Installation Precautions - Adherence to the following will aid in problem-free
installation with long-term reliability: WARNING - Several different sources of power
can be connected to the fire alarm control panel. Disconnect all sources of power
before servicing. Control unit and associated equipment may be damaged by
removing and/or inserting cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this unit until manuals are
read and understood. CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product must be tested in
accordance with NFP A 72 af ter any programming operation or change in site-specific
software. Re-acceptance testing is required after any change, addition or deletion of
system components, or after any modification, repair or adjustment to system
hardware or wiring. All components, circuits, system operations, or software functions
known to be affected by a change must be 100% tested. In addition, to ensure that
other operations are not inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified. This system meets NFPA requirements
for operation within the range of 0°C-49°C (32°F-120°F) or humidity within the range
of 10%-93% at 30°C (86°F) noncondensing. However, the useful life of the system's
standby batteries and the electronic components may be adversely affected by
extreme temperature ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with a normal room
temperature of 15-27º C/60-80º F. Verify that wire sizes are adequate for all
initiating and indicating device loops. Most devices cannot tolerate more than a 10%
I.R. drop from the specified device voltage. Like all solid state electronic devices,
this system may operate erratically or can be damaged when subjected to lightning
induced transients. Although no system is completely immune from lightning
transients and interference, proper grounding will reduce susceptibility. Overhead or
outside aerial wiring is not recommended, due to an increased susceptibility to
nearby lightning strikes. Consult with the Technical Services Department if any
problems are anticipated or encountered. Remove DC power prior to removing or
inserting circuit boards. Failure to do so can damage circuits. Remove all electronic
assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear. Before making modifications,
verify that they will not interfere with battery, transformer, or printed circuit board
location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may
damage threads, resulting in reduced terminal contact pressure and difficulty with
screw terminal removal. Fire alarm control panels contain static-sensitive
components. Always ground yourself with a proper wrist strap before handling any
circuits so that static charges are removed from the body. Use static suppressive
packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals.
151295
These instructions must be followed to avoid damage to the control panel and
associated equipment. FACP (Fire Alarm Control Panel) operation and reliability
depend upon proper installation.
While installing a fire alarm system may make lower insurance rates possible, it is not
a substitute for fire insurance! An automatic fire alarm system - typically made up
of smoke detectors, heat detectors, manual pull stations, audible warning devices,
and a fire alarm control with remote notification capability - can provide early warning
of a developing fire. Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire. Any fire alarm system may fail
for a variety of reasons: Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in walls, or roofs, or on the other side of
closed doors. Smoke detectors also may not sense a fire on another level or floor of
a building. A second floor detector, for example, may not sense a first floor or
basement fire. Furthermore, all types of smoke detectors, including ionization and
photoelectric types, have sensing limitations. No type of smoke detector can sense
every kind of fire caused by carelessness and safety hazards like smoking in bed,
violent explosions, escaping gas, improper storage of flammable materials,
overloaded electrical circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control
panel and in rooms used by the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If detectors are not so located, a
developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are
located on the other side of closed or partly open doors or are located on another
floor of a building. A fire alarm system will not operate without any electrical power.
If AC power fails, the system will operate from standby batteries only for a specified
time. Rate-of-Rise heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector should be tested at least
once per year by a qualified fire protection specialist. Equipment used in the system may not be technically compatible with the control. It is essential to use only
equipment listed for service with your control panel. Telephone lines needed to
transmit alarm signals from a premise to a central monitoring station may be out of
service or temporarily disabled.
malfunctions, however, is inadequate maintenance. All devices and system wiring
should be tested and maintained by professional fire alarm installers following written
procedures supplied with each device. System inspection and testing should be
scheduled monthly or as required by national and/or local fire codes. Adequate
written records of all inspections should be kept.
Special Characters Lists .........................................................................................................B-1
B.1Characters used for Naming ...................................................................................................B-1
Silent Knight Fire Product Warranty and Return Policy
Manufacturer Warranties and Limitation of Liability
IntelliKnight 5820XL Basic Operating Instructions
1512097
IntelliKnight 5820XL Installation Manual
8151209
Section 1
Introduction
The IntelliKnight 5820XL Fire Alarm Control/Communicator is an addressable fire
control system that meets the requirements of UL 864.
1.1Overview of Basic System
The IntelliKnight 5820XL base system is packaged as an assembled stack of 3 circuit
boards mounted to an aluminum housing.
1.1.1Hardware Features
•The IntelliKnight 5820XL panel has one signaling line circuit (SLC). Up to three
additional SLC loops can be added using the 5815XL SLC expander. The SLC(s)
support the SK series addressable detectors and modules or SD protocol
detectors and modules.
•Each SLC supports up to 99 detectors and 99 modules for a total of 396 detectors
and 396 modules per 5820XL panel when using SK series devices. Alternatively,
each SLC supports up to 127 SD devices for a total of 508 devices per 5820XL
panel.
•6.0A of output power is available through 6 sets of terminals for notification and
auxiliary applications. Each circuit is power limited per UL 864 and can source up
to 3.0A (total output power for all 6 circuits must not exceed 6.0A).
•Built-in dual phone line, digital alarm communicator/transmitter (DACT).
•Reports events to central station by point or by zone.
•UL Listed for pre-action and deluge releasing systems.
•Dedicated Form C trouble relay and two general purpose Form C programmable
relays.
•Basic system operation can be performed using a key or a user code.
•Can be used with up to 8 Model 5860 Remote Annunciators (sold separately).
•Supports the 5865-3, 5865-4, and 5880 in any combination for a total of eight
devices on one control panel. See sections 4.8 and 4.9 for additional information
on these models.
•Printing of detector status, event history, and real time event log available through
the Model 5824 Serial/Parallel Printer Interface Module (sold separately).
•Supports conventional 2-wire & 4-wire detectors using the 6 Flexput™ circuits.
•Add six Flexput™ circuits with each 5895XL Intelligent Power Module (up to eight
5895XLs per system). See note below.
•Add four notification/auxilia ry power circuits with each 5496 Intelligent Power
Module. See note below.
Note: The system can support a maximum of eight Intelligent Power modules, either the 5895XL or 5496, in any
1512091-1
IntelliKnight 5820XL Installation Manual
combination.
1.1.2Software Features
•125 software zones, 250 output groups.
•Advanced smoke detector features:
Automatic drift compensation
Maintenance alert region
Point status meets calibrated smoke test requirements for NFPA 72
•“JumpStart” feature for easy programming.
•Non-volatile event history stores 1000 events.
•A choice of output patterns available for notification outputs, including ANSI 3.41
temporal signal.
•Built-in synchronization appliance support for AMSECO, Faraday, Gentex®,
System Sensor®, and Wheelock®.
1.2About this Manual
This manual is intended to be a complete reference for all installation and operation
tasks for the 5820XL. Please let us know if the manual does not meet your needs in
any way. We value your feedback!
1.2.1Terms Used in this Manual
The following terminology is used with the IntelliKnight 5820XL system:
Table 1-1 Manual Terminology
TermDescription
SLCSignaling line circuit
ModuleThe term module is used for all hardware devices except for SLC
addressable devices and notification appliances. This includes the
5820XL panel itself and the built-in 5897 power supply. It also refers
to any (optional) 5815XL SLC expansion modules.
Input PointAn addressable sensing device, such as a smoke or heat detector or
a contact monitor device.
Input ZoneA protected area made up of input points.
Output Point
(or Output Circuit)
Group (or “Output Group”)A group of output points. Operating characteristics are common to all
Output (or “Cadence”) Pattern The pattern that the output will use, for example, Constant, March
MappingMapping is the process of specifying which outputs are activated
A notification point or circuit for notification appliances. Relay circuits
and auxiliary power circuits are also considered output points.
output points in the group.
Code, ANSI 3.41. Applies to zones and special system events. See
Section 7.7.3.2 for additional information.
when certain events occur in the system. Section 6.2 explains
mapping in detail.
1-2151209
Introduction
1.3Compatible Products
Table 1-2 lists the products available from Silent Knight for use with the IntelliKnight
5820XL.
Table 1-2: 5820XL Compatible Products
Ty pe of
Device
SK
Addressable
SLC
Devices
SD
Addressable
SLC
Devices
Other
Modules
Software
Misc.RBBRemote Battery Box for mounting backup batteries that are too large to fit into
See Section 5.1 for a list of compatible devices.
See Section 5.2 for a list of compatible devices.
5815XL SLC ExpanderAllows an additional 127 SD SLC devices, or 99 SK de tectors and 99 SK
5824 Serial/Parallel Printer
Interface Module
5895XL Intelligent Power
Module
5496 Intelligent Power
Module
5860 and 5860R Remote
Fire Alarm Annunciator
5860TG and 5860TR Trim
Ring Kit
5865-3 and 5865-4 LED
Annunciator
5880 LED I/O ModuleDriver for up to 40 LEDs. Interfaces with customized
5883 General Purpose
Relay Module
5660 Silent Knight
Software Suite (SKSS)
5670 Silent Knight
Software Suite (SKSS)
7860 Telephone CordRJ31X cord for connecting phone line to the 5820XL.
ModelDescription
modules to be added to the system. Up to three 5815XLs per system.
Allows a printer to be attached for the system for on-site event logging, detector
status and event history reports. Two maximum per system.
Provides additional power, six Flexput™ circuits, and
two Form C relays. Max. 8 per system see Model 5895 Installation Instructions P/N 151024.
Provides 4 additional Notification Appliance Circuits/
Auxiliary power. (Up to 8 per system.)
Same operation, similar appearance as on-board annunciator . Up to 8 5860s per
system. 5860 is gray; 5860R is red.
Trim ring kits for surface mounting the 5860 annunciator. 5860TG is gray;
5860TR is red.
LED annunciator can display up to 30 LEDs (15 red
and 15 yellow). 5865-4 has key switches for silence
and reset, and a system trouble LED.
annunciator boards. In addition the 5880 has eight
generic switch input points.
Provides 10 Form C relays. Designed to be driven by the 5880. Up to four, 5883s
can be used with each 5880 module.
For communication and panel programming with a Windows-based computer
and *modem (not sold by Silent Knight, see Table 1-3 for compatible modems).
Enables remote viewing of detector status and event history.
Facility management software. For remote viewing of detector status and event
history. Requires a modem (not sold by Silent Knight).
the main control panel cabinet.
Dimensions: 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D)
5895XLs and 5496s can
be used in any
combination, up to a
total of eight devices on
one system.
5865-3, 5865-4, and
5880 can be used in any
combination, up to a
total of eight devices on
one panel.
1512091-3
IntelliKnight 5820XL Installation Manual
The following modems have been tested by Silent Knight for compatibility with the
5820XL and the Silent Knight Software Suite software packages:
Table 1-3: Compatible Modems
ManufacturerModel
US Robotics28.8
LifeStyle
Motorola
MultiTechMT19321ZDX
28.8, 3400 series
Premier 33.6
1.4How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact
Silent Knight Technical Support at 800-446-6444.
To order parts, contact Silent Knight Customer Service at 800-328-0103.
1-4151209
Introduction
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a
protected premise following the recommendations of the current edition of the
National Fire Protection Association Standard 72 (NFPA 72), manufacturer’s
recommendations, State and local codes, and the recommendations contained in
Guide for the Proper Use of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management
Agency (an agency of the United States government) indicated that smoke detectors
may not go off or give early warning in as many as 35% of all fires. While fire alarm
systems are designed to provide warning against fire, they do not guarantee warning
or protection against fire. A fire alarm system may not provide timely or adequate
warning, or simply may not function, for a variety of reasons. For example:
•Particles of combustion or smoke from a developing fire may not reach the
sensing chambers of smoke detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit
particle or smoke flow.
Smoke particles may become cold, stratify, and not reach the ceiling or upper
walls where detectors are located.
Smoke particles may be blown away from detectors by air outlets
Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense
fires developing on another level.
•The amount of smoke present may be insufficient to alarm smoke detectors.
Smoke detectors are designed to alarm at various levels of smoke density . If such
density levels are not created by a developing fire at the location of detectors, the
detectors will not go into alarm.
•Smoke detectors, even when working properly, have sensing limitations.
Detectors that have photoelectronic sensing chambers tend to detect smoldering
fires better than flaming fires, which have little visible smoke. Detectors that have
ionizing-type sensing chambers tend to detect fast flaming fires better than
smoldering fires. Because fires develop in different ways and are often
unpredictable in their growth, neither type of detector is necessarily best and a
given type of detector may not provide adequate warning of a fire.
•Smoke detectors are subject to false alarms and nuisance alarms and may have
been disconnected by users. For example, a smoke detector located in or near a
kitchen may go into nuisance alarm during normal operation of kitchen
appliances. In addition, dusty or steamy environments may cause a smoke
detector to falsely alarm. If the location of a smoke detector causes an abundance
of false alarms or nuisance alarms, do not disconnect the smoke detector; call a
professional to analyze the situation and recommend a solution.
•Smoke detectors cannot be expected to provide adequate warning of fires caused
by arson, children playing with matches (especially within bedrooms), smoking in
bed, violent explosions (caused by escaping gas, improper storage of flammable
1512091-5
IntelliKnight 5820XL Installation Manual
materials, etc.).
•Heat detectors do not sense particles of combustion and are designed to alarm
only when heat on their sensors increases at a predetermined rate or reaches a
predetermined level. Heat detectors are designed to protect property, not life.
•Warning devices (including horns, sirens, and bells) may not alert people or wake
up sleepers who are located on the other side of closed or partially open doors. A
warning device that activates on a different floor or level of a dwelling or structure
is less likely to awaken or alert people. Even persons who are awake may not
notice the warning if the alarm is muffled by noise from a stereo, radio, air
conditioner or other appliance, or by passing traffic. Audible warning devices may
not alert the hearing-impaired (strobes or other devices should be provided to
warn these people). Any warning device may fail to alert people with a disability,
deep sleepers, people who have recently used alcohol or drugs, or people on
medication or sleeping pills.
Please note that:
i)Strobes can, under certain circumstances, cause seizures in people with con-
ditions such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm sig-
nal, do not respond or comprehend the meaning of the signal. It is the property
owner’s responsibility to conduct fire drills and other training exercises to make
people aware of fire alarm signals and instruct on the proper reaction to alarm
signals.
iii) In rare instances, the sounding of a warning device can cause temporary or
permanent hearing loss.
•Telephone lines needed to transmit alarm signals from a premises to a central
station may be out of service or temporarily out of service. For added protection
against telephone line failure, backup radio transmission systems are
recommended.
•System components, though designed to last many years, can fail at any time. As
a precautionary measure, it is recommended that smoke detectors be checked,
maintained, and replaced per manufacturer’s recommendations.
•System components will not work without electrical power. If system batteries are
not serviced or replaced regularly, they may not provide battery backup when AC
power fails.
•Environments with high air velocity or that are dusty or dirty require more frequent
maintenance.
In general, fire alarm systems and devices will not work without power and will not
function properly unless they are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance
rate, an alarm system is not a substitute for insurance.
Property owners should
continue to act prudently in protecting the premises and the people in their premises
and should properly insure life and property and buy sufficient amounts of liability
insurance to meet their needs.
1-6151209
Introduction
Requirements and recommendations for proper use of fire alarm systems including smoke detectors and other fire alarm devices:
Early fire detection is best achieved by the installation and maintenance of fire
detection equipment in all rooms and areas of the house or building in accordance
with the requirements and recommendations of the current edition of the National Fire
Protection Association Standard 72, National Fire Alarm Code (NFPA 72), the
manufacturer’s recommendations, State and local codes and the recommendations
contained in Guide for the Proper Use of System Smoke Detectors, which is made
available at no charge to all installing dealers. For specific requirements, check with
the local Authority Having Jurisdiction (ex. Fire Chief) for fire protection systems.
Requirements and Recommendations include:
•Smoke Detectors shall be installed in sleeping rooms in new construction and it is
recommended that they shall also be installed in sleeping rooms in existing
construction.
•It is recommended that more than one smoke detector shall be installed in a
hallway if it is more than 30 feet long.
•It is recommended that there shall never be less then two smoke detectors per
apartment or residence.
•It is recommended that smoke detectors be located in any room where an alarm
control is located, or in any room where alarm control connections to an AC
source or phone lines are made. If detectors are not so located, a fire within the
room could prevent the control from reporting a fire.
•All fire alarm systems require notification devices, including sirens, bells, horns,
and/or strobes. In residential applications, each automatic alarm initiating device
when activated shall cause the operation of an alarm notification device that shall
be clearly audible in all bedrooms over ambient or background noise levels (at
least 15dB above noise) with all intervening doors closed.
•It is recommended that a smoke detector with an integral sounder (smoke alarm)
be located in every bedroom and an additional notification device be located on
each level of a residence.
•T o keep your fire alarm system in excellent working order , ongoing maintenance is
required per the manufacturer’s recommendations and UL and NFPA standards.
At a minimum the requirements of Chapter 14 of NFPA 72, 2010 edition shall be
followed. A maintenance agreement should be arranged through the local
manufacturer’s representative. Maintenance should be performed annually by
authorized personnel only.
•The most common cause of an alarm system not functioning when a fire occurs is
inadequate maintenance. As such, the alarm system should be tested weekly to
make sure all sensors and transmitters are working properly.
1512091-7
IntelliKnight 5820XL Installation Manual
1-8151209
Section 2
Agency Listings, Approvals, and Requirements
2.1Federal Communications Commission (FCC)
1. The following information must be provided to the telephone company before the
IntelliKnight 5820XL can be connected to the phone lines:
AManufacturer:Silent Knight by Honeywell
BModel Number:IntelliKnight 5820XL
CFCC registration number:AC6USA-23901-AL-E
Ringer equivalence:0.8B
DType of jack:RJ31X
EFacility Interface Codes:Loop Start: 02LS2
FService Order Code:9.0F
This equipment complies with Part 68 of the FCC rules and the requirements adopted
by ACTA. On the inside cover of this equipment is a label that contains, among other
information, a product identifier. If requested, this inform ation must be provided to the
telephone company.
A plug and jack used to connect this equipment to the premises wiring and telephone
network must comply with the applicable FCC Part 68 rules and requirements
adopted by the ACTA. A compliant telephone cord (not provided) and modular jack
must be utilized with this product. It is designed to be used with a modular jack that is
also compliant.
The REN (ringer equivalence number) provided on this installation sheet is used to
determine the number of devices that may be connected to the public switched
telephone network. This number must not exceed 5.0. Since this product has an REN
of .8, the number of devices is limited. The REN number is embedded in the FCC
registration number as 10B.
If the 5820XL causes harm to the telephone network, the telephone company will
notify you in advance that the temporarily discontinuance of service may be required.
But if advance notice is not practical, the telephone company will notify the customer
as soon as possible. Also, you will be advised of your right to file a complaint with the
FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations or
procedures that could affect the operation of the equipment. If this happens the
telephone company will provide advance notice in order for you to make necessary
modifications to maintain uninterrupted service.
If trouble is experienced with the 5820XL, for repair or warranty information, please
contact Silent Knight at 1-800-328-0103 or www .silentknight.com. If the equipment is
causing harm to the telephone network, the telephone company may request that you
1512092-1
IntelliKnight 5820XL Installation Manual
disconnect the 5820XL until the problem has been resolved.
This product cannot be adjusted or repaired in the field. It must be returned to the
factory for service.
This equipment is not designed for use with party line service. Connection to party
line service is subject to state tariffs. You may contact the state public utility
commission, public service commission or corporation commission for information.
Since the 5820XL is a commercial fire alarm panel, it must be connected upstream of
all other equipment utilizing the phone lines. If you have questions about the
installation, contact your telephone company or a qualified installer.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following
conditions: (1) This device may not cause radio interference, and (2) This device must accept any
interference received, including interference that may cause undesired operation.
2-2151209
Agency Listings, Approvals, and Requirements
2.2Underwriters Laboratories (UL)
2.2.1Requirements for All Installations
General requirements are described in this section. When installing an individual
device, refer to the specific section of the manual for additional requirements. The
following subsections list specific requirements for each type of installation (for
example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems,
and so on). See Section 8.7 for information on releasing operation.
1. All field wiring must be installed in accordance with NFPA 70 National Electric
Code.
2. Use the addressable smoke detectors specified in Section 5.2 of this manual and/
or conventional detectors listed in the compatibility chart. (See Appendix A.)
3. Use UL listed notification appliances compatible with the 5820XL from those
specified in the Appendix at the back of this manual.
4. A full system checkout must be performed any time the panel is programmed.
Restricted Options:
•The loss of AC signal is defaulted to 3 hours, however the system allows settings
from 0 - 30 hours. For UL certified installations this number must be set from 1 to
3 hours.
•The system allows the use of non-latching spot type smoke detectors. This feature may not be used in commercial applications whereby a general alarm is
sounded. It is intended for elevator recall, door holding applications, and hotel/
motel room applications.
•The system allows the Alarm Verification time to be set from 1 to 255 seconds.
For UL certified installations the setting must be a minimum of 60 seconds.
•Call forwarding shall not be used.
•When two count is used: detector spacing shall be cut in half, you shall not use
the alarm verification feature, and no delay shall be used.
•P.A.S (positive alarm sequence) feature shall be used only with automatic detectors.
1512092-3
IntelliKnight 5820XL Installation Manual
2.2.2Requirements for Central Station Fire Alarm
Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the 5820XL sends an
automatic daily test to the central station.
3. The AC Loss Hours option must be set from 1-3 hours.
4. The Attempts to Report option must be set for 5.
2.2.3Requirements for Local Protected Fire Alarm
Systems
At least one UL listed supervised notification appliance must be used.
2.2.4Requirements for Remote Station Protected Fire
Alarm Systems
1. Do not exceed the current draw load restrictions shown in Section 3.6.
2. The AC Loss Hours option must be set from 15-30 hours.
2-4151209
Section 3
Before You Begin Installation
This section of the manual is intended to help you plan your tasks to facilitate a
smooth installation. Please read this section thoroughly , especially if you are inst alling
a 5820XL panel for the first time.
3.1What’s in the Box?
The IntelliKnight 5820XL ships with the following hardware:
•A cabinet with all hardware assembled
•Two keys for the front door
•Two keys for user operation of the on-board annunciator (installer operations
require the Installer’s Code)
•Ten 4.7K ohm end-of-line resistors
•A battery cable for batteries wired in series
3.2Environmental Specifications
It is important to protect the 5820XL control panel from water. To prevent water
damage, the following precautions should be FOLLOWED when installing the units:
•Intended for indoor use in dry locations only
•Do not mount directly on exterior walls, especially masonry walls (condensation)
•Do not mount directly on exterior walls below grade (condensation)
•Protect from plumbing leaks
•Protect from splash caused by sprinkler system inspection ports
•Do not mount in areas with humidity-generating equipment (such as dryers,
production machinery)
When selecting a location to mount the 5820XL control panel, the unit should be
mounted where it will NOT be exposed to: temperatures outside the range of 0°C49°C (32°F-120°F) or humidity exceeding 93% noncondensing.
1512093-1
IntelliKnight 5820XL Installation Manual
3.3Electrical Specification
Table 3-1 list the terminal block on the 5820XL as well as a description of each
individual terminal and their respective electrical rating.
Table 3-1: Terminal Descriptions and Electrical Specifications
RELAY 2General Purpose Relay 224 VDC2.5 A, resistiveN/A25C
SBUS communication5 VDC100 mA
SBUS power24 VDC1.0 A
VoltageCurrent
Rating
3.0A notification and
auxiliary power circuits
100 mA for initiation
circuits
3.0A notification and
auxiliary power circuits
100 mA for initiation
circuits
3.0A notification and
auxiliary power circuits
100 mA for initiation
circuits
3.0A notification and
auxiliary power circuits
100 mA for initiation
circuits
3.0A notification and
auxiliary power circuits
100 mA for initiation
circuits
3.0A notification and
auxiliary power circuits
100 mA for initiation
circuits
Earth Ground
Faults
0
0
0
0
0
0
0
*Regulated for NAC circuits, special application when used for releasing.
3-2151209
Before You Begin Installation
Table 3-1: Terminal Descriptions and Electrical Specifications
Terminal # and LabelDescription
27N.C.
RELAY 1General Purpose Relay 124 VDC2.5 A, resistiveN/A28C
29N.O.
30N.C.
TROUBLE Trouble Relay24 VDC2.5 A, resistiveN/A31C
32N.O.
33SC-L1
34SC+
35SC-L2
36SC+
37RingPhone Line 1 Telco Ring
38TipPhone Line 1 Telco Tip
39RingPhone Line 1 Premises Ring
40TipPhone Line 1 Premises Tip
41RingPhone Line 2 Telco Ring
42TipPhone Line 2 Telco Tip
43RingPhone Line 2 Premises Ring
44TipPhone Line 2 Premises Tip
45SC-
46SC+
SLC OUT
SLC IN
SLC terminals32 VDC150 mA0
Used for Class A installations0
SLC Programming Terminal ( )
SLC Programming T erminal ( +
)
Rating
VoltageCurrent
N/A0
N/A0
32 VDC150 mA
32 VDC150 mA
Earth Ground
Faults
0
1512093-3
IntelliKnight 5820XL Installation Manual
3.4Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere
with telephone communication or cause false alarms. To avoid induced noise, follow
these guidelines:
•Isolate input wiring from high current output and power wiring. Do not pull one
multi-conductor cable for the entire panel. Instead, separate the wiring as follows:
High voltageAC power, Terminals 1-3
SLC loopsTerminals 33-36
Audio input/output Phone line circuits,
•Do not pull wires from different groups through the same conduit. If you must run
them together, do so for as short a distance as possible or use shielded cable.
Connect the shield to earth ground at the panel. You must route high and low
voltages separately.
•Route the wiring around the inside perimeter of the cabinet. It should not cross the
circuit board where it could induce noise into the sensitive microelectronics or pick
up unwanted RF noise from the high speed circuits. See Figure 3-1 for an
example.
•High frequency noise, such as that produced by the inductive reactance of a
speaker or bell, can also be reduced by running the wire through ferrite shield
beads or by wrapping it around a ferrite toroid.
3-4151209
Battery cables from
under aluminum housing.
Maintain 1/4"
spacing between
battery cables
and input wiring.
Red
Black
To
AC Input
Route all low voltage
wiring through any
of these knockouts.
All circuits, except battery
cables and AC, are power limited.
Maintain at least 1/4" spacing
between power limited and
non-power limited circuits.
Separate high and low
voltage circuits.
To phone
lines
Fire alarm power-limited circuits are
installed using types FPL, FPLR, FPLP
or permitted substitute cables,
provided these power-limited cable
conductors extending beyond the
jacket are separated by a minimum of
0.25 in. (6.35 mm) or by a nonconductive
sleeve or nonconductive barrier from
all other conductors.
Before You Begin Installation
Figure 3-1 Wire Routing Example
1512093-5
IntelliKnight 5820XL Installation Manual
Chassis
Mounting
Nuts
Chassis
Mounting
Nuts
To ACOn-board Annunciator
Key Switch
Input
Programming
Ports
3.5Board Assembly Diagram
Figure 3-2 Model 5820XL Assembly
Figure 3-2 shows the circuit boards, metal housing and annunciator that attach the
5820XL assembly to the cabinet. If you should need to remove the board assembly
for repair, remove the four mounting nuts which hold the assembly in the cabinet.
Then lift the entire assembly out of the cabinet. Do not attempt to remove the circuit
boards from the metal bracket.
3-6151209
Loading...
+ 214 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.