Honeywell 201052A, 201052B Installation Instructions

201052A,B
Auxiliary Switch
INSTALLATION INSTRUCTIONS
APPLICA TION
Models:
201052A: Contains one auxiliary switch. 201052B: Contains two auxiliary switches.
Electrical Ratings:
50 VA, pilot duty at 24 Vac, selective not simultaneous.
Switching:
Single-pole, double-throw (spdt) micro switches.
Switch Differential:
Three angular degrees maximum.
Approvals:
Underwriters Laboratories Inc. Recognized: File No. E4436, Guide No. XAPX.
Dimensions:
See Fig. 1.
2-1/4 (57)
INST ALLATION
When Installing this Product...
1. Read instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check ratings and descriptions given in specifica­tions to make sure product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation. Actuators with auxiliary switches can have more than one disconnect.
CAUTION
Actuator Damage Hazard. Turning motor output hub by hand or wrench can damage internal gears.
Ensure declutch button is depressed while manually turning hub.
1. Determine desired switching action (if switch is to energize during clockwise or counterclockwise
rotation). With switch cam as shown in Fig. 2, the normally closed contact opens during counter­clockwise rotation and the normally open switch closes.
xxxxxxx
1-2/3 (42)
5/8 (15)
M2159B
Fig. 1. Dimension drawing in in. (mm).
®U.S. Registered Trademark Copyright © 1997 Honeywell Inc. • • All Rights Reserved
3-3/8 (86)
X-XX UL
63-2218-1
201052A,B AUXILIARY SWITCH
COM
NO NC
CCW
M2160
Fig. 2. Switching configuration for counterclockwise
Conversely, with the switch cam as shown in Fig. 3, the normally closed contact opens during clockwise rotation and the normally open switch closes.
Fig. 3. Switching configuration for clockwise
2. Align the switch hub with the set screws on the
actuator. See Fig. 4. Mount the switch on the actuator and tighten the three captive screws.
3. Engage the declutch and rotate the hub to the desired position for switch operation.
NOTE: When installed, the angular position indicator on
the switch face moves from 90° to 0° during counterclockwise motion and from 0° to 90° during clockwise motion.
4. Disengage declutch.
5. With a screwdriver, move cam inside switch
assembly to the appropriate position. Remember, the direction of travel of the cam for switching purposes (see Fig. 2 and 3). Monitor the switch closure with an ohmmeter for a continuity check. See Table 1.
rotation (top view).
COM
NO NC
CW
M2161
rotation (top view).
IMPORTANT
Make certain that the switch activates at the desired degree of stroke.
NOTES:
— For two switch models, cams align with their
respective switches and are each individu­ally set using the same procedure described in the Installation section.
— Switches may also be preset prior to
installation on the actuator if the angular switch position is known.
RANGE STOP PIN POINTED TOWARD SHAFT
90
75
60
45
30
15
0
Fig. 4. ML6161 DCA with 201052A Auxiliary Switch.
Table 1. Proper continuity measurements.
Normally Open Contacts Normally Closed Contacts
Switch Activated Zero ohms Infinite ohms
Switch Not Activated Infinite ohms Zero ohms
201052 AUXILIARY SWITCH
CW COM
CCW
N C
COM
M10250
N O
Home and Building Control
Honeywell Inc.
Home and Building Control
Honeywell Limited-Honeywell Limitée
M2H 3N7
XX-XXXX—X
63-2218—1 B.B. Rev. 10-97 Printed in Mexico
Helping You Control Your World
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or
2
resulting from, any modification to the literature by you.
®