Honeywell 700, 800 User Manual

Put Bar Code Here
Honeywell Model 700/800 Signal
Contents
Application ....................................................................... 1
Features ........................................................................... 1
Specifications ................................................................... 2
Approvals ......................................................................... 3
Installation ........................................................................ 3
Operation ......................................................................... 10
Modbus Communication .................................................. 14
Troubleshooting ................................................................ 17
Maintenance .................................................................... 17
Safety Manual: 700 Signal Processor .............................. 33
Safety Manual: S70X & 80X Viewing Head ..................... 36
Processor and Viewing Head
USER MANUAL
• Model 700ACSP Universal 85-265 VAC powered, plus 24VDC backup.
• Model 700DCSP 22-26VDC powered, plus 24VDC backup.
The two Model 700 signal processors are similar, with 12 push-buttons, a two-digit numeric display, and four LED status indicators for operator interface. The only difference between the two is that one accepts AC power and the other accepts DC power. Both models also accept 24VDC backup power. Most of the signal processor connections are made through Phoenix plug-in connectors. Communication connections are made through modular phone jacks located at the top of the signal processors (Fig. 8).
Both signal processor models mount on a standard 35 mm DIN rail. They snap into place and may be released from the rail using a flat screwdriver.

APPLICATION

The Honeywell Model 700ACSP and Model 700DCSP signal processors are single-channel, fail safe, flame monitoring systems when used In conjunction with the S70X/S80X viewing heads. They offer easy setup, excellent discrimination, and high reliability.

FEATURES

Viewing heads are interchangeable between the two signal processor models. Any viewing head in the two families will work with any of the signal processors.
Two signal processor models are available:
There are two types of viewing heads—IR/flicker-sensitive and UV-sensitive—with various features offered resulting in ten different models. See Table 1 on page 2 for details.
The S702 and S706 viewing head housings are larger in diameter than the S80X series, are made of aluminum, and are secured with over-center latches to their mounting blocks (Fig. 9). In contrast, the S802 and S806 viewing head housings are smaller in diameter and are made of stainless steel (Fig. 10). An 800 series viewing head is secured in its mounting block by a friction twist-lock.
The IR/flicker sensitive viewing heads have a high-pass filter that passes flicker frequencies above 33 Hz. Some models have a built-in high pass filter that only passes frequencies above 155 Hz. The high frequency filter models are identified by adding “HF” to the model number. The UV models respond to the level of UV radiation—not UV flicker—so there is no filter option.
66-2069-02
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
Table 1. Available viewing head models and associated features.
Pipe Fit Connection
0.5 in. NPTM with 50-ft
Model Connector
S702 X X X
S702HF X X X X
S702PF X X X
S702HFPF X X X X
S706 X X X
S706PF X X X
S802 X X X
S802HF X X X X
S806 X X X
1. All models include Electronic self-check.
2. Flicker Frequency filter settings available for IR sensor
models.
3. Gain Selection available through Signal Processor.
The viewing heads, the viewing head connector, and the cable provided are watertight, and have NEMA 4X ratings when the connector is properly tightened with pliers and the cable is protected from UV exposure.
The availability of both UV-sensing and IR/flicker-sensing viewing heads ensures that the flame monitoring systems can provide good discrimination in most single and some multiple burners firing a single fuel. UV sensing is appropriate for monitoring natural gas, some mixed gases and light oil flames. IR/ flicker sensing is appropriate for monitoring heavy oil and coal flames.
(15.2 m) pigtail
UVTron Sensor IR Sensor
UV Detector Spec
S706 & S706PF, S806: UVtron with spectral response 185nm
to 260nm and a peak response at 210nm
UV Optical
Angle of View: 5 degrees (1 inch per foot)
Cable & Connectors - S70X/S80X Viewing Heads
New installations - highest level of EMI shielding available:
ASY785 --> 50 foot C330S cable with pre-wired ASY786
connector.
ASY785-200 --> 200 foot C330S cable with pre-wired
ASY786 connector.
ASY786 --> Field wireable connector with shield.
Dimensions
Refer to Fig. 9 and Fig. 10.
High
Frequency
Filter 155Hz
Aluminum
Housing
Stainless Steel
Housing
Model 700ACSP & Model 700DCSP Signal

SPECIFICATIONS

Series 700 and 800 Viewing Heads
MODELS S702, S702PF, S702HF, S702HFPF, S706, S706PF, AND MODELS S802, S802HF, AND S806
Electrical
24VDC Power is supplied by Signal Processor
Environmental
Viewing Head Sealing: NEMA TYPE 4X rated when the
molded connector ring is tightened with pliers and a UV protection is provided for the cable by installing in conduit.
Ambient Temperature: -40°F to 185°F (-40°C to 85°C)
IR Detector Spec
S702, S702PF, S702HF, S702HFPF, S802, S802HF:
Germanium photodiode with spectral response 950nm to 1710nm (1/2 intensity points) and peak spectral response at 1400nm
High Pass Filter Pickup: 33 Hz standard, 155 Hz high
frequency option (-HF)
IR Optical
Angle of View: 1 degree (1.45 in. dia. at 6 ft. or 3.7 cm dia. at
1.8 m)
Processer
Electrical: Model 700ACSP
Primary Input Power: 85-265VAC, 50-60 HZ, 0.07A Max.
fused (with either V.H. connected)
Battery Backup Voltage: 22VDC to 26VDC, 0.2A DC Max.
fused (with either V.H. connected)
Electrical: Model 700DCSP
Primary Input Power: 22VDC to 26VDC, 250 mA Max. fused
(with either V.H. connected)
Battery Backup Voltage: 22VDC to 26VDC, 0.5A DC Max.,
fused (with either V.H. connected)
Outputs
Flame Relay: 2 form C contacts Self-Checking Relay: 1 form C contact Relay Contact Ratings: 5A at 125 VAC, 277 VAC, & 30 VDC;
1/8 HP 125 & 250 VAC
Analog Flame Signal: Isolated 0 to 20 mA or 4 to 20 mA
output for remote meters or DCS, 360 ohms maximum resistance
Environmental
Ambient Temperature: 32°F to 140°F (0°C to 60°C)
Dimensions
Refer to Fig. 11 and Fig. 12.
66-2069—02 2
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
WARNING

APPROVALS

S70X/S80X Viewing Heads (Connector series and Pipe fit series [PF])
CSA for CLASS I, DIV 2, GROUPS A, B, C, D & T4A FM 7610/NEMA 4X and CLASS 1, DIV 2, GROUPS A, B, C, D
& T4A* SIL 3 “Fit for Use” IECEx CSA 10.0003 Ex nA IIC T4 Gc
-40<Ta<85ºC, -40<TA<185ºF
*IP67/NEMA 4/4X rating applies when connector ring is
properly tightened and cable is UV shielded
700ACSP and 700DCSP Signal Processors
CSA (C, US) FM

INSTALLATION

When Installing These Products...

1. Read these instructions carefully. Failure to follow them
could damage the products or cause a hazardous condition.
2. Check the ratings given in the instructions and one the products to make sure the products are suitable for your application.
3. Installer must be a trained, experienced, flame safeguard control technician.
4. After installation is complete, check out product operation as provided in these instructions.

Signal Processor Mounting

The 700ACSP and 700DCSP signal processors mount on a standard 35mm DIN rail. They snap into place and may be released from the rail using a flat screwdriver.

Grounding and Shielding

NOTE: Installer must be a trained, experienced flame
safeguard service technician and should be familiar with the equipment operation and limitations and be aware of any applicable local codes and regulations.
1. Connect a safety ground to the viewing head housing (if
applicable). A ground screw is provided on the exterior of the viewing head housing for this purpose.
The viewing head housing is grounded through cable/signal processor, so you must ensure that AC/DC potentials at ground of signal processor and viewing head are the same, or damage to the cable or signal processor can result.
2. The viewing head and all associated cable/conduit must
be at least 12 inches (31 cm) from any source of high energy or voltage (for example, igniter equipment).
3. Install a ground wire from the ignition transformer case to the igniter assembly.
4. Ensure all igniter wires and cables show no signs of wear. Replace any igniter cables or wires that are frayed or cracked.
5. The viewing head must be electrically isolated from the burner front. a. Electrical isolation can be accomplished by
installing an Ultem nipple (R-518-13) or an Ultem locking coupler adapter (R-518-PT13 or R-518­PT13L) in conjunction with a locking coupler (R-518­CL13-HTG) between the viewing head flange and the burner mount.
b. The purge air line should also be isolated from the
viewing head. This can be accomplished by installing any insulating material, for example a rubber hose, in between the purge air line and the viewing head.

Signal Processor Power Connections

The Model 700ACSP power and relay connections are shown in Fig. 1. The AC power supply to the 700ACSP Signal Processor passes through a 2A fuse and an inrush current limiter.
The Model 700DCSP power and relay connections are shown in Fig. 2. The maximum current requirement for each 700DCSP is 250mA.
In the Model 700 signal processors the flame relay (RF A/B ON, OFF, COM) has two sets of FORM C (SPDT) contacts and the self-check relay (SC ON, OFF, COM) has one set (Fig. 1 and Fig. 2). The self-check relay is energized whenever the signal processor is powered and is operating normally, whether the flame relay is energized or not. Internally, the flame relay is wired in series with the self-check relay (not shown), which prevents the flame relay from energizing if the self-check relay is not energized.
Unique fail-safe circuitry for the self-check and flame relays ensure that in the event of any critical component failure occurrence, system response will be to de-energize the self­check relay, which in turn de-energizes the flame relay.
Some of the internal power wiring of the Model 700ACSP and Model 700DCSP signal processors is shown in Fig. 1 and Fig. 2. Rectifier diodes separate the battery backup input from the main power bus until the battery voltage exceeds the internal DC voltage plus a diode voltage drop. Resettable fuses (shown as resistors with slashes) and conventional fuses prevent internal failures from loading the power sources. With the Model 700DCSP, if a backup battery is to be used with a main power supply, the two power sources would be wired as shown in Fig. 2. If no backup battery is to be installed, the main power supply can be connected at +26V PWR and GND as shown in Fig. 2 or it can be connected to the +24V BATT input and GND. It is preferable to use the battery connections because it takes advantage of the resettable fuse at the battery input; resettable fuses recover automatically from a fault within a few seconds after power is removed. At the +26V PWR input and its associated GND, conventional1A fuses are used because they are able to protect against 240VAC being applied by accident (this could happen if a Model 700DCSP is installed in a cabinet wired for a Model 700ACSP).
3 66-2069—02
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
APPROVED
AC IN
GROUND
TO VIEWING HEAD
24 V BACKUP BATTERY (OPTIONAL)
0-20 OR 4-20 MA
FOR INDICATOR OR
INSTRUMENTATION 360 OHMS MAX
+
-
+
-
CHASSIS, EARTH, OR SYSTEM GND
M34280
+
+26VDC
GND
.125 A
.4A
2
A
AC POWER
SUPPLY
-t°
Fig. 1. Model 700ACSP Signal Processor Wiring.
66-2069—02 4
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
+
+26VDC
GND
.4A1A 1A
.125 A
LIM
M34282
APPROVED
24 V BACKUP BATTERY (OPTIONAL)
+
-
0-20 OR 4-20 MA
FOR INDICATOR OR
INSTRUMENTATION
360 OHMS MAX
+
-
CHASSIS, EARTH, OR SYSTEM GND
DC POWER SUPPLY
250 MA
+
-
+26
PWR
TO VIEWING HEAD
Fig. 2. Model 700DCSP Signal Processor Wiring.
5 66-2069—02
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
WHITE
BLACK
RED
GREEN
TERMINAL
VH SIG
VH SC
VH +V
VH GND
CONDUIT
ENCLOSURE
S702PF, S702HFPF OR S706PF
SHIELD
C330S YELLOW 4-CONDUCTOR WITH DRAIN AND SHIELD
STANDARD "PIGTAIL" LENGTH = 10 FEET (3 METERS)
M34285B

Viewing Head Connector and Wiring

Viewing heads are wired to the appropriate terminals located on bottom of the 700ACSP, 700DCSP, P531 or P532 signal processors. The terminals are listed functionally in Table 2.
Table 2. Terminal Descriptions.
700ACSP or
700DCSP
Ter minal
P531 or
P532
Terminal
VH SIG VH3 SIG Flame Signal from Viewing Head
VH SC VH3 SC Shutter Drive Signal to Viewing
Head
VH +V VH3 +V +24VDC Power to Viewing Head
VH GND VH3 GND GND Signal Ground
Connectors and cables are shown in Fig. 3, Fig. 4, and Fig. 5. Fig. 3 shows the viewing head cable with the 1/2 in. NPT pipe fitting and pigtail for use in a conduit. The PF model comes with 50 feet of Honeywell C330S cable. This cable is recommended for all new installations. It has ITC and CIC ratings for hazardous location. Figs. 4 and 5 describe the C330S cable used with the right angle field-wireable connector. Refer to “Accessories” on page 9 for part numbers.
The customer may also supply his own cable; a replacement mating viewing head connector should be ordered. Refer to
Description
“Accessories” on page 9 for part numbers. The use of 22g, 4­conductor cable with shield and drain is recommended. The shield should be foil and braid type surrounding all conductors. The shield should be connected to GND at the processor end. The cable diameter should not exceed 0.307" in order for it to go through the hex bushing in the connector. But note that wiring the cable to the connector is not easy because of the limited space. Also, the LED indicator assembly must be mounted inside the connector and, preferably, soldered in place. Thus, it is recommended to purchase a pre-wired cable and connector assembly from Honeywell.
NOTE: FOR CLASS I, DIV 2 RATING, CABLING IN
HAZARDOUS LOCATIONS MUST COMPLY WITH NEC ARTICLE 500 REQUIREMENTS AND APPLICABLE GOVERNING CODES.
In the U.S., cables should have UL’s ITC rating; in Canada, cables should have CSA’s CIC rating. The recommended C330S cable has both ratings.
NOTE: To obtain a NEMA 4X seal between the connector
and the viewing head, tighten the metal connector ring securely.
Fig. 3. Model 700 Viewing Head Cable With 1/2 in. NPT Fitting.
66-2069—02 6
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
NOTE: IMPORTANT INSULATE DRAIN WITH SHRINK TUBING LEAVING 3/8" STICKING OUT.
M35139
STRIP 3/8 INCH TYPICAL
1-19/64 (33) TYPICAL
VH SC
5-16 (8) MAX
VIEWING HEAD CONNECTOR LOOKING AT PINS
VH SIG
C330S YELLOW, 4 COND WITH FOIL/BRAID SHIELD AND DRAIN (ITC & CIC)
Fig. 4. Model 700/800 Viewing Head Cable Connections.

Cable Preparation

NOTE: This section will typically be used for reference
only. The S70X/S80X connector parts are very small and delicate and difficult to assemble. It is advisable to purchase pre-made cables from Honeywell.
GREEN LED
VH +V
VH GND
METAL CONNECTOR RING
2. Pull braided and foil shield back so that only drain wire
3. Insulate the drain wire with heat shrink.
4. Strip other wires as shown in Fig. 5.
ORANGE LED
CONNECTOR REAR VIEW WITH NUT LOOSENED AND COVER REMOVED
WHITE
BLACK
RED
SHIELD
GREEN
TERMINAL
VH SIG
VH SC
VH +V
VH GND
M34286A
is at 2 inch length. Trim the foil and braid shields at the cable jacket.
Honeywell C330S cable is recommended for use with the S70X/S80X viewing heads and signal processors. C330S has a UL ITC rating and can be used in the U.S. in hazardous locations.
NOTE: Shield shrink tubing is required on shield drain
wire at the signal processor end.
Preparation of the C330S cable at the signal processor should be done as follows:
1. Referring to Fig. 5, strip cable 2 inches back to expose the braided shield.
Fig. 5. C330S Signal Processor End Cable Preparation.
Connection of the Honeywell type C330 cable to the viewing head plug is shown in Fig. 6. Cable preparation should be done as follows:
1. Prepare C330S wire at plug end similarly to Fig. 5, but shorten the drain/shield to approximately 1/4 inch only at the plug end (see Fig. 6).
2. Assemble the field-wireable plug as shown in Fig. 6. Ensure that: a. Wires are in proper locations per Fig. 4. b. Shield is pressed against connector housing. c. Connector back plate gasket is in place before
installation.
d. After assembly, check that connector is tight and
well secured.
7 66-2069—02
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
Fig. 6. ASSY786 Viewing Head Plug Assembly with C330S.
M35140

Protecting the Viewing Head Cable (Connector Series)

Note that when the wiring needs to meet Class I, Division 2 requirements for use in hazardous locations and when conduit is used, the conduit must be sealed where the cable passes from the hazardous location to the non-hazardous location in order to keep potentially hazardous gases from being conducted into the non-hazardous area.

Viewing Head Connector LED Indicators

The viewing head connector has orange and green LEDs which can be viewed from the rear of the connector when the connector cover is removed.
The green LED displays the pulses out of the viewing head and the orange LED shows that the self-checking signal from the signal processor is reaching the viewing head. If power is on at the signal processor, the orange LED should flash at one pulse per second, even if the viewing head is not plugged in. This is helpful in troubleshooting.
With no flame signal present, the green LED will flash one pulse per second in step with the self-checking signal. The viewing head is sending back an ID pulse; this is part of the self-checking system. When a flame is present, the green LED will flash at a rate proportional to the flame signal, except when the pulses are interrupted once per second for the self­check pulse arrival at the viewing head. The pulse rate of the green LED flashes can be used for aiming the viewing head.
NOTE: The LED indicators are provided for alignment
and troubleshooting only. Reinstall cover with gasket correctly in place at all times, and ensure that connector coupling is tightened securely. This gasket and cover must be installed properly to maintain NEMA rating.

Viewing Head Mounting and Sighting

Mounting is 1/2-in. NPT (F) for all viewing head models with a 1/4-in. NPT (F) purge air connection. Before beginning installation, determine the best location for mounting the viewing head based upon the following factors:
Viewing Head Mounting Block
The S70X viewing heads are held firmly in place in their mounting blocks by two galvanized steel latches. The S80X viewing head is secured in its mounting block by a friction twist-lock. Refer to the ACCESSORIES section for part numbers.
Pressure
The S70X viewing head lens will withstand 50 psi (3.4 bar) while the S80X lens will withstand 90 psi (6.2 bar), provided the compression ring on the purge air adapter is tightened properly. If the lens assembly is exposed to greater pressures through the sight pipe, then an isolation unit must be used. Honeywell isolation units with purge air entrance are available as accessories; ISO-UNIT, ISO-UNITSS, ISO-UNITHPGT. Each has a quartz window, two 1-in. NPTF connections and a 1/2-in. NPTF purge port.
Temperature
The case temperature of the viewing head housing must not exceed 185°F (85°C) while the standard Delrin mounting block must not exceed 180°F (82°C) continuous service. Care should be taken to ensure the case housing and mounting block temperatures do not exceed these values.
Purge air will help reduce conducted heat through the sight pipe and flange. A heat insulating Ultem replacement viewing head mounting block is available for both the S70X/S80X models (part numbers 700UA and 800UA) with a continuous service rating of 320°F (160°C) as well a 1/2-in. NPTM Ultem nipple (part number R-518-13) or an Ultem locking coupler adapter (R-518-PT13 or R-518-PT13L) to reduce the conducted heat, but direct radiation can cause the housing case temperature to exceed limits. If the ambient heat (direct radiation) is excessive, then an air cooling canister with vortex cooler should be considered or alternately a fiber optic extension. The extension uses a fiber optic cable assembly between the sight pipe and the viewing head, allowing the viewing head to be placed further away from the heat source. Refer to the Fiber Optic Manual 69-2683 or contact your distributor or the factory for assistance with fiber optic selection and pricing.
Purge Air
Use a flexible air supply line, to allow for repositioning of the viewing head and sight pipe until a final and permanent
66-2069—02 8
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
position has been decided. A continuous flow of air must be maintained in order to reduce the conducted heat and to keep the sight pipe and viewing head lens free of dirt and debris. Air required is about 5 SCFM (0.13 Nm3 /min) delivered at 1 in. (25mm) above the maximum pressure as measured at the “Y” or “T” section of the purge air connection for each viewing head. The air supply must be clean, free of oils and water, and preferably cool. In order to electrically isolate the viewing head, the purge air line should be installed using an insulating material, such as a rubber hose, in between the purge air line and the viewing head.
Vibration
Do not install the viewing head where it could be subject to high vibration. Provide an anti-vibration mount if excessive vibrations are present.
Clearance
Make sure there will be sufficient room to remove the viewing head housing for servicing.
Viewing Head Mounting
Honeywell offers a range of swivel mounts, both pipe thread or flange mounting for use with sight pipes or direct wind box mounting. See “Accessories” on page 9 or the Honeywell website for further details.
Viewing Head Sighting
The sighting of the viewing head should be parallel to the center line of the burner in the direction of the flame. If used, the sight pipe should be mounted as close to the center line as possible so as to sight along the flame rather than across the flame. Doing so will ensure continuous flame detection under changing load conditions. See Fig. 15, 16 and 17.
Utilizing a sighting or the sight pipe aimed at the root of the flame (where the turbulent combustion air mixes with the flame) is a good starting point for optimizing the sighting. Where practical, using a swivel mount to “zero-in” on the highest signal will assure maximum performance. The optimum scanner location is parallel to the burner center line. The use of a swivel mount allows for line of sight adjustment, where practical to use.
Examples of viewing head installation with and without a swivel mount are shown in Fig. 13 and Fig. 14. If using a sight pipe, its diameter should be large enough to allow a reasonable field of view, and to allow for adjustment of the swivel mount angle.
In some instances, it may be beneficial to use two sets of setpoints for Flame On, Flame Off and gain. The two-channel capability (primary and alternate viewing head settings) is ONLY possible when using the P531 or P532 signal processors; it is not possible when using the 700ACSP or 700DCSP signal processors. The switch-over from Channel A to Channel B can be implemented from the burner control system. Refer to the P531/P532 user manual, 66-2068, for further information regarding switch-over and the use of Channels A and B with independent settings.

ACCESSORIES

Orifice disks (kit M-702-6) - Used to reduce the signal
brightness in cases where the signal brightness is too strong. Located immediately in front of the lens, it will reduce the amount of signal to the sensor. Bag assembly contains orifice disks and retaining rings. Orifice disks come with 3/8, 1/4, 3/16 and 1/8 inch diameter holes. Contact the factory for guidance in using orifice disks.
Insulating nipple (R-518-13) - 1/2-in. NPTM Ultem heat and electrical insulating nipple typically used in conjunction with a swivel mount and union.
VH insulating mounting block (700UA, 800UA) - 1/2 in. NPTF Ultem heat and electrical insulating mounting block, used in place of the supplied Delrin mounting block. 1/4 in. NPTF purge air connection. Typically used in conjunction with a swivel mount. Rated for continuous service up to 320°F (160°C).
Swivel mounts, small (700-1, 700-2, 700-3) - All have 1/2 in. NPTM viewing head connections on one end with varying process connections including 1 in. NPTF, 1/2 in. NPTF and 1/2 in. flanged.
Swivel mounts, large (M-701-1, M-701-2, M-701-2-FLG, M­701-2-SS, M-701-3, M-701-3P, M-701-4) - All have 1 in NPTF
viewing head connections, one end with varying process connections including 2 in. pipe slip on, 2 in. NPTF, 2 in. flanged, 2 in. NPTF in stainless steel construction, 4.5 in. flanged with 3 bolts, 3 in. NPTF and 2-bolt flanged. Appropriate fittings must be used to adapt the 1/2 in. NPTF viewing head process connections.
Insulating locking coupler adapters (R-518-PT13, R-518­PT13L) - 1/2 in. NPTM Ultem adapters insulate the viewing
head electrically and thermally and are used with the R-518­CL13-HTG locking couplers. The R-518-PT13L has a quartz lens.
Locking coupler (R-518-CL13-HTG) - Used with the R-518­PT13 and R-518-PT13L insulating locking coupler adapters. Process connection end is 1/2 in. NPTF.
Connector - ASY786 --> Replacement field wireable connector.
Cable and Connectors - S70X/S80X Viewing Heads ASY785 --> 50 foot C330S cable with pre-wired ASY786 connector. ASY785-200 --> 200 foot C330S cable with pre-wired ASY786 connector.
Cable (C330S) - 4-conductor with drain, foil/braided shield. Sold per foot.
Isolation Units (ISO-UNIT, ISO-UNITSS, ISO-UNITHPGT) - All have 1 in. NPTF connections with 1/2 in. NPTF purge ports and quartz window. Painted aluminum or stainless steel construction. The HPGT version has a 1/2 in. thick quartz window for higher pressures. Appropriate fittings must be used to adapt the 1/2 in. NPTF viewing head process connections.
Air cooling canister (700ACC, 800ACC) - Has an air inlet port on side. Used with vortex coolers. S80X models can be used with the 700ACC if the 800ACC-RING adapter is used.
9 66-2069—02
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
Vortex coolers (M3204, M3208, M3210, M4025) - Used with air cooling canister. Contact your distributor or the factory for selection assistance.
Cable restraints (800CR, 700CRLT) - Liquid tight S80X and S70X cable restraint versions. The 800CR includes the 700CRLT and the 800ACC-RING adapter.
S80X adapter ring (800ACC-RING) - Adapter ring to fit S80X viewing heads to 700ACC cooling jacket and 700CRLT liquid tight cable restraint.
Right angle adapter (700RAA) - S70X/S80X viewing head right angle adapter. 1/2 in. NPTF to 1/2 in. NPTM connections.
Mounting blocks (700DA, 700DA-1, 800DA) - Delrin replacement adapter/mounting blocks for S70X and S80X viewing heads. All have 1/4 in. NPTF purge air connections. Rated for continuous service up to 180F (82C). The 700DA and 800DA have 1/2 in. NPTF process connections while the 700DA-1 has a 1 in. NPTF process connection. For more 1 in. NPT accessories that can be used with the 700DA-1, refer to the S55XB/BE manual, 66-2064.
USB to RS422/RS485 Converter (COMMOD) - Protocol converter for use with external communication with a remote computer.
Fiber Optic System Compatibility - The S70X and S80X viewing heads are compatible with the Honeywell FASA fiber optic extension products. The S700FOAD and S800FOAD adapters are applicable, depending on the application. Contact your distributor or the factory for assistance with fiber optic selection and pricing.

OPERATION

IR Detector

The S702 and S802 viewing head models use a Germanium photodiode, which responds to IR radiation/flicker in the flame. Flame flicker is caused by the combustion, or forced air injected in to the flame. Combustion air can be mixed with the fuel (pulverized coal) or can be introduced separately. In either case, forced air is introduced in such a way as to aid the combustion process. This air is usually made turbulent by causing it to swirl with spin vanes located in the burner throat. Flame flicker is created when turbulent air mixes with the flame. It is composed of random frequencies and the amount of high frequency flicker is dependent on the fuel and the burner.
The S702, S702PF and S802 viewing head models respond to flicker frequencies above 33Hz while the S702HF, S702HFPF and S802HF viewing heads respond to flicker frequencies above 155Hz. All flicker frequencies below the filters are ignored, so it is important to sight the viewing head on the highly turbulent portion of the flame that contains the higher frequencies. The location of the higher frequencies can be predicted by examining the burner with regard to where the turbulent air enters the flame. The optimum scanner location is parallel to the burner center line (Fig. 15). The use of a swivel mount is encouraged to allow for line of sight.
Filter Selection for IR Viewing Head
If a good count ratio between BNR-ON and BNR-OFF cannot be obtained when using an IR viewing head—particularly when monitoring oil flames—an IR viewing head with the High Frequency (HF) filter option is recommended. The standard IR viewing head responds to flicker frequencies above 33 Hz; with the HF option, the IR viewing head responds to flicker frequencies above155 Hz.

UV Detector

The S706, S706PF and S806 viewing head models use the UVTron tube, with a spectral response of 185-260nm and peak response of 210nm to ultraviolet radiation. The output of the detector is a pulse stream of randomly spaced pulses whose average rate is proportional to the UV radiation present in the flame. The UV radiation is a direct result of the combustion process as oxygen combines with hydrocarbons in the fuel in the blue part of the flame. The yellow part of flames, and the background radiation from hot refractory, do not emit UV radiation.
The spectral range of the UV tube makes it ideal for discriminating between flame and glowing refractory. As with any UV radiation, it can be absorbed or masked by unburned fuel, smoke, oil mist, dirt dust and other impurities in the fuel. Care should be taken to select the proper viewing head for the fuel used. Additionally, the contaminants that mask UV can be diluted by providing a strong flow of air through the sight pipe to clear a viewing path through the attenuating material. See “Purge Air” on page 8.
It may also be desirable to sight the detector at an area containing fewer masking agents such as near the burner nozzle or near the entrance of the combustion air. Increasing the viewing area of the detector by shortening the sight pipe or by increasing the diameter of the sight pipe can also reduce the attenuating effects of the masking agents.
In general, the UV viewing heads will work well on natural gas and light oil flames. The sighting for both oil and gas flames should be parallel to the axis of the burner and aimed at the root of the flame, as with the IR detector. (See previous section, “IR Detector.”) The highest UV intensity occurs near the root of the flame (Fig. 16). In addition, the zone of higher UV intensity does not overlap the same zones of adjacent or opposing burner so that, with proper sighting, discrimination can be achieved.
With low NOx gas burners, the UV radiation is usually much less in intensity and spread out. Relatively high readings can be obtained from all over the furnace when many burners are in service. This is particularly true when flue gas recirculation is used. There will however, be a relatively stronger signal near the “root” of the flame and the more intense spot should be located during the aiming or sighting process. This “root” or intense spot may be further out than with the standard gas burner so it is imperative that a swivel mount be used when making sighting adjustments.
Another factor that needs to be considered when aiming the viewing head is the load condition of the boiler. The flames from a burner can be radically different at different loads. This is one of the reasons for choosing an optimum sighting initially that will minimize signal swing due to changing loads.
66-2069—02 10
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD

Self-Checking

The self-check circuitry guards against internal component failure. There are several tasks that require intelligent interaction between the viewing heads and the signal processor. If all of these interactions do not occur properly, the viewing head will not send pulses back to the signal processor and the flame relay will open.

Adjustment of VH Sighting and Gain

NOTE: Adjustment to the viewing head parameters
cannot be made unless the viewing head is connected and communicating with the signal processor.
The viewing head should be properly sighted before the setpoints are adjusted. Adjustment can be made easier by a 1/2 in. swivel joint, which Honeywell can supply if one is not available (refer to “Accessories” on page 9).
While the burner is firing, vary the viewing angle while observing the green LED on the connector at the rear of the viewing head. Adjust the viewing angle for the maximum pulse rate, then lock the swivel joint to preserve this mechanical setting. If the green LED pulse rate is very high or very low, see the two paragraphs below. The locked mechanical setting should still be correct when Model 700 viewing heads are interchanged, because inside each Model 700 viewing head the optical axis is aligned with the mechanical axis within ±1/4 degree. Also, the reading shouldn’t change when a viewing head is rotated in the mount.
For the above sighting adjustments to work properly, the flashing rate of the green LED in the connector at the rear of the viewing head must be reasonable. On the -PF (pipe fitting) version, there are no LEDs. The installer must observe the flame signal on the signal processor instead.
A count rate of 16 to 20 is recommended for proper operation. If the displayed count is above 25, the pulses begin to blur together, making changes in the pulse rate difficult to observe.
If the displayed count is less than 8 or 10, it will be difficult to maximize the count by adjusting the viewing head aim, since the pulses occur too infrequently. In such a case the gain should be increased. If the gain is set to a maximum and the count rate persists below 8 or 10, the system can still be made to work reliably as long as the count rate drops significantly when the flame is removed. However, the setup should be reviewed for proper viewing head aim and sight path to ensure it is optimized.

Orificing

Orifice disks have been used in applications with older viewing heads that did not have adjustable gain in order to reduce the extreme brightness of certain burner flames. The orifice disk kit is part number M-702-6. Orifice disks come with 3/8, 1/4, 3/ 16 and 1/8 inch diameter holes. Contact the factory for guidance is using orifice disks. The disks are installed with retaining rings in the flange at the edge of the 1/2 inch NPT female pipe thread for the process connection. An internal type retaining ring is first installed by positioning a ring in the machined groove inside the flange opening from the housing side. The orifice disk is then inserted. Use a second retaining
ring to hold it in place so that it is sandwiched tightly between the two retaining rings.
If the displayed flame count is 25 or higher when the gain is set to 1, an orificing disc inserted in the back end of the mounting block can be used. Choose a disc that gives a reading of 12 to 24 at a low fire firing rate. The discs have a range of orifice sizes; each size step results in about a 2:1 change in the counts displayed.

Signal Processor User Interface

The 700ACSP and 700DCSP signal processors have a user interface that includes four lights, a two-digit display and twelve push buttons for operation and programming. Each button has at least one specific purpose.
To enter a menu, press and hold the applicable button for 2 seconds. Adjustments to the applicable setpoint can be made via the INCREASE or DECREASE arrow buttons. To store the new setting, press the STORE button until “--” is shown, indicating the value has been accepted.
If no activity occurs for a period of four seconds while the menu value is displayed, it will revert back to the operating display.
To exit a menu at any time without saving changes, simply press the RESET/rE button.
The following describes the functions of the LED indicators, display and push buttons:
Front Panel LED Indicators and Display
• ON SEQ/AUTO SET LED (green):
— Used in conjunction with the BNR-ON SEQ START/
END and BNR-OFF SEQ START/END buttons during the automatic setup process
• OFF SEQ/FAULT LED (green):
— Used in conjunction with the BNR-ON SEQ START/
END and BNR-OFF SEQ START/END buttons during the automatic setup process
— Indicates a fault condition
• Two digit display
— When in operating mode, the display indicates the
current flame signal, which ranges between 00 and 29
— Upon power up, indicates whether an IR or UV viewing
head is attached and the selected gain setting; such as r7 (IR with gain of 7) or u5 (UV with gain of 5).
— Indicates various characters during the automatic
setup process as well as whether the panel is locked
• FLAME SIG LED (yellow):
— When a flame is present, LED flashes at a rate
proportional to flame signal, except when the pulses are interrupted once per second for viewing head self­checks.
• FLAME ON LED (red):
— When the flame signal is above the selected value, the
LED will be illuminated and the flame relay will be energized.
Push Button Functions
• RELAY ON SETPOINT button:
— Allows user to select flame on threshold value. When
the flame signal is above the selected value, the flame relay will be energized. Used in conjunction with the
11 66-2069—02
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
INCREASE, DECREASE and STORE buttons (range of 00 to 29).
• LOAD FACTORY DEFAULTS button:
— Used to restore all settings to the factory default
values
INCREASE button:
— Used to increase parameter value when in
programming mode
• RATIO (%) RELAY OFF/RELAY ON button:
— Used along with the INCREASE, DECREASE and
STORE buttons to set the RELAY OFF setpoint at a percentage of the RELAY ON setpoint. Adjustable from 20% to 80%.
•STORE button:
— Stores new parameter values during programming — After making changes “--” will be displayed indicating
the new values are accepted and stored
DECREASE button:
— Used to decrease parameter value when in
programming mode
• BNR-ON SEQ START/END button:
— Used to initiate and proceed through the automatic
parameter setup sequence, which includes the RELAY ON, RATIO (%) and GAIN settings (the FFRT, mA output and communication address must be set manually)
• BNR-OFF SEQ START/END button:
— Used during the automatic parameter setup sequence
• ACCEPT RATIO/SET GAIN button:
— Allows user to set the viewing head gain in conjunction
with the INCREASE, DECREASE and STORE buttons
— Used in conjunction with the BNR-ON SEQ START/
END and BNR-OFF SEQ START/END buttons during the automatic setup process
• FFRT 1/2/3 SEC OPTION button:
— Used to set the FFRT timing along with the
INCREASE, DECREASE and STORE buttons
• 0-20MA 4-20MA OPTION button:
— Used in conjunction with the INCREASE, DECREASE
and STORE buttons to select the proportional mA output for the flame signal
• RESET rE button:
— Resets a lockout condition — Also used to exit a menu while programming — Used to set the Modbus address along with the
INCREASE, DECREASE and STORE buttons

Manual Setup of Setpoints

The keypad of the signal processor is used to set the IR/UV GAIN, RELAY ON, RATIO % (Relay Off), FFRT and mA output option setpoints. The following section describes this process. Also refer to Fig. 22, 23, 24, 25 and 26.
To change the gain, press and hold the SET GAIN button for two seconds until the current value is displayed. Use the INCREASE and DECREASE buttons to change the setting as appropriate while the value is displayed. To store the new setting, press the STORE button until “- -” is shown, indicating the value has been accepted.
If no activity occurs for a period of four seconds while the value is displayed, the display will return to the operation mode without saving the new setpoint.
To exit the menu at any time without saving changes, simply press the RESET/rE button.
The gain is live; changes are effective immediately, but if the displayed gain value is not stored (by pressing STORE), and no other buttons are pressed, the processor returns to the previous setting after four seconds.
Relay On Setpoint
The two numeric digits on the Model 700 signal processor normally display the incoming count during operation; that is, the number of pulses that arrive between self-check pulses. This count ranges from 00 to 29.
Refer to Fig. 22 for a flowchart of setting the Relay On setpoint. Press and hold the RELAY ON SETPOINT key for two seconds to access this setpoint. The RELAY ON SET POINT value will be displayed. If no further keys are pressed, this display will disappear in four seconds and the incoming count will again be displayed. If the RESET key is pressed, the display will return immediately to displaying the incoming count.
While the RELAY ON SET POINT is displayed, you may increase or decrease the setting by using the INCREASE and DECREASE arrow keys. To store the new setting, press the STORE button until “- -” is shown, indicating the value has been accepted.
To exit the menu at any time without saving changes, simply press the RESET/rE button or wait 4 seconds until the display reverts to the incoming count value. To extend the display time, press the RELAY ON SETPOINT button again; the display will time out for four seconds after the key is released if no other buttons are pressed.
The displayed value of the RELAY ON SET POINT is live; that is, if the relay is off and the adjusted value falls below the current flame signal count, the relay will turn on immediately (FFRT settings are ignored). This immediate response can be seen if the count is low and the RELAY ON SET POINT is set above it; if the RELAY ON SET POINT is then adjusted down to the count level, the FLAME ON relay will be energized.

Setting the Viewing Head Gain

The gain of the IR and UV viewing heads can be adjusted. In addition to the information in this section, refer to Fig. 26. At power-up, the 700 signal processors display codes to tell the operator what type of viewing head and what gain is being used. Default values are “r5” for the IR viewing head and “u5” for the UV viewing head. The “r” or “u” denote IR or UV viewing heads, respectively, while the numeric digit indicates the current gain setting. The gain can be adjusted from 1 to 9 with a gain of 5 being the factory default gain.
66-2069—02 12
Ratio (%) Relay Off/Relay On Setpoint
For a flowchart of this setpoint process, refer to Fig. 23. The key labeled RATIO (%) RELAY OFF/RELAY ON is used to set the RELAY OFF SET POINT at a percentage of the RELAY ON SET POINT. This percentage is adjustable from 20% to 80%. For example, if the RELAY ON SET POINT is set to 16 and the RATIO (%) is set to 50% (the factory default values) the relay will energize if the displayed count goes to 16 or higher and de-energize when the count drops to 08 or less for one to three seconds, depending on the FFRT (Flame Failure Response Time) setting. The adjustment of the RATIO setting
Loading...
+ 28 hidden pages