Requires Compass Version 1.5.8.54A (or higher) for GSM Downloading
Table of Contents
SECTION 1: General Information ........................................................................................................... 1-1
System Overview ...................................................................................................................................................... 1-1
General Information ........................................................................................................................................... 1-1
System Features......................................................................................................................................................... 1-1
Modes of Operation................................................................................................................................................... 1-1
Zone Trigger Mode ............................................................................................................................................ 1-2
4204 Mode and Two-4204 Mode....................................................................................................................... 1-2
Module Supervision Features .................................................................................................................................... 1-2
SECTION 2: Mounting and Wiring.......................................................................................................... 2-1
Mounting the GSMHS............................................................................................................................................... 2-1
Wiring the GSMHS................................................................................................................................................... 2-2
Wiring a Telco Line Fault Monitor for Zone Mode ........................................................................................... 2-2
Wiring for ECP, 4204 and Two-4204 Modes..................................................................................................... 2-3
Wiring for Zone Trigger Mode........................................................................................................................... 2-3
Wiring for Module Fault Relay .......................................................................................................................... 2-5
Power Connections and Options................................................................................................................................ 2-5
Powering the Communication Module............................................................................................................... 2-5
SECTION 3: Programming the GSMHS ................................................................................................. 3-1
General Information .................................................................................................................................................. 3-1
Programming the Control Panel to work with the GSMHS ............................................................................... 3-1
Using the AlarmNet Direct Website................................................................................................................... 3-2
Using a 7720P Programming Tool..................................................................................................................... 3-2
Using the Control Panel Programming Mode .................................................................................................... 3-3
ECP Status Codes............................................................................................................................................... 3-8
Alternative Mode Programming (Zone Trigger, 4204 and Two-4204)..................................................................... 3-8
Zone Trigger Mode ............................................................................................................................................ 3-8
Alternative Mode Programming................................................................................................................................ 3-9
Registering the GSMHS............................................................................................................................................ 4-1
i
GSMHS Installation and Setup Guide
Registering through AlarmNet Direct Website .................................................................................................. 4-1
Using the Tamper Switch................................................................................................................................... 4-2
Using the Programming Tool............................................................................................................................. 4-2
Replacing an existing module using the programming tool ............................................................................... 4-3
Register by Phone............................................................................................................................................... 4-3
GSM Status Displays ......................................................................................................................................... 5-2
System Status Displays ...................................................................................................................................... 5-2
Appendix A : Summary of LED Operation...............................................................................................................A-1
Status Display Operation....................................................................................................................................A-1
Signal Strength (RSSI) / Mode and Status LEDs...............................................................................................A-3
Mode and Status Indicator Switch......................................................................................................................A-3
Appendix B : Central Station Messages .................................................................................................................... B-1
Appendix C : GSM Downloading .............................................................................................................................C-1
General Information ........................................................................................................................................... C-1
Direct Wire Setup............................................................................................................................................... C-1
Appendix D : Glossary ..............................................................................................................................................D-1
Summary of Connections Diagram…………………………………………………………..……….Inside Back Cover
ii
SECTION 1
General Information
System Overview
Introduction
Congratulations on your purchase of Honeywell's GSMHS High Security Digital Cellular
Communicator (henceforth referred to as GSMHS). It represents the latest and most
innovative communication technology for the security industry and uses the most
sophisticated encryption to ensure the highest level of security for your customer.
In addition to alarm reporting, the GSMHS provides upload/downloading capability of
Honeywell's control panel data over the Internet (via the AlarmNet-i network), using GSM
(Global System for Mobile) technology.
The GSMHS module requires an AlarmNet–i account. For new installations, please obtain the account
information from the central station prior to programming this module. For replacement installations,
the AlarmNet-i account is created automatically when the module is registered (based on the
existing account).
General Information
Honeywell's GSMHS Cellular Communicator transmits signals to the AlarmNet-i network
(GSM cellular network, which uses GPRS to complete these transmissions) and forwards
them to your central station.
System Features
Basic features of the GSMHS include:
Quick connection to compatible Honeywell series control panels
Simple programming using a 7720P programming tool
Reports fire, burg, and status messages via wireless network
Allows uploading and downloading of control panel data via the wireless network
Modes of Operation
The GSMHS provides four modes of operation so it can be used with various types of control
panels, as summarized below.
UL
ECP Mode
This mode is for use with Honeywell controls that support LRR-ECP communication
The module connects to the control’s keypad terminals and provides 2-way communication
with the control using ECP messaging
The control treats the module as a Long Range Radio (LRR) device, so program the control
accordingly, including setting the module’s proper LRR device address
Reports are sent in Contact ID format
The module also supports two hardwire zone trigger inputs (zones 6 and 7)
For UL installations, all signals must be transmitted via the GSMHS and the control panel
DACT. Closing ringback shall be provided via DACT.
1-1
GSMHS Installation and Setup Guide
Zone Trigger Mode
This mode is for use with controls that do not support LRR-ECP communication nor 4204
Relay Modules
The module provides six input zones. UL: Only zones 3-6 can be used for UL installations.
Each zone can be configured for +V, -V, or EOLR triggering
Each zone can be programmed for inverted operation, delayed reporting, and restoral
reporting. UL: Only inverted V+, V– modes can be used for UL installations; EOLR must
be non-inverted.
Reports are sent in ADEMCO High-Speed format
4204 Mode and Two-4204 Mode
This mode is for use with Honeywell controls that do not support LRR-ECP
communication, but do support 4204 Relay Modules
The module connects to the control’s keypad terminals
The control treats the module as a 4204 Relay Module(s), so program the control
accordingly, including setting the module’s proper 4204 device address
4204 mode provides up to four zone inputs, plus two optional trigger zones, depending on
options programmed
Two-4204 mode provides up to eight zone inputs, depending on options programmed
(Two-4204 mode not intended for UL installations.)
Each 4204 zone can be programmed for delayed reporting and restoral reporting
Reports are sent in ADEMCO High-Speed format
Module Supervision Features
The GSMHS provides the following types of supervision and module fault detection:
Network communication failure
messages from the device within 200 seconds, AlarmNet will notify the central station of a
communication failure.
Communication path failure
failure, the control panel can be notified of a trouble condition with the module after a
specified time has elapsed (“GSM Flt Time” option, 00-99 minutes).
Fault output
If used, the fault relay will trip when the following conditions occur: tamper*, power loss*,
low battery*, battery charger fault*, loss of network connectivity*, the device is not
registered and the device is remotely disabled by AlarmNet.
: Terminal 11 can serve as a fail-safe trigger for module fault conditions.
* Alarm reporting for the noted condition must be enabled for it to trigger the fault relay.
Primary power loss and low battery conditions (“Pwr Loss Rpt,” “Low Bat Rpt” options).
Cover tamper condition (“Tamper Rpt” option).
Antenna
The GSMHS comes equipped with an internal antenna. This feature provides additional
security to the installation by making the device tamper resistant.
AMPS antennas, such as the 7825-OC antenna, cannot be used with this product.
: In the event the AlarmNet network does not hear any
: In the event the module detects a communication path
1-2
Specifications
Mechanical
Dimensions: 8.4" x 8.0" x 1.5"
Weight: 2.4 lbs., with battery
Electrical
Input Power: 9VAC, 15VA transformer, Honeywell Model No. 1332
Backup Battery: 6V, 3.1AH, Honeywell part number K14139, (included)
Expected Battery Life: 5 Years (approx.)
Current Drain: 35mA average standby, 500mA peak transmit
Transceiver Type: Tri-Band GSM/GPRS Class 10
Modulation: GMSK
Antenna: Internal GSM quad-band antenna 1.3 dBi gain
Band
GSM 850
GSM 1800
GSM 1900
Section 1: General Information
Transmission
Frequency
(MHz)
824-849 33 869-894 -107 124 200 45
1710-1785 33 1805-1880 -106 374 200 95
1850-1910 33 1930-1990 -105.5 299 200 80
Transmit
Power
(dBm)
Receive
Frequency
(MHz)
Receive
Sensitivity
(dBm)
Number
of
Channels
Channel
Spacing
(MHz)
Duplex
Separation
(kHz)
Environmental
Compatibility
Operating temperature: -20º to +55ºC (UL Installations: 0º to 49ºC)
Storage temperature: -40º to +70ºC
Humidity: 0 to 95% relative humidity, non-condensing
Altitude: to 10,000 ft. operating, to 40,000 ft. storage
For a list of control panels that are compatible with various features of this device, go to:
After logging on, select the applicable communication product, and then select “Compatibility
Chart” under Essential Docs.
Compatible receivers are:
MX8000
7810iR-ENT
Ademco 685
1-3
GSMHS Installation and Setup Guide
1-4
SECTION 2
Mounting and Wiring
Mounting the GSMHS
The GSMHS must be mounted indoors.
RF Exposure
Warning - The antenna(s) used for this transmitter must be installed to provide a
separation distance of at least 20 cm from all persons and must not be collocated or
operating in conjunction with any other antenna or transmitter.
NOTE: The GSMHS must be installed in accordance with the National Fire Alarm Code,
ANSI/NFPA 72.
For mounting see Figure 2-1 and complete the following steps:
Unshielded, 22 AWG cable is recommended for GSMHS power/data wires.
1. Unpack the GSMHS and detach the case back by pushing up into the two tabs located at
the bottom of the GSMHS with the blade of a screwdriver while pulling the case back
and case front apart.
2. Temporarily connect the GSMHS to the AC transformer, supplied.
3. Choose the installation site with the best signal strength by observing the signal
strength (RSSI) bar graph (refer to Appendix A for information about signal strength
and status indications). Signal strength should be within 3-5 bars. The best signal
strength is usually found at the highest point in the building, near a window. Unplug
the transformer.
3 BARS MIN.
GYGGRY
7845i-GSM-025-V0
4. Locate the case back over the mounting surface such that the opening in the case back is
aligned with the wire/cable access opening (in the mounting surface) while passing the
wires/cable through the opening in the case back, or through the removable knockouts
located on the bottom of the back cover.
5. Secure the case back to the mounting surface using four screws (supplied).
6. When all wiring is completed, attach the case front of the GSMHS to the case back.
Attach the top of the GSMHS first then press the bottom section inward until it snaps
into place. Secure bottom using cover securing screw (supplied) as shown below,
(required for UL installations).
Installation must be in accordance with the National Electrical code and UL681, Installation and
Classification for Burglar and Hold-Up Alarm Systems.
GSMHS must be connected to a UL Listed dry contact or voltage trigger outputs of a UL Listed
compatible control unit.
All interconnecting wires between the UL Listed control and the GSMHS must be less than 3 feet in
length contained in the same room. All interconnecting wiring must be installed in rigid or EMT (where
exposed on interior walls) or in flexible metal tubing if run in the walls or ceiling.
A UL listed control must monitor the radio fault output of the GSMHS. An Ademco No. 659EN or other
UL listed Telco Line Fault Monitor’s output must be connected to an input zone on the control panel or
an input zone on the GSMHS if used in zone trigger mode. Premises openings and closings should
be sent via the UL listed control.
Only ECP and Zone Trigger modes have been evaluated by UL.
When using an Ademco No. 659EN Line Fault Monitor, follow the diagram below for wiring
information. (For detailed information, refer to the Ademco No. 659EN Installation
Instructions P3516-1V2.)
CONTROL PANEL
AUX
POWER
COVER SECURING SCREW
Figure 2-1. Mounting the GSMHS
No. 659EN Line Fault Monitor
6-14VDC
STAND BY: 5mA
BLK
RED
ACTIVE: 35mA
86753421
RED
BLK
7845GSM-015-V0
TO TELCO LINE
(Disregard Polarity)
OR
GSMHS High Security
Communicator
TB1
GND
4
ZONE 6
9
ZONE 7
10
GSMHS-003-V0
2-2
The Telco line fault monitor should utilize either zone 6 or zone 7 on the GSMHS. When
programming the GSMHS ensure the following programming is accomplished. The example
below is for Zone 6.
Programming Prompt Setting
Enable Zn6 [Y]
Zn6 Trigger Type [V+]
Invert Zn6 [Y]
Restore Zn6 [Y]
Delay Zn6 [00]
Rpt Zn6 ONLY if Armed [N]
For ECP and 4204 modes, the line fault monitor should be connected to a control panel zone.
Wiring for ECP, 4204 and Two-4204 Modes
Most Honeywell ADEMCO control panels support LRR-ECP data communication, (e.g.,
VISTA-10P, VISTA-15P, VISTA-20P, VISTA-128BP and VISTA-128FBP). However, there
are some panels that do not. Check the Installation and Setup Guide for the control panel
you are using to see if it supports ECP communication.
Connect the GSMHS to a compatible Honeywell VISTA control panel's ECP terminals, in
parallel with keypads and other peripheral devices such as RF receiver, VIP module, etc.
Wire length/gauge limitations are the same for the module as they are for keypads and other
peripheral devices. To wire the module for ECP or 4204 modes, see Figure 2-2 and make the
following connections:
Section 2: Mounting and Wiring
+12V AUX
DATA OU T
DATA IN
VISTA CONTROL PANEL
Figure 2-2. Wiring a VISTA for ECP Mode or 4204 Modes
Wiring for Zone Trigger Mode
To trip a zone on the GSMHS in V+ trigger mode, the positive triggering voltage from the
control panel must be within 6V-12V. UL Installations: Use inverted mode.
Trigger levels above this range may cause permanent damage to the unit.
Trigger levels below this range result in unreliable operation.
To trip a zone on the GSMHS in V- trigger mode, the negative triggering voltage must be less
than 1.0V.
Connect a wire from the triggering source (bell output, voltage trigger, etc.) of the control
panel to the zone input of the module, and connect a common ground between the module
and control panel. NOTE: This mode has not been evaluated by UL.
Examples of zone connections follow:
GND
RED
BLK
YEL
GRN
TRANSFORMER
TB1
AC INPUT 1
1
AC INPUT 2
2
ECP (+) VOLTAGE INPUT
3
GND
4
5
ECP DATA IN
ECP DATA OUT
6
COMMUNICATIONS
MODULE
J1
BATTERY
iGSMBR-005-V0
2-3
GSMHS Installation and Setup Guide
GND
+ TRIGGER
(VOLTAGE: 6-12V)
TRIGGERING DEVICE
TRANSFORMER
TB1
AC INPUT 1
1
AC INPUT 2
2
GND
4
5
ZONE INPUT Z1/Z2
COMMUNICATIONS
MODULE
J1
BATTERY
Figure 2-3. Wiring the GSMHS Zone 1 Input for a Positive (+) Trigger
GND
-
TRIGGER
(VOLTAGE: 0-1V)
TRANSFORMER
TB1
AC INPUT 1
1
AC INPUT 2
2
GND
4
5
ZONE INPUT Z1/Z2
GSMHS-001-V0
TRIGGERING DEVICE
NOTE: TRIGGER VOLTAGE
IS +V TO GROUND FALLING
EDGE TRIGGER
COMMUNICATIONS
MODULE
J1
BATTERY
iGSMBR-008-V0
Figure 2-4. Wiring the GSMHS Zone 1 Input for a Ground (-V) Trigger
TB1
1
AC
AC
2
GND
4
ZONE INPUT Z1/Z2
5
COMMUNICATIONS
MODULE
J1
BATTERY
iGSMBR-010-V0
2K EOL
RESISTOR
TRANSFORMER
N.O.
N.C.
Figure 2-5. Wiring the GSMHS Zone 1 Input for EOL Supervised N.O./N.C. Triggers
2-4
UL
Zones should use EOL resistors, and be programmed as V+ Inverted or V– Inverted operation
such that a cut line results in an alarm.
Do not use zones 1 and 2 for UL installations.
Wiring for Module Fault Relay
You may wire and program the module's fault output trigger for fail-safe mode (see the
question "FLT REL ON Y/N").
To sense a module fault at the control panel, make connections as shown in Figure 2-6,
including the proper EOL resistor required by the control.
Section 2: Mounting and Wiring
UL
Figure 2-6. Wiring the GSMHS Fault Relay to a Control Panel Zone for Normally Closed Fault
A 24 hour supervisory zone must be assigned on the control panel, with the GSMHS's fault relay wired to
that zone.
12V AUX
GND
ZONE IN (+)
CONTROL PANEL
TRANSFORMER
2K EOL
RESISTOR
TB1
AC INPUT 1
1
AC INPUT 2
2
ECP (+) VOLTAGE INPUT
3
GND
4
11
RAD FLT
COMMUNICATIONS
MODULE
J1
BATTERY
iGSMBR-011-V0
Power Connections and Options
Powering the Communication Module
Primary power for the GSMHS is provided by the AC plug-in transformer. For ECP
communication, you must also connect the +12VDC AUX voltage output of the control panel
(9.6V-13.8V typical) (see Figure 2-7).
In all installations, TB1-4 GND must be connected to ground (AUX –) on the control panel.
12V AUX
AUX
-
CONTROL PANEL
TRANSFORMER
TB1
AC INPUT 1
1
AC INPUT 2
2
3
ECP (+) VOLTAGE INPUT
4
GND
COMMUNICATIONS
MODULE
J1
BATTERY
iGSMBR-013-V0
Figure 2-7. Powering the GSMHS
NOTE:When calculating the total load on the auxiliary power output of the control panel, budget 10mA
for the GSMHS when using ECP mode.
2-5
GSMHS Installation and Setup Guide
Backup Battery Connection
The included battery (K14139) is used for backup in the event of a system power loss.
The battery can provide over 24 hours of system life in the event of a power failure.
A programmable power loss message can alert the AlarmNet Control Center when system
power is lost (power loss messages are reported within 1-3 hours of actual loss).
The module transmits a low-battery message (programmable) when the battery reaches
5.7V ±5%, indicating subsequent messages may not be transmitted.
The system shuts down when the battery reaches 5.1V, and radio transmissions are no
longer possible.
If system power is restored before the module shuts down, a power restore message is sent
within 1-3 hours after power is restored, and the battery is recharged using the GSMHS’s
built-in battery charger. If system power is restored after the GSMHS has shut down, a
power-on reset condition exists, the module initializes itself and the battery will recharge.
Install the battery as follows, and refer to the Summary of Connections diagram at the end of
this document.
1. Place the battery inside the case back.
2. Snap the right side of the battery clip onto the inside of the case back and secure the
left side with the screw provided.
Do not plug the battery in until after you have powered-up the GSMHS.
Initial Power-Up Sequence
Before connecting power, check that the following have been completed:
If using ECP, 4204 or 2-4204 Mode, terminal block TB1 V+ and GND terminals are
connected to the control panel’s auxiliary power output: 12VDC nominal.
Plug in the transformer.
Connect the red and black battery cables to the battery terminals. Connect battery cable
to connector J1.
Power up the control panel.
Initially, all GSMHS programming options are set to the factory default settings.
2-6
SECTION 3
Programming the GSMHS
General Information
The GSMHS is designed to deliver alarms via the GSM network to an AlarmNet central
station when it is registered with a valid AlarmNet account.
The GSMHS module requires an AlarmNet–i account. For new installations, please obtain the
account information from the central station prior to programming this module. For replacement
installations, the AlarmNet-i account is created automatically when the module is registered (based
on the existing account).
You can program a GSMHS by one of the following methods:
Through the AlarmNet Direct website
Through use of a 7720P Programming Tool
Through a programming mode in the control panel on panels that support this option
(e.g., VISTA-128BP and FBP)
UL
Only ECP and Zone Trigger modes have been evaluated by UL.
Programming the Control Panel to work with the GSMHS
For Residential and Commercial control panels, there are certain programming field settings
that must be adhered to for using the GSMHS. (For programming information, please refer
to the appropriate control panel guides.) Ensure the following programming fields are set as
follows:
RESIDENTIAL / COMMERCIAL Control Panels (Such as the VISTA-10P, 15P, and 20P series.)
Programming Field Setting
29 Menu Mode for IP/GSM Enable
54 Dynamic Signaling Delay
55 Dynamic Signaling Priority
1 (Enable LRR.)
0 (Dialer and LRR reports go out at the same time.)
0 (Primary dialer reports first.)
COMMERCIAL Control Panels (Such as the VISTA-128/250 series.)
Programming Field Setting
56 Dynamic Signaling Delay
57 Dynamic Signaling Priority
58 Comm Central Station #1
Category Enable
59 Comm Central Station #2
Category Enable
#93 Menu Mode
00 (Dialer and LRR reports go out at the same time.)
1 (Communicator, as first reporting.)
111111 (All events will be reported to the primary Central
Station.)
000000 (If Central Station #2 is not used.)
111111 (If Central Station #2 is used.)
Zone programming – set Zone 803 for Type 05.
Device programming – set Address 03 for Type 06 (LRR).
3-1
GSMHS Installation and Setup Guide
Using the AlarmNet Direct Website
To program the module via the website (if you are already signed up for this service), go to:
If you are not signed up for this service, click on “Dealer Sign-Up.”
Log in and follow the on-screen prompts.
Please have the following information available when programming the module:
1. Primary City ID (two-digit number)
2. Primary Central Station ID (two-digit hexadecimal number)
3. Primary Subscriber ID (four-digit number)
4. MAC ID and MAC CRC number (located on the outside of box and on label inside
module) or MIN number of the device you are replacing
After programming is complete, you must transfer the data to the module and the module
must be registered. Refer to Section 4: Registration, for further instructions.
Using a 7720P Programming Tool
Connect the 7720P Programming Tool as shown below. The GSMHS powers the 7720P
Programming Tool via the programming jack, and automatically senses the presence of the
7720P when it is plugged in.
7720P
PROGRAMMING
JACK
Shift
BS / ESC
/
N / Y
Shift
Xmit
SpaceEnter
7720PROGRAMMINGTOOL
A
B
123
DE
45
S
7
F
6
T
X
98
#0
C
J1
BATTERY
CONNECTOR
GPRS
RSSI
IBS
M0
M1
7845GSM-005-V2
Figure 3-1. Cable Connections
Each key of the 7720P has two possible functions: a normal function and a Shift function.
To perform a normal key function, simply press the desired key.
To perform a Shift function, press the [Shift] key, and then press the appropriate key.
The prompts in this document reflect use of the 7720P Programming Tool. Table 2-1 below
lists each normal and shift key function.
Table 2-1. 7720P Normal and Shift Key (shift LED lit) Functions
KEY NORMAL KEY FUNCTION SHIFT KEY FUNCTION
BS/ESC [BS]: Press to delete entry
/ []: Scroll down programming []: Scroll up programming
N/Y [N]: Press for "NO" answer [Y]: Press SHIFT-Y for "YES" answer
SHIFT
Press before pressing a SHIFT key function. Will light SHIFT LED. LED goes out once a key
is pressed. Press again for each SHIFT function desired.
1/A [1]: For entering the number 1 [A]: For entering letter A
2/B [2]: For entering the number 2 [B]: For entering letter B
[ESC]: Press to quit program mode; also can reset
programming defaults*
3-2
3/C [3]: For entering the number 3 [C]: For entering letter C
4/D [4]: For entering the number 4 [D]: For entering letter D
5/E [5]: For entering the number 5 [E]: For entering letter E
6/F [6]: For entering the number 6 [F]: For entering letter F
7/S [7]: For entering the number 7 [S]: For entering letter S
8/T [8]: For entering the number 8 [T]: For entering letter T
9/X [9]: For entering the number 9 [X]: For entering letter X
SPACE [SPACE]: For scrolling option list No SHIFT function
0 [0]: For entering the number 0 No SHIFT function
#/ENTER
[#/ENTER]: Starts programming mode;
Press to accept entries
*Active only when the "Exit Programming Mode" prompt is displayed.
Using the Control Panel Programming Mode
Some control panels support programming of the GSMHS through the control panel
programming mode (e.g., Vista-128BP). If programming through the control panel, only
the ECP Mode programming options are available. The "mode" questions will not be
displayed, and the mode cannot be changed. For a description of key functions on the
control panel keypad, and how they map to the 7720P Programming tool, refer to the
control panel's Programming Guide.
Programming Conventions
Programming is accomplished by answering a series of prompts (questions). Most prompts
require only a [Y]es or [N]o response, while others require a numerical response (ID
numbers, etc.).
The current value is displayed on the second line in parentheses ( ). A "?" indicates an
invalid entry.
Section 3: Programming the GSMHS
No SHIFT function
Use the [ENTER] key to accept the current entry and proceed to the next prompt. If the
entered value is invalid, pressing [ENTER] re-displays the prompt; the next prompt is not
displayed until a valid answer is entered.
Use the up/down arrow keys to scroll through the programming questions without changing
any values. Press the [ESC] key to go to the end of the list of questions.
ECP Mode Programming
The GSMHS supports ECP messaging to communicate with the control panel. LRR-enabled
control panels send Contact ID format alarms to the GSMHS directly on the 4-wire console
bus. Not all control panels support the LRR interface on ECP, so be sure to check the
Installation and Setup Guide of the control panel to see if it supports this feature.
Refer to Table 2-2 for ECP Mode programming and follow the prompts.
Press the [ENTER] key to begin programming.
NOTE: The central station can remotely block access to local
device programming. If this has been done, the following
prompt appears:
NOTE: The default programming values for ECP mode are listed in the prompts below.
Table 2-2. Programming a GSMHS for ECP mode only.
PROMPTS ENTRY OPTIONS DESCRIPTION
Strt Prog Mode?
1
(Y/N)_
Enter Password
2
[Y], [N]
[0-9, A-F, N,
S, T, X, Y]
Enters programming mode.
If a password has been previously assigned, this
prompt appears.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
The next prompt appears.
Access to Prog
Mode Denied
3-3
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.