-SPEC_Unit_HON.doc 07/2011 1/9
Installation Instructions for Honeywell ALL-SPEC Air Sampling Smoke Detection System
1 Operating indicator light
2 Alarm indicator light for detector
3 Alarm indicator light for detector
module I
4 Indicator light for common fault
5 Pre-punched cable entries for connection to the central fire panel or power supply (input/output)
6 Connection pipe system I
7 Connection pipe system II
8 Connection for air return
8
5
5
1
2
6
7
5
3
4
ALL-SPEC_Unit_HON.doc 07/2011 2/9
Installation of the Detector Module
Please note:
Only the detector modules of the type ASD-TP-05, ASD-TP-01 and ASD-TP-001 that have been approved by the VdS-certification authority with the approval number G 202064 may be used.
1. Carry out the following works only if the device is powered down.
2. Open the device by carefully unlocking the housing snap-in closures by means of a screwdriver. Then lift the housing lid a little bit.
3. Carefully pull the connection cable of the display board off and remove the housing lid.
Note:
Shall the device only be provided with one detector module, please skip to point 6. Shall the device however be provided with two modules please follow the following instructions.
4. If you want to install a second detector module you have to recover carefully the ventilator cover for the second air sampling duct (self-adhesive plastic cover). Take for this if necessary a screwdriver.
5. Break carefully the clasp for the connection of the second pipe system (predetermined breaking point, marked by “II“) with a screwdriver from the housing.
Note:
The knocked clasp is to removed completely from the device.
6. Make the required settings at the detector module by setting the contacts of switch S1 accordingly (see also “Settings of the detector module”).
7. Carefully spread a bit the support clamps used to fix the detector module in the corresponding mounting position.
8. Carefully place the detector module in between them until it audibly snaps in and thus is fixed by the support clamps.
Note:
Make sure that the inserted detection module is fixed tight and save by the brackets by pressing the brackets additional by hand.
9. Connect the detector module via the ribbon cable with the connection “Head 1” (detector module I) or “Head 2” (detector module II) to the base
board. Note the labelling of the base board.
10. Reconnect the display board to the base board. Note the connections and labelling of the base board.
9
S1
8
10
7
6
5
8
4
4
ALL-SPEC_Unit_HON.doc 07/2011 3/9
Detector Module Settings
In the following tables the switch S1 has two positions:
on off
The standard settings have a grey background.
Setting the response sensitivity
detector module
DM-TP-
50
DM-TP-
10
DM-TP-
01
S1. 1
S1. 2
0,8 %/m 0,12 %/m
on on
0,4 %/m 0,06 %/m
off on
1,0 %/m
0,2 %/m 0,03 %/m
on off
0,5 %/m 0,1 %/m 0,015%/m
off off
Setting the alarm delay
S1. 3 S1. 4
0 seconds off off
10 seconds on off
30 seconds off on
60 seconds on on
Setting the activating threshold “air flow fault”
S1. 5 S1. 6
I on off
II off on
III off off
IV on on
Setting the delay “air flow fault”
S1. 7 S1. 8
0.5 minutes off on
2 minutes on off
15 minutes on on
60 minutes off off
Setting the fault signal
S1. 9
non-latched off
latched on
Setting LOGIC
SENS
S1.10
off off
on on
Loading...
+ 6 hidden pages