Irrigation is one of the most important operation in agriculture. With proper
irrigation the quality and quantity of crops can be significantly enhanced.
Correct irrigation is not a simple process: the quantity of water must be sufficient for crops, and if not, photosynthesis and overall growth is impeded.
However, if the amount of water is more than required, plant growth may
become excessive producing a taller, softer and/or damaged product. The
Fertigation Controller can control the quantity of irrigation water based on
time or volume. Different sectors can be irrigated at different times during a
day with different water quantities. In the Fertigation Controller each irrigation
program provides control of pH and of the amount of fertilizer released to the
fields. When necessary, a specific program performs a pH correction by the
introduction of an acid or base into the irrigation water. pH control is based
on sensor input and a specified set point, while fertilizer control is based on
sensor input and setpoint or based on volume measuring. When the Fertigation Controller commands the addition of 1 or multiple fertilizers to the irrigation stream, digital counters continuously monitor the quantity of fertilizer released in the irrigation stream and the overall amount of fertilizer is maintained based on a target prescription. Fertilization can be also controlled
based on conductivity of stream. The Fertigation Controller can command the
addition of multiple (1 to 4) fertilizers to irrigation water. The amount of fertilizer is set by the user for and controlled by a specific program (based on a
prescription). If a pH or conductivity control problem arises, the program
generates an alarm to inform the user. All operations of both control processes are stored in memory and if needed takes the proper action. The Fertigation Controller performs all necessary operations in the monitoring and
control of irrigation and fertilization processes. These operations are conducted continuously throughout the day, month and year. To use and manage
the system properly, all the necessary control values must be set (Setup mode).
During monitoring operations (Consulting mode) the user can obtain information about how the system and irrigation process are functioning, in addition to the history of all operations for current and previous days. To view the
required information on the display or set a specific parameter, the appropriate display panel has to be selected, as explained in this manual.
4
GENERAL DESCRIPTIONGENERAL DESCRIPTION
GENERAL DESCRIPTION
GENERAL DESCRIPTIONGENERAL DESCRIPTION
The Fertigation Controller is a micro-processor-based system used in fertilization and irrigation control for greenhouses or open fields with powerful, flexible programming features.
The main function of the Fertigation Controller is supplying and controlling
the necessary water and fertilizers for crops according to several parameters
such as acidity, conductivity and ambient temperature.
The user interface is structured in two parts:
1. Consulting (numbered panels indicated by Cxx)
2. Setting (numbered panels indicated by Sxx).
This instruction manual will present the interface in 2 forms:
1. Fertigation Controller functions
2. Panel order
Fertigation Controller is capable of executing the following functions:
- Irrigation control by time or by volume
- pH control
- Fertilization control
- Manual correction
- Agitator control
- Filter control
- Water supply control
- Pumps control
- Sector control
- Serial communication
- Alarm function
- Logging function
5
FUNCTIONAL DESCRIPTIONFUNCTIONAL DESCRIPTION
FUNCTIONAL DESCRIPTION
FUNCTIONAL DESCRIPTIONFUNCTIONAL DESCRIPTION
In this chapter the main functions of the Fertigation Controller are presented. For a better understanding see the typical installation schemes
utilized for irrigation and fertilization presented in the Appendixes, Installation Block Diagram.
IRRIGAIRRIGA
IRRIGA
IRRIGAIRRIGA
The Fertigation Controller can control up to 24 sectors (one valve per
sector) for each of the ten irrigation programs:
24 valves (sectors) can be selected specifying the sector’s number and the
desired value of irrigation time or volume for a specified irrigation program using
set sectors for the respective irrigation program.
Panel
irrigation extension and “Done” time or volume value) for the selected
irrigation program and sector.
Irrigation can be controlled by time or volume – irrigation control mode
can be switched between time and volume using panel
MODE).
Each irrigation program can be started by:
•
using panel
option on panel
•
signed the external tank (level indication) input which can start the specified irrigation program – this option is set using panel
DITION).
•
S47 S47
S47 (PROG MAN START). A program can be stopped using panel
S47 S47
(PROG MAN STOP).
Each irrigation program can be repeated a specified number of repetitions. The number of repetitions as well as pause time between two repetitions can be specified using panel
Each irrigation program can be given a priority in relation to others (6
priority levels). Priorities and maximum open sectors per group can be
specified for each program and can be set using panel
ITY).
TION CONTROLTION CONTROL
TION CONTROL
TION CONTROLTION CONTROL
S43 S43
Panel
S43 (SET SECTORS). The panel displays the number of
S43 S43
C13 C13
C13 (SECTOR STATE) displays the current status (set value plus
C13 C13
S55 S55
S55 (IRRIG CTRL
S55 S55
TIME:TIME:
TIME: 1 to 6 different timetables (values) per program can be set
TIME:TIME:
S33 S33
S33 (SET START TIME). “Start cond” must be the selected
S33 S33
S32 S32
S32 (START CONDITION).
S32 S32
EXTERNAL TEXTERNAL T
EXTERNAL T
EXTERNAL TEXTERNAL T
MANUMANU
MANU
MANUMANU
ANK LEVELANK LEVEL
ANK LEVEL: Each irrigation program can be as-
ANK LEVELANK LEVEL
S32 S32
S32 (START CON-
S32 S32
AL AAL A
CTIVCTIV
AA
TIONTION
AL A
AL AAL A
CTIV
CTIVCTIV
: :
A
TION
: A program can be started using panel
AA
TIONTION
: :
S34 S34
S34 (PROGRAM REPEATS).
S34 S34
S31 S31
S31 (SET PRIOR-
S31 S31
S48S48
S48
S48S48
6
The following are setting requirements for each irrigation program:
- the working period (between start date (day/month) and end date
(day/month)) – use panel
- the working time during a day (between start time and end time) – use
S29 S29
panel
S29 (ACTIVE TIMETABLE)
S29 S29
- the cycle work / rest day can be set using panel
- the working days in a week – use panel
Working time status for each irrigation program, if selected (irrigation
program is in work period of month, day and week) is displayed in panel
C07 C07
C07 (WORK TIME COND).
C07 C07
The percent of irrigation time or set volume can be automatically modified
by the following:
MANU MANU
-
MANU
MANU MANU
TEMPERA TEMPERA
-
TEMPERA
TEMPERA TEMPERA
Total correction percentage, time or volume value is displayed on panel
C11 C11
C11 (TOTAL CORRECTION).
C11 C11
In each irrigation program the pre-irrigation and post-irrigation time or
volume value (used to clean the irrigation pipes with pre-irrigation water)
can be set using panel
Panel
active sectors.
The active irrigation program is displayed on panel
Related data regarding the active irrigation program (active irrigation program number, last start condition and current / set repetition number) are
displayed on panel
Information about selected irrigation program, priority and irrigation program conflict are displayed on panel
value data, correction value and irrigation completion (“Done”) value
are displayed on panel
Information about each program’s previous start condition, date and time
are displayed on panel
Total accumulation value from a previous date is displayed on panel
(TOTAL ACCUMUL).
Accumulation value from previous date and activation number for a selected irrigation program are displayed on panel
ACCUMUL).
Accumulation value from previous date, for selected sector, is displayed in
AL FAL F
AA
CTCT
AL F
AL FAL F
GATION CORR). Percentage and corresponding value of time or
volume can be viewed using panel
TION CORR).
C01 C01
C01 (GENERAL INFO) displays the active irrigation program and
C01 C01
OROR
A
CT
OR: This option can be set using panel
AA
CTCT
OROR
TURETURE
TURE: This option can be set using panel
TURETURE
S35 S35
S35 (PRE/POST IRRIG).
S35 S35
C04 C04
C04 (PROGRAM STATE).
C04 C04
C9 C9
C9 (IRRIG STATE).
C9 C9
C16 C16
C16 (PROG LAST START).
C16 C16
S29 S29
S29 (ACTIVE TIMETABLE)
S29 S29
S30 S30
S30 (WORKDAY)
S30 S30
S30 S30
S30 (WORKDAY)
S30 S30
C10 C10
C10 (MAN CORRECTION).
C10 C10
C03 C03
C03 (SENSORS STATE).
C03 C03
C08 C08
C08 (PRIOR&CONFLICTS).
C08 C08
C18 C18
C18 (PROGRAM
C18 C18
S44 S44
S44 (IRRI-
S44 S44
S44S44
S44 (IRRIGA-
S44S44
Set
C17C17
C17
C17C17
7
C19 C19
panel
C19 (SECTOR ACCUMUL). In addition, this panel displays the
C19 C19
valve number assigned with the corresponding sector.
Accumulations erase mode can be chosen on panel
TICS). The accumulation erase can be performed for all programs and
sectors using one of the following ways:
- Manually
- Every day at specified hour
- Automatically whether the accumulations counter values overflows
S65S65
S65 (ERASE STATIS-
S65S65
FERTILIZAFERTILIZA
FERTILIZA
FERTILIZAFERTILIZA
Fertilization can be made mixing the irrigation water with 4 types of fertilizers from 4 tanks. Dosing of these fertilizers is controlled by conductivity
or by volume (ratiometric or volume). Volume fertilizer control mode is
available only if the program works in volume irrgation mode. In all cases
is available a correction of fertilization with temperature. The temperatures
for correction of fertilization are set in panel
The type of control used for fertilization is selected in panel
CTRL MODE):
•
Conductivity control is used to control fertilization based on the conductivity of irrigation water. A reference for the conductivity is set in
CONTROL) and a prescription for the proportion of fertilizers is set in
(SET FERTILIZERS) and the controller will dose the prescribed proportion of
fertilizers in such a manner to keep the EC water within specified range:
EC refernce minus or plus minimum and maximum offset values. In addition to this mode a differential conductivity control is available (set in
(EC DIFF CTRL CFG). In this mode the controller will dose the fertilizers in
a way that the irrigation water will have the conductivity of reference added
with the conductivity of input water. In this way the amount of fertilizer
dosed is the same even if the input water is contaminated with some substances that produce the rising of EC. Conductivity sensor status and
conductivity reference are displayed on panel
tion, the conductivity sensor value is displayed on panels
ERAL INFO) and
tion and input EC are displayed on panel
The conductivity control is made in accordance with a preset conductivity
reference value, specific for each irrigation program. In addition, the conductivity reference has a proportional band and a dead band that can be
set using panel S38(EC CONTROL). If the difference between setpoint and
the EC of the water is greater than the dead band for a period of time an
TION CONTROLTION CONTROL
TION CONTROL
TION CONTROLTION CONTROL
CONDUCTIVITY CONTROLCONDUCTIVITY CONTROL
CONDUCTIVITY CONTROL
CONDUCTIVITY CONTROLCONDUCTIVITY CONTROL
C03C03
C03 (SENSORS STATE). Temperature reference correc-
C03C03
S44S44
S44 (IRRIGATION CORR).
S44S44
S37 S37
S37 (FERT
S37 S37
S38S38
S38 (EC
S38S38
C06C06
C06 (EC STATE). In addi-
C06C06
C01 C01
C01 (GEN-
C01 C01
C12C12
C12 (EC CORRECTION).
C12C12
S39S39
S39
S39S39
S40S40
S40
S40S40
8
alarm is triggered. For more information on the propotional band please
consult the proportional control section.
Given a conductivity alarm condition, conductivity control can be maintained if “Ctrl on EC alarm” is selected using panel number
BEHAVIOR).
Statistical values of total conductivity are displayed on panel
AVERAGES). For the average conductivity of each irrigation program see
C21C21
panel
C21 (PROGRAM AVERAGES) and for average conductivity of each
C21C21
individual sector see panel
RARA
•
In this mode the user has to specify for each program the quantity of each
fertilizer to be dosed. The quantity can be specified in volume or in weight
of active substance. All these settings are made in panel
CTRL). If the volume is set Y, the proportion is dosed for each fertilizer as
volume of fertilizer solution in volume of irrigation water. If the volume is
set to N, the weight of active substance is specified together with the concentration of fertilizer solution. The controller will dose then the volume of
fertilizer that contains the specified active substance.
•
This mode is available only if the program works with irrigation in volume.
The settings are made in panel
the volume of fertilizer solution and the volume of irrigation water in which
is to be mixed.
TIOMETRIC CONTROLTIOMETRIC CONTROL
RA
TIOMETRIC CONTROL
RARA
TIOMETRIC CONTROLTIOMETRIC CONTROL
VOLUME CONTROLVOLUME CONTROL
VOLUME CONTROL
VOLUME CONTROLVOLUME CONTROL
C22C22
C22 (SECTOR AVERAGES).
C22C22
S42S42
S42 (FERT VOL CTRL). Here is specified
S42S42
S54S54
S54 (ALARM
S54S54
C20C20
C20 (TOTAL
C20C20
S41 S41
S41 (RATIOMETRIC
S41 S41
PH CONTROLPH CONTROL
PH CONTROL
PH CONTROLPH CONTROL
pH control is necessary to correct and maintain the pH of irrigation water
within specified range: pH reference minus or plus dead band value.
The pH control also has a dead band and a proportional band. These
values are set using panel
The value of pH sensor and the reference value are displayed on panel
C05C05
C05 (pH STATE).
C05C05
pH sensor value is displayed also on panel
C01C01
C01 (GENERAL INFO).
C01C01
pH control will generate a pH alarm if for a period of time (more than the
time specified using panel
specified range. Given a pH alarm condition, pH control can be maintained if “Ctrl on PH alarm” is selected using panel number
BEHAVIOR). Also given a pH alarm condition, irrigation can be maintained if “Irrig on PH alarm” is selected using panel number
BEHAVIOR).
S36S36
S36 (pH CONTROL).
S36S36
C03C03
C03 (SENSORS STATE) and in
C03C03
S36S36
S36 (PH CONTROL)) the pH is not within the
S36S36
S54S54
S54 (ALARM
S54S54
S54S54
S54 (ALARM
S54S54
9
Statistical values of pH are displayed on panel
For each irrigation program the pH average is available on panel
C20C20
C20 (TOTAL AVERAGES).
C20C20
C21C21
C21
C21C21
(PROGRAM AVERAGES) and for each individual sector the pH average
is available on panel
be deleted manually or at specified time of day using panel
C22C22
C22 (SECTOR AVERAGES). All pH averages can
C22C22
S65 S65
S65 (ERASE
S65 S65
STATISTICS)
PROPORTIONAL CONTROLPROPORTIONAL CONTROL
PROPORTIONAL CONTROL
PROPORTIONAL CONTROLPROPORTIONAL CONTROL
EC and pH control is performed using a proportional controller.
The role of this controller is to maintain a pH and EC value of the irrigation water (see diagram). The control of pH and EC is made separately.
Reagent
A simplified schematic of the process (pH and EC) is presented above.
The components are as follows:
−The mixing tank where input water and additives are combined.
−The additive solution tank containing an acid, base or fertilizer
−The valve for introducing the additive solution into the mixing tank con-
trolled by the proportional controller.
−P(proportional) Controller
−The input water source.
−The irrigation pump used to pump water from the mixing tank to the
irrigation sectors.
The Fertigation controller automatically provides a command output signal to a control element such as a pump or valve based on a sensor input
signal. The function of the proportional controller is to control the dosage
of acid/base or fertilizer in such a way that pH and EC of the process will
have the values close to specified set point. The output signal commands
the opening and closing of a valve through which the additive solution is
10
circulated. The amount of additive solution added is relative to the opening of the valve, which is directly proportional to the magnitude of difference between the “water pool” pH and the set point.
Set point (reference value) is the desired value of the measurement.
Error is define as the difference between set point and measurement:
The descriptions and definitions of the individual control actions are as
follows:
Proportional control so called because the controller output is proportional to the magnitude of error. However, proportional control is subject
to one major limitation, steady state offset (steady deviation from the set
point). Increasing the sensitivity of the controller (controller gain) can
reduce the steady state offset but only with slow processes. Because of this
proportional control by itself is used primarily for slow, consistent processes that can tolerate high controller gain (like the control of pH and EC
in irrigation applications), which minimizes steady state offset. Both pH
and EC are controlled by using the same proportional control method.
The proportional control acts on the closing and opening timings of the
motorized valves.
The control cycle used for the pH and EC control can be set by using
panel S60 (SET PROP CTRL). To regulate the aperture of the motorized
valves the proportional control will control the opening and closing times.
These timings are in fact pecentages from the control cycle length.
The sensivity factor simply divides the times used for the actual command
of the motorized valves. It can be used for a fine time of the proportional
control. For each program and for each of the controls (pH or EC) two
parameters define the behavior of thecontroller around a designated setpoint:
- the dead band is the area around the setpoint where the dosage is “in
limits” therefore the actuators need not to change their position.
- the proportional band is the an area around the setpoint where the
proportional control takes place. Outside of these two areas the controller
will open or close the motrized valve with 80% of the control cycle.
11
Valve
Opening
pH, EC
Max pH
Max EC
Setpoint
Valve
Opening
P Control
No Valve Control
P Control
Proportional Band
Dead Band Dead Band
Proportional Band
High Alarm Area
Low Alarm Area
Control cycle
percentage
80%
100%
0
80%
100%
12
AGITAGIT
AA
AGIT
AGITAGIT
For HI8060:For HI8060:
For HI8060:
For HI8060:For HI8060:
The agitator output is active in the irrigation phase of a program if the fertilizer
control is enabled. This output also commands the fertilization pumps.
For HI8050:For HI8050:
For HI8050:
For HI8050:For HI8050:
During the irrigation program, the agitators can be stopped (if working time is
zero), work continuously (if pause time is zero) or intermittently (if working time
and pause is different than zero) and can start during preirrigation, before the
fertilizer tanks are used. The agitators are set using panel S45 and can be
consulted using panel C15.
FILTER CONTROLFILTER CONTROL
FILTER CONTROL
FILTER CONTROLFILTER CONTROL
Fertigation Controller has the capability to check and automatically clean
two filters controlled by two filter-cleaning programs. Each filter cleaning
program can be started by the following conditions:
1. Following one specified irrigation program. This irrigation program
2. When a “dirty filter” alarm is activated. Cleaning by this option is set
The working time for filter cleaning programs can be set using panel
(FIL(FIL
(FIL
(FIL(FIL
MANUAL FUNCTIONSMANUAL FUNCTIONS
MANUAL FUNCTIONS
MANUAL FUNCTIONSMANUAL FUNCTIONS
TOR CONTROLTOR CONTROL
A
TOR CONTROL
AA
TOR CONTROLTOR CONTROL
can be set in panel
using panel
TERS CTRL).TERS CTRL).
TERS CTRL).
TERS CTRL).TERS CTRL).
S46 S46
S46 (FILTERS CTRL).
S46 S46
S46 S46
S46 (FILTERS CTRL).
S46 S46
S45S45
S45
S45S45
The Fertigation Controller has the following Manual function capabilities:
− To switch the controller state between STOP, WORK and INIT, use panel
S49 S49
S49 (CONTROLLER STATE). The controller state can be checked using
S49 S49
C01 C01
panel
C01 (GENERAL INFO)
C01 C01
− To manually start a program use panel
− To manually stop a program use panel
− To check and to change the value for each of the outputs, use panel
S50 S50
S50 (OUTLET MAN CTRL)
S50 S50
− To erase all statistics, use panel
cates pH and conductivity averages for all irrigation programs and sectors in addition to average total irrigation accumulation. They also show
the volume of water and fertilizers on sectors, on programs and total
volumes.
− To erase the settings of one irrigation program or to erase all settings for
all irrigation programs, use panel
S65 S65
S65 (ERASE STATISTICS).
S65 S65
S47 S47
S47 (PROG MAN START)
S47 S47
S48 S48
S48 (PROG MAN STOP)
S48 S48
S66 S66
S66 (ERASE SETTINGS).
S66 S66
13
Statistics indi-
ALARMSALARMS
ALARMS
ALARMSALARMS
Fertigation controller has the capability to supervise and generate an alarm
for the following conditions:
- Conductivity sensor out of range. Reference, minimal and maximal offset
and time-out for conductivity alarm are set using panel
TROL). The current values of conductivity sensors are displayed on panel
C06 C06
C06 (EC STATE)
C06 C06
− pH sensor out of range. Reference, minimum and maximum offset and
time-out for pH alarm are set using panel
current values of pH sensors are displayed on panel
− Problems with the water supply.
− Dirty filters.
− Low levels in fertilizer and acid tanks.
− Waste of fertilizers.
− Main irrigation counter fail.
− Overdose and underdose of fertilizer.
The system will take appropriate action and record the alarm. These actions can be:
..
.
..
S36 S36
S36 (PH CONTROL).
S36 S36
S38 S38
S38 (EC CON-
S38 S38
The
C05 C05
C05 (pH STATE)
C05 C05
•Given a pH alarm condition, the irrigation process can be set to
stop or continue using panel
S54 S54
S54 (ALARM BEHAVIOR).
S54 S54
•Given an EC alarm condition, the irrigation process can be set to
stop or continue using panel
S54 S54
S54 (ALARM BEHAVIOR).
S54 S54
•Given a dirty filter alarm condition, start the filter cleaning program
in accordance with the priority and working time settings
•Given a water supply alarm situation the controller goes in BLOCK state.
•All alarm situations are displayed on panel
All anomalies (old alarm conditions) are displayed in panel
(ANOMALY).
− The Fertigation controller has the capability to log the most important
occurred events and values of different parameters that can offer a description of the evolution of the entire process;
− The most important values are:
- Number and time period of every program activation;
- Filter cleanings;
- Averages of pH, conductivity and temperature;
- Accumulations;
14
- Values of sensors.
- Sectors irrigated by a program.
- Alarms;
The records of log can be searched by date. To start a search set the desired
date in panel C24 (VIEW LOG DATE). Logging records are displayed on
panel C26 (LOG).
The average value of sensors and accumulation of volumes are available
through panes C17 (TOTAL ACCUMUL) to C22 (SECTOR AVERAGES).
DADA
TE AND TIME CONTROLLER SETTINGSTE AND TIME CONTROLLER SETTINGS
DA
TE AND TIME CONTROLLER SETTINGS
DADA
TE AND TIME CONTROLLER SETTINGSTE AND TIME CONTROLLER SETTINGS
The controller date and time can be consulted on panel
INFO) and can be set using panel
PASSWORD SETUP PASSWORD SETUP
PASSWORD SETUP
PASSWORD SETUP PASSWORD SETUP
Access to Fertigation Controller can be restricted by a password. This
password can be set using panel
can be disabled using the same panel.
SERIAL COMMUNICASERIAL COMMUNICA
SERIAL COMMUNICA
SERIAL COMMUNICASERIAL COMMUNICA
The fertigation controller is able to connect with a PC and can be remotely
controlled by the PC through the Agricare program. To be able to connect
the PC must have a serial port available and a Windows operating system. The serial cable must be crossover and with male – female connector. For more details please consult the help of the Agricare program.
S28 S28
S28 (SET DATE & TIME).
S28 S28
S64 S64
S64 (SET PASSWORD). The password
S64 S64
TIONTION
TION
TIONTION
C01 C01
C01 (GENERAL
C01 C01
15
USER INTERFACEUSER INTERFACE
USER INTERFACE
USER INTERFACEUSER INTERFACE
The user interface of the Fertigation Controller consists of a 4 x 20 character LCD and a 23 key keyboard (see depiction below).
KEYBOARD STRUCTUREKEYBOARD STRUCTURE
KEYBOARD STRUCTURE
KEYBOARD STRUCTUREKEYBOARD STRUCTURE
Fig. 1.1: Fig. 1.1:
Fig. 1.1: Keyboard layout.
Fig. 1.1: Fig. 1.1:
OPERAOPERA
OPERA
OPERAOPERA
The Fertigation controller operates primarily in two major modes: Consulting Mode and Setting Mode. User interface panels (screens) are broken
down into two categories:
1. CONSULTING PANELS
2. SETTING PANELS
Both modes of operation a readily available to the user.
TING MODESTING MODES
TING MODES
TING MODESTING MODES
1. CONSUL TING MODE:
The consulting mode allows the user to view the current state and set
conditions of the Fertigation Controller. While in consulting mode (
key not pressed) all 68 panels can be viewed by one of 2 browsing methods. The primary consulting screens are designated from C
2727
C
27. The following outline highlights the functions of the consulting mode.
2727
PP
− two browsing methods are enabled. See Section
METHODSMETHODS
METHODS for more details.
METHODSMETHODS
ARROWS KEYSARROWS KEYS
−
ARROWS KEYS can be used to move the cursor within a currently
ARROWS KEYSARROWS KEYS
selected panel to select specific data (only if data items are selectable) to
be viewed.
16
ANEL BROWSINGANEL BROWSING
P
ANEL BROWSING
PP
ANEL BROWSINGANEL BROWSING
0101
01 through
0101
SETSET
SET
SETSET
ESCESC
−
ESC key can be used as a shortcut key to access the
ESCESC
STATE) panel from any currently viewed panel.
HOMEHOME
−
HOME key can be used as a shortcut key to access the
HOMEHOME
ERAL INFO) panel from any currently viewed panel.
ENDEND
−
END key can be used as a shortcut key to access the
ENDEND
STOP) panel from any currently viewed panel.
TT
ABAB
−
T
AB key can be used to switch the focus between the
TT
ABAB
objectobject
object and the
objectobject
dexed. If there is no index parameter present on the current panel, the
TT
ABAB
T
AB key has no effect. The program number indexes panels. For ex-
TT
ABAB
ample, panel
each program. Once panel
the focus (cursor) is shifted from the panel number to the program number “Prog 01”. The
each program state consecutively without leaving the panel.
ENTERENTER
−
ENTER key is used to confirm any new values entered in any of the
ENTERENTER
selected panels. This is only possible if data items on a panel (screen) are
selectable.
panels index parameterpanels index parameter
panels index parameter if the current panel is in-
panels index parameterpanels index parameter
C04 C04
C04 (PROGRAM STATE) displays the current state for
C04 C04
C04C04
C04 is selected and the
C04C04
ARROW KEYSARROW KEYS
ARROW KEYS can now be used to scroll through
ARROW KEYSARROW KEYS
C04C04
C04 (PROGRAM
C04C04
C01 C01
C01 (GEN-
C01 C01
S48 S48
S48 (PROG MAN
S48 S48
panel numberpanel number
panel number
panel numberpanel number
TT
ABAB
T
AB key pressed,
TT
ABAB
2. SETTING MODE:
The setting mode allows configuration of all adjustable parameters of the
S28S28
Fertigation controller. The setting screens are designated from
All 68 panels can be viewed by one of 2 browsing methods. The setting
mode is executed by selecting the appropriate screen and pressing the
SETSET
SET key. Once the setting mode is entered both panel-browsing methods
SETSET
are disabled and navigation is allowed only within the currently selected
panel. The following outline highlights the functions of the Setting Mode.
− Both panel (screen) browsing methods are disabled. See Section
BROWSING METHODSBROWSING METHODS
BROWSING METHODS
BROWSING METHODSBROWSING METHODS
− Focus (cursor location) is automatically shifted to the first editable data
object on the selected panel.
UPUP
, DOWN, DOWN
−
UP
, DOWN
UPUP
, DOWN, DOWN
objects within the current panel.
LEFTLEFT
, RIGHT arrow keys, RIGHT arrow keys
−
LEFT
, RIGHT arrow keys allow navigation within the currently fo-
LEFTLEFT
, RIGHT arrow keys, RIGHT arrow keys
cused
object then the focus is transferred to the previous or next editable item
within the current panel.
TT
ABAB
−
T
AB key can be used to move only in a forward direction, from one data
TT
ABAB
object to the next within the selected panel.
ENTERENTER
−
ENTER key confirms all data entered in a current panel. Once the
ENTERENTER
arrow keysarrow keys
arrow keys allows navigation between all editable data
arrow keysarrow keys
data object.data object.
data object. If the cursor exceeds the boundaries of the data
data object.data object.
S28 to
S28S28
S68S68
S68.
S68S68
PP
ANELANEL
P
ANEL
PP
ANELANEL
17
ENTERENTER
ENTER key is pressed and data confirmed, the controller reverts to con-
ENTERENTER
sulting mode. The
ESCESC
−
ESC key cancels new data entered in the currently focused data object
ESCESC
and exits the setting mode. The change of data is not saved in the current
object and the previous setting is maintained.
NONO
TETE
NO
TE: Data that has been changed in an editable data object is saved
NONO
TETE
once focus has been removed from that object by pressing the
KEYSKEYS
KEYS or
KEYSKEYS
PP
ANELS BROWSING METHODSANELS BROWSING METHODS
P
ANELS BROWSING METHODS
PP
ANELS BROWSING METHODSANELS BROWSING METHODS
In consulting mode, 2 browsing methods are available to view each of the
68 panels (screens) of the Fertigation controller.
−
keys allows consecutive navigation from one panel to the next. Direction
is dependent upon which key is selected.
−
entered directly using the panel number located on the bottom right corner of every panel, prefixed by a
initially focused object on each screen. After entering the value by using
the key pad and
panel.
NONO
NO
NONO
setting mode, both browsing methods are disabled.
TT
ABAB
T
AB.
TT
ABAB
StepStep
-by-by
--
Step
StepStep
Direct access browsingDirect access browsing
Direct access browsing: the number of the desired panel can be
Below are described all the panels in the controllers. The panels are divided in
three sections: Initialization panels, consulting panels and setting panels. The
data fields within each panel are described from left to right unless otherwise
specified.
INITIALIZAINITIALIZA
INITIALIZA
INITIALIZAINITIALIZA
INITIALIZATION PANEL
This panel is shown during Fertigation Controller INITIALIZATION state and
contains the HANNA INSTRUMENTS logo and the name of the controller.
The last line is used to display the current status of the initialization sequence.
This panel is also used to display any possible errors that may occur during
the start up sequence.
START PANEL
This panel is displayed after successful initialization or whenever the password
authentication sequence fails (user will be logged off due to incorrect password entry). This panel displays the date and time and the bottom left corner
it is shown the Fertigation Controller functional state.
It is important to note that the Fertigation Controller is normallyIt is important to note that the Fertigation Controller is normally
It is important to note that the Fertigation Controller is normally
It is important to note that the Fertigation Controller is normallyIt is important to note that the Fertigation Controller is normally
functioning at this point if the required external conditions arefunctioning at this point if the required external conditions are
functioning at this point if the required external conditions are
functioning at this point if the required external conditions arefunctioning at this point if the required external conditions are
met even if the user is logged off.met even if the user is logged off.
met even if the user is logged off. At this stage, when the user presses
met even if the user is logged off.met even if the user is logged off.
ENTERENTER
the
ENTER key another login opportunity will be given if the password au-
ENTERENTER
thentication process is enabled. This feature can be specified via panel
(SET PASSWORD).
TION PTION P
TION P
TION PTION P
HANNA INSTRUMENTS
HI8050 V00.01-004E
INITIALIZATION:
Loading StringTable
HANNA INSTRUMENTS
HI8050 CONTROLLER
Fri 15-03-2000 13:15
STOP PRESS ENTER
ANELSANELS
ANELS
ANELSANELS
S64S64
S64
S64S64
24
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.