Honeywell 5820XL User Manual

Page 1
INTELLIKNIGHT
5820XL
Addressable Fire System
®
Installation and Operations Manual
Document 151209-L8 01/24/2013 Rev:
P/N 151209-L8:U ECN 12-0955
Page 2
Page 3
Installation Procedure
Installation Precautions - Adherence to the following will aid in problem-free
installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFP A 72 af ter any programming operation or change in site-specific software. Re-acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation within the range of 0°C-49°C (32°F-120°F) or humidity within the range of 10%-93% at 30°C (86°F) noncondensing. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F. Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Remove DC power prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. Fire alarm control panels contain static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals.
151295
Page 4
These instructions must be followed to avoid damage to the control panel and associated equipment. FACP (Fire Alarm Control Panel) operation and reliability depend upon proper installation.
While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance! An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability - can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire. Furthermore, all types of smoke detectors, including ionization and photoelectric types, have sensing limitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time. Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. malfunctions, however, is inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection and testing should be scheduled monthly or as required by national and/or local fire codes. Adequate written records of all inspections should be kept.
The most common cause of fire alarm
Page 5

Contents

Section 1
Introduction .............................................................................................................................................. 1-1
1.1 Overview of Basic System ........................................................................................................1-1
1.1.1 Hardware Features ............................................................................................................1-1
1.1.2 Software Features ..............................................................................................................1-2
1.2 About this Manual .....................................................................................................................1-2
1.2.1 Terms Used in this Manual ................................................................................................1-2
1.3 Compatible Products .............................................................................. ... ... ... .... ... ... ... ... .........1-3
1.4 How to Contact Silent Knight ....................................................................................................1-4
Section 2
Agency Listings, Approvals, and Requirements ................................... 2-1
2.1 Federal Communications Commission (FCC) ..........................................................................2-1
2.2 Underwriters Laboratories (UL) ................................................................................................2-3
2.2.1 Requirements for All Installations ................................ .... ... ... ... ... .... ..................................2-3
2.2.2 Requirements for Central Station Fire Alarm Systems ......................................................2-4
2.2.3 Requirements for Local Protected Fire Alarm Systems ................................ ... ... ... ... .... ... ..2-4
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems ......... ............................ 2-4
Section 3
Before You Begin Installation ..........................................................................................3-1
3.1 What’s in the Box? ...................................................................................................................3-1
3.2 Environmental Specifications .......................................................................................... .... . ....3-1
3.3 Electrical Specification .............................................................................................................3-2
3.4 Wiring Specifications ................................................................................................................3-4
3.5 Board Assembly Diagram ...................... ... .... ............................................................................3-6
3.6 Calculating Current Draw and Standby Battery ........................................................................3-7
3.6.1 Current Draw Worksheet Requirements ....................................................................... .....3-7
3.6.1.1 Current Draw Worksheet for SK SLC Devices .........................................................3-8
3.6.1.2 Current Draw Worksheet for SD SLC Devices .......................................................3-11
3.6.1.3 Maximum Battery Standby Load ............................................................................3-13
3.7 Installation Tasks Overview ....................................................................................................3-14
151209 1
Page 6
IntelliKnight 5820XL Installation Manual
Section 4
Control Panel Installation ......................................................................................................4-1
4.1 Mounting the Control Panel Cabinet ........................................................................................4-1
4.1.1 Preventing Water Damage .................................................................................................4-1
4.1.2 Removing the 5820XL Assembly from the Housing ..........................................................4-1
4.2 AC Connection ............................. ... ... ... ... .... ............................................................. ... ............4-2
4.3 Battery Connection ...................................................................................................................4-3
4.3.1 RBB Accessory Cabinet .....................................................................................................4-4
4.3.1.1 Installing the RBB Accessory Cabinet and Batteries ...............................................4-4
4.4 SBUS Wiring .. .... ... ... ... .... ... ............................................................. ... .... ... ... ... .... ... ... ...............4-6
4.4.1 Calculating Wiring Distance for SBUS Modules ................................................................4-6
4.4.2 Wiring Configurations .........................................................................................................4-9
4.5 Remote Annunciator 5860 Installation ...................................................................................4-10
4.5.1 Mounting the 5860 ...........................................................................................................4-11
4.5.1.1 Flush Mounting .......................................................................................................4-12
4.5.1.2 Surface Mounting ...................................................................................................4-14
4.5.2 Model 5860 Connection to the Panel ............................................... ... ... ... .... ... ... ... ... .... ...4-15
4.6 5815XL Installation .................................................................................................................4-16
4.6.1 5815XL Connection to the Panel .....................................................................................4-17
4.7 5824 Serial/Parallel Interface Module Installation ..................................................................4-18
4.7.1 Selecting 5824 Options ....................................................................................................4-19
4.8 5880 LED I/O Module .............................................................................................................4-21
4.8.1 5880 Board Layout ...........................................................................................................4-21
4.8.2 5880 Connection to Panel .................. .... ... ... ... .... ... ... ... .... ................................................4-22
4.8.3 LED Wiring .......................................................................................................................4-23
4.8.4 Dry Contact Wiring ...........................................................................................................4-24
4.9 5865-3 / 5865-4 LED Annunciator Installation ........................ ................ ................ ................4-25
4.9.1 FACP Connection ............................................................................................................4-26
4.9.2 5865 Mounting .................................................................................................................4-27
4.10 Configuring Modules .............................................................................................................4-29
4.10.1 Assigning Module IDs .....................................................................................................4-29
4.11 Telephone Connection ...........................................................................................................4-30
4.12 Flexputs
4.12.1 Conventional Notification Appliance ............................................................................... 4-31
4.12.2 Conventional Input Switch Circuits .................................................................................4-34
4.12.3 Installing 2-Wire Smoke Detectors .................................................................................4-36
4.12.4 Installing 4-Wire Smoke Detectors .................................................................................4-38
4.12.5 Auxiliary Power Installation .............................................................................................4-40
4.13 On-Board Relays (Conventional) ...........................................................................................4-41
I/O Circuits ............................................................................................................4-31
4.12.1.1 Class B Notification Wiring ....................................................................................4-31
4.12.1.2 Class A Notification Wiring ....................................................................................4-33
4.12.2.1 Class B Inputs .......................................................................................................4-34
4.12.2.2 Class A Inputs .......................................................................................................4-35
4.12.3.1 Installing 2-Wire Class B Smoke Detectors ..........................................................4-36
4.12.3.2 Installing 2-Wire Class A Smoke Detectors ..........................................................4-37
4.12.4.1 Installing a Class B 4-Wire Smoke Detectors .......................................................4-38
4.12.4.2 Installing 4-Wire Class A Smoke Detectors ..........................................................4-39
4.12.5.1 Door Holder Power ................................................................................................4-40
4.12.5.2 Constant Power .....................................................................................................4-40
4.12.5.3 Resettable Power ........................ ...................................... .................................... 4-41
2 151209
Page 7
Contents
4.13.1 Trouble Relay .................................................................................................................4-41
4.13.2 Programmable Relays ....................................................................................................4-41
4.14 Remote Station Applications ..................................................................................................4-42
4.14.1 Keltron Model 3158 Installation ......................................................................................4-42
4.14.2 City Box Connection Using the 5220 Module ................................................................. 4-44
4.14.3 NFPA 72 Polarity Reversal .............................................................................................4-45
4.14.3.1 Using the 5220 Module .........................................................................................4-45
4.14.3.2 Using the 7644 Module .........................................................................................4-46
4.14.4 Using the SD500-ARM Addressable Relay Module .......................................................4-48
4.14.5 Using a MR-201/T Control Relay From Air Products ............................... ....................... 4-49
4.14.6 Transmitter Activated by Dry Contacts ...........................................................................4-50
Section 5
SD and SK SLC Device Installation ..........................................................................5-1
5.1 List of SK SLC Devices ............................................................................................................5-1
5.2 List of SD SLC Devices ............................................................................................................5-2
5.3 Maximum Number of Devices ..................................................................................................5-3
5.4 Wiring Requirements for SLC Devices ............................ ................................................ .........5-4
5.4.1 Wiring 5815XL in Style 4 (Class B) Configuration .............................................................5-4
5.4.2 Wiring 5815XL in Style 6 & 7 (Class A) Configuration .......................................................5-6
5.5 Wiring SK SLC Detectors .........................................................................................................5-7
5.6 Addressing SK SLC Devices ....................................................................................................5-8
5.7 Wiring SD Detectors .................................................................................................................5-9
5.8 Addressing SD Devices ..........................................................................................................5-10
5.8.1 SD505-APS, SD505-AHS, & SD505-AIS .........................................................................5-10
5.8.2 SLC Devices with DIP Switches ......................................................................................5-11
Section 6
Programming Overview ...........................................................................................................6-1
6.1 JumpStart Autoprogramming ...................................................................................................6-1
6.1.1 Input Points ........................................................................................................................6-2
6.1.2 Output Points .....................................................................................................................6-2
6.1.3 Running JumpStart ............................................................................................................6-3
6.2 Mapping Overview ....................................................................................................................6-5
6.2.1 Input Point Mapping ............................................................................... ... .... ... ... ... ... .........6-6
6.2.2 Output Circuit Mapping ......................................................................................................6-7
6.2.3 Zone Event Mapping ..........................................................................................................6-8
6.2.4 Mapping LED Points ........................................................................................................6-10
6.3 Programming Using the 5660 Silent Knight Software Suite ......... ... ... .... ... ... ... .......................6-11
6.4 Programming Using an Annunciator ......................................................................................6-11
6.4.1 Entering & Exiting the Program Menu ..............................................................................6-11
6.4.1.1 Moving through the Menus .....................................................................................6-12
6.4.1.2 Selecting Options and Entering Data .....................................................................6-12
6.4.1.3 Editing Keys ...........................................................................................................6-13
6.5 Programming Menu Quick Reference .................................................................................... 6-14
151209 3
Page 8
IntelliKnight 5820XL Installation Manual
Section 7
Programming ......................................................................................................................................... 7-1
7.1 UL 864 Programming Requirements ...................................... ................................................ ..7-1
7.2 SLC Family ...............................................................................................................................7-2
7.3 Modules ................................. ............................................. ......................................................7-2
7.3.1 Edit Modules ......................................................................................................................7-2
7.3.1.1 Naming Modules ......................................................................................................7-2
7.3.1.2 Setting the 5815XL Wiring Class .............................................................................7-3
7.3.2 Adding a Module .................... ... ... ... ... .... ... ... ............................................................. .........7-3
7.3.3 Deleting a Module ..............................................................................................................7-4
7.4 Zone .........................................................................................................................................7-5
7.4.1 Edit Zone ............................................................................................................................7-5
7.4.1.1 Edit Zone Name .......................................................................................................7-5
7.4.1.2 Edit Zone Properties ................................................................................................7-6
7.4.1.3 Zone Outputs ...........................................................................................................7-8
7.4.1.4 Cadence Patterns ..................................................................................................7-12
7.4.1.5 Zone Accessory Options ........................................................................................7-13
7.4.2 Add Zone .........................................................................................................................7-13
7.4.3 Delete Zone .....................................................................................................................7-13
7.4.4 View Zone Points .............................................................................................................7-15
7.5 Group .....................................................................................................................................7-16
7.5.1 Edit Group ........................................................................................................................7-16
7.5.1.1 Edit Group Name ...................................................................................................7-16
7.5.1.2 Edit Group Properties .............................................................................................7-17
7.5.2 Add Group ........................................................................................................................7-19
7.5.3 Delete Group ................................................................................ .... ... ... ..........................7-19
7.5.4 View Group Points ...........................................................................................................7-20
7.5.5 Edit Output Group Templates ..........................................................................................7-20
7.6 Point .......................................................................................................................................7-22
7.6.1 Point Programming For 5815XL Module ..........................................................................7-22
7.6.2 Point Programming For Internal or External Power Module (5895XL) .......................... ...7-26
7.6.3 Point Programming For 5880 and 5865 Modules ..................................... .... ... ... ... ... .... ...7-28
7.6.3.1 Assigning a Name to Points ...................................................................................7-28
7.7 System Options ............... ... ... ... .... ............................................................. ... ... .......................7-30
7.7.1 Reporting Account ...........................................................................................................7-30
7.7.1.1 Edit Accounts .........................................................................................................7-31
7.7.1.2 Auto Test Time .......................................................................................................7-33
7.7.2 Phone Lines .....................................................................................................................7-34
7.7.2.1 Dialing Prefix ..........................................................................................................7-34
7.7.2.2 Number of Answer Rings ................... ............................................................. .... ...7-35
7.7.2.3 Dial Option (TouchTone or Pulse) ..........................................................................7-35
7.7.2.4 Rotary Format ........................................................................................................7-35
7.7.2.5 Line Monitor ...........................................................................................................7-35
7.7.2.6 Answering Machine Bypass ......... ... ... ....................................................................7-36
7.7.3 Sys. Event Outputs ..........................................................................................................7-36
7.7.3.1 Trouble Events .......................................................................................................7-37
7.7.3.2 System Alarm Cadence ........................ .................................................................7-38
7.7.4 Miscellaneous Options 1 ..................................................................................................7-39
7.7.4.1 Water Flow Delay ...................................................................................................7-39
7.7.4.2 Low AC Report Delay ......... ... ... .... ... ... ... .............................................................. ...7-40
4 151209
Page 9
7.7.4.3 Automatic Daylight Savings Adjustment ................................... ... ... .......................7-40
7.7.4.4 Clock Display Format (AM/PM or Military) .............................................................7-40
7.7.4.5 Change AC Line Frequency ............... ................................................. ...................7-40
7.7.5 Miscellaneous Options 2 ..................................................................................................7-41
7.7.5.1 Synchronize Strobes Active During Silence ...........................................................7-41
7.7.5.2 Auto Display Oldest Event .....................................................................................7-41
7.7.5.3 Report by Zone or by Point ....................................................................................7-41
7.7.6 Miscellaneous Options 3 ..................................................................................................7-42
7.7.6.1 Alarm Verification Time ..........................................................................................7-42
7.7.6.2 Plex Door Option ....................................................................................................7-42
7.7.6.3 Daylight Saving Time Start and End ......................................................................7-43
7.7.7 Edit Banner Message .......................................................................................................7-44
7.8 JumpStart Autoprogramming .................................................................................................7-45
7.9 Computer Account ..................................................................................................................7-46
7.10 Access Codes ........................................................................................................................7-47
7.10.1 Profile Edit Menu ............................................................................................................7-48
7.10.1.1 Edit Name .............................................................................................................7-48
7.10.1.2 Edit Access Code ................................. ....................................... .......................... 7-48
7.10.1.3 Panel Functions ....................................................................................................7-48
Section 8
Contents
System Operation ............................................................................................................................ 8-1
8.1 User and Installer Default Codes .............................................................................................8-1
8.2 Annunciator Description ...........................................................................................................8-1
8.2.1 LCD Displays .....................................................................................................................8-2
8.2.2 Banner ...............................................................................................................................8-2
8.3 Key Operation ..........................................................................................................................8-2
8.4 Menu System .................................................................................................. .... ... ... ...............8-3
8.4.1 Main Menu Overview .........................................................................................................8-3
8.4.2 Using the Menus ................................................................................................................8-4
8.5 Basic Operation ........................................................................................................................8-4
8.5.1 Setting Time and Date .......................................................................................................8-4
8.5.2 Disable / Enable NACs by Group .......................................................................................8-4
8.5.3 Disable / Enable a Template ..............................................................................................8-4
8.5.4 Disable / Enable a Zone .....................................................................................................8-5
8.5.5 Disable / Enable a Point .....................................................................................................8-5
8.5.6 View Event History .............................................................................................................8-6
8.5.6.1 To clear the event history .........................................................................................8-6
8.5.7 Conduct a Fire Drill ................................ ... ... ... .... ... ... ... ......................................................8-6
8.5.8 Conduct an Indicator Test .................................................................................................. 8-6
8.5.9 Conduct a Walk Test ..........................................................................................................8-7
8.5.10 Conduct a Dialer Test .......................................................................................................8-7
8.5.11 Silence alarms or troubles ................................................................................................8-8
8.5.12 Reset alarms ....................................................................................................................8-8
8.5.13 Check Detector Through Point Status ..............................................................................8-8
8.5.14 View Status of a Point ......................................................................................................8-9
8.5.15 View Alarms or Troubles ..................................................................................................8-9
8.5.16 View System Information ................................................................................................8-10
8.5.17 Reset dialer ....................................................................................................................8-10
8.5.18 Communicating with a Remote Computer ......................................................................8-10
8.5.19 Working with a Printer ....................................................................................................8-11
8.6 Operation Mode Behavior .. ... ... .... ... ... ... ... .... ... ... ... .... ... ... .......................................................8-12
151209 5
Page 10
IntelliKnight 5820XL Installation Manual
8.7 Releasing Operations ................................................... ... ... .... ................................................8-17
8.7.1 Single Interlock Zone Releasing ......................................................................................8-18
8.7.2 Double Interlock Zone Releasing ........................... ... ... .... ... ... ... ... .... ... ... ... .......................8-19
8.8 Smoke Alarm Verification ................ ... ... ... .... ................................................................ ..........8-21
Section 9
Reporting .....................................................................................................................................................9-1
9.1 Receivers Compatible with the Control Panel .............. ... ... .... ... ... ... ... .... ... ... ... .... ... ..................9-1
9.2 Reporting Formats Dialer Outputs ..........................................................................................9-1
Section 10
Testing and Troubleshooting .........................................................................................10-1
10.1 Troubleshooting ........................................ ................. ................... ................ ..........................10-1
10.2 Common Problems .......................... ... ... ... .... ... ................................................................ .......10-1
10.2.1 Periodic Testing And Maintenance ................................. ................................................ 10-2
10.2.2 Event History ..................................................................................................................10-3
10.3 Built-in Troubleshooting and Testing Tools ............................................................................10-4
10.3.1 SLC Device Locator ....................... .......................... .......................... .............................10-4
10.3.2 SLC Multi Locator ...........................................................................................................10-5
10.3.3 I/O Point Control .............................................................................................................10-6
10.3.4 Earth Fault Resistance ...................................................................................................10-7
Section 11
Installation Records ....................................................................................................................11-1
11.1 SLC Point Record ...................................................................................................................11-1
11.2 Conventional Output Point Record ............................... ............................................. .............11-8
6 151209
Page 11
Contents
Appendix A
Compatible Devices ..................................................................................................................... A-1
A.1 Notification Appliances ............................................................................................................ A-1
A.2 Two-Wire Smoke Detectors .................................. .... ... ... ... .... ... ... ... ... .... ... ... .........................A-12
Appendix B
Special Characters Lists .........................................................................................................B-1
B.1 Characters used for Naming ...................................................................................................B-1
Silent Knight Fire Product Warranty and Return Policy Manufacturer Warranties and Limitation of Liability IntelliKnight 5820XL Basic Operating Instructions
151209 7
Page 12
IntelliKnight 5820XL Installation Manual
8 151209
Page 13

Section 1 Introduction

The IntelliKnight 5820XL Fire Alarm Control/Communicator is an addressable fire control system that meets the requirements of UL 864.

1.1 Overview of Basic System

The IntelliKnight 5820XL base system is packaged as an assembled stack of 3 circuit boards mounted to an aluminum housing.

1.1.1 Hardware Features

The IntelliKnight 5820XL panel has one signaling line circuit (SLC). Up to three additional SLC loops can be added using the 5815XL SLC expander. The SLC(s) support the SK series addressable detectors and modules or SD protocol detectors and modules.
Each SLC supports up to 99 detectors and 99 modules for a total of 396 detectors and 396 modules per 5820XL panel when using SK series devices. Alternatively, each SLC supports up to 127 SD devices for a total of 508 devices per 5820XL panel.
6.0A of output power is available through 6 sets of terminals for notification and auxiliary applications. Each circuit is power limited per UL 864 and can source up to 3.0A (total output power for all 6 circuits must not exceed 6.0A).
Built-in dual phone line, digital alarm communicator/transmitter (DACT).
Reports events to central station by point or by zone.
UL Listed for pre-action and deluge releasing systems.
Dedicated Form C trouble relay and two general purpose Form C programmable relays.
Basic system operation can be performed using a key or a user code.
Can be used with up to 8 Model 5860 Remote Annunciators (sold separately).
Supports the 5865-3, 5865-4, and 5880 in any combination for a total of eight devices on one control panel. See sections 4.8 and 4.9 for additional information on these models.
Printing of detector status, event history, and real time event log available through the Model 5824 Serial/Parallel Printer Interface Module (sold separately).
Supports conventional 2-wire & 4-wire detectors using the 6 Flexput™ circuits.
Add six Flexput™ circuits with each 5895XL Intelligent Power Module (up to eight 5895XLs per system). See note below.
Add four notification/auxilia ry power circuits with each 5496 Intelligent Power Module. See note below.
Note: The system can support a maximum of eight Intelligent Power modules, either the 5895XL or 5496, in any
151209 1-1
Page 14
IntelliKnight 5820XL Installation Manual
combination.

1.1.2 Software Features

125 software zones, 250 output groups.
Advanced smoke detector features:
Automatic drift compensation Maintenance alert region Point status meets calibrated smoke test requirements for NFPA 72
“JumpStart” feature for easy programming.
Non-volatile event history stores 1000 events.
A choice of output patterns available for notification outputs, including ANSI 3.41 temporal signal.
Built-in synchronization appliance support for AMSECO, Faraday, Gentex®, System Sensor®, and Wheelock®.

1.2 About this Manual

This manual is intended to be a complete reference for all installation and operation tasks for the 5820XL. Please let us know if the manual does not meet your needs in any way. We value your feedback!

1.2.1 Terms Used in this Manual

The following terminology is used with the IntelliKnight 5820XL system:
Table 1-1 Manual Terminology
Term Description
SLC Signaling line circuit Module The term module is used for all hardware devices except for SLC
addressable devices and notification appliances. This includes the 5820XL panel itself and the built-in 5897 power supply. It also refers to any (optional) 5815XL SLC expansion modules.
Input Point An addressable sensing device, such as a smoke or heat detector or
a contact monitor device. Input Zone A protected area made up of input points. Output Point
(or Output Circuit) Group (or “Output Group”) A group of output points. Operating characteristics are common to all
Output (or “Cadence”) Pattern The pattern that the output will use, for example, Constant, March
Mapping Mapping is the process of specifying which outputs are activated
A notification point or circuit for notification appliances. Relay circuits
and auxiliary power circuits are also considered output points.
output points in the group.
Code, ANSI 3.41. Applies to zones and special system events. See
Section 7.7.3.2 for additional information.
when certain events occur in the system. Section 6.2 explains
mapping in detail.
1-2 151209
Page 15
Introduction

1.3 Compatible Products

Table 1-2 lists the products available from Silent Knight for use with the IntelliKnight 5820XL.
Table 1-2: 5820XL Compatible Products
Ty pe of
Device
SK
Addressable
SLC
Devices
SD
Addressable
SLC
Devices
Other
Modules
Software
Misc. RBB Remote Battery Box for mounting backup batteries that are too large to fit into
See Section 5.1 for a list of compatible devices.
See Section 5.2 for a list of compatible devices.
5815XL SLC Expander Allows an additional 127 SD SLC devices, or 99 SK de tectors and 99 SK
5824 Serial/Parallel Printer Interface Module
5895XL Intelligent Power Module
5496 Intelligent Power Module
5860 and 5860R Remote Fire Alarm Annunciator
5860TG and 5860TR Trim Ring Kit
5865-3 and 5865-4 LED Annunciator
5880 LED I/O Module Driver for up to 40 LEDs. Interfaces with customized
5883 General Purpose Relay Module
5660 Silent Knight Software Suite (SKSS)
5670 Silent Knight Software Suite (SKSS)
7860 Telephone Cord RJ31X cord for connecting phone line to the 5820XL.
Model Description
modules to be added to the system. Up to three 5815XLs per system. Allows a printer to be attached for the system for on-site event logging, detector
status and event history reports. Two maximum per system. Provides additional power, six Flexput™ circuits, and
two Form C relays. Max. 8 per system see Model 5895 Installation Instructions P/N 151024.
Provides 4 additional Notification Appliance Circuits/ Auxiliary power. (Up to 8 per system.)
Same operation, similar appearance as on-board annunciator . Up to 8 5860s per system. 5860 is gray; 5860R is red.
Trim ring kits for surface mounting the 5860 annunciator. 5860TG is gray; 5860TR is red.
LED annunciator can display up to 30 LEDs (15 red and 15 yellow). 5865-4 has key switches for silence and reset, and a system trouble LED.
annunciator boards. In addition the 5880 has eight generic switch input points.
Provides 10 Form C relays. Designed to be driven by the 5880. Up to four, 5883s can be used with each 5880 module.
For communication and panel programming with a Windows-based computer and *modem (not sold by Silent Knight, see Table 1-3 for compatible modems). Enables remote viewing of detector status and event history.
Facility management software. For remote viewing of detector status and event history. Requires a modem (not sold by Silent Knight).
the main control panel cabinet. Dimensions: 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D)
5895XLs and 5496s can be used in any combination, up to a total of eight devices on one system.
5865-3, 5865-4, and 5880 can be used in any combination, up to a total of eight devices on one panel.
151209 1-3
Page 16
IntelliKnight 5820XL Installation Manual
The following modems have been tested by Silent Knight for compatibility with the 5820XL and the Silent Knight Software Suite software packages:
Table 1-3: Compatible Modems
Manufacturer Model
US Robotics 28.8
LifeStyle
Motorola
MultiTech MT19321ZDX
28.8, 3400 series Premier 33.6

1.4 How to Contact Silent Knight

If you have a question or encounter a problem not covered in this manual, contact Silent Knight Technical Support at 800-446-6444.
To order parts, contact Silent Knight Customer Service at 800-328-0103.
1-4 151209
Page 17
Introduction
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer’s recommendations, State and local codes, and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off or give early warning in as many as 35% of all fires. While fire alarm systems are designed to provide warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons. For example:
Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow. Smoke particles may become cold, stratify, and not reach the ceiling or upper walls where detectors are located. Smoke particles may be blown away from detectors by air outlets Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires developing on another level.
The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density . If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors are subject to false alarms and nuisance alarms and may have been disconnected by users. For example, a smoke detector located in or near a kitchen may go into nuisance alarm during normal operation of kitchen appliances. In addition, dusty or steamy environments may cause a smoke detector to falsely alarm. If the location of a smoke detector causes an abundance of false alarms or nuisance alarms, do not disconnect the smoke detector; call a professional to analyze the situation and recommend a solution.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially within bedrooms), smoking in bed, violent explosions (caused by escaping gas, improper storage of flammable
151209 1-5
Page 18
IntelliKnight 5820XL Installation Manual
materials, etc.).
Heat detectors do not sense particles of combustion and are designed to alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Heat detectors are designed to protect property, not life.
Warning devices (including horns, sirens, and bells) may not alert people or wake up sleepers who are located on the other side of closed or partially open doors. A warning device that activates on a different floor or level of a dwelling or structure is less likely to awaken or alert people. Even persons who are awake may not notice the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or other devices should be provided to warn these people). Any warning device may fail to alert people with a disability, deep sleepers, people who have recently used alcohol or drugs, or people on medication or sleeping pills.
Please note that: i) Strobes can, under certain circumstances, cause seizures in people with con-
ditions such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm sig-
nal, do not respond or comprehend the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct on the proper reaction to alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or
permanent hearing loss.
Telephone lines needed to transmit alarm signals from a premises to a central station may be out of service or temporarily out of service. For added protection against telephone line failure, backup radio transmission systems are recommended.
System components, though designed to last many years, can fail at any time. As a precautionary measure, it is recommended that smoke detectors be checked, maintained, and replaced per manufacturer’s recommendations.
System components will not work without electrical power. If system batteries are not serviced or replaced regularly, they may not provide battery backup when AC power fails.
Environments with high air velocity or that are dusty or dirty require more frequent maintenance.
In general, fire alarm systems and devices will not work without power and will not function properly unless they are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate, an alarm system is not a substitute for insurance.
Property owners should continue to act prudently in protecting the premises and the people in their premises and should properly insure life and property and buy sufficient amounts of liability insurance to meet their needs.
1-6 151209
Page 19
Introduction
Requirements and recommendations for proper use of fire alarm systems in­cluding smoke detectors and other fire alarm devices:
Early fire detection is best achieved by the installation and maintenance of fire detection equipment in all rooms and areas of the house or building in accordance with the requirements and recommendations of the current edition of the National Fire Protection Association Standard 72, National Fire Alarm Code (NFPA 72), the manufacturer’s recommendations, State and local codes and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. For specific requirements, check with the local Authority Having Jurisdiction (ex. Fire Chief) for fire protection systems.
Requirements and Recommendations include:
Smoke Detectors shall be installed in sleeping rooms in new construction and it is
recommended that they shall also be installed in sleeping rooms in existing construction.
It is recommended that more than one smoke detector shall be installed in a
hallway if it is more than 30 feet long.
It is recommended that there shall never be less then two smoke detectors per
apartment or residence.
It is recommended that smoke detectors be located in any room where an alarm
control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire.
All fire alarm systems require notification devices, including sirens, bells, horns,
and/or strobes. In residential applications, each automatic alarm initiating device when activated shall cause the operation of an alarm notification device that shall be clearly audible in all bedrooms over ambient or background noise levels (at least 15dB above noise) with all intervening doors closed.
It is recommended that a smoke detector with an integral sounder (smoke alarm)
be located in every bedroom and an additional notification device be located on each level of a residence.
T o keep your fire alarm system in excellent working order , ongoing maintenance is
required per the manufacturer’s recommendations and UL and NFPA standards. At a minimum the requirements of Chapter 14 of NFPA 72, 2010 edition shall be followed. A maintenance agreement should be arranged through the local manufacturer’s representative. Maintenance should be performed annually by authorized personnel only.
The most common cause of an alarm system not functioning when a fire occurs is
inadequate maintenance. As such, the alarm system should be tested weekly to make sure all sensors and transmitters are working properly.
151209 1-7
Page 20
IntelliKnight 5820XL Installation Manual
1-8 151209
Page 21

Section 2 Agency Listings, Approvals, and Requirements

2.1 Federal Communications Commission (FCC)

1. The following information must be provided to the telephone company before the
IntelliKnight 5820XL can be connected to the phone lines:
A Manufacturer: Silent Knight by Honeywell B Model Number: IntelliKnight 5820XL C FCC registration number: AC6USA-23901-AL-E
Ringer equivalence: 0.8B D Type of jack: RJ31X E Facility Interface Codes: Loop Start: 02LS2 F Service Order Code: 9.0F
This equipment complies with Part 68 of the FCC rules and the requirements adopted by ACTA. On the inside cover of this equipment is a label that contains, among other information, a product identifier. If requested, this inform ation must be provided to the telephone company.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68 rules and requirements adopted by the ACTA. A compliant telephone cord (not provided) and modular jack must be utilized with this product. It is designed to be used with a modular jack that is also compliant.
The REN (ringer equivalence number) provided on this installation sheet is used to determine the number of devices that may be connected to the public switched telephone network. This number must not exceed 5.0. Since this product has an REN of .8, the number of devices is limited. The REN number is embedded in the FCC registration number as 10B.
If the 5820XL causes harm to the telephone network, the telephone company will notify you in advance that the temporarily discontinuance of service may be required. But if advance notice is not practical, the telephone company will notify the customer as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations or procedures that could affect the operation of the equipment. If this happens the telephone company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service.
If trouble is experienced with the 5820XL, for repair or warranty information, please contact Silent Knight at 1-800-328-0103 or www .silentknight.com. If the equipment is causing harm to the telephone network, the telephone company may request that you
151209 2-1
Page 22
IntelliKnight 5820XL Installation Manual
disconnect the 5820XL until the problem has been resolved. This product cannot be adjusted or repaired in the field. It must be returned to the
factory for service. This equipment is not designed for use with party line service. Connection to party
line service is subject to state tariffs. You may contact the state public utility commission, public service commission or corporation commission for information.
Since the 5820XL is a commercial fire alarm panel, it must be connected upstream of all other equipment utilizing the phone lines. If you have questions about the installation, contact your telephone company or a qualified installer.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1) This device may not cause radio interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
2-2 151209
Page 23
Agency Listings, Approvals, and Requirements

2.2 Underwriters Laboratories (UL)

2.2.1 Requirements for All Installations

General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for additional requirements. The following subsections list specific requirements for each type of installation (for example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems, and so on). See Section 8.7 for information on releasing operation.
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use the addressable smoke detectors specified in Section 5.2 of this manual and/ or conventional detectors listed in the compatibility chart. (See Appendix A.)
3. Use UL listed notification appliances compatible with the 5820XL from those specified in the Appendix at the back of this manual.
4. A full system checkout must be performed any time the panel is programmed.
Restricted Options:
The loss of AC signal is defaulted to 3 hours, however the system allows settings from 0 - 30 hours. For UL certified installations this number must be set from 1 to 3 hours.
The system allows the use of non-latching spot type smoke detectors. This fea­ture may not be used in commercial applications whereby a general alarm is sounded. It is intended for elevator recall, door holding applications, and hotel/ motel room applications.
The system allows the Alarm Verification time to be set from 1 to 255 seconds. For UL certified installations the setting must be a minimum of 60 seconds.
Call forwarding shall not be used.
When two count is used: detector spacing shall be cut in half, you shall not use the alarm verification feature, and no delay shall be used.
P.A.S (positive alarm sequence) feature shall be used only with automatic detec­tors.
151209 2-3
Page 24
IntelliKnight 5820XL Installation Manual
2.2.2 Requirements for Central Station Fire Alarm
Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the 5820XL sends an automatic daily test to the central station.
3. The AC Loss Hours option must be set from 1-3 hours.
4. The Attempts to Report option must be set for 5.
2.2.3 Requirements for Local Protected Fire Alarm
Systems
At least one UL listed supervised notification appliance must be used.
2.2.4 Requirements for Remote Station Protected Fire
Alarm Systems
1. Do not exceed the current draw load restrictions shown in Section 3.6.
2. The AC Loss Hours option must be set from 15-30 hours.
2-4 151209
Page 25

Section 3 Before You Begin Installation

This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly , especially if you are inst alling a 5820XL panel for the first time.

3.1 What’s in the Box?

The IntelliKnight 5820XL ships with the following hardware:
A cabinet with all hardware assembled
Two keys for the front door
Two keys for user operation of the on-board annunciator (installer operations require the Installer’s Code)
Ten 4.7K ohm end-of-line resistors
A battery cable for batteries wired in series

3.2 Environmental Specifications

It is important to protect the 5820XL control panel from water. To prevent water damage, the following precautions should be FOLLOWED when installing the units:
Intended for indoor use in dry locations only
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler system inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, production machinery)
When selecting a location to mount the 5820XL control panel, the unit should be mounted where it will NOT be exposed to: temperatures outside the range of 0°C­49°C (32°F-120°F) or humidity exceeding 93% noncondensing.
151209 3-1
Page 26
IntelliKnight 5820XL Installation Manual

3.3 Electrical Specification

Table 3-1 list the terminal block on the 5820XL as well as a description of each individual terminal and their respective electrical rating.
Table 3-1: Terminal Descriptions and Electrical Specifications
Terminal # and Label Description
1 L AC input (hot) 120 VAC, 60 Hz 2.5 A N/A 2 Earth ground N/A N/A N/A 3 N AC input (neutral) 120 VAC 60 Hz 2.5 A N/A
4X
*I/O 6 Flexput™ Circuits 24 VDC
5O
6 X
*I/O 5 Flexput™ Circuits 24 VDC
7 O
8X
*I/O 4 Flexput™ Circuits 24 VDC
9O
10 X
*I/O 3 Flexput™ Circuits 24 VDC
11 O
12 X
*I/O 2 Flexput™ Circuits 24 VDC
13 O
14 X
*I/O 1 Flexput™ Circuits 24 VDC
15 O 16 B
17 A 18 + 19 ­20 B 21 A 22 + 23 ­24 N.C.
26 N.O.
SBUS OUT
SBUS IN Used for Class A installations 0
RELAY 2 General Purpose Relay 2 24 VDC 2.5 A, resistive N/A25 C
SBUS communication 5 VDC 100 mA
SBUS power 24 VDC 1.0 A
Voltage Current
Rating
3.0A notification and auxiliary power circuits
100 mA for initiation circuits
3.0A notification and auxiliary power circuits
100 mA for initiation circuits
3.0A notification and auxiliary power circuits
100 mA for initiation circuits
3.0A notification and auxiliary power circuits
100 mA for initiation circuits
3.0A notification and auxiliary power circuits
100 mA for initiation circuits
3.0A notification and auxiliary power circuits
100 mA for initiation circuits
Earth Ground
Faults
0
0
0
0
0
0
0
* Regulated for NAC circuits, special application when used for releasing.
3-2 151209
Page 27
Before You Begin Installation
Table 3-1: Terminal Descriptions and Electrical Specifications
Terminal # and Label Description
27 N.C.
RELAY 1 General Purpose Relay 1 24 VDC 2.5 A, resistive N/A28 C 29 N.O. 30 N.C.
TROUBLE Trouble Relay 24 VDC 2.5 A, resistive N/A31 C 32 N.O. 33 SC- L1 34 SC+ 35 SC- L2 36 SC+ 37 Ring Phone Line 1 Telco Ring 38 Tip Phone Line 1 Telco Tip 39 Ring Phone Line 1 Premises Ring 40 Tip Phone Line 1 Premises Tip 41 Ring Phone Line 2 Telco Ring 42 Tip Phone Line 2 Telco Tip 43 Ring Phone Line 2 Premises Ring 44 Tip Phone Line 2 Premises Tip
45 SC-
46 SC+
SLC OUT
SLC IN
SLC terminals 32 VDC 150 mA 0
Used for Class A installations 0
SLC Programming Terminal ( ­)
SLC Programming T erminal ( + )
Rating
Voltage Current
N/A 0
N/A 0
32 VDC 150 mA
32 VDC 150 mA
Earth Ground
Faults
0
151209 3-3
Page 28
IntelliKnight 5820XL Installation Manual

3.4 Wiring Specifications

Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or cause false alarms. To avoid induced noise, follow these guidelines:
Isolate input wiring from high current output and power wiring. Do not pull one multi-conductor cable for the entire panel. Instead, separate the wiring as follows:
High voltage AC power, Terminals 1-3 SLC loops Terminals 33-36 Audio input/output Phone line circuits,
Terminals 37-44 Notification circuits Terminals 4-15 SBUS Terminals 16-23 Relay circuits Terminals 24-32
Do not pull wires from different groups through the same conduit. If you must run them together, do so for as short a distance as possible or use shielded cable. Connect the shield to earth ground at the panel. You must route high and low voltages separately.
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits. See Figure 3-1 for an example.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid.
3-4 151209
Page 29
Battery cables from under aluminum housing.
Maintain 1/4" spacing between battery cables and input wiring.
Red
Black
To
AC Input
Route all low voltage
wiring through any
of these knockouts.
All circuits, except battery
cables and AC, are power limited.
Maintain at least 1/4" spacing
between power limited and
non-power limited circuits.
Separate high and low
voltage circuits.
To phone
lines
Fire alarm power-limited circuits are
installed using types FPL, FPLR, FPLP or permitted substitute cables, provided these power-limited cable conductors extending beyond the jacket are separated by a minimum of
0.25 in. (6.35 mm) or by a nonconductive
sleeve or nonconductive barrier from all other conductors.
Before You Begin Installation
Figure 3-1 Wire Routing Example
151209 3-5
Page 30
IntelliKnight 5820XL Installation Manual
Chassis Mounting Nuts
Chassis Mounting Nuts
To ACOn-board Annunciator
Key Switch Input
Programming Ports

3.5 Board Assembly Diagram

Figure 3-2 Model 5820XL Assembly
Figure 3-2 shows the circuit boards, metal housing and annunciator that attach the 5820XL assembly to the cabinet. If you should need to remove the board assembly for repair, remove the four mounting nuts which hold the assembly in the cabinet. Then lift the entire assembly out of the cabinet. Do not attempt to remove the circuit boards from the metal bracket.
3-6 151209
Page 31
Before You Begin Installation

3.6 Calculating Current Draw and Standby Battery

This section is for helping you determine the current draw and standby battery needs if you are using SK addressable devices (Table 3-2) or SD addressable devices (Table 3-3).

3.6.1 Current Draw Worksheet Requirements

The following steps must be taken when determining 5820XL current draw and standby battery requirements.
1. You will use the Current Draw Worksheet to determine current draw and standby battery requirements. Use Table 3-2 if installing SK SLC Devices and Table 3-3 if installing SD SLC Devices. For the 5820XL, the worst case current draw is listed for the panel, addressable devices, and all SBUS expanders. Fill in the number of addressable devices and expanders that will be used in the system and compute the current draw requirements for alarm and standby. Record this information in the Current Draw Worksheet on Line A.
2. Add up the current draw for all auxiliary devices and record in the table on Line B.
3. Add up the current draw for all notification appliances and record in the table on Line C.
4. For notification appliances and auxiliary devices not mentioned in the manual, refer to the device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the panel itself, does not exceed 6.0 A. This is the maximum alarm current for the 5820XL control panel.
If the current is above 6.0 A you will need to use a notification power expander(s) such as the Silent Knight 5495 or the 5895XL intelligent power expander, to dis­tribute the power loads so that the 5820XL or the power expanders do not exceed their power ratings. Refer to the current draw worksheets provided with the 5495 or the 5895XL manuals so you do not exceed their power ratings.
6. Complete the remaining instructions in the appropriate Current Draw Worksheet for determining battery size requirements.
151209 3-7
Page 32
IntelliKnight 5820XL Installation Manual
3.6.1.1 Current Draw Worksheet for SK SLC Devices
Use Table 3-2 to determine current requirements during alarm/battery standby operation when SK SLC devices are installed. You can install up 99 SK detectors per loop (396 max per panel) and 99 SK modules per loop (396 max per panel). Copy this section if additional space is required.
Table 3-2: Current Draw Worksheet for SK SLC Devices
Device # of Devices Current per Device
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (battery current draw)
Addressable SLC Detectors SK-Photo SK-Photo-T mA mA SK-Ion mA mA SK-Heat mA mA SK-Heat-HT mA mA SK-Acclimate mA mA SK-Heat-ROR mA mA
5
SK-Duct
SK-Beam (without integral test)
SK-Beam-T
SK-FIRE-CO SLC
(includes PhotoR)
4
(with integral test)
1
(99 max/loop
& 396 max/
panel)
Standby: 215 mA 215 mA Alarm: 385 mA 385 mA
Standby: .30 mA Alarm: 6.5 mA
1
SLC Standby/Alarm: 2 mA
Aux. Pwr
SLC Standby/Alarm: 2 mA
Aux. Pwr
Standby: 2 mA mA Alarm: 8.5 mA mA
Standby: 2 mA mA Alarm: 8.5 mA mA Standby: .30mA mA Alarm: 7.2mA mA
Standby
Current
mA mA
mA mA
Alarm
Current
3-8 151209
Page 33
Before You Begin Installation
Device # of Devices Current per Device
Addressable SLC Modules SK-Monitor SK-Minimon mA mA SK-Pull-SA mA mA SK-Pull-DA SK-Monitor-2 Standby/Alarm: .75 mA mA mA SK-Mon-10 Standby/Alarm: 3.5 mA mA mA
SK-Control
SK-Control-6
SK-Relay Standby/Alarm: .255 mA mA mA SK-Relay-6 Standby/Alarm: 1.45 mA mA mA
SK-Relaymon-2
SK-Zone
SK-Zone-6
B200SR Sounder Base
B200S Sounder Base
B224RB Relay Base Standby/Alarm: 0.5 mA mA mA RTS151/151 KEY Alarm: 7.5 mA RA100Z Alarm: 10 mA SK-Iso (Isolator Module) (100 max/loop
B224BI Isolator Base Standby/Alarm: .5 mA mA mA Accessories Modules
5815XL SLC Expander (3 max.) Standby/Alarm: 55 mA mA mA 5860 Remote Fire Alarm
Annunciator 5824 Serial/Parallel Printer
Interface Module 5496 Intelligent Power Module 5895XL IntelliKnight Power
Module
(99 max/loop
& 396 max/
panel)
(99 max/loop
& 396 max/
panel)
&400 max/
panel)
(8 max.)
(2 max.)
(8 max.)
Standby/Alarm: .375 mA
SLC
Aux Pwr
SLC
Aux Pwr
1
Standby: 1.3 mA mA Alarm: 24 mA mA
Aux Pwr
SLC
Aux Pwr SLC Standby/Alarm 2 mA mA mA Aux Pwr SLC Standby .30 mA mA Aux SLC Standby .30 mA mA
Standby/Alarm: .45 mA mA mA
Standby: 20 mA mA Alarm: 25 mA mA Standby/Alarm: 45 mA mA mA
Standby/Alarm: 10 mA mA mA Standby/Alarm: 10 mA mA mA
Standby: 2.25 mA mA Alarm: 2.25 mA mA Standby: 1.7 mA mA Alarm: 7 mA mA Standby: 2.25 mA mA Alarm: 2.25 mA Standby: 8 mA mA Alarm: 20 mA mA
Standby 12 mA mA Alarm 90 mA mA Standby/
Alarm .27 mA Standby 50 mA mA Alarm 270 mA mA
Standby: .50 mA mA Alarm: 35 mA mA
Standby .50 mA mA Alarm (high vol) 35 mA mA
Standby
Current
mA mA
mA mA
Alarm
Current
mA mA
151209 3-9
Page 34
IntelliKnight 5820XL Installation Manual
Device # of Devices Current per Device
5865-4 LED Annunciator (with reset and silence
Standby
Current
Standby: 35 mA mA Alarm: 145 mA mA
Alarm
Current
switches) 5865-3 LED Annunciator
5880 I/O Module
(8 max.)
Standby: 35 mA mA Alarm: 145 mA mA Standby: 35 mA mA Alarm: 200 mA mA Standby: 0 mA mA
5883 Relay Interface (32 max.)
Alarm: 220 mA
mA
(22 mA per relay)
A Total System Current
Auxiliary Devices
2
Refer to devices manual for current rating.
Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA
B Auxiliary Devices Current
Notification Appliance Circuits Refer to device manual for current rating.
Alarm: mA Alarm: mA
mA
mA Alarm: mA mA Alarm: mA
C Notification Appliances Current
mA
mA
D Total current ratings of all devices in system (line A + line B + C) mA mA E Total current ratings converted to amperes (line D x .001): A A F Number of standby hours: H G Multiply lines E and F. Total standby AH AH H Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H I Multiply lines E and H. Total alarm AH J
Add lines G and I.
3
Total ampere hours
required
AH
AH
1. Total does not include isolator devices or accessory bases.
2. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that time. However, during normal operation, door holders draw current and must be included in the
6.0A total current that can be drawn from the panel.
3. Use next size battery with capacity greater than required.
4. SK-Beam-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. this should be considered when determining auxiliary power capacity but not calculated into current requirements for day to day operation.
5. The SK-Duct housing contains a vacant mount for a SK-Relay (sold separately). Current draw for the SK-Relay is calculated by increasing the SK-Relay row of the calculation sheet by one for each SK-Relay used with a SK-Duct.
3-10 151209
Page 35
Before You Begin Installation
3.6.1.2 Current Draw Worksheet for SD SLC Devices
Use Table 3-3 to determine current requirements during alarm/battery standby operation when SD SLC devices are installed. You can install up 127 SD devices per loop (508 max per panel). Copy this section if additional space is required.
Table 3-3: Current Draw Worksheet for SD SLC Devices
2 2
Standby
Current
mA mA
mA
Device # of Devices Current per Device
For each device use this formula: This column X This column = Current per number of devices. IntelliKnight 5820XL Fire Panel
(Current draw from battery) Addressable SLC Devices
SD500-AIM SD500-MIM mA mA SD500-PS SD500-ARM mA mA SD505-AHS mA mA SD505-AIS mA mA SD505-APS mA mA
SD500-ANM
SD500-SDM
SD500-LED
SLC Accessory Bases SD505-6RB (508 max.) Standby/Alram: .082 mA mA mA
SD505-6SB (508 max.)
SD505-DUCTR (508 max.)
SD505-DTS-K (508 max.) None, included with SD505-DUCTR worst case. SD505-DUCT (508 max.) None, included with detector current. SLC Isolator Devices SD500-LIM (1024 max.) SD505-6IB (508 max.) Accessories Modules 5815XL SLC Expander (3 max.) Standby/Alarm: 55 mA mA mA
5860 Remote Fire Alarm Annun. (8 max.) 5824 Serial/Parallel Printer
Interface 5895XL IntelliKnight Power
Expander 5496 Intelligent Power Module Standby/Alarm: 10 mA mA mA
1
(508 max.)
(508 max.)
(508 max.)
(100 max.)
(2 max.)
(8 max.)
Standby: 215 mA 215 mA Alarm: 385 mA 385 mA
1
Standby/Alarm: .55 mA
Aux. Pwr
1
SLC Standby/Alarm: .55 mA mA mA SLC Standby/Alarm: .55 mA mA
1
Aux. Pwr
Aux. Pwr
1
SLC Standby/Alarm: .55 mA mA mA
Aux. Pwr
SLC Standby/Alarm .082 mA mA mA
Aux. Pwr
SLC Standby/Alarm: .5 mA mA mA
Standby/Alarm .092 mA mA mA
Standby: 20 mA mA Alarm: 25 mA mA Standby/Alarm: 45 mA mA mA
Standby/Alarm: 10 mA mA mA
Standby: 8 mA mA Alarm: 60 mA mA
Standby: 20 mA mA Alarm: 106 mA mA Standby: 10 mA mA Alarm: 220 mA mA LED: 10 mA mA mA
Standby: 1 mA mA Alarm: 32 mA mA
Standby: 20 mA Alarm: 62 mA
Alarm
Current
mA
151209 3-11
Page 36
IntelliKnight 5820XL Installation Manual
Device # of Devices Current per Device
5865-4 LED Annunciator (with reset and silence switches)
5865-3 LED Annunciator
5880 LED I/O Module
(8 max.)
Standby
Current
Standby: 35 mA mA Alarm: 145 mA mA Standby: 35 mA mA Alarm: 145 mA mA Standby: 35 mA mA Alarm: 200 mA mA
Alarm
Current
Standby: 0 mA mA
5883 Relay Interface (32 max.)
Alarm: 220 mA
mA
(22 mA per relay)
A Total System Current
Auxiliary Devices
3
Refer to devices manual for current rating.
Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA
B Auxiliary Devices Current
Alarm: mA Alarm: mA Alarm: mA Alarm: mA
C Notification Appliances Current
mA mA mA mA
mA D Total current ratings of all devices in system (line A + line B + C) mA mA E Total current ratings converted to amperes (line D x .001): A A F Number of standby hours: H G Multiply lines E and F. Total standby AH AH H Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H I Multiply lines E and H. Total alarm AH J
Add lines G and I.
4
Total ampere hours
required
AH
AH
1. Total does not include isolator devices or accessory bases.
2. If using 24 VDC aux power only. No standby or alarm current for battery calculation if us ing 24 VAC, 120 VAC or 240 VAC.
3. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that time. However, during normal operation, door holders draw current and must be included in the
6.0A total current that can be drawn from the panel.
4. Use next size battery with capacity greater than required.
3-12 151209
Page 37
Before You Begin Installation
3.6.1.3 Maximum Battery Standby Load
Table 3-4 shows the maximum battery standby load for the 5820XL based on 24 and 60 hours of standby. The standby load calculations of line D in the Current Draw Calculation Worksheet (Table 3-2 for SK devices and Table 3-3 for SD devices) must be less than the number shown in Table 3-4 for the battery size used and standby hours required. * 33AH max battery size for FM (Factory Mutual) installations.
Table 3-4: Maximum Battery Standby Load
Rechargeable Battery Size
7 AH 270 mA 105 mA 12 AH 475 mA 190 mA 18 AH 685 mA 270 mA 35 AH 1.3 A 540 mA
* Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and
Remote Station Protected Fire Alarm systems (Polarity Reversal ) and Digital Alarm Communicator/ Transmitter (DACT).
Max. Load for 24 hrs.
Standby, 5 mins. Alarm
*Max. Load for 60 hrs.
Standby, 5 mins. Alarm
Warning!
Silent Knight does not support the use of batteries smaller than those listed in Table 3-4. If you use a battery too small for the installation, the system could overload the battery resulting in the installation having less than the required 24 hours standby power. Use Table 3-4 to calculate the correct battery amperes/hour rating needed for your installation.
151209 3-13
Page 38
IntelliKnight 5820XL Installation Manual

3.7 Installation Tasks Overview

This section provides a chart listing tasks that need to be performed when installing the IntelliKnight 5820XL system. The chart is intended to be a handy way for you to make sure you have completed all necessary tasks. Unless noted, these tasks do not have to be performed in the order they are listed here.
Important: Connect and address SLC devices before running JumpStart.
Task
Main Panel Hardware Installation
Mount the control panel cabinet 4.1 Connect AC. 4.2 Connect phone lines. 4.11 Install 5815XL SLC expander modules (if needed). Required if more than 127
SLC devices are used. Install 5860 Remote Fire Alarm Annunciator modules if used. 4.5 Install 5865 or LED Annunciator modules if used. 4.9 Install 5880 LED I/O module if customized LED annunciation will be used. 4.8 Install notification appliances. 4.12 Install auxiliary power devices. 4.12.5 Install the 5824 Serial/Parallel Printer Interface module. 4.7 Connect batteries (typically last step). 4.3
SLC Device Hardware Installation
Perform these steps before running JumpStart.
Connect device bases to the loop. SK 5.5
Set device addresses. SK 5.6
Physically connect detectors to their bases. Connect relay and contact monitor modules.
JumpStart
JumpStart is for initial system programming. JumpS t art automatically selects some options for SLC devices. See “Input Point SLC Device) Configuration” section of this chart for other options.
JumpStart makes selections for the following options. You can customize options, if necessary.
Device type (detector or switch) configured by JumpStart. To change, see
Program type of detector (heat, photoelectric, or ionization) selected by JumpStart.
System Software Configuration
Select low AC hours report time (6 hours by default). 7.7.4.2 Select Auto Test Time (2:00 AM by default). 7.7.1.2 Enable/disable automatic DST adjustment feature (enabled by default). 7.7.4.3 Change clock display format (12-hour with AM/PM by default). 7.7.4.4
See Sec.
(for more info.)
5.4 & see device instructions
6.1 & 7.8
To change, see
4.6
SD 5.7
SD 5.8
install
7.6
7.6
3-14 151209
Page 39
Before You Begin Installation
Task
Set up reporting accounts. 7.7.1 Select options for phone lines. 7.7.2 Select system-wide response to trouble conditions, if desired. 7.7.3 Select system-wide cadence patterns for special conditions (fire drill, Aux1
and Aux2 alarms) if desired. Customize banner message (message that displays on LCD in normal mode)
if desired.
Input Point (SLC Device) Configuration
JumpStart automatically selects some options for SLC devices (see “JumpS tart” section of this chart). You can change options selected by JumpStart, if necessary and further customize input point options.
Select device family (SK or SD). Only one device family can be used per control panel.
Program type of switch (manual pull, fire drill, and so on), if necessary. (JumpStart assigns all switches as Manual Pull type.)
If the installation includes duct detectors, program detector type. (JumpStart does not distinguish duct detectors from ordinary smoke detectors.)
Assign a name (or description) to a point. 7.6.3.1 Assign input points to zones, if necessary. (JumpStart assigns all input points
to Zone 1.)
Zone Configuration
Add a zone to the system if it does not already exist. (Zone 1 created by JumpStart.)
Assign a name (or description) to a zone. 7.4.1.1 Select alarm delay options (detection characteristics) for zone. 7.4.1.2 Select heat detector trip temperature. (JumpStart selects 150°F for heat
detectors.)
Output Point Configuration
Conventional notification circuits (circuits 1-6):
Enable circuits used for notification appliances through programming (if necessary). (JumpStart enables circuits 1-6 as Notification.)
Conventional relay circuits (circuits 7-8):
Select options for relay circuits, if desired. Note: Relay circuits will always output continuously (constant pattern), even if assigned to an Output Group that uses a different output pattern.
Auxiliary power circuits (circuits 1-6):
Enable any circuit used for auxiliary power devices through programming. 7 .6 Select type of power (door holder, constant, or resettable) 7.6
Addressable relay modules
Assign addressable relay modules to output groups through programming. (JumpStart assigns all relay modules to Group 1.)
LED output points (from the 5880 LED I/O module or 5865/66 LED Annunciator)
Assign LED modules to output groups through programming. 7.6.3
All output circuits (1-8):
See Sec.
(for more info.)
7.7.3
7.7.7
7.2
7.6
7.6
7.6
7.4.2
7.4.1.2
7.5.1
7.5.1
7.6
151209 3-15
Page 40
IntelliKnight 5820XL Installation Manual
Task
Disable (set to UNUSED) any unused circuits. If you do not disable unused output circuits, they will cause a trouble condition (unless an EOL resistor is used).
Select a name for the point. 7.6
Output Group Configuration
Add a group to the system if it does not already exist. 7.5.2 Assign output points to a group. 7.6 Assign a name (or description) for a group. 7.5.1.1
Select “group properties” (see below).
Latching / non-latching 7.5.1 Silencing option 7.5.1 Select options for activation with system switches. 7.5.1 Map zones to output groups that will activate when zone goes into alarm. 7.4.1.3 Select a cadence pattern for outputs in the zone. 7.4.1.3
See Sec.
(for more info.)
7.6
3-16 151209
Page 41

Section 4 Control Panel Installation

Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing.

4.1 Mounting the Control Panel Cabinet

Read the environmental specifications in Section 3.2 before mounting the control panel cabinet. This will ensure that you select a suitable location.
The panel should be accessible to main drop wiring runs. It should be mounted as close to the center of the building as possible and located within a secured area, but should be accessible for testing and service.
Mount the control panel cabinet so it is firmly secured to the wall surface. When mounting on concrete, especially when moisture is expected, attach a piece of 3/4­inch plywood to the concrete surface and then attach the cabinet to the plywood. Also mount any other modules to the plywood.
The cabinet can be surface- or flush-mounted. If you flush-mount the cabinet, the hole for the enclosure should be 14.75" W x 25" H x 4" D. Do NOT flush-mount in a wall designated as a fire break.

4.1.1 Preventing Water Damage

Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.

4.1.2 Removing the 5820XL Assembly from the Housing

If it should ever be necessary to remove the control panel assembly from the cabinet for repair, do so by unscrewing the nuts that connect the control panel assembly to the cabinet. Do not attempt to disassemble the circuit boards. See Section 3.5 for location of the nuts.
151209 4-1
Page 42
IntelliKnight 5820XL Installation Manual

4.2 AC Connection

At installation, connect the AC terminals to the power source as shown in Figure 4-1. It may be necessary for a professional electrician to make this connection.
The AC terminals are rated at 120 VAC, 50 or 60 Hz, 2.5A.
Figure 4-1 120 VAC Power Connection
4-2 151209
Page 43
Control Panel Installation
To Control Panel
Red
Black
Battery Jumper
(P/N 140694)
Shipped With Panel
UL Recognized
UL Recognized 12V Battery
12V Battery

4.3 Battery Connection

The control panel battery charge capacity is 7.0 to 35 AH. Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Section 3.6).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating. It is recommended that you replace batteries every five years.
Figure 4-2 Battery Connection
151209 4-3
Page 44
IntelliKnight 5820XL Installation Manual
Cabinet
Mounting Holes

4.3.1 RBB Accessory Cabinet

The Model RBB Accessory cabinet can be used when you are required to use backup batteries that are too large to fit into the main control panel cabinet.
The RBB cabinet holds batteries up to the 35 AH size. The RBB dimensions are 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D).
4.3.1.1 Installing the RBB Accessory Cabinet and Batteries
To properly install the accessory cabinet and backup batteries, follow these steps:
1. Mount the accessory cabinet. See Figure 4-3 for the four cabinet mounting holes.
If mounting onto drywall the accessory cabinet must be mounted onto 3/4-inch plywood. This is necessary because the weight of the batteries inside the accessory cabinet could cause the cabinet to pull away from the drywall.
When mounting on concrete, especially when moisture is expected, attach a piece of ¾" plywood to the concrete surface and then attach the RBB cabinet to the plywood.
If using the battery cable extenders provided (P /N 140643), mount the RBB cabinet no more than 18" away from the main control panel cabinet. This will ensure that the battery cables reach the battery terminals.
Figure 4-3 RBB Cabinet Mounting Holes
2. Connect the main control panel battery cables to the battery cable extenders as shown in Figure 4-4.
Figure 4-4 Splicing Control panel Battery Cable to RBB Battery Cable Extenders
4-4 151209
Page 45
Control Panel Installation
Conduit
Conduit Coupler
+
+
-
-
RBB Cabinet Cover Screws
RBB Cabinet Cover Screws
Cover Plate
Mounting Keyholes
3. Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4-5.
Figure 4-5 Battery Connections in the RBB Cabinet
Note: Figure 4-5 is an example of how the wire connections can be routed. However, any other cabinet
knock-outs (on either the main control panel or the RBB cabinet), that are not previously being used may be utilized to connect conduit between the two cabinets.
4. Connect battery leads to the backup battery terminals. See Figure 4-5.
Observe the proper polarity to prevent damage to the batteries or the control
panel.
5. Insert the RBB cover screws into the cover mounting holes. See Figure 4-5.
Screw the cover screw 3/4 of the way into the cover mounting hole.
6. Align the cover plate mounting keyhole over the cover mounting screws. See Fig­ure 4-6.
Figure 4-6 Cover Plate Mounting Keyholes and Cover Mounting Screws Alignment
7. Slide the cover into place and tighten the cover mounting screws. See Figure 4-6
151209 4-5
Page 46
IntelliKnight 5820XL Installation Manual

4.4 SBUS Wiring

This section contains information on calculating SBUS wire distances and the types of wiring configurations (Class A and B).

4.4.1 Calculating Wiring Distance for SBUS Modules

The following instructions will guide you in determining the type of wire and the maximum wiring distance that can be used with control panel SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the control panel, it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. The individual worst case values are shown in the table below.
Note: Total worst case current draw on a single SBUS cannot exceed 1 amp. If a large number of ac-
cessory modules are required, and the worst case current draw will exceed the 1 amp limit, then the current draw must be distributed using 5895XL Power Expanders. Each 5895XL Power Ex­pander provides an additional SBUS, with an additional 1 amp of SBUS cu rrent. Wiring d istance calculations are done separately for each 5895XL, and separately for the control pan el itself.
Model Number Worst Case Current Draw
5860 Fire Annunciator .100 amps 5824 Serial/Parallel Printer Interface Module .040 amps 5880 LED I/O Module .250 amps 5865 LED Annunciator .200 amps 5895XL Intelligent Power Supply .010 amps 5496 Intelligent Power Supply .010 amps
Note: Refer to Table 3-3 for maximum number of each type of device that can be used per system.
After calculating the total worst case current draw, Table 4-1 specifies the maximum distance the modules can be located from the panel on a single wire run. The table ensures 6.0 volts of line drop maximum. In general, the wire length is limited by resistance, but for heavier wire gauges, capacitance is the limiting factor.
4-6 151209
Page 47
Control Panel Installation
These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used. The formula used to generate this chart is shown in the note below.
Table 4-1: Wire Distances Per Wire Gauge Using Copper Wire
Wiring Distance: SBUS Modules to Panel
Total Worst Case
Current Draw (amps)
0.100 1852 ft. 4688 ft. * 6000 ft. * 6000 ft.
0.200 926 ft. 2344 ft. 3731 ft. 5906 ft.
0.300 617 ft. 1563 ft. 2488 ft. 3937 ft.
0.400 463 ft. 1172 ft. 1866 ft. 2953 ft.
0.500 370 ft. 938 ft. 1493 ft. 2362 ft.
0.600 309 ft. 781 ft. 1244 ft. 1969 ft.
0.700 265 ft. 670 ft. 1066 ft. 1687 ft.
0.800 231 ft. 586 ft. 933 ft. 1476 ft.
0.900 206 ft. 521 ft. 829 ft. 1312 ft.
1.000 (Max) 185 ft. 469 ft. 7 46 ft. 1181 ft.
22 Gauge 18 Gauge 16 Gauge 14 Gauge
Note: The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms) =
Maximum Wire Length (Feet) =
(6000 feet maximum)
where: Rpu = Ohms per 1000 feet for various wire gauges (see table below)
Total Worst Case Current Draw (amps)
Maximum Resistance (Ohms)
6.0 Volts
Rpu
* 500
Table 4-2: Typical Wire Resistance Per 1000 ft. Using Copper Wire
Wire Gauge Ohms per 1000 feet (Rpu)
22 16.2 18 6.4 16 4.02 14 2.54
151209 4-7
Page 48
IntelliKnight 5820XL Installation Manual
Wiring Distance calculation example:
Suppose a system is configured with the following SBUS modules: 2 - Module 5860 Fire Annunciator 1 - 5895XL Intelligent Power Expander 1 - 5865 LED Annunciator 1 - 5824 Serial/Parallel Interface Module
The total worst case current is calculated as follows:
5860 Current Draw = 2 x .100 amps = .200 amps 5895XL Current Draw = 1 x .010 amps = .010 amps 5865 Current Draw = 1 x .200 amps = .200 amps 5824 Current Draw = 1 x .040 amps = .040 amps Total Worst Case Current Draw = .450 amps
Using this value, and referring to the Wiring Distance table, it can be found that the available options are:
370 feet maximum using 22 Gauge wire 938 feet maximum using 18 Gauge wire 1493 feet maximum using 16 Gauge wire 2362 feet maximum using 14 Gauge wire
4-8 151209
Page 49
Control Panel Installation
Supervised Power Limited
Caution
For proper system supervision do not use looped wire under terminals marked A, B, +, and
- of the SBUS device connectors. Break wire runs to provide supervision of connections.
Supervised Power Limited

4.4.2 Wiring Configurations

Figure 4-7 illustrates Class A wiring configuration and Figure 4-8 illustrates Class B configuration.
151209 4-9
Figure 4-7 SBUS Class A Wiring
Figure 4-8 SBUS Class B Wiring
Page 50
IntelliKnight 5820XL Installation Manual

4.5 Remote Annunciator 5860 Installation

The optional Model 5860 Remote Annunciator, shown in Figure 4-9, performs the same functions as the on-board annunciator. Up to 8 annunciators can be added to the IntelliKnight 5820XL system.
Figure 4-9 Model 5860 Remote Annunciator, Front View
5860 installation involves the following steps:
1. Make sure power is off at the panel.
2. Mount the 5860 in the desired location (see Section 4.5.1).
3. Connect the 5860 to the panel (see Section 4.5.2).
4. Use the on the back of the 5860 to assign an ID# to the 5860 (see Section 4.10.1).
5. The new 5860 module must be added to the system through programming. Jump­St art will add the module automatically (see Section 6.1). You can also add it man­ually (see Section 7.3.2). Select a name, if desired (see Section 7.3.1.1).
4-10 151209
Page 51
Control Panel Installation

4.5.1 Mounting the 5860

This section of the manual describes mounting the remote annunciator. The annunciator can be flush- or surface-mounted.
Figure 4-10 shows the parts of the annunciator. Instructions for disassembling and mounting appear on the following pages.
Figure 4-10 Annunciator Parts
151209 4-11
Page 52
IntelliKnight 5820XL Installation Manual
Set screw location.
Loosen set screws to remove bezel
when disassembling annunciator.
Knockout holes
Holes for surface mounting.
Holes for inserting wires for flush mounting (located in all corners).
Stand-off
(throughout)
Screw for placement
of mounting wires
(top and bottom).
The 5860 comes from the factory fully assembled. You must disassemble it for mounting. To disassemble the annunciator, use a 5/64 hex wrench to remove the set screws, located on the bottom of the annunciator bezel. (See Figure 4-11 for location of the set screws.)
4.5.1.1 Flush Mounting
This section of the manual describes flush mounting. You can flush-mount with or without an electrical box.
4-12 151209
Figure 4-11 Annunciator Back Box and Bezel Details
Page 53
Control Panel Installation
Sheet rock
Sheet rock
Electrical Box
Annunciator
back box
1-3/8"
When flush-mounting using an
electrical box, the box must be
1-3/8" from face of wall.
Electrical box applications require
2 by 4 construction minimum.
studs
electrical
box
annunciator
back box
(outline)
wall
Examples of Electrical Box Use
Electrical Box Placement
Flush Mounting with an Electrical Box
The 5860 annunciator can be used with the following types of electrical boxes: 4S, single-gang, and double-gang.
If an electrical box is used, the box must be 1-3/8” back from the face of the wall to accommodate the annunciator. Studs used with an electrical box must be two by fours (or larger).
Flush Mounting Steps
1. Cut a hole in the sheet rock to the following dimensions: 8¼” W x 6-5/8” H. If an electrical box is used, the box must be 1-3/8” back from face of wall to accommo­date the annunciator (see Figure 4-12).
2. Remove knockout holes as needed for wires.
3. Fit the annunciator back box into the hole and stabilize with mounting wires. Angle the mounting wires into the first hole past the sheet rock. Secure the wires behind the screws as shown in Figure 4-13. When all four wires are in place, the back box should fit snugly into the hole in the sheet rock.
151209 4-13
Figure 4-12 Placement of Electrical Box for Flush Mounting
Page 54
IntelliKnight 5820XL Installation Manual
Insert wires at an angle into the first holes past the sh eet rock.
Secure the wires behind this screw.
Attach second set of wires to top of back box.
4. After the annunciator wiring to the panel has been completed (described in Sec­tion 4.5.2), replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel.
Figure 4-13 Flush Mounting the Back Box
4.5.1.2 Surface Mounting
The 5860 can be mounted directly to a surface or can be attached to a single, double, or four-square electrical box. The Model 5860TG/TR trim ring kit is available for use when surface mounting.
1. Drill holes in the surface to match the screw holes on the back box.
2. Fit the trim ring over the back box.
3. Attach the back box to the surface using screws provided.
4. After the annunciator wiring to the panel has been completed (described in Sec­tion 4.5.2), replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel.
4-14 151209
Page 55

4.5.2 Model 5860 Connection to the Panel

Supervised Power Limited
Connect the 5860 to the panel as shown in Figure 4-14.
Control Panel Installation
Figure 4-14 Model 5860 Connection to the Panel
151209 4-15
Page 56
IntelliKnight 5820XL Installation Manual

4.6 5815XL Installation

The 5815XL SLC expander lets you add 127 SD addressable devices or 99 SK detectors and 99 SK modules. Add up to three 5815XLs to a system to achieve the maximum number of devices on the system.
To install the 5815XL:
1. Make sure power is off at the panel.
2. Mount the 5815XL in the 5820XL cabinet, the 5895XL cabinet, or the 5815RMK remote mounting kit. Use the standoffs located under the control panel board assembly and secure with screws provided with the 5815XL. For additional infor­mation, also see Model 5895XL Installation Instructions (P/N 151142) or 5815RMK Remote Mounting Kit Installation Instructions (P/N 151391).
3. Connect the 5815XL to the control panel. (See Section 4.6.1.)
4. Use on-board DIP switches to select an SBUS ID#. (See Section 4.10.1.)
5. The new 5815XL module must be added to the system through programming. JumpSt art will add the module automatically (see Section 6.1). You can also add it manually (see Section 7.3.2). Select a name, if desired (see Section 7.3.1.1).
6. You are now ready to connect SLC devices to the 5815XL (see Section 5.4).
Figure 4-15 is a drawing of the 5815XL board, showing the location of terminals and DIP switches.
Figure 4-15 5815XL Board
4-16 151209
Page 57
Control Panel Installation
Supervised Power Limited

4.6.1 5815XL Connection to the Panel

Connect the 5815XL to the control panel as shown in Figure 4-16. After the 5815XL is connected to the panel, it must be added to the system. This programming step is described in Section 4.10.
Figure 4-16 5815XL Connection to Main Panel Assembly
151209 4-17
Page 58
IntelliKnight 5820XL Installation Manual
Supervised Power Limited
4.7 5824 Serial/Parallel Interface Module
Installation
The 5824 serial/parallel interface module allows you to connect a printer to the panel, so you can print a real-time log of system events, a report of detector status, and event history. Instructions for installing the 5824 appear below. The 5824 is for ancillary use only.
5824 installation involves the following steps:
1. Make sure power is off at the panel.
2. Connect the 5824 to the panel as shown in Figure 4-17.
Note: Two 5824s per panel maximum.
3. Use the DIP switches on the back of the 5824 board to assign an SBUS ID# to the
5824. See Section 4.10.1.
4. Configure the 5824 device through programming. See Section 4.7.1.
5. Connect a printer to the 5824 as shown in Figure 4-18.
Figure 4-17 5824 Connection to the Panel
4-18 151209
Page 59
Figure 4-18 Printer Connection
Model 5824 (with housing)
To Parallel Printer
T o Se r ial Prin te r

4.7.1 Selecting 5824 Options

Control Panel Installation
Configuring the 5824 includes the following steps:
Add the module to the system. JumpStart will add the module automatically (see Section 6.1). You can also add it manually (see Section 7.3.2).
Select a name, if desired (see Section 7.3.1.1).
Select options for the printer and the output port. See below.
151209 4-19
Page 60
IntelliKnight 5820XL Installation Manual
Printer and Output Port Options
1. From the Installer Main Menu, select for Program Menu.
2. Select for Module.
3. Select for Edit Module.
4. From the list that displays, select the 5824 module you want to configure.
5. Press to bypass the next two screens. A screen similar to the one shown in Figure 4-19 will display.
Figure 4-19 Selecting Printer and Output Port Options
6. Select options for the printer as needed for your installation. Most printers are par­allel.
7. If you are using a serial printer, use the next screen to select serial port options as required for your printer. Refer to your printer manual if you need more informa­tion.
Option Choices
Baud Rate: 75 - 19200 Data Bits: 5 - 8 Stop Bits: .5, 1, 2 Parity: None, Even, Odd
4-20 151209
Page 61
Control Panel Installation
SBUS Connection
SBUS Address DIPs
Dry Contact Inputs

4.8 5880 LED I/O Module

The 5880 is an LED driver board that can be used in a wide variety of applications, including as an interface with most customized floor plan annunciator boards. The 5880 can drive up to 40 LEDs and has one PZT controller. The 5880 also has eight inputs for monitoring. The following sub-sections describe hardware installation. Refer to Section 6 for programming information.

4.8.1 5880 Board Layout

Figure 4-20 shows the locations of screw terminals for connection to the panel and contact monitor wiring; pin connectors for connecting LEDs; and the DIP switch for selecting an SBUS ID number for the 5880.
Figure 4-20 5880 Board Layout
151209 4-21
Page 62
IntelliKnight 5820XL Installation Manual
Supervised Power Limited

4.8.2 5880 Connection to Panel

The 5880 connects to the panel via the SBUS. Make connections as shown in Figure 4-21. After the 5880 is connected to the panel, it must be added to the system. This programming step is described in Section 4.10.
Figure 4-21 5880 Connection to Main Control Panel Assembly
4-22 151209
Page 63
Control Panel Installation
11
20
12 13 14
15 16 17 18 19
LED Power
no connection
Anode
Cathode
LEDs
P2
5880 LED Outputs
1
10
2 3 4
5 6 7 8 9
LED Power
Programmable Open Collector Output
Not mappable.
Matches PZT pattern
on on-board
annunciator
Anode
Cathode
LEDs
P1
Connectors P3 and P4 wired same as P2.

4.8.3 LED Wiring

There are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its power from Pin 11. Internal resistors are sized so that there is approximately 10 mA of current for each LED, no series resistors are required. LED outputs can be mapped to output circuits. See Section 6 for programming details.
Wire the LEDs as shown in Figure 4-22. On connector P1, Pin 12 is an open collector output for controlling a PZT. If used, the
5880 PZT will match the PZT pattern of the on-board (or 5860) annunciator.
Note: The circuit connected to “Open Collector Output” (last pin on P1) must be current limited so that
no more than 100 mA of current is allowed to flow into the open collector transistor.
151209 4-23
Figure 4-22 5880 Board Layout
Page 64
IntelliKnight 5820XL Installation Manual
Model 7628
Supervised/Power Limited
4.7k EOL

4.8.4 Dry Contact Wiring

The 8 input circuits on the 5880 board are for monitoring switch inputs-any type of switch supported by the control panel can be used with the 5880. For example, you can use a 5880 to monitor pull stations, water flow , ta mper, reset, or silence switches.
Wire dry contacts as shown in Figure 4-23. Notice grouping of terminals; power terminals are shared by two inputs.
Figure 4-23 Dry Contact Wiring
4-24 151209
Page 65
Control Panel Installation
SILENCE
TROUBLE
RESET
5865-4 Board Assembly
5865-3 Board Assembly
Plexiglass plate mounted to LED board at factory.
Do not remove.
5865-4 switches follow main FACP; no installation or programming required.
Numbers indicate point numbers for
5865. (They do not appear on board assembly.)
12
9
10
11 12
21 22
19 20
29 30
34
5
6
7
8
13
14
15
16
17
18
23
24
25 26
27
28

4.9 5865-3 / 5865-4 LED Annunciator Installation

The 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30 mappable LEDs, remote silence and reset key switches, and a general system trouble LED. The 5865­3 has 30 mappable LEDs only. These are arranged as 15 pairs of red (typically used for alarm) and yellow (typically used for trouble) LEDs.
Installation of the 5865-5 and 5865-4 is identical. The key switches and the trouble LED follow the behavior of other system annunciators and do not require any installation steps. The following sub-sections describe how to install the 5865-3 and 5865-4 hardware. Refer to Section 6 for programming information.
Note: This manual uses “5865” when referring to aspects of the 5865-3 and 5865-4 that are common
to both models.
151209 4-25
Figure 4-24 5865-3 and 5865-4 Assembly (front view)
Page 66
IntelliKnight 5820XL Installation Manual
Supervised Power Limited

4.9.1 FACP Connection

The 5865 connects to the panel via the SBUS. Make connections as shown in Figure 4-25. After the 5865 is connected to the panel, it must be added to the system. This programming step is described in Section 4.10.
Figure 4-25 5865 Connection to the FACP
4-26 151209
Page 67
Control Panel Installation

4.9.2 5865 Mounting

Mount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a standard 3-gang electrical box. In Figure 4-26, the 5865-4 attached to a 4-gang box is used as an example.
Figure 4-26 5865 Mounting Example
The 5865 ships with a set of zone description labels that can be inserted into the 5865 board assembly. These labels can be used in a typewriter or can be written on by hand. Slide the labels under the plexiglass as shown in Figure 4-27. The LEDs will
151209 4-27
Page 68
IntelliKnight 5820XL Installation Manual
show through the label when illuminated.
Figure 4-27 Inserting Zone Description Labels
4-28 151209
Page 69
Control Panel Installation

4.10 Configuring Modules

This section describes how to configure any system hardware modules that have been added to the system.

4.10.1 Assigning Module IDs

When installing a hardware module (such as, 5815XL, 5824, 5860, 5895XL, 5865-3 or 5865-4), you must use the DIP switches on the module to assign an ID# to the module.
Figure 4-28 shows all possible DIP switch positions and their correlation to a numerical ID. For example, to select ID 2, place DIP switch 2 in the up position.
Figure 4-28 Possible module addresses
Refer to 7.3 to edit, add, delete, and view module list.
151209 4-29
Page 70
IntelliKnight 5820XL Installation Manual

4.11 Telephone Connection

Connect the telephone lines as shown in Figure 4-29. The Model 7860 phone cord is available from Silent Knight for this purpose.
A number of programmable options are available for customizing telephone lines. These options are described in Section 7.7.
Figure 4-29 Connection of Telephone Lines
4-30 151209
Page 71
Control Panel Installation
4.12 Flexputs
The six Flexput™ circuits are an innovative and versatile feature of the control panel. They can be used as: Class A or B notification circuits, Class A or B initiation circuits (either 2 or 4 wire detectors), or as auxiliary power (resettable, continuous, or door holder).
The polarity of the Flexput terminals differs depending on whether the circuit is programmed as an input or and output circuit. If the circuit is programmed as an input circuit (for a detector or normally open contact) the X terminal is negative and O terminal is positive. If the circuit is programmed as an output circuit (Aux power or NAC) then the X terminal is positive and the O terminal is negative.
This section of the manual explains how to install conventional notification appliances and initiating devices to be used with the system.
I/O Circuits

4.12.1 Conventional Notification Appliance

This sub-section of the manual explains how to install conventional notification appliances for Class A (Style Z) and Class B (Style Y) configurations.
4.12.1.1 Class B Notification Wiring
Y ou must use an appliance from the list of comp atible appliances in the Appendix A at the back of this manual.
To install a circuit:
1. Wire Class B Notification appliances as shown in Figure 4-30.
151209 4-31
Page 72
IntelliKnight 5820XL Installation Manual
Alarm Polarity
UL Listed EOL
Model 7628
4.7 k
Supervised Power Limited
Notification Wiring
Max. Impedance: 1.5
Regulated 24 VDC Full Wave Rectified
27.4 VDC, 3A per Circuit, 6A max Combined
2. Configure the circuit through programming (see Section 7.6).
Figure 4-30 Class B Notification Appliance Circuit Wiring
4-32 151209
Page 73
Control Panel Installation
Supervised Power Limited
Regulated 24 VDC Full Wave Rectified
27.4 VDC, 3A per Circuit, 6A max Combined
4.12.1.2 Class A Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix at the back of this manual.
To install a Class A notification appliance circuit:
1. Wire the Class A notification appliances as shown in Figure 4-31.
Caution
For proper system supervision do not use looped wire under terminals marked O and X of the Flexput connectors. Break wire runs to provide supervision of connections.
2. Configure the circuit for Class A in programming (see Section 7.6).
Figure 4-31 Class A Notification Appliance Circuit Configuration
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is
used to refer to the circuit pair. For example, Figure 4-31 uses both Flexput circuit 5 and 6, so in programming it would be referred to as point 5.
151209 4-33
Page 74
IntelliKnight 5820XL Installation Manual
UL Listed EOL
Model 7628
4.7 k
Supervised Power Limited

4.12.2 Conventional Input Switch Circuits

This section of the manual explains how to install conventional initiating devices for Class A (Style D) or Class B (Style B) configurations.
4.12.2.1 Class B Inputs
You can connect conventional Class B switches, such as waterflow switches and pull stations, directly to the Flexput circuits of the control panel.
To install a Class B switch:
1. Wire the Class B switch as shown in Figure 4-32.
2. Configure the circuit through programming (see Section 7.6).
Figure 4-32 Class B Input Switches
4-34 151209
Page 75
Control Panel Installation
Note: Flexput circuit 5 and 6
used as an example. Any Flexput point pairing could be used.
Supervised Power Limited
4.12.2.2 Class A Inputs
You can connect conventional Class A switches, such as waterflow switches and pull stations, directly to the Flexput circuits of the control panel.
To install a Class A switch:
1. Wire the Class A switch as shown in Figure 4-33.
2. Configure the circuit through programming (see Section 7.6).
Figure 4-33 Class A initiating Switches
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is
used to refer to the circuit pair. For example, Figure 4-33 uses both Flexput circuit 5 and 6, so in programming it would be referred to as point 5.
151209 4-35
Page 76
IntelliKnight 5820XL Installation Manual
Note: Flexput circuit 5
used as an example. Any Flexput circuit could be used.
UL Listed EOL
Model 7628
4.7 k
Supervised Power Limited

4.12.3 Installing 2-Wire Smoke Detectors

Any compatible U.L. listed two-wire smoke detector can be used with the control panel (see Appendix A for list of compatible smoke detectors). Figure 4-34 and Figure 4-35 illustrate how to connect a UL listed 2-wire detector to the control panel.
4.12.3.1 Installing 2-Wire Class B Smoke Detectors
To install a Class B two-wire smoke detector, wire as shown in Figure 4-34.
4-36 151209
Figure 4-34 Two-Wire Class B Smoke Detector
Page 77
Control Panel Installation
Note: Flexput circuit 5 and 6
used as an example. Any Flexput point pairing could be used.
Supervised Power Limited
4.12.3.2 Installing 2-Wire Class A Smoke Detectors
To install a Class A two-wire smoke detector, wire as shown in Figure 4-35.
Figure 4-35 Two-Wire Class A Smoke Detector Connections
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is
used to refer to the circuit pair. For example, Figure 4-35 uses both Flexput circuit 5 and 6, so in programming it would be referred to as point 5.
151209 4-37
Page 78
IntelliKnight 5820XL Installation Manual
Air Products
PAM-2
Model 160150
Supervision
Module
UL Listed
EOL Resistor
Model 7628
ESL 449CT
Note: Flexput circuit 5 and 6
used as an example. Any Flexput point pairing could be used.
Supervised Power Limited

4.12.4 Installing 4-Wire Smoke Detectors

Any compatible U.L. listed four-wire smoke detector can be used with the control panel (see Appendix A for list of compatible smoke detectors). Figure 4-34 and Figure 4-35 illustrate how to connect a UL listed four-wire detector to the control panel.
4.12.4.1 Installing a Class B 4-Wire Smoke Detectors
Figure 4-36 illustrates how to install a 4-wire Class B smoke detector. Conventions used for wiring 4-wire Class B loops:
1. Up to three Class B 4-wire smoke detector loops can be connected to the control panel at once.
2. Each Class B loop input is paired with a unique power source as shown in Figure 4-36.
3. Each loop gets smoke power from the even numbered Flexput circuit and the con­tact input is connected to the odd numbered Flexput circuit.
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is
used to refer to the circuit pair. For example, Figure 4-36 uses both Flexput circuit 5 and 6, so in programming it would be referred to as point 5.
4-38 151209
Figure 4-36 Class B 4-Wire Smoke Detector Connections
Page 79
Control Panel Installation
Air Products
PAM-2
Model 160150
Supervision
Module
Air Products
PAM-2
Model 160150
Supervision
Module
Supervised Power Limited
4.12.4.2 Installing 4-Wire Class A Smoke Detectors
Figure 4-37 illustrates how to install 4-wire Class A detectors. Conventions used for wiring 4-wire Class A loops:
1. Up to two Class A 4-wire loops can be connected to the control panel at once.
2. Smoke power is supplied to each Class A loop as shown in Figure 4-37.
Figure 4-37 Class A 4-Wire Smoke Detector Connections
Note: In programming any point that uses multiple Flexput circuits are always referred to as the lowest
Flexput circuit number used. For example, Figure 4-37 uses Flexput circuits 1, 2, 3 together an d 4, 5, 6 together. In programming (1, 2, 3) would be referred to as point 1, and (4, 5, 6) would be referred to as point 4.
151209 4-39
Page 80
IntelliKnight 5820XL Installation Manual

4.12.5 Auxiliary Power Installation

Flexput Circuits 1-6 on the control panel can be used as auxiliary power circuits. The three types of auxiliary power available are:
Door Holder Power (see Section 4.12.5.1)
Constant Power (see Section 4.12.5.2)
Resettable Power (see Section 4.12.5.3)
Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for all Flexput circuits must not exceed 6.0 A).
To install an auxiliary power circuit:
1. Wire the Flexput circuit(s) that will be used for auxiliary power. See Figure 4-38 for location of Flexput circuits.
2. Configure the auxiliary power output through programming (see Section 7.6).
Figure 4-38 Flexput Circuit Location
4.12.5.1 Door Holder Power
Door holder power is intended for fire door applications. When there are no alarms in the system and the panel has AC power, door holder circuits have 24-volt power present at their terminals. Any alarm will cause power to disconnect. Power will be re­applied when the system is reset. If AC power is off for more than 15 seconds, the auxiliary door holder power will be disconnected to conserve the battery backup. When AC power is restored, power is immediately restored to the door holder circuits.
Use a UL listed door holder ESL DHX-1224, for this application.
4.12.5.2 Constant Power
Use constant power for applications that require a constant auxiliary power source. Power is always present at Constant circuits.
4-40 151209
Page 81
Control Panel Installation
4.12.5.3 Resettable Power
Resettable power is typically used to power beam detectors, flame detectors and conventional 4-wire smoke detectors. For circuits selected as Resettable, 24-volt power is always present at the terminals unless a system reset occurs. If a system reset occurs, power is disconnected from the terminals for 30 seconds, then re­applied.

4.13 On-Board Relays (Conventional)

The control panel has two built-in programmable relays and a built-in trouble relay . All relays are Form C rated at 2.5 A @ 24 VDC.
Figure 4-39 Location of Conventional Relay Circuits

4.13.1 Trouble Relay

The control panel has a dedicated Form C trouble relay built into terminals 30-32. The relay provides a normally open and a normally closed contact. The trouble relay will deactivate under any trouble condition.
Note: The N.C. contact is the relay contact that is closed when the panel has power and there are no
trouble conditions.

4.13.2 Programmable Relays

The control panel has two Form C programmable relays built into terminals 24-29. Each relay provides a normally open and a normally closed contact.
To install one or two programmable relays, follow these steps.
1. Wire Relay 1 and/or Relay 2 as needed for your application. See Figure 4-39 for the location of the relay terminals.
2. Configure the relay through programming (see Section 7.6).
151209 4-41
Page 82
IntelliKnight 5820XL Installation Manual

4.14 Remote Station Applications

4.14.1 Keltron Model 3158 Installation

The control panel is compatible with Keltron Model 3158, used for direct connection to a Keltron receiver. The 3158 reports alarms, supervisories, and troubles.
The steps for connecting the 3158 to the control panel. Refer to the 3158 installation instructions for complete information.
1. Wire the 3158 to the control panel as shown in the connection list and Figure 4-
40.
2. Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in con­duit.
3. Program control panel Relay 1 for alarm.
4. Program Flexput circuit 5 for alarm.
5. Program Flexput circuit 6 for supervisory non latching.
Table 4-3: Keltron 3158 to Control Panel Connections
Terminal # Connects To Terminal # Connects To
3158 Term. 1 To Keltron receiving
equipment
3158 Term. 2 To Keltron receiving
equipment 3158 Term. 3 Earth ground 3158 Term. 10 Control panel Term. 4 3158 Term. 4 Not used; no connection. Control panel Term. 6Control panel Term. 29
3158 Term. 5 Control panel Term. 18 Control panel Term. 28Control panel Term. 31
3158 Term. 6 Control panel Term. 19 Control panel Term. 29Control panel Term. 30
3158 Term. 7 Control panel Term. 7
3158 Term. 8 Control panel Term. 28
3158 Term. 9 Control panel Term. 5
4-42 151209
Page 83
Figure 4-40 Keltron 3158 Connection to Control Panel
Not suitable for remote station where separate transmission supervisory (if applicable), an d
protected premise service circuits are required for fire trouble signals. Intended for connection to a
polarity reversal circuit of a remote station receiving unit having compatible ratings.
Example
Control Panel Installation
151209 4-43
Page 84
IntelliKnight 5820XL Installation Manual

4.14.2 City Box Connection Using the 5220 Module

This section describes how to connect the control panel to a local energy municipal fire alarm box or “city box” as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service. The city (master) box is an enclosure that contains a manually operated transmitter used to send an alarm to the municipal communication center which houses the central operating part of the fire alarm system.
City Box Standby Current: 0 (Notification supervision current
accounted for in control panel draw.)
Alarm Current: 1 Amp for 1 second
27.2 VDC max The maximum coil and wire resistance (combined) must not exceed 30 ohms. To install the 5220 for city box connection:
1. Use one of the knockouts on the right side of the control panel to connect the
5220 using a short piece of conduit (must not exceed 20 feet in length).
2. Wire the 5220 to the control panel as shown in Figure 4-41. This drawing also
shows how to connect the city box coil to terminals 3 and 4 on the 5220. Do not install an EOL resistor in the terminals of the Flexput circuit used for this applica­tion.
3. Connect earth ground wire to the 5220 chassis with mounting screw.
4. Program the Flexput circuit used as a notification circuit, continuous and non-
silencing. Refer to Section 7.6.1 for zone grouping and mapping.
It is not possible to reset the remote indication until you clear the condition and reset
4-44 151209
Page 85
the control panel.
Note: Flexput Circuit 1 used as an example. Any Flexput circuit could be used.
All circuits non-power-limited.
All wiring non-supervised.
Control Panel Installation
Figure 4-41 City Box Connection

4.14.3 NFPA 72 Polarity Reversal

Note: Intended for connection to a polarity reversal circuit of a control unit at the prot ec te d pr em ise s
having compatible rating.
4.14.3.1 Using the 5220 Module
When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.
Standby Current: 100 mA, 24 VDC Alarm: 100 mA, 24 VDC
To install the 5220 for polarity reversal, follow the steps below:
1. Locate the knockout on the right side of the control panel cabinet to connect the
5220 using a short piece of conduit (must not exceed 20 feet in length).
2. Wire the 5220 to the control panel using the four-wire pigtail provided as shown in
Figure 4-42. This diagram also shows how to connect the 5220 to the remote indi­cator . Do not inst all an EOL resistor in the terminals of the Flexput circuit used for this application.
3. Connect earth ground wire to the 5220 chassis with mounting screw.
151209 4-45
Page 86
IntelliKnight 5820XL Installation Manual
All circuits power-limited.
All wiring supervised.
Note: Flexput circuit 1 and Relay 1 used as examples. Any Flexput circuit and either relay 1 or relay 2 could be used.
Jumper these terminals when City Box is not used.
Intended for connection to a Polarity Reversal circuit of a Remote Station receiving unit having compatible ratings.
4. Program the Flexput circuit used as a notification circuit, continuous and non-
silencing. Refer to Section 7.4.1 for zone grouping and mapping.
5. If necessary, adjust loop current using the potentiometer (R10) on the 5220 board
. Normal loop current is 2-to-8 mA with a 1k ohm remote station receiving unit. Maximum loop resistance is 3k ohm.
Figure 4-42 Polarity Reversal Connection Using the 5220 Module
4.14.3.2 Using the 7644 Module
When the 7644 is used for polarity reversal, it allows alarm and trouble events to be reported to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
To install the 7644 for polarity reversal:
1. Wire the 7644 to the control panel as shown in Figure 4-43. Do not install an EOL
resistor on the terminals of the Flexput circuit used.
Note: Use only Flexput circuits on the control panel for reverse polarity.
2. Program the Flexput circuit as a notification circuit. See Section 7.6.2.
3. Map the group to activate constant on from the zone event. See Section 7.4.1.3.
4-46 151209
Page 87
Control Panel Installation
4. Program the output group characteristics as non-silenceable and reverse polarity.
See Section 7.5.1.2.
Figure 4-43 Polarity Reversal Connection Using the 7644
151209 4-47
Page 88
IntelliKnight 5820XL Installation Manual
UL Listed Model 7642
1 k
To City Box
Intended for Connection to a Polarity Reversal Circuit of A Remote Station Receiving Unit Having Compatible Rating.
Must be installed in City Box enclosure

4.14.4 Using the SD500-ARM Addressable Relay Module

When the SD500-ARM is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
Wire the SD500-ARM as shown in Figure 4-44.
4-48 151209
Figure 4-44 Polarity Reversal Connection Using the SD500-ARM Module
Page 89
Control Panel Installation
Intended for Connection to a Polarity Reversal Circuit of A Remote Station Receiving Unit Having Compatible Rating.

4.14.5 Using a MR-201/T Control Relay From Air Products

When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.
Current: 15 mA max. Operating V oltage: 24 VDC nominal Resistance: 4 K To install the MR-201/T for polarity reversal, follow the steps below:
1. Wire the MR-201/T as shown in Figure 4-45.
Figure 4-45 Wiring the MR-201/T
2. Program the Flexput circuit for non silence NAC circuit (see Section 7.6).
151209 4-49
Page 90
IntelliKnight 5820XL Installation Manual

4.14.6 Transmitter Activated by Dry Contacts

This section describes the connection of a UL 864 listed remote station transmitter to the 5820XL FACP dry contacts. The FACP contacts must be supervised by the remote station transmitter module using end-of-line resistors (ELRs) with a value determined by the transmitter manufacturer. Power is also provided by the remote station transmitter manufacturer. Refer to the remote station transmitter manufacturer’s manual for details.
4-50 151209
Page 91

Section 5 SD and SK SLC Device Installation

Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing.

5.1 List of SK SLC Devices

The following SK SLC devices can be used with the control panel. See the appropriate section number in this manual or the device installation instructions (packaged with the device) for more information.
Note: The control panel supports the use of either SK SLC devices or SD SLC devices. You cannot
install both SLC device types on the control panel.
SK
Part Number
SK-Photo Photoelectric smoke detector SK-Photo-T Photoelectric smoke detector with thermal (135°F) SK-PhotoR Photoelectric detector with remote test capability SK-Acclimate Multi-criteria photoelectric smoke detector with thermal (135°F) SK-Beam Reflected beam smoke detector without test feature SK-Beam-T Reflected beam smoke detector with test feature SK-Ion Ionization smoke detector I56-3428-001 SK-Duct Photoelectric duct smoke detector with extended air speed range I56-3432-000 SK-Heat Fixed temperature thermal detector (135°F)
SK-Heat-HT Fixed high temperature thermal detector (190°F) SK-Pull-SA Addressable single action pull station I56-3446-001 SK-Pull-DA Addressable dual action pull station I56-3447-001 SK-ISO Fault isolator module I56-3445-000 SK-Monitor Monitor module I56-3442-000 SK-Minimon Mini monitor module I56-3444-000 SK-Monitor-2 Dual input monitor module I56-3435-000 SK-Mon-10 10 input monitor module I56-3443-000 SK-Relay Addressable relay module I56-3438-000 SK-Relay-6 Six relay control module I56-3439-000 SK-Relaymon-2 Dual relay/monitor module I56-3735-000 SK-Zone Addressable zone interface module I56-3440-000 SK-Zone-6 Six zone interface module I56-3441-000 SK-Control Supervised control module I56-3436-000 SK-Control-6 Six circuit supervised control module I56-3437-000 SK-FIRE-CO CO Smoke Detector I56-3945-000
Model Name/Description
Installation
Instruction PN
I56-3426-001
I56-3433-001
I56-3429-000SK-Heat-ROR Rate-of-rise thermal detector with 135° fixed temperature
151209 5-1
Page 92
IntelliKnight 5820XL Installation Manual
SK
Part Number
B200S Sounder Base I56-3387-00 B201LP 6" mounting base I56-0595-00 B224BI 6" isolator base I56-0725-00 B224RB 6" relay base I56-3737-00 B200SR Sounder base I56-3392-00 B501 4" mounting base I56-0357-00
Model Name/Description
Installation
Instruction PN

5.2 List of SD SLC Devices

The following SD SLC devices can be used with the control panel. See the appropriate section number in this manual or the device installation instructions (packaged with the device) for more information.
Note: The control panel supports the use of either SD SLC devices or SK SLC devices. You cannot in-
stall both SLC device types on this control panel.
Model Number Model Name/Description
SD505-APS Photoelectric smoke detector.
SD505-AHS Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C). SD505-6AB 6" base for use with the SD505-AHS, SD505-AIS, and SD505-APS. 150955 SD505-6IB 6" short circuit isolator base for use with the SD505-AHS, SD505-AIS, and SD505-
APS SD505-6RB 6" relay base for use with the SD505-AHS, SD505-AIS, and SD505-APS 151192 SD505-6SB 6" sounder base for use with the SD505-AHS, SD505-AIS, and
SD505-APS SLC devices SD505-DUCT Duct Smoke Detector. Duct Housing including the SD505-APS Analog Photoelectric
Smoke Sensor. Intake tubing for duct available in three lengths:
SD505-T2.5 (2.5 foot); SD505-T5 (5 foot); SD505-T10 (10 foot) SD505-DUCTR Duct Detector housing with relay base. Duct housing with relay base including
SD505-APS Analog Photoelectric Smoke detector pre-installed SD500-PS/-PSDA Single or dual action addressable pull station 151177 SD500-AIM Addressable input module (switch input), standard size, DIP switch configurable 151071 SD500-MIM Mini input monitor module (switch input), small size, DIP switch configurable. Fits in
single-gang box with manual pull station switch. SD500-ANM Addressable notification module 151109 SD500-ARM Addressable relay module DIP switch configurable. 151091 SD500-SDM Addressable smoke detector module. Use to assign an address to a loop of
conventional devices. SD500-LIM Line isolator module. Fits in a double gang box. 151125 SD500-LED Addressable LED driver module. Capable of driving up to 80 LEDs. Up to 40 SD500-
LED Driver Modules can be used per SLC loop. SD505-DTS-K Remote test switch & LED indicator for the SD505-DUCTR 1700-09882
Installation
Instructions PN
1700-09980SD505-AIS Ionization smoke detector
151175
151191
1700-09882
1700-09882
151071
151193
151232
5-2 151209
Page 93
SD and SK SLC Device Installation

5.3 Maximum Number of Devices

The 5820XL supports SK or SD devices on one 5820XL system. The maximum number of devices per system varies depending on device protocol and the number of 5815XL signaling circuit loop (SLC) expanders added to the system. Device support is as follows:
SK Devices–A 5820XL system can support a total of 396 SK detectors and 396 SK modules. 99 detectors and 99 modules can be connected to the built-in SLC loop. Each optional 5815XL adds another 99 detectors and 99 modules. Add up to three 5815XLs to a system to achieve the maximum number of devices on the system.
OR
SD Devices–A 5820XL system can support a total of 508 SLC detectors and mod­ules, in any combination. 127 devices can be connected to the built-in SLC loop. Each optional 5815XL adds another 127 devices.
151209 5-3
Page 94
IntelliKnight 5820XL Installation Manual

5.4 Wiring Requirements for SLC Devices

The following information applies to all SLC devices. Refer to the section that describes the type of device you are installing for details.

5.4.1 Wiring 5815XL in Style 4 (Class B) Configuration

No special wire is required for addressable loops. The wire can be untwisted, unshielded, solid or stranded as long as it meets the National Electric Code 760-51 requirements for power limited fire protective signaling cables. Wire distances are computed using copper wire.
Maximum wiring resistance is 40 ohms for SK devices and 50 ohms for SD devices. Maximum loop length depends on the wire gauge. See Table 5-1 and Table 5-2.
Table 5-1 Maximum wiring distance for SK modules
Wire Gauge Max. Distance for SK
22 AWG 1200 feet 18 AWG 3100 feet 16 AWG 4900 feet 14 AWG 7900 feet 12 AWG 10,000 fe et
Table 5-2 Maximum wiring distance for SD devices
Wire Gauge Max. Distance for SD
22 AWG 1500 feet 18 AWG 3900 feet 16 AWG 6200 feet 14 AWG 10,000 fe et
5-4 151209
Page 95
SD and SK SLC Device Installation
Figure 5-1 and Figure 5-2 show how wire length is determined for out-and-back tap and T-tap style wiring.
Figure 5-1 Calculating wire run length for a simple out and back tap
When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet. This requirement must be met in addition to the maximum distance requirements for the various wire gauges.
Figure 5-2 Calculating Wire Run Length for a T-tap
151209 5-5
Page 96
IntelliKnight 5820XL Installation Manual

5.4.2 Wiring 5815XL in Style 6 & 7 (Class A) Configuration

Figure 5-3 illustrates how to wire the SLC loop for Style 6 or Style 7 Class A installations.
Note: Style 6 does not use short circuit isolator devices. Note: No t-taps allowed on class A SLC loops.
Figure 5-3 Class A SLC Configuration.
Caution
For proper system supervision do not use looped wire under terminals marked SLC + and – of the SLC device connectors. Break wire runs to provide supervision of connections.
5-6 151209
Page 97
SD and SK SLC Device Installation
Caution: Do not loop wire under Terminal 1 or 2.
Break wire run to provide supervision of connections.
Class A wiring:
Class B wiring:
...............

5.5 Wiring SK SLC Detectors

This section describes how to install SK heat and smoke detectors. All detectors ship with installation instructions. Refer to the detector’s installation instructions for more detailed information.
This information applies to the following SK models:
SK-Photo Photoelectric Smoke Detector
SK-Photo-T Photoelectric Smoke Detector with Thermal
SK-Acclimate Photoelectric Smoke Detector with Thermal
SK-Heat Fixed Temperature Detector
SK-Heat-T High Temperature Thermal Detector
SK-Heat-ROR Rate-of-Rise Thermal Detector
SK-Ion Ionization Smoke Detector
SK-FIRE-CO CO Detector
Wiring SK detectors:
1. Wire device bases as shown in Figure 5-4.
2. Set the address for each device as described in Section 5.6.
Figure 5-4 Heat and Smoke Detector Connection to the Panel.
151209 5-7
Page 98
IntelliKnight 5820XL Installation Manual
Example 1: Device Set to 01.
Example 2: Device Set to 42.
All dials labeled for ONES
or TENS position.

5.6 Addressing SK SLC Devices

All SK devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones place in a one or two digit number, and use the TENS rotary dial to set the tens place in a two digit number.
SK device addresses are handled differently than SD device addresses. The control panel recognizes when an SK detector or SK module is installed. For this reason, SK detectors can be assigned any address from 1 to 99, and SK modules can also be assigned any address from 1 to 99. For example SK-Photo (detector) can be addressed as 1 and SK-Monitor (module) and also be addressed as 1. (0 is a invalid address).
SD detectors and modules use unique addresses 1 through 127. Example 1: To select device address 1, turn the ONES rotary dial to 1 and the TENS
rotary dial to 0 as shown in Figure 5-5. Example 2: To select device address 42, turn the ONES rotary dial to 2 and the
TENS rotary dial to 4 as show in Figure 5-5.
Figure 5-5 SK SLC Device Addressing Using Rotary Dials
5-8 151209
Page 99
SD and SK SLC Device Installation

5.7 Wiring SD Detectors

The information in this section applies to the following SD models: This section describes how to install SD heat and smoke detectors. All detectors ship with installation instructions. Refer to each detectors' installation instructions for more detailed information.
To wire SD detectors:
1. Wire device bases as shown in Figure 5-6.
2. Set the address for each device as described in Section 5.8.
3. If you are connecting to the main panel, do not connect any devices to terminals 35 and 36. If you are connecting to the 5815XL, do not connect any devices to “SLC IN”.
Figure 5-6 Heat or Smoke Detector Connection to the FACP
151209 5-9
Page 100
IntelliKnight 5820XL Installation Manual
SILENCE

5.8 Addressing SD Devices

This section explains how to address SD detectors and modules.

5.8.1 SD505-APS, SD505-AHS, & SD505-AIS

The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and SD505-AIS ionization smoke detector are easily addressed at the FACP. The Installer Code is required to perform this task.
To address a SD505-APS, SD505-AHS, or SD505-AIS:
1. Connect a detector base temporarily to the programming terminals as shown in Figure 5-7. (You can use the same base for each detector).
Figure 5-7 Temporary Connection of Detector Base to Panel for Addressing
2. Enter the Installer code, then press .
3. Select for Point Functions.
4. Select for Set SLC Dev Addr.
5. Select “Y es” by pressing the up arrow, then press . (The panel will go into trouble at this point. You can use the key to stop the PZT. The trouble will
clear automatically when the panel re initializes when you finish programming).
6. When the wait message clears, the following options display:
for Read Address. Use to read (or check) a single detector’s address. for Write Address. Use to program a single detector’s address. for Seq. Programming. Use to program more than one detector in sequential
order.
7. If you are changing addresses, write the programmed address on the back of the device.
8. To exit press left arrow until fully exited.
5-10 151209
Loading...