Honeywell AD365A, AD365A-IV Installation And Maintenance Instructions Manual

REMOTE
CAUTION
TENS ONES
9
10
11 12
13
14
15
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
INSTALLATION AND MAINTENANCE INSTRUCTIONS
AD365A and AD365A-IV Multi-Criteria Photoelectric, Thermal and Infrared Sensor
SPECIFICATIONS
Operating Voltage Range: 15 to 32 VDC Operating Current @ 24 VDC: 200 uA (one communication every 5 seconds with green LED blink on communication) Maximum Alarm Current: 2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on) Maximum Current: 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on) Operating Humidity Range: 15% to 90% Relative Humidity, Non-condensing Operating Temperature Range: 32°F to 100°F (0°C to 38°C) Air Velocity: 0 to 300 ft./min. (0 to 91.4 m/min.) Height: 2.0˝ (51 mm) installed in B300A-6 Base Diameter: 6.2˝ (156 mm) installed in B300A-6 Base; 4.1˝ (104 mm) installed in B501 Series Base Weight: 3.4 oz. (95 g) Isolator Load Rating: 0.0063*
*Please refer to your isolator base/module manual for isolator calculation instructions.
CAN/ULC S529 listed for Open Air Protection CAN/ULC S530 listed for Heat Detectors
This sensor must be installed in compliance with the control panel sys­tem installation manual. The installation must meet the requirements of the Authority Having Jurisdiction (AHJ). Sensors offer maximum perfor­mance when installed in compliance with CAN/ULC S524. For a complete list of compatible bases, refer to the Base/Sensor Cross Reference Chart at systemsensor.com.
GENERAL DESCRIPTION
Models AD365A and AD365A-IV are plug-in type multi-criteria smoke sen­sors that offer a photoelectric sensing chamber combined with a 135°F (57.2°C) fixed temperature heat detector and infrared (IR) sensors. The AD365A and AD365A-IV also transmit an alarm signal due to heat (135°F/57.2°C) per CAN/ULC S530.
All sensors transmit an analog representation of smoke density over a commu­nication line to a control panel. Rotary dial switches are provided for setting the sensor’s address. (See Figure 2.)
Two LEDs on the sensor are controlled by the panel to indicate sensor status. An output is provided for connection to an optional remote LED annunciator (P/N RA100ZA).
Fire-Lite panels offer different features sets across different models. As a result, certain features of the photoelectric sensors may be available on some control panels, but not on others.
AD365A will support only LiteSpeed® protocol mode. AD365A-IV will support either LiteSpeed or CLIP (Classic Loop Interface Protocol) mode. The pos­sible features available in the multi-criteria smoke sensors, if supported by the control unit are:
1. The sensor’s LEDs can operate in three ways—on, off, and blinking–and they can be set to red, green, or amber. This is controlled by the panel.
2. The remote output may be synchronized to the LED operation or con­trolled independent of the LEDs.
3. Devices are point addressable up to 159 addresses.
Please refer to the operation manual for the ULC listed control panel for spe­cific operation. The photoelectric sensors require compatible addressable communications to function properly. Connect these sensors to listed-compat­ible control panels only.
SPACING
Fire-Lite recommends spacing sensors in compliance with CAN/ULC S524. In low air flow applications with smooth ceilings, space sensors 30 feet apart (9.1 m). For specific information regarding sensor spacing, placement, and special applications, refer to CAN/ULC S524 and the System Smoke Detector Application Guide, available from Fire-Lite.
WIRING GUIDE
All wiring must be installed in compliance with the Canadian Electrical Code, applicable local codes, and any special requirements of the Authority Having Jurisdiction. Proper wire gauges should be used. The installation wires should be color-coded to limit wiring mistakes and ease system troubleshooting.
1 I56-9140-000 2/21/2019
I56-9140-000
10 Whitmore Road
Woodbridge, Ontario L4L-7Z4
Phone: 1-800-778-9958
Improper connections will prevent a system from responding properly in the event of a fire.
Remove power from the communication line before installing sensors.
1. Wire the sensor base (supplied separately) per the base wiring diagram. (See Figure 1.)
2. Set the desired address on the sensor address switches. (See Figure 2.)
3. Install the sensor into the sensor base. Push the sensor into the base while turning it clockwise to secure it in place.
5. Test the sensor(s) as described in the TESTING section of this manual.
FIGURE 1. WIRING DIAGRAM
ANNUNCIATOR
+-
(+)
2
1
3
C0129-04CDN
(–)
CONTROL PANEL
(–)
ULC LISTED COMPATIBLE
(+)
2
1
3
CLASS A OPTIONAL WIRING
2
1
3
Do not loop wire under terminal 1 or 2. Break wire run to provide supervision of connections.
FIGURE 2. ROTARY ADDRESS SWITCHES
C0162-00
FIGURE 3. FEATURES OF THE PTIR DETECTOR
CAUTION
CAUTION
Infrared
Light
Pipe
Base Alignment Notch
LEDs
Thermistors
Magnet Test Point
Infrared
Light
Pipe
C2050-00
FIGURE 4. CLEANING THE PTIR DETECTOR
Sensor Cover
Cover
Removal
Tabs
Sensing Chamber
Thermistors
Infrared
Light
Pipe
Cover and Screen
Sensing
}
Chamber
C2044-00
Dust covers provide limited protection against airborne dust particles during shipping. Dust covers must be removed before the sensors can sense smoke. Remove sensors prior to heavy remodeling or construction.
TAMPER RESISTANCE
Models AD365A and AD365A-IV include a tamper-resistant capability that prevents removal from the base without the use of a tool. Refer to the base manual for details on making use of this capability.
TESTING
Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily be out of service. Disable the system to prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Test­ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when tested and maintained in compliance with CAN/ULC S536. Sensitivity readings are available through the fire alarm control panel (FACP). Refer to the manufac turer’s published instructions for proper use.
The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)
This sensor can be functionally tested with a test magnet. The test magnet
electronically simulates smoke in the sensing chamber, testing the sensor electronics and connections to the control panel.
a. Hold the test magnet in the magnet test area as shown in Figure 3. b. The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel to indicate sensor
status. Coded signals, transmitted from the panel, can cause the LEDs to blink, latch on, or latch off. Refer to the control panel technical documen­tation for sensor LED status operation and expected delay to alarm.
NOTE: The magnet test initiates an approximately 10 minute period when
the detector's signal processing software routines are not active.
B. Smoke Entry
Canned aerosol simulated smoke (canned smoke agent) may be used for
smoke entry testing of the smoke detector.
The multi-criteria smoke sensor uses algorithms to process signals re-
ceived from multiple sensors to determine alarm conditions and reduce false alarms. Therefore, a single burst of canned smoke will not immedi­ately place the detector into an alarm condition because the detector al­gorithms correctly determine a burst of canned smoke is not fire. In order to perform functional testing of the photoelectric sensor, the device must be placed into test mode. Test mode allows the detector to isolate the indi­vidual sensors for testing. The device can be placed into test mode through either of the following methods.
a. Put the device into test mode by holding a test magnet in the magnet
test area as shown in Figure 3 for 6-12 seconds.
NOTE: If the magnet is held in place for too long the fire alarm test func-
tion will be triggered. (See Magnet Test, above.) Reset the panel and pro­ceed with testing the smoke entry portion of the device.
b. Perform smoke entry testing immediately following the magnet test. The
magnet test initiates an approximately 10 minute period when the detec­tor’s signal processing software routines are not active.
Once in test mode, test the smoke detector using one of the tested and ap­proved aerosol smoke products. Refer to the manufacturer’s published instruc­tions for proper use of the canned smoke agent. When used properly, the canned smoke agent will cause the smoke detector to go into alarm.
Tested and approved aerosol smoke products include:
Manufacturer Model
HSI Fire and Safety 25S, 30S (PURCHECK)
SDi SMOKE CENTURION , SOLO A10,
SMOKESABRE, TRUTEST, SOLO 365
No Climb TESTIFIRE 2000
Canned aerosol simulated smoke (canned smoke agent) formulas will vary by manufacturer. Misuse or overuse of these products may have long term adverse effects on the smoke detector. Consult the canned smoke agent manu­facturer’s published instructions for any further warnings or caution statements.
C. Direct Heat Method (Hair Dryer of 1000-1500 watts)
A hair dryer of 1000-1500 watts should be used to test the thermistors. Di-
rect the heat toward the thermistor, holding the heat source approximately 12 inches (30 cm) from the detector in order to avoid damaging the plastic housing. The detector will reset only after it has had sufficient time to cool. Make sure both thermistors are tested individually.
D. Multi-Criteria Testing
Testifire® by SDi provides testing of the smoke and heat sensors. Consult the
manufacturer’s published instructions for complete usage instructions.
A sensor that fails any of these tests may need to be cleaned as described under CLEANING, and retested. When testing is complete, restore the system to normal operation and notify the proper authorities that the system is back in operation.
CLEANING
Before removing the detector, notify the proper authorities that the smoke detector system is undergoing maintenance and will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent un­wanted alarms.
1. Remove the sensor to be cleaned from the system.
2. Remove the sensor cover by pressing firmly on each of the four removal tabs that hold the cover in place.
3. Vacuum the screen carefully without removing it. If further cleaning is required continue with Step 4, otherwise skip to Step 7.
4. Remove the chamber cover/screen assembly by pulling it straight out.
5. Use a vacuum cleaner or compressed air to remove dust and debris from the sensing chamber.
6. Reinstall the chamber cover/screen assembly by sliding the edge over the sensing chamber. Turn until it is firmly in place.
7. Replace the cover using the LEDs to align the cover and then gently push­ing it until it locks into place. Make sure that the thermistors do not be­come bent under the cover.
8. Reinstall the detector.
9. Test the detector as described in TESTING.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back on line.
SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS
Smoke detectors are not to be used with detector guards unless the combina­tion has been evaluated and found suitable for that purpose.
2 I56-9140-000 2/21/2019
Loading...
+ 2 hidden pages