Henny Penny HC-5, HHC-900, HHC-902, HHC-903, HHC-906 Operation Manual

...
Page 1
Model HHC-90X/Model HC-5/15
SECTION 3. OPERATION
3-1. INTRODUCTION
3-2. OPERATING CONTROLS AND COMPONENTS
This section provides operating procedures for the heated holding cabinets. The Introduction, Installation and Operation Sections should be read, and all instructions should be followed before operating the cabinet.
Figures 3-1 through 3-5 identify and describe the function of all the operating controls and the major components of the cabinet.
Figure 3-1
Figure 3-3
Figure 3-2
Figure 3-4
203 3-1
Figure 3-5
Page 2
Model HHC-90X/Model HC-5/15
3-2. OPERATING CONTROLS AND COMPONENTS (Continued)
Fig. Item No. No. Description Function
3-1 1 Power Switch A toggle switch that switches electrical current to the unit
3-1 2 Power Light Illuminates when the power switch is in the ON position and the components are energized
3-1 3 Thermometer Indicates the air temperature inside the cabinet
3-1 4 Heat Light Illuminates when the thermostat turns on the heaters
3-1 5 Thermostat An electromechanical device that controls the temperature inside the cabinet
3-2 6 Blower Motor Used to recirculate the hot humid air throughout the cabinet; there are two blower motor assemblies in the cabinets
3-2 7 Heater Two, open-resistance, wire type heaters that provide heat throughout the cabinet; a standard full sized 120 VAC unit will have 1000 watt heaters; a standard full sized 240 VAC unit will have 1500 watt heaters; a standard 120V, HHC-903 unit will have 750 watt heaters
3-2 8 High Limit A safety device mounted next to the heater which protects the unit from overheating
3-3 9 Fuse A protective device that breaks the circuit when current exceeds the rated value; the fuse provides an overload protection for the electrical components; to remove the fuse, twist and pull the cap; the fuse is used only on the 120V/2000 watt units
3-4 10 Water Pan Holds the water for creating humidity in the cabinet
3-5 11 Venting System Controls the humidity levels in the cabinet (Units with vent adjustment only)
3-2 203
Page 3
3-3. START-UP
Model HHC-90X/Model HC-5/15
Before using the heated holding cabinet, the unit should be thoroughly cleaned as described in the Cleaning Procedures Section of this manual.
1. To put the unit into operation, move the power switch to the ON position. The power light should now be illuminated and the blowers should be in operation.
2. Remove the water pan and put approximately 1” of hot water in the pan. Return the pan to its location.
Step 1
Be sure to push the water pan in as far as it will go so that it does not block air from the thermometer and thermostat capil­lary tubes. This will ensure proper operation of these compo­nents.
Step 2
3. Set the thermostat at #7 or approximately 180°F (82°C). When the heat light goes out, the unit is ready for operation.
The unit should take approximately 25-35 minutes to heat to temperature during start up. Be sure that the temperature light goes out before loading with product.
203 3-3
Page 4
Model HHC-90X/Model HC-5/15
3-4. OPERATION WITH PRODUCT
3-5. VENT ADJUSTMENT
1. Place the hot product on bun pans and insert between the cabinet racks.
2. Serve the product f rst that has been in the cabinet the
longest.
3. In order to maintain a constant temperature, open the doors only as necessary to load and unload product.
As mentioned in the Operating Controls and Component Section, the vent system limits the humidity level of the cabinet. The vent adjustments are very easy to follow.
The vent setting corresponds to the number of trays of product. With one tray of product, set the vent at No. 1. With two trays of product, set the vent at No. 2 and so on.
3-6. CLEANING PROCEDURES
Step 3
1. Turn all controls to the OFF position.
2. Disconnect the electrical supply to the cabinet.
To avoid burns, allow the unit to cool before cleaning.
3. Open the doors and remove all trays from the cabinet.
4. Take the trays to a sink and clean them thoroughly.
5. Remove the water pan and clean it with a soft cloth, soap,
and water.
3-4 203
Page 5
Model HHC-90X/Model HC-5/15
3-6. CLEANING PROCEDURES (Continued)
Step 6
6. Wipe the control panel with a damp cloth. Do not splash water around the controls.
7. Clean the exterior of the cabinet with a damp cloth.
Do not use steel wool, other abrasive cleaners or cleaners/sanitizers containing chlorine, bromine, iodine or ammonia chemicals, as these will deteriorate the stainless steel material and shorten the life of the unit.
Do not use a water jet (pressure sprayer) to clean the unit, or component failure could result.
8. Open the doors and remove side racks. Clean the racks with soap and water.
Step 8
9. Clean the interior of the cabinet thoroughly with a cloth and soap water.
10. Put the side racks and water pan back into the cabinet.
11. Leave at least one door open over night to allow the unit to thoroughly dry out.
203 3-5
Page 6
Model HHC-90X/Model HC-5/15
3-7. OPERATING CONTROLS ­ COUNTDOWN TIMERS (if applicable)
These instructions are for both 13 and 5 count down timers.
Start-Up
1. Turn the power switch to the ON position.
2. The display shows the increase in temperature, indicating the unit is heating.
3. When the preset temperature is reached, the HEAT ON LED turns off and the display stays at the preset temperature.
Temperature Regulation
1. Press and hold the PROGRAM button.
2. The control beeps and “Prog Enter Code” shows in display.
3. Enter access code 1, 2, 3.
4. Press the INCREASE or DECREASE buttons to change the f ashing setpoint temperature.
5. Press and hold the PROGRAM button to set the temperature and exit the programming mode.
Timer Operation
Each of the timers can be started, stopped, or cancelled, and not affect the status of the other timers.
1. Press the desired timer button.
2. The time remaining shows in the display.
3. At end of time cycle, an alarm sounds and “0:00” is dis­played.
4. Press the timer to stop alarm and “---” is displayed.
Press and hold an active timer to cancel.
3-6 203
Page 7
Model HHC-90X/Model HC-5/15
3-7. OPERATING CONTROLS ­ COUNTDOWN TIMERS (if applicable) (Continued)
Timer Regulation - All timers can be set to a different starting
time.
1. Press and hold the PROGRAM button.
2. The control beeps and “Prog Enter Code” shows in display.
3. Enter access code 1, 2, 3.
4. Press the PROGRAM button, and “---” is displayed, along with all the timer settings.
5. Press the desired timer and the starting time f ashes.
6. Press the INCREASE and DECREASE buttons to change the starting time.
7. Press the timer button to set the new starting time, and now a different timer button can pressed, and it’s starting time can be changed.
8. When f nished setting timers, press and hold the PRO­GRAM button to exit programming.
Exit the program mode at any time by pressing and holding the PROGRAM button. Also, if no buttons are pressed for 2 minutes, programming is exited automatically.
Timing Through Power Down
If a power failure occurs while a timer is running, the timer re­sumes the countdown when power is restored.
203 3-7
Page 8
Model HHC-90X/Model HC-5/15
3-7. OPERATING CONTROLS ­ COUNTDOWN TIMERS (if applicable) (Continued)
Special Program Mode - Consists of Setup Mode and Tech
Mode.
Setup Mode
• Fahrenheit or Celsius
• Initialize System - One button programming for times and temperatures
Fahrenheit or Celsius
1. Press and hold the PROGRAM button for 4 seconds.
2. “SetUP” and “Tech” are displayed.
3. Press a timer button under the word “SetUP”.
Ex: Setup
1 2 Press either 1 or 2.
4. Enter access code 1, 2, 3.
5. “SetUP deg. F” is displayed.
6. Press the INCREASE or DECREASE buttons to toggle from
“F” (Fahrenheit) and “C” (Celsius).
7. When correct setting displays, press the PROGRAM button
to move to initialize system, or press and hold the PRO­GRAM button to exit programming.
CE and international units must have the temperature read­ings in Celsius. Follow above procedures and set to “C”.
Initialize System
1. Press and hold the PROGRAM button for 4 seconds.
2. “SetUP” and “Tech” are displayed.
3-8 203
Page 9
Model HHC-90X/Model HC-5/15
3-7. OPERATING CONTROLS ­ COUNTDOWN TIMERS (if applicable) (Continued)
Initialize System (Continued)
3. Press a timer button under the word “SetUP”.
Ex: “SetUP”
1 2 Press either 1 or 2.
4. Enter access code 1, 2, 3.
5. “SetUP deg. F” is displayed.
6. Press PROGRAM button and “SetUP init sys” is displayed.
7. Press and hold either the INCREASE or DECREASE but­ton.
8. The control beeps and the display counts down, 5, 4, 3, 2, 1,
0.
9. When display reaches “0”, release the button and the initial­ization is complete.
If the INCREASE or DECREASE button is released before “0” is displayed, the control will not initialize.
10. Press the PROGRAM button to return to the Fahrenheit/Cel­sius mode, or press and hold the PROGRAM button to exit programming.
Tech Mode
• Output test - heaters
• CPU calibration
• T emperature calibration
• Display tests
• Push-button test
• T otal initialization
The Tech Mode is mostly used at the factory level. The out­put tests and temperature probe calibration are given below. For further information, call the Technical Services Depart­ment at Henny Penny, 1-800-417-8405, or 1-937-456-8405.
203 3-9
Page 10
Model HHC-90X/Model HC-5/15
(Continued)
3-7. OPERATING CONTROLS ­ COUNTDOWN TIMERS (if applicable)
Output System
1. Press and hold the PROGRAM button for 4 seconds.
2. “SetUP” and “Tech” are displayed.
3. Press a timer button under the word “Tech”.
Ex: “Tech”
4 5 Press either 4 or 5.
4. Enter access code 1, 1, 2, 2, 1, 1, 2, 2.
5. “outP test Htr” is displayed.
6. Press the 5 timer button (under “Htr”) to turn heat and heat LED on and off.
7. Press the PROGRAM button to move to the next step, or press and hold the PROGRAM button to exit programming.
Temperature Calibration
1. Press and hold the PROGRAM button for 4 seconds.
2. “Setup” and “Tech” are displayed.
3. Press a timer button under the word “Tech”.
Ex: “Tech”
4 5 Press either 4 or 5.
4. Enter access code 1, 1, 2, 2, 1, 1, 2, 2.
5. “outP test Htr” is displayed.
6. Press the PROGRAM button 3 times until “CAL OFS Hi Probe 185” is displayed.
7. Press and hold number 1 timer (under “CAL”), while press­ing the INCREASE and DECREASE buttons and set the display to match the actual cabinet temperature.
8. Press the PROGRAM button to move to the next step or press and hold the PROGRAM button to exit programming.
3-10 203
Page 11
Model HHC-90X/Model HC-5/15
3-8. SIMPLEHOLD CONTROLS (if applicable)
Operation
1. Turn the power switch to the ON position and the actual tem­ perature shows in the display. To check the setpoint temperature, press and hold .
2. Remove water pan and put about 1” (25.4 mm) of hot water in pan. Return pan to cabinet.
Be sure to push the water pan in as far as it will go, so that it does not block the air to the temperature probe, to ensure an accurate temperature reading
3. Allow unit to heat 25 to 30 minutes to reach setpoint tem perature, and the heat LED f ashes, before loading product into cabinet.
Programming
To change the setpoint temperature, press and hold and then use to set the desired setpoint temperature.
If the controls are locked the setpoint cannot be changed until the controls are unlocked. See Special Programming below .
To access the Special Program Mode:
With the Power Switch OFF, press and hold , and then turn the power switch on.
1. “ºF” or “C”shows in the display. To toggle between Fahrenheit and Celsius, press .
405 3-11
Page 12
Model HHC-90X/Model HC-5/15
3-8. SIMPLEHOLD CONTROLS (if applicable) (Continued)
2. After entering the Special Program Mode, press once
and “int” shows in the display. Press and hold or
and the display counts down “In3-In2-In1”. This reinitializes the controls and sets all controls to 0.
3. After entering the Special Program Mode, press and release twice, and “Cal” shows in the display, followed by
the current probe temperature. The probe can be calibrated + 10º F, and can be changed by using .
4. After entering the Special Program Mode, press and release three times, and “OP” shows in the display.
Use to toggle between “888” and a blank display. “888” turns all heat outputs on, and a blank display turns them off.
5. After entering the Special Program Mode, press and release four times, and P=L, or P=U, shows in the display.
Use to toggle between L (lock), and U (unlock).
3-12 405
Page 13
Model HHC-90X/Model HC-5/15
3-9. FRONT & REAR OPERATING CONTROLS-HHC-903-10 CDT
Front Controls
Rear Controls
Start-UP
1. Turn the power switch to the ON position.
2. The display shows the increase in temperature, indicating the unit is heating.
Press and hold to view the setpoint temperature.
3. When the preset temperature is reached, the “HEAT ON” LED turns off and display stays at the preset temperature.
Timer Operation
Each of the timers can be started, stopped, or cancelled, and not affect the status of the other timers.
1. Press the desired timer button, from either the front or rear of the unit.
2. The time remaining f ashes in both front and rear displays. If #2 timer is started on the front, #2 timer also shows timing down on the rear of the unit. If more than one timer is running, the timer with the least amount of time remaining f ashes.
3. At end of time cycle, alarm sounds and “0:00” displays.
4. Press the timer to stop alarm and “---” is displayed.
Press and hold an active timer to cancel.
Vent Adjustment
The vent adjustment on the rear panel limits the humidity level inside the unit. Sliding the knob to a setting of 5 opens the two vent holes completely and a setting of 0 closes them.
1106 3-13
Page 14
Model HHC-90X/Model HC-5/15
3-9. FRONT & REAR OPERATING CONTROLS-HHC-903-10 CDT (Continued)
Programming Temperature and Timers
1. Press and hold until “Prog” shows in the display
2. Press to change the f ashing setpoint temperature.
If “LOC” shows in the display at this time, the programming controls are locked and must be unlocked. See Special Program Mode Section.
3. Press and release to program the timers. Press any of the timer buttons, on either side of the unit, and when they are f ashing, use to set the timer in minutes
and seconds. If a timer is f ashing on one side of the unit,
the corresponding timer on the other side of the unit also f ashes. For example, if timer #2 on the front of the unit is f ashing, #2 on the rear of the unit also f ashes. So, both front and rear timers are programmed at the same time.
More than one timer can be programmed at the same time
if they are to be programmed with identical times. Just press the timers to be programmed and when they are all f ashing, use to set the time in all timers. Again, both
front and reartimers will be programmed.
4. Press and hold to exit the Program Mode and all settings are now programmed.
SPECIAL PROGRAM MODE
This mode consists of:
• Fahrenheit or Celsius Programming
• Initialize System - One button programming for times and temperatures
Probe Calibration
• Locking or Unlocking Programming
Outputs Test
1. Turn power switch OFF and press and hold until “SP” shows in the display, followed by the software ver­sion.
3-14 1106
Page 15
Model HHC-90X/Model HC-5/15
3-9. FRONT & REAR OPERATING CONTROLS-HHC-903-10 CDT (Continued)
2. Press when “oF” or “oC” shows in the display, use
to change the temperature reading from Fahrenheit
to Celsius, or vice-versa.
3. Press and release and “int” shows in the display.
4. Press and hold or and display counts down,
“in-3, in-2, in-1”. When “int SYS” shows in the display,
release the or and the initialization is complete. The temperature and timers are now programmed to fac­tory presets.
5. Press and release and “CAL” shows in the display, followed by the probe temperature, inside the unit.
6. Use to set the displayed temperature to match the actual temperature inside the unit.
7. Press and release twice and “P= L or U” shows in the display. “P=L” means Locked and the setpoint
temperature and timers CANNOT be programmed. “P=U”
means Unlocked and the setpoint temperature and timers CAN be programmed. Use the to toggle the display from
“P=L” to “P=U” or vice-versa.
8. Press and release and “OP” shows in the display. Use the to toggle the outputs ON & OFF. When the
outputs are ON, the HEAT ON LED should come on and
“8888” shows in the display, indicating the outputs are working correctly.
9. Press and hold to exit Special Program Mode and all modes will now be set.
1106 3-15
Loading...