These kits replace the power supplies with W8600E solidstate performance indicators (SSPI) used in the F50F and
F58F Electronic Air Cleaners. See Table 1.
NOTE: The W8600E Remote Performance Indicator
driver circuit board has been calibrated with the
power supply in this kit. False wash indications
will occur if used with a different power supply.
Table 1. Power Supply Replacement Guide.
Nominal Size
(in.)(mm)
F50F120 Vac, 60 Hz16 x 20406 x 5081.33208414G
16 x 25406 x 6351.65208414B
20 x 20508 x 5081.65208414B
20 x 25508 x 6352.10208414A
20 x 12-1/2508 x 3181.05208414C
220/240 Vac,
50/60 Hz
F58F120 Vac, 60 Hz20 x 25508 x 6352.10208414A
20 x 12-1/2508 x 3181.05208415C
NOTE: Use the 120 Vac replacement power supply
indicated in Table 1 when servicing the F50F or
F58F electronic air cleaners which have been
modified with the 203365A transformer kit to
operate at 220/240 Vac.
Ionizer Current Replacement Power Supply
(mA)(OS No.)
INST ALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition such as electrical shock.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
ELECTRIC SHOCK HAZARD. SAFETY HAZARD.
CAN CAUSE ELECTRICAL SHOCK OR
EQUIPMENT DAMAGE
Disconnect power before removing old power
supply board and installing replacement power
supply board.
T o Remove Old Power Supply Board
NOTE: It is advisable to observe the location of
leadwires to be replaced on the power supply.
Tag the leadwires as they are removed to help
you correctly reconnect them.
■■Open access door. See Fig. 1.
■■Open power box.
X-XX UL
69-1136-1
Page 2
208414, 208415 REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER
REMOVING COVER
FROM POWER BOX.
2
1
3
M5676A
Fig. 1. Remove cover from power box.
■■Disconnect the leads from 1, 2, 3, 4, P1, P2, P3, P4,
P5, P12, P14, P17, P18 and P21 on the old power
supply. See Fig. 2 through 5.
Install New Power Supply
■■When replacing the power supply, reuse the remain-
ing leadwires in the air cleaner when removing the old
power supply.
■■Install W8600E terminal block and wiring supplied
with this kit using screws previously removed.
■■Align the mounting holes and mount the new power
supply in the air cleaner, using the sheetmetal screws
removed earlier. Orient the power supply so P1 and
P2 are toward the front (closest to the switch and
neon light).
■■Route the remaining leads so the P3 and P4 leads
are separate from the low voltage leads. Route all
high voltage leads around, rather than over, the power
supply board. Low voltage leads can go over the
power supply board.
■■Connect leads to the terminals on the new power supply.
IMPORTANT
■■Plug the electronic air cleaner directly into the correct
NOTE: To reduce the risk of electric shock, this product
Do not splice ionizer and collector leads. These
leads must be unbroken to avoid electrical shock
through the connector or tape covering the splice.
voltage and frequency outlet or reconnect power for
directly wired devices. See Fig. 3 or 4 for internal
schematic. The air cleaner will operate properly at any
fan speed on a multispeed or modulated speed
system wired with conduit or plugged in.
has a grounding type plug that has a third
(grounding) pin. This plug will only fit into a
grounding type power outlet. If the plug does not
fit into the outlet, contact a qualified electrician to
install the proper outlet. Do
in any way.
not
change the plug
POWER
SUPPLY
M5764
Fig. 2. Power supply location on F50F and F58F.
■■Remove and discard W8600E terminal block and
wiring. Set aside screws for future use.
■■Remove and set aside the sheetmetal screws holding
the board in place.
■■Discard the old power supply.
CHECKOUT
CA UTION
The following instructions are for use by qualified
personnel only.
With all components in place, turn on the air cleaner switch
and energize the system blower. Check the following
points of operation:
1. The neon light next to the on-off switch is on. If a
W8600E is part of the installation, check the wall
panel and make sure the ON LED is lit. The
W8600E CHECK LED will come on if there is a
problem with the high voltage power supply.
2. Turn off the system blower. The neon light should go
off after a few seconds. The neon light shows that
the air cleaner is energized and the high voltage
power supply is working properly.
3. Turn on the system blower. With the air cleaner
energized, push the test button. A snapping sound
indicates that the collector voltage is present on the
cell. The W8600E CHECK LED will come on when
the test button is held down.
4. With a multispeed blower, repeat steps 1 through 3
for each fan speed.
5. If operation is not as described, refer to the Troubleshooting and Service section.
69-1136—1
2
Page 3
208414, 208415 REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER
INTERNAL SCHEMATIC FOR ELECTRONIC AIR CLEANER WITH W8600E.
BLACK COLLECTOR
RED IONIZER
5
BLACK
P3
BLACK
P4
P5
P12
2
P21
TERMINAL STRIP
FRONTBACK
1
1
TO
W8600E
WALL
PANEL
1 INTERLOCK SWITCH.
2 OUTPUT REDUCTION JUMPER.
3 AIRFLOW SWITCH DISABLE JUMPER.
4 RESISTOR FOR W8600 WASH INDICATION THRESHOLD. PRESENT ON POWER
SUPPLIES MANUFACTURED WITH DATE CODE 9430 AND EARLIER.
5 ONE-CELL UNIT SIMILAR, BUT WITH JUST ONE CELL.
6 P1, P2 TERMINALS ON 120V MODELS ONLY. POWER CONNECTIONS ON 240V MODELS ARE TO QUICK-CONNECTS ON POWER
SUPPLY TRANSFORMER. BROWN LEAD GOES TO TOP TERMINAL AND BLACK LEAD TO BOTTOM TERMINAL.
2
2
3
3
4
4
P17
BLACK
1
BLACK
P18
4
J2
3
R43
1
2
J7
P14
4
POWER
SUPPLY
6
P2
P1
BLACK
GREEN
BROWN
BLACK
RED
ORANGE
GRAY
VIOLET
BLACK
WHITE
TEST
BUTTON
BLACK
W4 W2 W1 W3
GREEN
AIRFLOW SWITCH BOARD
CONTACT
BOARD
3
M15096
Fig. 3. Internal schematic for F50F and F58F Electronic Air Cleaner with W8600E.
Fig. 4. Retrofitted schematic for F50F and F58F Electronic Air Cleaner with W8600E.
TEST
BUTTON
BLACK
BLACK
CONTACT
BOARD
WHITE
GREEN
M15097
3
69-1136—1
Page 4
208414, 208415 REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER
BLACK COLLECTOR
BLACK
TEST
BUTTON
RED IONIZER
BLACK
7
BLACK
P3
P4
E5
E6
RED
CONTACT
BOARD
2
E4 E3
4
BLUE
B4
RED
R3
YELLOW
Y2
GREEN
G1
1 INTERLOCK SWITCH.
2 SHORTING BAR.
3 AIRFLOW SWITCH DISABLE JUMPER.
4 W8600E REMOTE PERFORMANCE INDICIATOR DRIVER.
5 TOP TERMINAL ON TRANSFORMER
6 INPUT POWER. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
7 NEON LIGHT.
5
3
2
1
J1
J2
J1
Fig. 5. Retrofitted schematic for 220/240 Vac F50% Electronic Air Cleaner with W8600E.
TROUBLESHOOTING AND SERVICE
W ARNING
ELECTRIC SHOCK HAZARD.
CAN CAUSE PERSONAL INJURY OR EQUIPMENT DAMAGE.
The following procedures expose hazardous live
parts. Disconnect from power between checks and
proceed carefully. These instructions are only for
use by qualified personnel.
Tools And Equipment
Troubleshooting the electronic air cleaner requires:
• Needle nose pliers for stringing ionizer wires and
inserting edge connectors.
• Test meter.
Although a meter is needed for some steps, the primary
diagnostic tools are the
See Fig. 6.
neon light
and the
test button
.
J5
E2
E1
ORANGE
GRAY
VIOLET
BLACK
W4 W2 W1 W3
AIRFLOW SWITCH BOARD
Test Button
When pushed, the
to ground. The resulting arcing sound indicates that high
voltage is being supplied to the collector. The solid state
power supply controls current flow to the collector. On air
cleaners with a W8600E, the CHECK LED will come on
when the
5
BROWN
BLACK
3
test button
1
BLACK
test button
is held down.
BLACK
GREEN
WHITE
BLACK
6
L1L2
220/240V
50/60 Hz
M15098
shorts from collector voltage
COLLECTOR
TERMINAL
IONIZER
TERMINAL
COLLECTOR
TERMINAL
Neon Light (On Power Box)
The neon light is powered through the power supply and is
on when the power supply output voltage is normal.
69-1136—1
M6155
Fig. 6. Use an ohmmeter to check the electronic cells
for short circuits.
4
Page 5
208414, 208415 REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER
Check Led (Air Cleaners With W8600E)
The CHECK LED is on the W8600E. It lights to indicate
the following problems: excessive dirt loading (beyond
that required to activate the WASH LED), partial shorting
The solid state power supply assembly has no field
serviceable components. If troubleshooting indicates a
power supply or solid state performance indicator problem,
replace the entire power supply assembly.
of the collector, continuous ionizer or collector arcing,
power supply failure, excessive ionizer current, or any
condition causing a major reduction in high voltage.
Troubleshooting Procedure
The electronic air cleaner Troubleshooting chart shows
how to quickly isolate an air cleaner problem. The primary
Power Supply
diagnostic tools are the
Some steps require a meter. See Fig. 7.
W ARNING
ELECTRIC SHOCK HAZARD.
CAN CAUSE PERSONAL INJURY.
Always turn off power and remove access door
before removing the power box or its cover.
TROUBLESHOOTING AIR CLEANERS WITH SOLID STATE PERFORMANCE INDICATOR.
START
MAKE SURE ELECTRONIC
CELL(S) ARE CLEAN, DRY
AND PROPERLY INSTALLED.
MAKE SURE PREFILTER(S)
ARE IN CABINET SLOT
FARTHEST FROM FURNACE.
TURN ON ELECTRONIC AIR
CLEANER AND SYSTEM
FAN.
TO USE THIS CHART:
1.
FOLLOW THE STEPS IN ORDER; DO NOT SKIP AROUND.
2.
EACH TIME YOU ISOLATE AND FIX A PROBLEM, GO BACK TO START.
3.
REPEAT ALL THE STEPS UNTIL THE AIR CLEANER CHECKS OUT OK.
THESE SERVICING INSTRUCTIONS ARE FOR USE BY QUALIFIED PERSONNEL
ONLY. TO REDUCE RISK OF ELECTRIC SHOCK, DO NOT PERFORM ANY
SERVICING OTHER THAN CONTAINED IN THE OPERATING INSTRUCTIONS
UNLESS YOU ARE QUALIFIED TO DO SO.
neon light
and the
WARNING
RISK OF ELECTRIC SHOCK
test button
.
CHECK NEON LIGHT.
ON
CORRECT
WIRING.
WIRING
NOT OK
CHECK WIRING BETWEEN
W8600E AND AIR CLEANER.
USE MAX NO. 18 4-WIRE
THERMOSTAT CABLE
CONNECTED 1(G) TO 1(G),
2(Y) TO 2(Y), 3(R) TO 3(R),
AND 4(B) TO 4(B).
WIRING OK
REPLACE
W8600E.
1
FOR POWER SUPPLY REPLACEMENT, SEE FORM 69-0776.
2
W8600E HAS THREE LIGHT-EMITTING DIODES (LEDS):
ON, WASH, AND CHECK.
3
W8600E OPERATION CAN BE CHECKED SEPARATELY.
SEE W8600E INSTRUCTIONS.
3
PUSH TEST BUTTON AND
LISTEN FOR SNAPPING
SOUND.
OFF
CHECK ON LED IN
W8600E
OFF
DEPRESS AND HOLD DOWN
TEST BUTTON. CHECK
LED IN W8600E
SHOULD COME ON
ON
TURN OFF AIR CLEANER
AND REMOVE CELL(S)
ONLY (NOT PREFILTERS).
CLOSE ACCESS DOOR
AND TURN ON AIR CLEANER.
WASH LED IN W8600E
SHOULD COME ON.
OFF
ON
ELECTRONIC AIR CLEANER
AND W8600E ARE OK.
YES
Fig. 7. Troubleshooting air cleaners with solid-state performance indicator.
ON
PUSH TEST BUTTON
OFF
AND LISTEN FOR
SNAPPING SOUND.
NO
NO
TURN OFF AIR CLEANER
AND REMOVE CELL(S)
ONLY (NOT PREFILTERS).
CLOSE ACCESS DOOR
AND TURN ON
2
2
2
AIR CLEANER.
CHECK NEON LIGHT.
ON
INSPECT CELL(S) FOR:
BENT COLLECTOR
•
PLATES
BROKEN IONIZER
•
WIRES
DIRT ON INSULATORS
•
DAMAGED IONIZER
•
OR COLLECTOR
CONTACT TABS
YES
REPAIR OR
REPLACE
CELL(S).
WITH OHMMETER,
CHECK FOR SHORT
BETWEEN:
••CELL FRAME AND
IONIZER SECTION
CELL FRAME AND
COLLECTOR SECTION
CELL
SHORTED
REPLACE
CELL.
CELL OK.
YES
OFF
NO
INFINITE
RESISTANCE
REPLACE LIGHT ASSEMBLY.
WARNING
THIS STEP EXPOSES
DANGEROUSLY HIGH
VOLTAGE. ONLY A
QUALIFIED SERVICE
TECHNICIAN SHOULD
ATTEMPT THIS STEP.
CHECK FOR CORRECT INPUT
VOLTAGE ACROSS P1 AND P2
TERMINALS ON POWER SUPPLY.
NO
FIX
WIRING.
TURN OFF AIR CLEANER,
REPLACE CELLS(S) AND
DISCONNECT FOUR W8600E
LEADS AT AIR CLEANER.
REPLACE ACCESS DOOR.
TURN ON AIR CLEANER. PUSH
TEST BUTTON AND LISTEN
FOR SNAPPING SOUND.
NO
REPLACE
POWER
BOX OR
POWER SUPPLY.
AIR CLEANER OK. TURN OFF
AIR CLEANER AND RECONNECT
W8600E LEADS 1(G) TO 1(G),
2(Y) TO 2(Y), 3(R) TO 3(R), AND
4(B) TO 4(B).
YES
YES
1
M5609E
5
69-1136—1
Page 6
208414, 208415 REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER
Modification To Reduce Ozone Odor
W ARNING
ELECTRIC SHOCK HAZARD.
CAN CAUSE PERSONAL INJURY.
Always disconnect power before opening the
power supply cover.
The electronic air cleaner generates a small amount of
ozone in normal operation. During the first or second week
of operation, the amount may be higher because of sharp
edges on some of the new high voltage metal parts.
Normal use quickly dulls these edges.
The average person can detect the odor of ozone in
concentrations as low as 0.003 to 0.010 parts per million
(ppm). The electronic air cleaner contributes 0.005 to
0.010 ppm of ozone to the indoor air. The U.S. Food and
Drug Administration and Health and Welfare Canada
recommend that indoor ozone concentration does not
outdoor
exceed 0.050 ppm. As a comparison, the
level in major cities is sometimes as high as 0.100 ppm.
However, if desired, the ozone generated by the air
cleaner can be reduced in one of two ways:
ozone
1. Install an activated carbon filter downstream from
the air cleaner. Make sure particles from the air filter
cannot fall into the air cleaner.
W ARNING
ELECTRIC SHOCK HAZARD.
CAN CAUSE PERSONAL INJURY.
Only a trained service technician should perform
the following procedure.
2. This will reduce ozone production about 20 to 25
percent and reduce efficiency about seven to ten
percent, depending on actual airflow delivered by
the furnace blower.
a.Unplug or disconnect power supply to the air
cleaner.
b.Open the access door.
c.Remove the power box cover. See Fig. 1.
d.Locate J5 shorting bar on the power supply.
See Fig. 8. Remove the shorting bar and
reinstall on only one pin.
NOTE: The ozone will be reduced, but the shorting
bar is available for reinstallation if needed.
e.Replace the power supply cover and access
door. Turn on the power.
f.Repeat the checkout procedure before leaving
the job.
P3
J5 SHUNT
IN OZONE
REDUCTION
POSITION
J5 IN
NORMAL
POSITION
P4
E5
E6
J4
J5
E4 E3
E2
E1
J3
J1
P2
P1
M15099
Fig. 8. Move J5 shorting bar to reduce ozone production about 20 to 25 percent.
69-1136—1
6
Page 7
208414, 208415 REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER
LIMITED TWO-YEAR WARRANTY
Honeywell warrants this product to be free from defects in the workmanship or materials, under normal use and service,
for a period of two (2) years from the date of purchase by the consumer. If, at any time during the warranty period, the
product is defective or malfunctions, Honeywell shall repair or replace it (at Honeywell’s option) within a reasonable period
of time.
If the product(s) is defective, please contact:
a) the dealer from whom you purchased it, or
b) the local Honeywell Authorized Repair Station, or
c) the local Honeywell Home and Building Control Office, or
d) the Honeywell Customer Assistance Center toll free at 1-800-468-1502, or
e) package the defective cell, power supply or other component with care, along with a bill of sale, receipt, or other
dated proof of purchase, and a short description of the malfunction, and ship it, prepaid, to the following address:
Honeywell, Inc.
Return Goods Department
1050 Berkshire Lane
Plymouth, MN 55441-4437
This warranty does not cover removal or reinstallation costs. This warranty shall not apply if it is shown by Honeywell that
the defect or malfunction was caused by damage that occurred while the product was in the possession of a consumer.
Honeywell sole responsibility shall be to repair or replace the product within the terms stated above. HONEYWELL SHALL
NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL
DAMAGES RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WARRANTY, EXPRESS OR
IMPLIED, OR ANY OTHER FAILURE OF THIS PRODUCT. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so this limitation may not apply to you.
THE WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE, AND HONEYWELL EXPRESSLY DISCLAIMS ALL
OTHER WARRANTIES, WHETHER WRITTEN, ORAL, IMPLIED OR STATUTORY, INCLUDING BUT NOT LIMITED TO
ANY WARRANTIES OF MERCHANTABILITY, WORKMANSHIP, OR FITNESS FOR A PARTICULAR PURPOSE.
This warranty gives you specific legal rights, and you may have other rights which vary from state to state.
If you have any questions concerning this warranty, please write our Customer Assistance Center, Honeywell Inc.,
P.O. Box 524, MN27-2164, Minneapolis, Minnesota 55440-0524 or call toll-free at 1-800-468-1502, Monday-Friday,
7:00 a.m.-5:30 p.m. Central time. In Canada, Honeywell Limited/Honeywell Limitee, 155 Gordon Baker Road, North
York, Ontario M2H 3N7.
7
69-1136—1
Page 8
208414, 208415 REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER
Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis, MN 55408-0524
69-1136—1
69-1136—1 J.H. Rev. 11-97
Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
M2H 3N7
Printed in Mexico
8
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.