Groen HY-6GCE Service Manual

IMPORTANT INFORMATION, KEEP FOR OPERATOR
This manual provides information for:
HY-6G(CE) HYPERSTEAM
ATMOSPHERIC CONVECTION STEAMER INTERNATIONAL
· Self-Contained
· Gas Heated
· Capacity: 6 Steamer Pans (305 x 508 x 64mm)
THIS MANUAL MUST BE RETAINED FOR FUTURE REFERENCE. READ, UNDERSTAND AND FOLLOW THE INSTRUCTIONS AND WARNINGS CONTAINED IN THIS MANUAL.
NOTIFY CARRIER OF DAMAGE AT ONCE
It is the responsibility of the consignee to inspect the container upon receipt of same and to determine the possibility of any damage, including concealed dam age. Unified Brands suggests that if you are suspicious of damage to make a notation on the delivery receipt. It will be the responsibility of the consignee to file a claim with the carrier. We recommend that you do so at once.
Manufacture Service/Questions 888-994-7636.
PART NUMBER 128805, REV. E (1/09)
PART NUMBER 128805, REV. C (4/06)
-
1055 Mendell Davis Drive
Jackson, MS 39272
888-994-7636, fax 888-864-7636
unifiedbrands.net
2 OM/SM-HY-6G(CE)
IMPORTANT — READ FIRST — IMPORTANT
IT IS MOST IMPORTANT THAT THESE INSTRUCTIONS AND THE OPERATOR AND SERVICE MANUALS BE CONSULTED BEFORE INSTALLING AND COMMISSIONING THE APPLIANCE. FAILURE TO COMPLY WITH
SPECIFIED PROCEDURES MAY RESULT IN DAMAGE OR THE NEED FOR A SERVICE CALL.
THESE APPLIANCES HAVE BEEN CE MARKED ON THE BASIS OF COMPLIANCE WITH THE GAS APPLIANCE DIRECTIVE, EMC AND LOW VOLTAGE DIRECTIVE FOR THE COUNTRIES, GAS TYPES AND PRESSURES AS STATED ON THE DATA PLATE.
THESE APPLIANCES MUST BE INSTALLED BY A COMPETENT PERSON IN CONFORMITY WITH THE INSTALLATION AND SERVICING INSTRUCTIONS AND NATIONAL REGULATIONS IN FORCE AT THE TIME. PARTICULAR ATTENTION MUST BE PAID TO THE FOLLOWING:
I. E. E. REGULATIONS FOR ELECTRICAL INSTALLATIONS ELECTRICITY AT WORK REGULATIONS GAS SAFETY (INSTALLATION AND USE) REGULATIONS HEALTH AND SAFETY AT WORK ACT LOCAL AND NATIONAL BUILDING REGULATIONS FIRE PRECAUTIONS ACT
DETAILED RECOMMENDATIONS ARE CONTAINED IN INSTITUTE OF GAS ENGINEERS PUBLISHED DOCUMENTS: IGE/UP/1, IGE/UP/2, BS6173 AND BE5440.
FURTHERMORE, IS A NEED ARISES TO CONVERT THE APPLIANCE FOR USE WITH ANOTHETR GAS, A COMPETENT PERSON MUST BE CONSULTED. THOSE PARTS WHICH HAVE BEEN PROTECTED BY THE MANUFACTURER MUST NOT BE ADJUSTED BY THE USER.
USERS SHOULD BE CONVERSANT WITH THE APPROPRIATE PROVISIONS OF THE FIRE PRECAUTIONS ACT AND THE REQUIREMENTS OF THE GAS SAFETY REGULATIONS. IN PARTICULAR THEY SHOULD BE AWARE OF THE NEED FOR REGULAR SERVICING BY A COMPETENT PERSON TO ENSURE THE CONTINUED SAFE AND EFFICIENT PERFORMANCE OF THE APPLIANCE.
WARNING: TO PREVENT SHOCKS, ALL APPLIANCES GAS OR ELECTRIC, MUST BE EARTHED.
UPON COMPLETION OF THE INSTALLATION, THE OWNERS MANUAL SHOULD BE HANDED TO THE USERS AND THE INSTALLER SHOULD INSTRUCT THE RESPONSIBLE PERSON(S) IN THE CORRECT OPERATION AND MAINTENANCE OF THE APPLIANCE.
THIS EQUIPMENT IS ONLY FOR PROFESSIONAL USE, AND SHALL BE OPERATED BY QUALIFIED PERSONS. IT IS THE RESPONSIBILITY OF THE SUPERVISOR OR EQUIVALENT TO ENSURE THAT USERS WEAR SUITABLE PROTECTIVE CLOTHING AND TO DRAW ATTENTION TO THE FACT THAT, SOME PARTS WILL, BY NECESSITY, BECOME VERY HOT AND WILL CAUSE BURNS IF TOUCHED ACCIDENTALLY.
WARNING: BEFORE REMOVING ANY PARTITION OR PANEL, ALWAYS TURN OFF THE ELECTRIC
POWER AND ALLOW THE FAN TO STOP ROTATING. BEFORE WORKING ON ANY ELECTRICAL COMPONENT, DISCONNECT THE POWER SOURCE FROM THE UNIT.
NOTE: IT IS IMPORTANT THAT THE END-USER ROUTINELY EXAMINE THE FLUE OUTLET ON A
REGULAR BASIS. DEBRIS COVERING THE FLUE OUTLET CAN CAUSE A POTENTIALLY HAZARDOUS CONDITION. REMOVE ANY FOREIGN MATERIAL BEFORE USING THIS PIECE OF EQUIPMENT.
WARNINGS AND CAUTIONS PROVIDED IN THE BASIC OPERATOR AND SERVICE MANUALS (OM-HY-6G AND GROEN HYPERSTEAM SERVICE MANUAL) MUST BE COMPLIED WITH.
OM/SM-HY-6G(CE) 3
Table of Contents
1.0 EQUIPMENT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.0 INSPECTION AND UNPACKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
3.0 WATER CONDITIONING/REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
4.0 INSTALLATION, START-UP AND CONVERSION INSTRUCTIONS . . . . . . . . . . . . . . .
6
5.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6.0 CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
8.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
9.0 PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
10.0 SERVICE PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
11.0 SCHEMATIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
12.0 SERVICE LOG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
WARRANTY PROTECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
References
UNDERWRITERS LABORATORIES, INC. 333 Pfingsten Road Northbrook, Illinois 60062
KLENZADE SALES CENTER ECOLAB, Inc. 370 Wabasha St. Paul, Minnesota 55102 800 328-3663 or 612 293-2233
NATIONAL FIRE PROTECTION ASSOCIATION 60 Battery March Park Quincy, Massachusetts 02269
NFPA/70 The National Electrical Code
NATIONAL SANITATION FOUNDATION 3475 Plymouth Road Ann Arbor, Michigan 48106
NSF INTERNATIONAL 789 N. Dixboro Rd. P.O. Box 130140 Ann Arbor, Michigan 48113-0140
4 OM/SM-HY-6G(CE)
The HY-6G (CE) has two independent cavities, each with its own base-mounted steam generator.
The unit will be delivered in a heavy carton, strapped to a wooden skid.
1.0 - Equipment Description
Your Groen HY-6G (CE) HyPerSteam Convection Steamer is designed to give years of service. It has two stainless steel cavities (cooking chambers) which are served by twin, independent atmospheric steam generators which are gas-heated. A powerful blower circulates the steam in each cavity to increase heating efficiency.
Each cavity holds up to three steam table pans (305 x 508 x 64 mm). A 1.5 mm stainless steel case encloses the cavities, the steam generators and the control compartment that houses electrical components. Door hinges are reversible (the doors may be set to open from the left or right). Operating Controls are on the front panel.
HY-6G (CE) steamers are equipped with fully electronic controls and a button-activated, preprogrammed CLEAN cycle.
The drain system includes a spray condenser, which helps keep steam from escaping down the condensate drain.
2.0 - Inspection and Unpacking
Your HY-6G HyPerSteam will be delivered completely assembled in a heavy shipping carton and attached to a skid. On receipt, inspect the carton carefully for exterior damage.
CAUTION SHIPPING STRAPS ARE UNDER TENSION AND CAN SNAP BACK WHEN CUT.
Carefully cut the straps around the carton and detach the sides of the carton from the skid. Be careful to avoid personal injury. Strap edges may be very sharp, particularly where cut. Write down the model number, serial number and installation date. Space for these entries is provided in the Service Log at the back of this manual. Keep the manual near the equipment for reference and update as needed.
CAUTION THIS UNIT WEIGHS 550 LBS. (250 KG). GET HELP AS NEEDED AND USE MATERIAL HANDLING EQUIPMENT TO MOVE IT.
When installing, use material handling equipment to lift the unit straight up from the skid. Check packing materials for any loose parts.
OM/SM-HY-6G(CE) 5
The BPST Connection on the right rear side of the steamer.
3.0 - Water Conditioning
It is essential to supply the steam generator with water that will not form scale. Even though the steam generator is engineered to minimize scale formation, scale development depends on the hardness of your water and the number of hours the equipment operates.
In some areas of the country, water is low enough in minerals to avoid scale formation. But most water supplies are full of minerals which form scale. It is this scale which could lead to an early component failure.
Your water utility can tell you about the minerals in your water. The water going to the steam generator should have between 10 and 30 parts per million (ppm) total dissolved solids (TDS) and should have a pH (acidity rating) of 7.0 or higher. Please follow these simple precautions:
3.1 Do not rely on unproven water treatments which are sold as scale prevention or scale removers. They don’t always work. The best way to prevent scale is to supply the purest possible water (10 - 30 ppm TDS).
3.2 If your water contains scale-forming minerals, as most water does, use a well-maintained water softener. Whether an exchangeable softener cartridge or a regenerating system is chosen, a regular exchange system is essential.
3.3 Installing a water meter between the softener and the steamer will provide an accurate gauge of water use, and will help determine when to exchange cartridges or regenerate the softener. Using a water softener will provide longer generator life, higher steam capacity, and reduce maintenance requirements.
3.4 If you notice a slowdown in steam production, check the unit for scale build-up. Heavy scale reduces the unit’s ability to boil water, and can even cause heating elements in the steam generator to overheat and burn out.
MINIMIZE SCALE PROBLEMS BY USING AND MAINTAINING A SOFTENER, AND BY CLEANING THE STEAMER REGULARLY.
6 OM/SM-HY-6G(CE)
4.0 - Installation, Start-Up and Conversion
WARNING THE UNIT MUST BE INSTALLED BY PERSONNEL WHO ARE QUALIFIED TO WORK WITH ELECTRICITY AND PLUMBING. IMPROPER INSTALLATION CAN CAUSE INJURY TO PERSONNEL AND/OR DAMAGE TO THE EQUIPMENT. THE UNIT MUST BE INSTALLED IN ACCORDANCE WITH APPLICABLE CODES.
CAUTION DO NOT INSTALL THE UNIT WITH THE RIGHT SIDE VENTS BLOCKED OR WITHIN 30 CENTIMETERS OF A HEAT SOURCE (SUCH AS A BRAISING PAN, DEEP FRYER, CHAR BROILER, OR KETTLE).
TO AVOID DRAINAGE PROBLEMS, LEVEL THE UNIT FRONT TO BACK, OR PITCH IT SLIGHTLY TO THE REAR.
4.1 General
4.1.1 Model Number and Dimensions
MODEL
WIDTH
mm (in.)
DEPTH
mm (in,)
HEIGHT
mm (in.)
WEIGHT
Kg (lbs)
HY-6G(CE)
549
(21.6)
894
(35.2)
1464
(57.6)
193
(425)
4.1.2 Siting and Clearances
The HY-6G(CE) steamer is suitable for installation in combustible and noncombustible locations. Minimum clearances for installation are:
Right Side 300 mm (12 inches) Left Side 0 mm (0 inches) Rear of Flue 150 mm (6 inches)
However, for easy service at least 300 mm (12 inches) clearance is required for the right side of the unit, and it may not be installed within 300 mm (12 inches) of a heat source, as stated in the Caution above.
The unit must be installed in a well-ventilated room with an adequate air supply. The steamer must be installed beneath a ventilation hood, since gas combustion products exit the appliance.
Any item which might obstruct or restrict the flow of air for combustion and ventilation must be removed. Do not obstruct the flue cover or any front, side, rear, or top vents after installation.
The area directly around the appliance must be cleared of all combustible material. The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1, latest edition, including the following:
The unit and its individual shutoff valve must be
disconnected from the gas supply system during any pressure testing of that system at test pressures in excess of ½ PSI (3.45 kPa). It must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ PSI (3.45 kPa).
4.2 Electrical Supply Connection
The unit is designed for connection to fixed wiring. A suitably rated isolating switch with contact separation of at least 3 mm on both poles must be fitted to the installation.
Wiring must be executed in accordance
with the regulations listed on page 2 of this manual.
Cable entry is at the bottom rear right side of the appliance. To gain access the panel must be removed. Open the lower front panel by removing its screws. Lift the panel and swing its bottom toward you. Set the panel aside.
Provide 230 Volt, 50 Hz, Single Phase, 15 Ampere service. Maximum load is 2½ amps. The electrical schematic is located in the service compartment. A copy is also printed at the rear of this manual.
CAUTION
THE UNIT MUST HAVE
A SEPARATE EARTHING
WIRE FOR SAFE OPERATION.
4.3 Gas Supply Connection
Incoming service must be of sufficient size to supply full rate without excessive pressure drop. A gas meter is connected to the service pipe by the Gas Supplier. Any existing meter should be checked out by the Gas Supplier to ensure that it has adequate capacity to provide the required rate of gas to the steamer, in addition to any other equipment.
OM/SM-HY-6G(CE) 7
Gas input is through a ½ inch B.S.P.T connection at the left rear of the unit.
GAS INPUT RATE BTU/HR AND KW
HY-6G(CE)
Natural Gas
9.25 mBar
(3.7 in. W.C)
Propane Gas
26.25 mBar
(10.5 in. W.C.)
Individual
Steamer Cavity
40950 BTU/hr
12 KW
40950 BTU/hr
12 KW
Total
Both Cavities
81900 BTU/hr
24 KW
81900 BTU/hr
24 KW
Installation pipe work must be fitted in accordance with IGE/UP/2.
The appliance governor is suitable for both natural and propane gas without conversion. The governor is incorporated in the gas control valve, which is inside the control cabinet.
Connection to the gas supply can be completed with ½” B.S.P.T. pipe. Although the immediate connection to the appliance is ½” B.S.P.T., gas supply piping must be large enough to provide 90,000 BTU/hour. Minimum supply pressure must be 20 mBar for natural gas, or 37 mBar for propane gas.
An isolating cock must be located close to the appliance to allow shut down in an emergency, or for servicing. The installation must be tested for gas soundness and purged as specified in IGE/UP/1.
4.3.1 Gas Pressure Adjustment
Gas pressure has been set at the factory but should be checked by connecting a manometer to the pressure tap on the burner manifold. The adjusted gas pressures is shown in the table below.
G20 Natural Gas G31 Propane Gas
mBar Inch W.C. mBar Inch W.C.
9.25 3.7 26.25 10.5
If necessary, the gas pressure may be readjusted as described in the Service Manual.
NOTE:
With reference to gas rate, pressure adjustments and conversions, this appliance is CE-approved for use with C20 natural gas and G31 propane gas in Ireland and the United Kingdom.
Use of the appliance with non-approved gases in a listed country, or use in other countries, will void CE certification.
4.3.2 Injector Diameters
Natural Gas Propane Gas
Injector
Dia. (mm)
No. of
Injectors
Injector
Dia. (mm)
No. of
Injectors
Main Burner
1.49 4 x 2 0.94 4 x 2
Standby Burner
0.99 1 x 2 0.57 1 x 2
Pilot Burner
0.60
1 0.25 1
4.3.3 Burner Air Adjustment
The unit is equipped with fixed aeration type burners which have no provision for air inlet adjustment.
4.3.4 Equipotential Terminal
In accordance with national regulations, each unit is fitted with an equipotential terminal.
4.4 Water Supply Connection
The HY-6G CE model is fitted for a 3/4 inch B.S.P.T. cold water connection. The water supply must be provided at a rate of not less than 2.7 liters (0.70 gallons) per minute. Pressure must be 2.0 to 4.0 Bar (30 to 60 PSI) maximum.
Water quality minimums require totally dissolved solids (T.D.S.) of 30 parts per million maximum, and a water pH of 7.0 or greater. If the available water supply fails to meet these requirements, water treatment equipment must be provided to ensure steamer reliability and operating life.
8 OM/SM-HY-6G(CE)
Leave an air gap between the hose and the building drain, and don’t allow water traps in the hose.
Install a WRAS approved double-check valve or an equally effective backflow preventive device in the incoming cold water line at the point of connnection(s) to the steamer and in compliance with all local plumbing codes. This installation must be per WRAS-IRN R160 Schedule 2-15(1). For units with the dual water connection option, a double-check valve shall be installed on each water line.
Do not allow the connection to have any leak, regardles
s
of how small.
4.
5 Drain Connection
The HY-6G (CE)Steamer must be leveled front to back. A 38mm (1½ inch) ID hose may be attached to the drain pipe (supplied) by means of a hose.
DO NOT
CONNECT THE HOSE DIRECTLY TO
A BUILDING
DRAIN
. There must be a free air gap between the end
of the hose and the building drain. The free air gap should be as close as possible to the unit drain. There must also be no other elbows or other restrictions between the unit drain and the free air gap
.
CAUTIO
N DO NOT USE PLASTIC PIPE. THE DRAIN MUST WITHSTAND HOT WATER.
Install the drain line with
a constant downward pitch.
IMPORTANT
: Do not allow any water traps in the line. A trap can cause pressure to build up inside the cavity during steaming, which will make the doo
r
gasket leak.
4.
6 Initial Start-Up
After the HY-6G(CE) Steamer has been installed, test it to ensure that the unit is operating correctly
.
4.6.
1 Remove all literature and packing materials
from the interior and exterior of the unit.
4.6.
2 Make sure the water supply line is open.
4.6.
3 Make sure that the gas supply line is open
and that the manual knob on the main gas valve is turned t
o the “on” position. This valve is located behind the front access panel on the righ
t side of the unit.
4.6.
4 Turn on electrical service to the unit. The
HY-6G(CE) will not operate without electrica
l power. Do not attempt to operate the unit during
a power failure.
4.6.
5 The steamer will not operate until the pilot
burner has been ignited. To light the pilo
t burner, activate the pilot switch located at the lower front, next to the main gas valve. When the pilot ignition sequence has been successful, a green light on the pilot switch will glow
.
4.6.
6 The “trial for ignition” period is roughly 90
seconds. If the pilot burner does not light wi
thin about 90 seconds after the switch is activated, the ignition system automatically stops gas flow to the pilot burner and stops the ignition trial. If this happens, turn off the pilot switch and repeat the trial for ignition. Du
ring the initial start-up, the pilot may require several trials for ignition until all the air is bled from the gas piping. Subsequent start-ups should require only about 5 seconds to achieve pilot ignition. Reinstal
l panel(s). NOTE: See Automatic Operation of Pilot at the end of this section.
4.6.7
. Once the pilot burner flame has been
es
tablished (the green light on the electrical panel is on), press the ON/OFF touch pad for the desired steamer cavity. The steam generator will fill with water
.
NOTE: The door MUST be closed for the main (high) burner
to work.
4.6.
8 When the steam generator has filled with
water, the main and low burners will ignit
e
au
tomatically. Within 6-8 minutes the READY light will come on, indicating that the water has reached its standby temperature. When the READY light is displayed, you ma
y
take any one of the following steps:
OM/SM-HY-6G(CE) 9
OM/SM-HY-6G(CE)
a. Set the timer to the desired time for timed
steaming.
b. Turn the timer knob to the manual ON
position for continuous steam.
c. Let the unit stay at standby temperature.
WARNING
WHEN YOU OPEN THE DOOR, STAY
AWAY FROM STEAM COMING OUT OF THE UNIT. THE STEAM CAN CAUSE BURNS.
4.6.9 To shut down the unit, press the ON/OFF touch pad into the off position. The steam generator will then drain. You may also switch off the pilot switch to conserve energy.
4.6.10 If the HY-6G(CE) Steamer behaves as described, the unit is functioning correctly and ready for use.
4.6.11 Automatic Operation of Pilot
Once the pilot burner is lit, it essentially functions as a standing pilot. In this state, if the pilot is accidentally extinguished (by a very strong gust of wind for example), it will re-ignite automatically. The unit will completely shut down for a few seconds while the pilot is re-ignited.
Then the unit will come back on and resume operation in the mode and with the (running) timer value existing just prior to shutdown. The pilot switch may be turned off during “off hours” to conserve energy.
After the unit has been running, if the pilot burner ever fails to re-ignite automatically within 90 seconds, wait 5 minutes before you attempt to reactivate it. In the unlikely event that ignition problems persist, contact your authorized Groen Service Agency.
NOTE: For operation at high altitudes (2000 feet and above) please consult the Groen Food Service Engineering Department.
4.7 Gas Type Conversion (See Paragraph 4.3.1 for important information for gas conversion. Verify the type of gas to be used).
To change the type of gas used (e.g. G20 to/from G31) change the following:
Burner injector Pressure setting on Main Gas Valve Data plate Gas pressure Regulator Springs
The governor spring does not need to be changed; only the pressure setting. ALL CONVERSIONS
MUST BE FOR APPROVED GAS IN THE COUNTRIES LISTED IN PARAGRAPH 4.3.1
10 OM/SM-HY-6G(CE)
OM/SM-HY-6G(CE)
5.0 - Operation
WARNING ANY POTENTIAL USER OF THE EQUIPMENT SHOULD BE TRAINED IN SAFE AND CORRECT OPERATING PROCEDURES.
5.1 Controls
Operator controls are on the front right of the unit. The control panel has the following touch pads and
indicator lights. (Your controls may have either words or the symbols shown below):
The ON/OFF touch pad gets the HyPerSteam ready for use, or shuts it off.
The READY indicator light shows that the steam generator is at standby temperature and the cavity is hot enough to begin steaming.
The CLEANING indicator lights when the unit is operating in the cleaning mode.
The SERVICE indicator light shows when the water level probes have stopped working, and need to be cleaned (normally an indication of lime deposits).
When one probe is not working, the SERVICE light flashes briefly every few seconds. When both probes fail, the light will flash continuously and the beeper will sound.
The HI TEMP indicator light comes on when the steam generator is too hot.
The unit will automatically shut off, and cannot be turned on again until it has been serviced.
The TIMING indicator light stays on when the timer is running.
The CLEAN touch pad is used to start the automatic 50 minute cleaning cycle.
The timer is used in three ways:
1 In the OFF position the steam generator stays at a
low boil or “holding” temperature.
2 When a cook time is set, the unit steams until the
timer reaches OFF. The steaming stops, a red light comes on and a beeper sounds.
3 With the timer turned to the ON position, the unit
steams continuously. The green light stays lit. The steamer will not time down.
Gas Lockout Indicator and Reset Control
Should the pilot fail to ignite during start-up, a yellow indicator on the control panel (see page 11) will light and the supply of gas to the unit will be halted.
When this occurs, the ignition process may not be started again for five minutes. After that time, press the Lockout Reset Switch located behind the front panel and attempt to start the unit again. If the lockout continues to occur after three attempts, contact your Groen Service Agency for assistance.
5.2 Operating Procedure
5.2.1 Press the ON/OFF touch pad for the steamer. The steam generator will fill, and heat until the READY light comes on. (About 10 minutes.)
5.2.2 Load food into pans in uniform layers. Pans should be filled to about the same levels, and be even on top. The maximum allowable weight of food is 9.8 kilograms (21.6 lbs.) per pan.
5.2.3 Open the door and slide the pans onto the supports. If you will only be steaming one pan, put it in the middle position.
5.2.4 Close the door.
With the READY indicator lit,
take one of the following steps:
If you want to steam the food for a certain
length of time, set the timer for that period. The timer will automatically run the steamer for the set time and then turn it off. A red light will come on and a beeper will sound. Steam production stops.
To steam continuously, turn the timer to the
manual ON position. A green light will come on. The unit will continue steaming until you stop it by turning the timer to OFF. When steaming continuously YOU MUST CONTROL STEAMING TIME.
WARNING WHEN YOU OPEN THE DOOR, STAY AWAY FROM THE STEAM COMING OUT OF THE UNIT. THE STEAM CAN CAUSE BURNS.
5.2.5 Open the door. Remove the pans from the steamer, using hot pads or oven mitts to protect your hands from the hot pans.
5.2.6 To shut down the unit, press the ON/OFF touch pad OFF. The steam generator will drain.
OM/SM-HY-6G(CE) 11
Upper Portion of HY-6G(CE) Control Panel
12 OM/SM-HY-6G(CE)
6.0 - Cleaning
To keep your HY-6E Steamer in proper working condition/order, use the following procedure to clean the unit. This regular cleaning will reduce the effort required to clean the steam generators and cavities.
6.1 Suggested Tools
1. Mild detergent
2. Stainless steel exterior cleaner such as Zepper®
3. Steam generator de-liming agent, such as Groen Delimer Descaler, Lime-Away® or an equivalent. A liquid de-liming agent will be easier to use than crystals or powders. See the warning about chlorides, below
4. De-greaser, such as EncompasS®, Malone 34®, Puritan Puribrute®, or Con-Lie®
5. Cloth or sponge
6. Plastic wool or a brush with soft bristles
7. Spray bottle
8. Measuring cup
9. Nylon pad
10. Towels
11. Plastic disposable gloves
12. Funnel
6.2 Procedure
6.2.1 Outside of Steamer
1. Prepare a warm solution of the mild detergent as instructed by the supplier. Wet a cloth with this solution and wring it out. Use the moist cloth to clean the outside of the unit. Do not allow freely running liquid to touch the controls, the control panel, any electrical part, or any open louver.
2. To remove material which may be stuck to the unit, use plastic wool, a fiber brush, or a plastic or rubber scraper with a detergent solution.
3. Stainless steel surfaces may be polished with a recognized stainless steel cleaner such as Zepper®.
WARNING
DISCONNECT THE POWER SUPPLY BEFORE CLEANING THE OUTSIDE OF THE STEAMER.
KEE P W ATER AND CLE A N ING SOLUTIONS OUT OF CONTROLS AND ELECTRICAL COMPONENTS. NEVER HOSE OR STEAM CLEAN ANY PART OF THE UNIT.
DON’T MIX DE-LIMING AG
ENTS (ACID) WIT H DE -GREA S E R S ( A L K ALI) ANYWHERE IN THE UNIT
A V O I D CO N T A C T W I T H A N Y CLEANERS, DE-LIMING AGENT OR DE­GREASER AS RECOMMENDED BY THE SUPPLIER. MANY ARE HARMFUL. READ THE WARNINGS
AND FOLLOW
THE DIRECTIONS!
EVEN WHEN THE UNIT HAS BEEN SHUT OFF, DON’T PUT HANDS OR TOOLS INTO THE COOKING CHAMBER UNTIL THE FAN HAS STOPPED TURNING.
DON’T OPERATE THE UNIT UNL
ESS THE TWO REMOVABLE INTERIOR PARTITIONS HAVE BEEN PUT BACK IN THEIR PROPER LOCATIONS.
DON’T USE ANY CLEANING OR DE­LIMING AGENT THAT CONTAINS ANY SULFAMIC AGENT OR ANY CHLORIDE, INCLUDING HYDROCHLORIC ACID (HCl). TO CHECK FOR CHLORIDE CONTENT SEE ANY MATERIAL SAFETY DATA SHEETS PROVIDED BY THE CLEANING AGENT MANUFACTURER
.
IMPORTANT
DO NOT USE ANY METAL MATERIAL (SUCH AS METAL SPONGES) OR METAL IMPLEMENT (SUCH AS
A
SPOON, SCRAPER OR
WIRE BRUSH) THAT MIGHT SCRATCH THE SURFACE. SCRATCHES MAKE THE
SURFACE HARD TO CLEAN AND PROVIDE PLACES FOR BACTERIA TO GROW . DO NOT USE STEEL
WOOL
, WHICH MAY LEAVE PARTICLES IMBEDDED IN THE SURFACE WHICH COULD EVENTUALLY CAUSE
CORROSION AND PITTING.
Loading...
+ 28 hidden pages