Haier AE072XCBAA, AE092XCBAA, AE142XCBAA, AE212XCBAA, AE122XCBAA Operation And Installation Manual

...
Page 1
Please read this operation manual before using the air conditioner.
Please keep this manual carefully and safely.
No. 0010573573
A
CEILING CONCEALED TYPE AIR CONDITIONER
Operation & Installation
Manual
Page 2
Cautions
Part Description
Important Points of Safety
Trouble Shooting
When Fault Occurs
Notice to Users
Installation Precautions
Installation Procedure
Installation Check and Trial Run
1-2
3
4-6
7-8
9
10
11-12
13-19
20
Table of Contents
Page 3
1
Cautions
Page 4
2
Cautions
Page 5
3
When the unit have the Return air box (see the following picture) when shipping from the factory and they are of back-side return air type. During the installation, the unit also can be changed to a Down-side Return air according to the user's need.
D
NOTE
Electrical control box
Page 6
Important Points of Safety
The following four important points of safety and suggestions should be paid great attention:
Warning: Misuse may cause fatal result such as death or serious injury etc.
Attention: Misuse may cause human injury or damage of machine, in some case fatal results. : Content marked with this ì forbiddenî sign should be absolutely forbid­ den, otherwise may cause damage of machine and human injury of the user. : Content marked with this ì compulsoryî sign should be executed comp­ ulsively, otherwise may cause damage of machine and human injury of the user.
Comply with the following important points of safety. Put these important points of attention and suggestions nearby and convenient for reference in need. Hand over this instruction manual to new user if you resell this machine.
Warning for installation
Entrusted Installation Installation of the machine should be entrusted to certified person of after service. Unauthorized install­ation may cause water leakage, electric shock or fire hazard for improper operation.
To prevent leakage of refrigerant, let certified person of after service do it.
Leakage of refrigerant over certain consistence may result in shortage of oxygen. Enough precautions MUST be done to avoid oxygen shortage in case of refrigerant lea­king if the room where the air­conditioner is installed is small.
The power supply must be fitted with earth line to ensure valid earthing of the air-conditioner. No or incomplete earthing connection may cause the risk of electric shock.
!
!
!
!
!
Test run After indoor units are installed,all cassettes hinded models should be tested.when the units are confirmed to be normal,other fitments can be installed.
!
!
4
Warning
!
Page 7
Important Points of Safety
Warning
Avoid your body being blown directly by cold wind for long period, otherwise your health may be affected.
Donít extend your fingers or any other article into the inlet or outlet during operation of the machine for touching re­ volving fans may cause human injury or damage of machine.
If something abnormal (e.g.: burnt smell etc.) occurs, stop running the machine, shut down the manual power switch and contact after service. Continuous operation in disorder may cause fire hazard or electric shock etc.
Warning for use
Warning for move and repair
When you have to disassemble and reinstall the machine, entrust it to after service. Improper inst­ allation may cause fire hazard, electric shock or damage of ma­ chine.
Unauthorized alteration or repair work is strictly forbidden. Impr­ oper alteration or maintenance may cause fire hazard, electric shock or water leakage. Repair work should be entrusted to cert­ ified person of after service.
Attention
Attention points for installation
Ensure the drainage hose work normally during installation. Improper installation of drainage can cause water leakage and damp articles.
DO NOT install the machine in place where flammable gas releases easily to avoid fire hazard.
Ensure electric leakage breaker being installed. Electric leakage breaker MUST be installed, otherwise electric shock may be caused.
If the power supply cord is damaged, call a certified electrician of the manufacturer or other maintenance department to replace it.
! !
!
!
5
!
!
Page 8
6
Important Points of Safety
Attention
Attention points for use
* Ensure ventilation of the room if the machine is used with burning facilities. Deficient ventilation can cause oxygen shortage.
* Check whether installation bench of the machine is damaged after a long period of use. Machine on damaged bench may fall down and cause human injury or other damage.
* In place where winds produced by the machine can reach, donít lay any animals or plants which may be hurt otherwise.
* Donít put vases containing water or other else on the unit assembly. Otherwise, the machine may be immersed internally and result in bad electric insulation causing electric shock.
* The is machine CANNOT be used for the purpose of prese­ rving food, animals, plants, precision instruments and artwork etc., which may be destroyed otherwise.
* DONíT replace fuse with ma­ terial other than fuse of proper capacity. Replacing fuse with metal wire or copper etc. can cause fire hazard or other faults.
* DONíT lay any burning facilities in place where winds produced by the machine can reach. Incomplete combustion of burning facility may be caused otherwise.
* DONíT clean the machine with water. Electric shock may occur otherwise.
* DONíT put flammable spray articles nearby or spray them to the machine. Fire hazard may occur otherwise.
* DONíT operate switch with wet hand. Electric shock may occur otherwise.
* Stop operation and shut down manual power switch before cleaning and maintenance.
* The power supply MUST be of rated voltage and connected with special electrical supply circuit.
!
Page 9
Trouble Shooting
The following cases are not troubles.
During operation, the air conditioner may sometimes exhibit a sound of "clatter" or "rumble". This is the common sound of refrigerant flow but not a trouble.
A sound of "Pi-Pa" is generated.
Smells are given off.
During operation, mist or steam are blown out.
During COOL operation, it automatically changes to FAN mode.
The system couldnt be re-started immediately after turning off.The unit can't start?
This is caused by the thermal expansion or cold shrinkage of plastics.
Sometimes there are smells in the air flow from the indoor unit. This is caused by the smell of cigarettes or paint coatings inside the unit.
During COOL or DRY operation, the unit may blow out a thin mist. This is the con­densate water mist caused by sudden co­oling of the indoor air blown out from the indoor unit.
In order to prevent frost accumulation on the heat exchanger in the indoor unit, sometimes it will automatically transfers to FAN mode, but soon will return to COOL mode.
This is due to the systems self-protection function, which prevents it from restarting in 3 min after stops.
Please wait for 3 min.
"Hua-Hua"
Water flow sound is heard.
7
Page 10
Trouble Shooting
ON
OFF
During DRY operation, there is no air sent out or fan speed cant be changed.
In HEAT mode, the outdoor unit generates water or steam.
This occurs during removal of the frost (in defrosting operation) on the radiator of outdoor unit.
Defrost operation
In HEAT mode, the indoor fan still keeps running even the unit operation stops.
After the unit stops, the indoor fan will continue to run for a while to eliminate residual heat.
Before asking for after-service to an authorized service center, please check your air conditioner for the following items
The system couldn't start
Is power on/off switched on?
The power on/off switch is not at position of "ON".
Is the power supply line normal?
Is current leakage breaker triggered?
Please do immediately cut off power supply and contact the authorized service center.
Power failure?
8
Page 11
When Fault Occurs
Poor cooling or heating
Is the operation controller adjusted as required?
Are there any obstructs before the air inlet or outlet?
Is there any door or window left open?
Poor cooling
Is there any other heat source in the room?
Is there any direct sunlight into the room?
Are there too many people in the room?
If, after the above checks and the corresponding corrective actions, the system remains
abnormal operation, or the following facts appear, please turn off the air conditioner and
then contact the local authorized service center.
Frequent open of fuse or breaker.
There is water leakage during COOL or DRY operation.
The operation is abnormal or abnormal sound is heard.
9
Page 12
Notice to Users
Notice to users
To ensure proper operation of the system, the user shall follow this instruction manual to install the unit. When handling the air conditioner, please be care not to scratch the case surface. This instruction manual describes the installation method aided with the installation
tools specified by manufacturer . The maximum length of connection pipe is 50 m, and the maximum difference between levels of indoor unit and outdoor unit shall be 30 m. Please keep the installation instruction manual well for reference in maintenance or changing installation position.
After installed, please follow the operational instruction manual to use the air conditioner properly.
Information about application
Adjust your desired air flow direction Avoid direct sunlight and gas flow
Keep appropriate room temperature Too cool or too warm wont benefit to your health, but causes an incre­ased energy consumption.
Effectively use the timer Using TIMER mode you can enjoy a comfortable room temperature when wake up or come back home.
Maximum temperature
Caution: After installation, please confirm no refrigerant leaks.
10
Page 13
Installation Precautions
11
Warning
!
Before installing, do read this "Safety precautions" carefully to guarantee the proper installation. The below attentive matters are divided into" Warning" " and " Note" two parts. When the wrong installation occur, it is very possible death and severe injury and other serious accidents will happen. For those items are listed in" Warning" part. But even the items listed in "
Note" part can also cause serious accidents. Above all, both the two parts are very important contents related to safety, so they must be obeyed. After finishing the installation work, do test run to verify everything is normal. After that please explain the using and maintenance methods to the user. Additionally, give this installation manual and operation manual to the user and ask them to keep it properly.
The distributing shop, where you bought the air conditioner, or the specified shops shall do the installation work. If you do the installation work by yourself, the improper installation will cause water leakage, electric shock fire and other accidents. The installation work shall be in line with what the installation manual specified. If installation is not proper, water leakage, electric shock, fire and other accidents will occur. Install the air conditioner to a place where can definitely stand its weight. Places not firm enough will cause drop down of unit resulting in body hurt. The installation work shall be preventive to typhoon and earthquake. If the installation work is not met with the requirements, overturn of the unit will occur resulting in accidents. The wiring work shall be done by a qualified person and referred to the " technical standard of electric equipment" , "indoor wiring regulation" and what the manual specified. Do use special circuit. If the capacity of the circuit is not enough or bad work, electric shock, fire and other accidents will happen. Using the specified cable to do wiring work and connecting firmly and properly. Fix the connecting part of the terminals to prevent it from the external force.Improper connection and fixing will cause heating and fire etc. accidents. Wiring shall be kept in correct shape avoiding extrusion. After installation, the electric box cover and the external panel shall not nip the wire. Improper installation will cause heating and fire etc. accidents. When setting or moving the air conditioner do not let the air and things alike get into the refrigeration system except the specified refrigerant. If air and other things enter, abn­ormal high pressure will occur, which easily cause break and body injuries etc. Accidents. When installing, do use the accessories or specified parts. If not using the parts specified by our company, water leakage, electric shock, fire and refrigerant leakage will occur. Do not lead the drainpipe to drain where the sulfur gas may be involved. Otherwise, the poisonous gas will enter into the indoor. During installation, if refrigerant leakage occurs, do the ventilation work immediately. As soon as the refrigerant gas meets fire, poisonous gas will be produce. If the refrigerant gas enters into room and meet the air blowing heater, heater or stove etc. fire source, the poisonous gas may be produced. After installation, confirm there is no leakage of refrigerant. Do not install the unit in a place where the combustible gas may be leaked. In any case the combustible gas leaks and accumulated around the unit, fire accident will occur. Do heat insulation work to the refrigerant gas pipes and liquid pipes to reach the purpose of heat preservation. If the heat insulation measure is not sufficient, water generated by condensing dew will drip leading to wet the floor and indoor articles.
Note
!
Do grounding work.Do not connect the grounding wire to gas pipe,tap,lighting rod or telephone line.Improper grounding will cause electric shock. After electric installation,power on them to do electric leakage test.
! !
!
!
Page 14
Installation Precautions
This description does not address to all possible cases. For new requirement and query, please consult the regional sales center of Haier Air Conditioner General Co., Ltd.
This instruction manual must be read carefully before beginning of installation, improper ins­tallation may cause accidents and thus bring about machine damage and personal casualty.
Installing tools
1. Screw driver 6. Pipe cutter 10. Leakage detector or soap water
2. Hacksaw 7. Pipe expander 11. Measuring tape
3. Driller of 70mm diameter 8. Knife 12. Scraper
4. Spanner (diameter 17, 27mm) 9. Pinchers 13. Refrigeration oil
5. Spanner (14, 17, 19, 27mm)
12
! Attention
! Warning
Indoor unit
1. Select suitable places the outlet air can be sent to the entire room, and convenient to lay out the connection pipe, connection wire and the drainage pipe to outdoor.
2. The ceiling structure must be strong enough to support the unit weight.
3. The connecting pipe, drain pipe and connection wire shall be able to go though the building wall to connect between the indoor and outdoor units.
4. The connecting pipe between the indoor and outdoor units as well as the drain pipe shall be as short as possible. (See Figure 1)
5. If its necessary to adjust the filling amount of the refrigerant, please refer to the installation manual attached with the outdoor unit.
6. The connecting flange should be provided by the user himself.
7. The indoor unit have 2 drainage outlet, one outlet be jamedwith rubber cap, during installation only use another outlet (In/Out liquid pipe side). When necessary, use the two together.
8. Do not place the TV, equipment, facility, piano etc, expensive goods below the AC. This is to prevent the water dropping down from the AC and lead to damage to the goods.
Fig 1
The indoor unit shall be installed at locations where cold and hot air could evenly circulated. The following locations should be avoided:
Places with rich saline matters (seaside regions). Places with plenty of gas sulfides (mainly in warm spring areas where the copper tube and
braze weld is prone to corrosion).
Locations with much oil (including mechanical oil) and steam. Locations using organic solvents. Places where there are machines generating HF electromagnetic waves.
Positions adjacent to door or window in contact with high-humidity external air. (Easy to generate dew). Locations frequently using special aerosols. Less than 2.7 meters above the floor for air outlet opening.
Page 15
Installation Procedure
13
1.For electrical heating unit, the air outlet not allowed directly connecting with canvas etc. easy catching fire goods.
2.This series' indoor unit are all middle static pressure(50 Pa external static pressure ).
3.An access port must be provided during installation of indoor unit for maintenance.
After selecting the unit installation location, proceed the following steps:
1. Drill a hole in the wall and insert the connecting pipe and wire through a PVC wall-through tube purchased locally. The wall hole shall be with a outward down slope of at least 1/100. (See Figure 2)
2. Before drilling check that there is no pipe or reinforcing bar just behind the drilling position. Drilling shall avoid at positions with electric wire or pipe.
3. Mount the unit on a strong and horizontal building roof. If the base is not firm, it will cause noise, vibration or pipe broken and refrigerant leakage (see Figure 6).
4. Support the unit firmly.
5. Change the form of the connection pipe, connection wire and drain pipe so that they can go through the wall hole easily.
Figure showing installation dimensions: (unit:mm)
Model
a
b
c
d
e
f
g
i
Series 18-21
Series 07-09
Series 12-14
648
125
804
125
1024
125
615
770
990
452
452
452
225
225
225
55
55
55
225
225
225
100
100
100
Fig 2
Notes
a
i
e
g
f
b
c
d
Page 16
Installation Procedure
14
Each air return and supply duct should fix to the floor precast slab by using an iron stand. Use glue to seal the interface closely. Recommend the distance between the air return duct and the wall is more than 150mm.
The distance between air duct outlet and air conditioner outlet is according to the length of actually installed air duct and in service behavior of the static pressure terminal: Installation sketch map for long and short air duct is showed below, when connect to short air duct, using low static terminal (terminal color is white), the distance between air duct outlet and air conditioner outlet is no more than 0.5m; when connect to long air duct, using middle static terminal (terminal color is red), the distance between air duct outlet and air conditioner outlet could be within 5m at this point.
When installing the ceiling concealed type indoor unit, a specially designed return air bellows shall be installed, as shown in Figure 3, Figure 4.
A
Installing building roof
Ceiling
Air supply
Air outlet duct
Unit
Return air
Return air bellows
Figure 3
Figure 6
M8 broad foundation bolt
M8 suspension screw
M8 broad lock ring
M8 nut
Unit
Air outlet grille
Air supply No obstacles
within 1 m(0Pa)
Unit
Return air
Return air bellows
*0.5m(0Pa)or*5m(50Pa)
As figure shown, suspend and install the unit.
Drain piping of condensed water should keep a downhill grade of 1% or more. Use insulating pipe to cover the drain piping of condensed water to keep warmth.
Figure 4
air return shutter
air return duct
sling dog
drain piping
transition air duct
air outlet duct
air diffuser
joint of air diffuser
Figure 5
Figure 6
Page 17
15
Installation Procedure
Indoor unit
flexible joint or static pressure box
transitive air duct
circular air duct
joint of air diffuser
air diffuser
Fig1: Duct connected
indoor unit
air return shutter
rivet
air return duct
galvanized board
glue nail
insulating fabric
tinfoil
adhesive tape
glue nail cover
Installation for air duct of indoor unit
1. Installation of air discharge duct This type of unit uses circular air duct with its caliber of 180mm. An additional transitive air duct is necessary for the circular air duct to connect to the air
supply inlet. It should be also connected to its respective air diffuser separately. See Fig.1. Adjust the wind speed of each air diffuser outlet to keep in line on the whole, so as to meet a demand of the air conditioner in the room.
2. Installation of air return duct
Use rivets to connect the air return duct to the air return inlet of the indoor unit. The other end connects to the air return shutter. as shown in Fig.2.
Fig2: Duct return connected
3. Air duct insulation Insulation layer is needed for air supply and return duct. First, paste a glue nail to the air duct, and then attach the insulation cotton that has a tinfoil layer and use the glue nail cover to fix. Finally, seal the air duct interface with tinfoil adhesive tape closely. as shown in Fig3.
Fig3
Page 18
Installing the suspension screw:
Use M8 or M10 suspension screws (4, prepared in the field) (when the suspension screw height exceeds 0.9 m, M10 size is the only choice). These screws shall be installed as follows with space adapting to air conditioner overall dimensions according to the original building structures.
Wooden structure
A square wood shall be supported by the beams and then set the suspension screws.
Square wood
Suspension screw
Beam
New concrete slab
To set with embedded parts, foundation bolts etc.
Iron reinforcement
Knife embedded part
Foundation bolt
Guide plate embedded part Pipe suspension foundation bolt
Original concrete slab
Use hole hinge, hole plunger or hole bolt.
Steel reinforcement structure
Use steel angle or new support steel angle directly.
Hanging bolt
Suspension screw
Support steel angle
Hanging of the indoor unit
l Fasten the nut on the suspension screw and then hang the suspension screw in the T
slot of the suspension part of the unit.
l Aided with a level meter, adjust level of the unit within 5 mm.
16
Installation Procedure
Page 19
! Caution
In order to drain water normally, the drain pipe shall be processed as specified in the installation manual and shall be thermal insulated to avoid dew generation. Improper hose connection may cause indoor water leakage.
Requirements
The indoor drain pipe shall be thermal insulated. The connection part between the drain pipe and the indoor unit shall be insulated so as to prevent dew generation. The drain pipe shall be slant downwards (greater than 1/100). The middle part shall not be of S type elbow, otherwise abnormal sound will be produced. The horizontal length of the drain pipe shall be less than 20 m. In case of long pipe, suppo­rts shall be provided every 1.5 ñ 2m to prevent wavy form. Central piping shall be laid out according to the following figure. Take care not to apply external force onto the drain pipe connection part.
Pipe and insulation material
Rigid PVC pipe VP31.5mm (internal diameter)
Foamed PE with thickness above 7mm
Pipe
Insulation
Hose
Drain pipe size: ÿ 19.05mm
2
(3/4") PVC pipe
The hose is used for adjusting the off-center and angle of the rigid PVC pipe. Directly stretch the hose to install without making any deformation. The soft end of the hose must be fastened with a hose clamp. Please apply the hose on horizontal part
Insulation treatment:
Wrap the hose and its clamp until to the indoor unit without any clearance with insulating material, as shown in the figure.
Drain confirmation
During trial run, check that there is no leakage at the pipe connection part during water draining even in winter.
Hose Hose clamp
Subsidiary insulation
Insulation
Rigid PVC pipe
Wall
Outside
Slant
Drain pipe (supplied by the user)
VP30
To the largest (app. 10cm)
Down slope above 1/100
S type elbow
1.5m~2m
Support
Insulation (supplied by the user)
Down slope above 1/100
17
Installation Procedure
Page 20
18
Supplementary refrigerant
The refrigerant supplementation shall be as specified in the installation instructions attached with the outdoor unit. The added refrigerant shall be R22. The adding procedure shall be aided with a measuring meter for a specified amount of supplemented refrigerant
Requirement
Overfilling or underfilling of refrigerant will cause compressor fault. The amount of the added refrigerant shall be as specified in the instructions.
Connection of refrigerant pipe
The connection of indoor unit pipes must use double spanners. The installing torque shall be as given in the following table.
Double-spanner operation
Connecting pipe
O.D.(mm)
ÿ 6.35
ÿ 9.52
ÿ 12.70
ÿ 15.88
Installing torque
(N-m)
11.8 (1.2kgf-m)
24.5 (2.5kgf-m)
49.0 (5.0 kgf-m)
78.4 (8.0 kgf-m)
Increased installing
torque (N-m)
13.7 (1.4 kgf-m)
29.4 (3.0 kgf-m)
53.9 (5.5 kgf-m)
98.0 (10.0 kgf-m)
Conduct flared connection work to connect all refrigerant pipes.
Pipe cutting and expanding
If the pipe is too long or the flare is damaged, it needs to be cut or expanded.
Pipe expander
Pipe expansion dimensions as follows:
A
Allowable pipe length and drop
These parameters differ according to the outdoor unit. See the instruction manual attached with the outdoor unit for details.
Installation Procedure
1. Pipe cutting 2. Removing burrs 3.Insertion nut 4. Pipe expansion
Slope Damage Bur Partial Overlong
Correct
Incorrect
6.35 mm (1/4") 0.8 ~ 1.5
9.52 mm (3/8") 1.0 ~ 1.8
12.7 mm (1/2") 1.2 ~ 2.0
15.88 mm (5/8") 1.4 ~2.2
Pipe diameter ÿ Size A (mm)
Page 21
19
Vacuum pumping
With a vacuum pump, create vacuum from the stop valve of the outdoor unit.
l Emptying with refrigerant sealed in the outdoor unit is absolutely forbidden.
Open all valves
Open all the valves on the outdoor unit.
Gas leakage detection
Check with a leakage detector or soap water that if there is gas leakage at the pipe connections and bonnets.
Insulation treatment
Conduct insulation treatment on both the gas side and liquid side of pipes respectively.
During cooling operation, both the liquid and gas sides are cold and thus shall be insulated
so as to avoid dew generation.
l The insulating material at gas side shall be resistant to a temperature above 120*. l The indoor unit pipe connection part shall be insulated.
The notch upward (Attached detail view)
Indoor unit
Subsidiary insulation tube
Field piping side
Installation Procedure