APPENDIX C – LIQUID SPEED OF SOUND....................................................46
IMPORTANT NOTE: This instrument is manufactured and calibrated to meet product specifications.
Please read this manual carefully before installation and operation. Any unauthorized repairs or
modifications may result in a suspension of the warranty.
If this product is not used as specified by the manufacturer, protection may be impaired.
Available in Adobe Acrobat pdf format
Page 3
SENSOR INSTALLATION
TTFM 1.0 Transit Time Flow Meter
Page 4
TTFM 1.0 Transit Time Flow Meter
CONNECTIONS:
POWER INPUT: The standard model requires AC power input between 100 to 240 VAC 50/60Hz. No
adjustments are necessary for voltages within this range. Connect L (Live) N (Neutral) and AC Ground.
Optional DC input model requires 9-32 VDC/9 Watts. Connect to + and - terminals.
Optional Thermostat and Heater modules are available rated for 115 VAC or 230 VAC.
IMPORTANT NOTE: To comply with CSA/UL electrical safety standards, AC power input and relay
connection wires must have conduit entry to the instrument enclosure. Installation requires a switch,
overcurrent fuse or circuit breaker in the building (in close proximity to the equipment) that is marked as
the disconnect switch.
Risk of electric shock. Loosen cover screw to access connections. Only qualified personnel
should access connections.
Note: Use of instrumentation over 40°C ambient requires special field wiring.
Note: User replaceable fuse is 2 Amp 250V (T2AL250V), located on the power supply.
Page 5
CONNECTIONS
TTFM 1.0 Transit Time Flow Meter
Page 6
TTFM 1.0 Transit Time Flow Meter
COMPOUND
~0.8”
20 mm
QUICK BENCH TEST:
In the TTFM Setup menu set parameters to perform a bench test:
-Set Fluid = Water
-Set Temperature = 20°C
-Set Pipe OD = 0.15 inch
-Set Pipe Wall = 0.06 inch
-Set Pipe material = ABS
-Set Lining = None
-Set Crossings = 4
-Press to view Signal Strength at bottom of menu.
Apply coupling compound to the face of sensors and press together as indicated in the illustration below.
The menu should indicate large Signal Strength display.
COUPLING
Page 7
TTFM 1.0 Transit Time Flow Meter
KEYPAD SYSTEM
The diagram on page 9 shows the TTFM 1.0 menu system. Arrows show the four directions to leave a
menu box. Pressing a corresponding keypad arrow will move to the next item in the direction shown.
Move the cursor (highlighted) under numerals and increase or decrease numerals with the and
keys.
To store calibration values permanently (even through power interruptions), press the .
Page 8
CALIBRATION MENU
TTFM 1.0 Transit Time Flow Meter
Page 9
ICONS
TTFM 1.0 Transit Time Flow Meter
Page 10
TTFM 1.0 Transit Time Flow Meter
MAIN DISPLAY
The MAIN display shows the units selected from the Units/Mode menu, Flow or
Velocity rate being measured, TOTALIZER and RELAY states. The TTFM 1.0
will start-up with this display.
MESSAGE ICON
Press from the MAIN display to view status of the data logger and
error/warning messages provided by the instrument. The Message Icon will
appear on the MAIN display if error messages are being generated by the
instrument. Press to return to the main display.
STATUS
Press from the MAIN display to view instrument status.
VelocityDisplayed in ft/sec or m/sec.
Signal Strength Displays magnitude of signal being received by the ultrasonic
sensor.
RelaysEnergized relays will display as a white character on a
black background.
Page 11
TTFM 1.0 Transit Time Flow Meter
24 HR LOG (Data Logging option only)
Press from the MAIN display to view a formatted flow report from instruments
with a built-in data logger. Press to scroll down one day or repeatedly to scroll
to a specific date. Up to 365 days can be stored. Newest date will overwrite the
oldest. Press to return to the main display.
PASSWORD
The password (a number from 0000 to 9999) prevents unauthorized access to the
Calibration menu.
From the Main display press the key to get to Password. Factory default
password is 0000 and if it has not been changed press the to proceed to the
Menu Selections screen.
If a password is required, press to place the cursor under the first digit and or
to set the number, then to the second digit, etc. Press or to proceed to
the Menu Selections screen.
A new password can be stored by going to Special Functions/New Password.
Page 12
TTFM 1.0 Transit Time Flow Meter
UNITS/MODE
From Mode press the and then the or to select Flow or Velocity.
Flow mode displays the flow rate in engineering units (e.g. gpm, litres/sec, etc.)
Press the to store your selection then the to the next menu item and to
enter.
From Linear press the key and then the or to select your units of
measurement. Press the to store your selection.
Press the key to move the symbol to each subsequent menu item and the
to save your selections.
Note: the volume selection "bbl" denotes U.S. oil barrel.
Press or to return to the Menu Selections screen.
Page 13
SET UP
TTFM 1.0 Transit Time Flow Meter
Sensor Select
Fluid Vel
V/C(@25C)
Fluid
Fluid Temp
Pipe OD
Pipe Wall
Choose SE16B.
When Fluid = Other – Enter the fluid velocity at 25C
from table or other reference in units of m/s
When Fluid = Other – Enter fluid velocity adjustment
factor over change in temperature in units of m/s per °C.
Select fluid type.
Other will require additional information.
Enter average fluid temperature.
Highlight the digits and thenorto change the
numbers and decimal point. Pipe OD should be entered
as the exact outside diameter of the pipe where the sensor
is mounted. Refer to the Pipe Charts Appendix in this
manual for outside diameter of common pipe types and
sizes.
Enter wall thickness.
Refer to the Pipe Charts Appendix in this manual for
thickness of common pipe materials and sizes.
Pipe Vel
Pipe
Lining Thick
Lining Vel
Lining
When pipe = Other – Enter pipe material speed of sound
(consult factory).
Select pipe material.
When Lining – Enter lining thickness
When Lining = Other – Enter speed of sound of lining
material.
Select Lining material.
None represents no liner. Other will require additional
information.
Page 14
Crossings
TTFM 1.0 Transit Time Flow Meter
1 = Z mounting
2 = V mounting
4 = W mounting
Zero Tare
To suppress readings or fluctuations at zero flow. Set
Calibration/Damping to 5% and under no flow conditions
and full pipe select Yes to force readings to zero.
Sens Space
Velocity
Signal Strength
Displays the calculated sensor spacing
Displays the measured velocity.
Displays magnitude of signal being received by the
ultrasonic sensor.
Press to return to Menu Selections.
NOTE:
Sensor separation distance is automatically calculated by
the instrument and will be displayed in the Setup menu
Page 15
TTFM 1.0 Transit Time Flow Meter
CALIBRATION
Press to Calibration and to enter. Use or to position before each
menu item and to enter. When settings are completed press to store and
return to the Calibration menu.
20mA at
4mA at
Min Flow
Damping
Pressthenorto change the numbers and decimal
point. Use this menu to set the corresponding flow rate
that will be represented by 20mA analog output. If
maximum flow is unknown, enter an estimated flow rate
and observe actual flow to determine the correct
maximum value. Any velocity or flow rate up to +40
ft/sec (12.2 m/sec) may be selected.
Pressorto set the flow rate corresponding to 4mA
analog output. This setting may be left at zero flow (or
velocity or can be raised to any value less than the 20mA
setting, or lowered to any velocity or corresponding flow
rate down to -40 ft/sec (-12.2 m/sec).
Flow rates below this setting will be displayed as zero
flow.
Increase damping to stabilize readings under turbulent
flow conditions. Decrease for fast response to small
changes in flow. Damping is shown in percentage
(maximum is 99%). Factory default is 20%.
Press to return to Menu Selections.
Page 16
RELAY PARAMETERS
TTFM 1.0 Transit Time Flow Meter
Relay
Function
Flow
Pressandorto select a corresponding relay number (2
relays are standard, 4 additional are optional).
Pressorto select Off, Pulse or Flow.
Mode Select Pump, Low Alarm or Hi Alarm.
Pump mode provides separate On/Off settings where the relay
will energize at one flow rate and de-energize at another.
On Highlight the numerals and press or to set digits to
the required relay On set point.
Off set digits to the required Off set point.
Low Alarm mode relay will energize at a programmable flow
rate and remain energized with flow below the set point. When
flow rises above the set point, the relay will de-energize.
Hi Alarm mode relay will energize at a programmable flow
rate and remain energized with flow above the set point. When
flow falls below the set point, the relay will de-energize.
Pulse
Pressand set digits to the flow volume increment required
between relay pulses. Use this feature for remote samplers,
chlorinators or totalizers. Minimum time between pulses is
2.25 seconds and pulse duration is 350 milliseconds.
Return to Relay and change settings for each relay number.
Press to return to Menu Selections.
Page 17
DATA LOGGING (OPTIONAL)
Refer to Options section of this manual.
SPECIAL FUNCTIONS
TTFM 1.0 Transit Time Flow Meter
Language
Analog Out
Backlight
Reset Totalizer
Negative Totals
Select English, French or Spanish
Select 4-20mA or 0-5V mode for the analogue
output.
Select High, Medium or Low for continuous
backlight.
Select Key Hi/Lo for high backlight for 1 minute
after a keypress and then Lo backlight until a key
is pressed again.
Select Key High, Med or Low for backlight for
1 minute after a keypress and then backlight off until
a key is pressed again.
Pressand select Yes to erase and restart the
totalizer at zero.
Select Yes to have reverse flow readings deducted
from the totalizer. Select No to totalize forward
flow only and ignore reverse flow.
Cal Constant
Factory set during calibration. (Refer to the
calibration certificate supplied with your instrument.)
Restore Defaults
Select Yes and press to erase all user settings
and return the instrument to factory default settings.
New Password
Select any number from 0000 to 9999 and press .
Default setting of 0000 will allow direct access to the
calibration menus. Setting of any password greater
than 0000 will require the password to be entered to
access the calibration menus.
Press to return to Menu Selections.
Page 18
TTFM 1.0 Transit Time Flow Meter
SIMULATION
Exercises the 4-20mA output, digital display and control relays.
Simulate a Flow /Velocity reading. Press and then or to change the
simulated output. Press to begin simulation. The 4-20mA output and relay
states will be displayed on the screen below.
Press the to terminate simulation and return to the Menu Selections screen.
Page 19
TTFM 1.0 Transit Time Flow Meter
SENSOR MOUNTING LOCATION
The position of the sensor is one of the most important considerations for accurate Transit Time flow
measurement. The same location guidelines apply to Transit Time as most other types of flow meters.
Before permanently mounting a Transit Time sensor onsite testing is recommended to determine
optimum mounting position. Use the sensor coupling compound (supplied with each Greyline flow
meter, or petroleum gel, acoustic compound or electrocardiograph gel). Take several readings around the
axis of the pipe and then at several points upstream and downstream from the selected position,
checking for consistent readings. Avoid high or low reading areas. Mount the sensors where consistent
(average) readings were obtained or continue testing on another pipe section.
VERTICAL OR HORIZONTAL PIPE - Vertical pipe
1 TO 5 O'CLOCK POSITION
ON HORIZONTALPIPES
runs generally provide evenly distributed flow. On
Horizontal pipes and liquids with high concentrations
of gas or solids, the sensors should be mounted on the
side (1 to 5 o’clock positions) to avoid concentrations
of gas at the top of the pipe, or solids at the bottom.
VERTICALPIPE USUALLY
HAS EVENLY DISTRIBUTED FLOW
VELOCITY INCREASING DEVICES: Generally the sensors must be mounted away from flow
disturbances such as valves, pumps, orifice plates, venturis or pipe inlets and discharges which tend to
increase flow velocity. Velocity increasing devices often cause cavitation, or rapid release of gas
bubbles, and readings both up and downstream may be intermittent or inaccurate. As a guideline, mount
the sensor at least 20 diameters upstream or 30 diameters downstream from velocity increasing devices.
Required distance from a velocity increasing device will vary in applications depending on the flow
velocity and the characteristics of the liquid itself.
TURBULENCE INCREASING DEVICES: Elbows,
flanged connections and tees tend to introduce
desirable conditions of an evenly distributed flow
profile. Sensor mounting 6 pipe diameters upstream
and 10 diameters downstream from these disturbances
is generally optimum.
The sensors are designed to mount longitudinally on a straight section of pipe. Do not attempt to mount
it on bends, elbows or fittings.
Page 20
TTFM 1.0 Transit Time Flow Meter
SENSOR MOUNTING
Prepare an area 2" wide by 4" long (50mm x 100mm) for sensor bonding by removing loose paint, scale
and rust. The objective of site preparation is to eliminate any discontinuity between the sensor and the
pipe wall, which would prevent acoustical coupling.
A TMK1 Sensor Mounting Kit is supplied with each Greyline flow meter. It includes recommended
coupling compound in a plastic applicator and a stainless steel mounting bracket with adjustable pipe
straps. Use the Alignment Bar (included) to align sensor brackets for V and W mode mounting.
Page 21
TTFM 1.0 Transit Time Flow Meter
SEPARATION DISTANCE
Measure separation distance with a ruler or tape measure. Separation distance is automatically calculated
by the TTFM 1.0 based on parameters entered in the Set-up menu. Sens Space is displayed in the
Setup menu.
Transducer Installation in Wet Locations
The TTFM 1.0 Transit Time Flowmeter transducers
are rated for accidental submersion up to 10 psi (0.75
bar). The flowmeter will continue to operate and
measure flow accurately during periods of
submergence. Plastic seal jackets on the cables can
be filled with coupling compound to provide
additional moisture protection for the BNC cable
connectors.
Page 22
TTFM 1.0 Transit Time Flow Meter
SENSOR COUPLING
For permanent or temporary bonding, the following are recommended:
a)Dow Corning silicon compound #4 (supplied)
Additional supply: order Greyline Option CC
b)Water-based sonic compound: Order Greyline Option CC30
c)Electrocardiograph gel
d)Petroleum gel (Vaseline)
The above are arranged in their order of preferred application.
d & e are only good for temporary bonding at room temperature.
DO NOT USE: Silicon RTV caulking compound (silicon rubber).
Use the pipe clamp and rail (supplied) as illustrated on previous page or use
a loop of electrical tape for temporary mounting. Apply silicon coupling
compound #4 to the colored face of the sensor. A bead, similar to toothpaste
on a toothbrush, is ideal. Do not overtighten (crush the sensor).
The sensor must be fixed securely to the pipe with coupling material
between the sensor face and the pipe. Sensor installation with excessive
coupling compound can result in gaps or voids in the coupling and cause
errors or loss of signal. Insufficient coupling compound will create
similar conditions.
Over time temporary coupling compounds (e.g. Petroleum Gel) may gradually sag away from the sensor
resulting in reduced signal strength and finally complete loss of signal. Warm temperatures, moisture
and vibration will accelerate this process. Dow Corning Silicone Compound #4 as supplied with the
TTFM 1.0 (and available from Greyline Instruments) is recommended for semi-permanent installations.
Page 23
TTFM 1.0 Transit Time Flow Meter
BAD
GOOD
SENSOR MOUNTING/COUPLING RECOMMENDATIONS
Page 24
TTFM 1.0 Transit Time Flow Meter
ENCLOSURE INSTALLATION
Locate the enclosure within 20 ft (6 m) of the sensor (250 ft - 75 m optional). The enclosure can be wall
mounted with the four mounting screws (included) or panel mounted with Option PM Panel Mount kit
from Greyline Instruments.
Avoid mounting the enclosure in direct sunlight to protect the electronics from damage due to
overheating and condensate. In high humidity atmospheres, or where temperatures fall below freezing,
Option TH Enclosure Heater and Thermostat is recommended. Seal conduit entries to prevent moisture
from entering enclosure.
NEMA4X (IP66) WITH CLEAR COVER
1. Open hinged enclosure cover.
2. Insert #12 screws (supplied) through the four enclosure mounting holes
to secure the enclosure to the wall or mounting stand.
Additional conduit holes can be cut in the bottom of the enclosure when
required. Use a hole saw or Greenlee-type hole cutter to cut the required
holes.
DO NOT make conduit/wiring entries into the top of the enclosure.
Note: This non-metallic enclosure does not automatically provide grounding between conduit
connections. Grounding must be provided as part of the installation. Ground in accordance with the
requirements of the National Electrical Code. System grounding is provided by connecting grounding
wires from all conduit entries to the steel mounting plate or another point which provides continuity.
CLEANING
Cleaning is not required as a part of normal maintenance.
Page 25
FIELD TROUBLESHOOTING
TTFM 1.0 Transit Time Flow Meter
Possible Causes:
METER READING WHEN THERE IS NO FLOW?
Erratic measurement (set damping to 0% to check) due
to electrical noise or poor signal quality.
Variable Speed Drive interference
Corrective Action:
Set Calibration/ Damping to 5% with zero flow
use Setup / Tare function.
Ensure all Flowmeter wiring is in METAL
conduit and sensor shield is properly connected
to Ground.
Ensure correct power input Ground connection
(<1 ohm resistance).
Ensure 4-20mA Shield connected to Instrument
Ground stud.
Try adjusting sensor spacing (+/- 10%) and
contact Greyline for further assistance.
Adjust Calibration / Min Flow setting.
Follow Drive manufacturers wiring and
Grounding instructions
Relocate Flowmeter electronics, Sensor and
wiring away from VSD
Sensor cable connections incorrect or loose
METER READING LOWER THAN EXPECTED?
Calibration Error
Lower flow rate than expected
Erratic measurement (set damping to 0% to check) due
to electrical noise or poor signal quality.
Refer to Connections diagram. Disconnect and
reconnect sensor cables ensuring that cable is
properly inserted into terminals and tightened.
Review calibration menu. Pipe dimensions and
fluid selection/fluid velocity.
Investigate pump/valves. Compare velocity
with alternate instrument.
Ensure all Flowmeter wiring is in METAL
conduit and sensor shield is properly grounded.
Ensure correct power input Ground connection
(<1 ohm resistance).
Ensure 4-20mA Shield connected to Instrument
Ground stud.
Try adjusting sensor spacing (+/- 10%) and
contact Greyline for further assistance.
Page 26
TTFM 1.0 Transit Time Flow Meter
Possible Causes:
NO ECHO INDICATION Icon: No Echo
Sensor Connections
Sensors not mounted to Pipe or mounted improperly
Empty pipe or partially filled
Coupling compound washed out, or sensor loose on
pipe.
METER READING HIGHER THAN EXPECTED?
Calibration Error
Corrective Action:
Check sensor connections at TTFM and at
sensor junction box.
Note: Refer to Sensor Cable Resistance Test to
test final connections.
Apply coupling compound and mount sensors
to pipe with proper sensor spacing.
Pipe must be fluid filled and acoustically
transparent in order to obtain echoes.
Remount sensor
Use Dow Corning Silicone #4
Review calibration menu. Pipe dimensions and
fluid selection/fluid velocity.
Higher flow rate than expected
Erratic measurement (set damping to 0% to check) due
to electrical noise or poor signal quality.
Pipe not Full
High viscosity fluid
Investigate pump/valves. Compare velocity
with alternate instrument.
Ensure all Flowmeter wiring is in METAL
conduit and sensor shield is properly grounded.
Ensure correct power input Ground connection
(<1 ohm resistance).
Ensure 4-20mA Shield connected to Instrument
Ground stud.
Try adjusting sensor spacing (+/- 10%) and
contact Greyline for further assistance.
Verify pipe is full by mounting sensors at top
of pipe and check echo icon.
No echo if pipe is not full.
Laminar flow profile due to high viscosity fluid
requires an adjustment to Cal Const.
Page 27
TTFM 1.0 Transit Time Flow Meter
SENSOR CABLE RESISTANCE TEST
Unplug the green sensor terminal from the Transit Time board and connect the sensor wires. With a
multimeter, perform resistance checks for each set of wires. One single loose terminal may cause false
readings.
Test across shield and core of each wire: TDR1 (black) and TDR2 (black/white). Resistance should be
around 10K ohms for any cable length. High readings indicate an open circuit and low readings indicate
a short or partial short in the sensor cable connections.
Note: The TTFM 1.0 will automatically detect connectivity to the sensors. Confirm that TTFM 1.0
indicates “SensorGood’ in the messages menu.
Page 28
TTFM 1.0 Transit Time Flow Meter
COMMON QUESTIONS AND ANSWERS
The pipe vibrates. Will it affect the flow meter?
Common vibration frequencies are far lower than the sonic frequencies used by the Greyline flow meter,
and will not normally affect accuracy or performance. However, applications where very weak Transit
Time signal is present (when sensitivity is adjusted to maximum and signal strength is low), accuracy
may be affected by pipe vibration, or the flow meter may show readings under no-flow conditions.
Attempt to relocate the sensor on a pipe section where vibration is reduced, or arrange pipe mounting
brackets to reduce vibration at the sensor mounting location.
The flow meter must be installed in a high noise environment. Will this affect operation?
Greyline flow meters are designed to discriminate between environmental noise and the Transit Time
signal. High noise environments may affect the flow meter’s performance where low signal strength
and/or low flow velocities are being measured. Relocate the sensor in a quieter environment if possible.
Will pipe corrosion affect accuracy of the flow meter?
Yes. Rust, loose paint etc. must be removed from the outside of the pipe to provide a clean mounting
position when installing a Transit Time sensor. Severe corrosion/oxidation on the inside of the pipe may
prevent the Transit Time signal from penetrating into the flow. If the pipe cannot be cleaned, a spool
piece (PVC recommended) should be installed for sensor mounting.
What effect do pipe liners have on the flow meter?
The air gap between loose insertion liners and the pipe wall prevent the Transit Time signal from
entering the flow. Better results can be expected with bonded liners such as cement, epoxy or tar,
however an on site test is recommended to determine if the application is suitable for a Transit Time
flow meter.
Why is Transit Time recommended for clean liquids?
The Transit Time sensor transmits sound across the flow stream in order to measure sound velocity and
therefore requires a fluid medium that is relatively transparent to the acoustic signal. The Transit Time
system will not function when there is high volume of solids or aeration. As a guideline, Greyline
Transit Time flow meters are recommended for clean liquids with solids or bubbles content less than
2%. Most applications such as water, chemicals and oils will meet this minimum requirement.
Can the sensor be submerged in water?
Yes, for short periods of time or by accident, but it is not recommended for continuous operation. The
sensor is constructed to withstand submersion to 10 psi (0.7 Bar) without damage.
What is the purpose of the Signal Strength Display?
The primary function of the signal strength display is to assist as a feedback when mounting sensors.
Signal Strength can also be a useful diagnostics tool when troubleshooting problems with an installation.
A low signal strength (< 20%) will cause the TTFM to be more susceptible to environmental noise and
may indicate a problem with the installation or other qualitative issues.
Page 29
TTFM 1.0 Transit Time Flow Meter
Can I change the length of the sensor cable?
Yes. Technological advances in Greyline Transit Time design allow cable lengths up to 250 ft (75 m).
Extended cable (Greyline Option DXC) should be installed in rigid or flexible conduit for mechanical
protection. Use only Greyline shielded coaxial pair (RG174U) cable. BNC coaxial connectors (TV cable
type) are not recommended for cable splices.
Does the TTFM 1.0 require periodic recalibration?
TTFM 1.0 calibration does not drift over time. The solid state sensor has no moving parts to wear and
affect calibration. All Greyline timing/counting circuits use crystal-controlled frequency references to
eliminate any drift in the processing circuitry.
ISO 9000 or similar quality management systems may require periodic and verifiable recalibration of
flow meters. TTFM 1.0 Flow Meters may be returned to Greyline for factory calibration and issue of a
new NIST traceable certificate. Refer to the ‘Product Return Procedure’ section of this manual for return
instructions.
Page 30
TTFM 1.0 Transit Time Flow Meter
APPLICATIONS HOTLINE
For applications assistance, advice or information on any Greyline Instrument contact your Sales Representative,
write to Greyline or phone the Applications Hotline below:
United States:Tel: 315-788-9500Fax: 315-764-0419
Canada:Tel: 613-938-8956Fax: 613-938-4857
Toll Free:888-473-9546
Email:info@greyline.com
Web Site:www.greyline.com
Greyline Instruments Inc.
CanadaUSA:
16456 Sixsmith Drive11451 Belcher Road South
Long Sault, Ont. K0C 1P0Largo, FL 33773
PRODUCT RETURN PROCEDURE
Instruments may be returned to Greyline for service or warranty repair.
1Obtain an RMA Number from Greyline -
Before shipping a product to the factory please contact Greyline by telephone, fax or email to obtain an
RMA number (Returned Merchandise Authorization). This ensures fast service and correct billing or
credit.
When you contact Greyline please have the following information available:
1.Model number / Software Version
2.Serial number
3.Date of Purchase
4.Reason for return (description of fault or modification required)
5.Your name, company name, address and phone number
2Clean the Sensor/Product -
Important: unclean products will not be serviced and will be returned to the sender at their expense.
1. Rinse sensor and cable to remove debris.
2. If the sensor has been exposed to sewage, immerse both sensor and cable in a solution of 1 part
household bleach (Javex, Clorox etc.) to 20 parts water for 5 minutes. Important: do not immerse
open end of sensor cable.
3. Dry with paper towels and pack sensor and cable in a sealed plastic bag.
4. Wipe the outside of the enclosure to remove dirt or deposits.
5. Return to Greyline for service.
Page 31
TTFM 1.0 Transit Time Flow Meter
Contact
Title/Dept
Company
Address
Address
Tel
Fax
Email
Mobile
Pipe Run
[ ] Vertical
[ ] Horizontal
Pipe Full
[ ] Yes
[ ] No
Fluid Type
% of Solids
Nominal Pipe Size and
Schedule
P
ipe
Outside Diameter
Wall Thickness
Pipe Material
Liner Material
Liner Thickness
Normal Flow
Maximum Flow
Minimum Flow
Maximum Temp
erature
Maximum Pressure
Vibration
[ ] Yes
[ ] No
Hazardous Rating
Notes
/ Additional Comments /
Pipe Run
Diagram
:
FLOW METER DATA SHEET
[ ] 16456 Sixsmith Drive, Long Sault, ON K0C 1P0
Tel: 613-938-8956 / Fax: 613-938-4857
[ ] 11451 Belcher Road South, Largo, FL 33773
Tel: 315-788-9500 / Fax: 315-764-0419
Contact Information
Service Conditions
Please complete and return this form to Greyline. It is important. We
use this information to check our database for performance of Greyline
flow meters in similar applications, and to provide advice and
recommendations to you. Thank you for your cooperation.
Page 32
TTFM 1.0 Transit Time Flow Meter
LIMITED WARRANTY
_____________________________________
Greyline Instruments warrants, to the original purchaser, its
products to be free from defects in material and workmanship for a
period of one year from date of invoice. Greyline will replace or
repair, free of charge, any Greyline product if it has been proven to
be defective within the warranty period.This warranty does not
cover any expenses incurred in the removal and re-installation of
the product.
If a product manufactured by Greyline should prove defective
within the first year, return it freight prepaid to Greyline
Instruments along with a copy of your invoice.
This warranty does not cover damages due to improper installation
or handling, acts of nature, or unauthorized service. Modifications
to or tampering with any part shall void this warranty. This
warranty does not cover any equipment used in connection with the
product or consequential damages due to a defect in the product.
All implied warranties are limited to the duration of this warranty.
This is the complete warranty by Greyline and no other warranty is
valid against Greyline. Some states do not allow limitations on how
long an implied warranty lasts or limitation of incidental or
consequential damages, so the above limitations or exclusions may
not apply to you.
This warranty gives you specific legal rights, and you may also
have other rights which vary from state to state.
Greyline Instruments Inc.
Page 33
TTFM 1.0 Transit Time Flow Meter
APPENDIX A – OPTIONS
EXTRA SENSOR CABLE
(OPTION DXC)
Each Greyline flow meter includes 25 ft / 7.6m (or 50 ft / 15 m optional) continuous shielded coaxial
pair cable. Additional cable and Cable Junction Box (Option JB2X) may be ordered with the Flow
Meter, or the cable may be spliced and extended up to 250 ft (75 m) as required during installation. No
adjustment is required when the sensor cable is extended or shortened. Use only Greyline shielded
coaxial pair (RG174U) cable.
Extended sensor cable should be installed in conduit for mechanical protection. Recommended
installation with a NEMA4X junction box is illustrated below:
COAXIAL CABLE PREPARATION
DXC Transit Time sensor cable can be cut and spliced up to a maximum length of 250 ft (75 m). Cable
ends must be prepared as illustrated below.
Page 34
SENSOR INTRINSIC SAFETY
TTFM 1.0 Transit Time Flow Meter
Page 35
TTFM 1.0 Transit Time Flow Meter
ENCLOSURE HEATER AND THERMOSTAT - Option TH
Instruments can be factory-equipped with an Enclosure Heater and Thermostat or the module can be
customer-installed. The Thermostat is factory set to turn ON at 40°F (4.5°C) and OFF at 60°F (15.5°C).
Power consumption is 15 Watts.
ENCLOSURE SUNSCREEN - Option SCR
Do not mount instrument electronics in direct sunlight. Overheating will reduce the life of electronic
components and condensate may form during the heat/cool cycles and cause electrical shorts.
Page 36
TTFM 1.0 Transit Time Flow Meter
POWER INPUT OPTION
9-32VDC
TTFM 1.0 Flow Meters may be ordered factory-configured for 9-32VDC power input.
CONNECTIONS:
POWER INPUT: Connect 9-32VDC to the + and - terminals. The Power Input GND terminal must be
connected to the nearest Ground pole. A 1 amp fuse in line is recommended.
Page 37
TTFM 1.0 Transit Time Flow Meter
DATA LOGGING (Optional)
Setup
Select Data Logging from Menu Selections.
Log Site IDEnter a number from 00 to 99. The site ID will become
part of the downloaded file name to help distinguish
downloads from different instruments. Press to store the
setting.
ModeSelect Velocity (e.g. ft/sec or m/sec). Flow (e.g. USGPM or
l/sec). Press to store the setting.
Set DatePress or to scroll and select Month, Day and Year. Press
to store the setting.
Set TimePress or to select the current time in Hours, Minutes and
Seconds. Press to store the setting.
IntervalPress or to select the logging interval.
Press to store the setting.
LogStop, Start or Delete the log file.
Press or to Delete and to delete the log file.
Press or to Start and to start the logger.
Note: You MUST delete old log and start a new log AFTER having set changes
to Log Site ID, Mode and/or Interval for those changes to be applied to
the log file.
RETRIEVE LOG FILE
Plug a USB Flash Memory Drive (not supplied by Greyline) into the USB output
cable from the instrument. The instrument display will show the icon until the log
file is transferred to the memory card. The USB flash drive may be removed.
Download file names will appear in this format:
Tag is set according to the Log Site ID entered in the instrument Data Logging
menu.
Page 38
TTFM 1.0 Transit Time Flow Meter
Download letter will be A for the first download from an instrument. B for the
second, then C etc. At the letter Z a - character will appear indicating that the
maximum number of downloads for that instrument are on the USB flash drive.
Older files can be erased or moved from the flash memory drive or a new memory
drive can be used.
OPENING LOG FILES
Install Greyline Logger on your PC or laptop. Refer to the Help menu in the
program for detailed instructions.
Select File/Open/Instrument Log (.log) to open the log file from your USB flash
drive.
Page 39
SPECIFICATIONS
7.4 / 188 mm
"
LOCATION
TTFM 1.0 Transit Time Flow Meter
Flow Rate Range:±0.07 to 39 ft/sec (±0.02
6.46 / 1 64 mm"
to 12 m/sec) typical
Pipe Size:2” to 48” (50 to 1200
mm)
Accuracy:±1% of flow rate,
Repeatability and
Linearity: ±0.25%
Displays:White, backlit matrix -
displays flow rate,
totalizer, relay states,
operating mode and
calibration menu
TTFM 1.0
Open Channel
Flow Monitor
10 .94"/ 278 mm
Calibration:built-in 5-key calibrator
with English, French or
Spanish language
CONDUITENTRY
selection
Power Input:100-240VAC, 50/60Hz, 30 Watts or
Optional 9-32VDC, rated 9W (typical 4.0W with standard features)
Enclosure:watertight, dust tight NEMA4X (IP 66) polycarbonate with a clear
shatter-proof face
Environmental Conditions:Relative humidity up to 80%, -23 to 60°C ambient temperature,
maximum 5000 m altitude, pollution degree 4, Installation Category II.
Electrical Surge Protection:Sensor, 4-20mA output and AC power input
Approximate Shipping Weight:12 lbs (5.5 kg)
5.12 / 130 mm"
10 / 254 mm"
SIDEVIEW
SE16 Transit Time Sensor
Pipe Diameter:2” to 48” (50 to 1200 mm)
Operating Temperature:-40° to 300°F (-40° to 150°C)
Operating Frequency:1.28 MHz
Sensor Cable:25 ft (7.6 m) including TTJB Junction Box, BNC connectors and seal
Submersion Rating:Withstands accidental submersion pressure up to 10 psi (0.7 Bar)
jackets
Optional 50 ft (15 m) or 100 ft (30 m) including TTJB Junction Box, BNC
connectors and seal jackets
Page 40
TTFM 1.0 Transit Time Flow Meter
CONVERSION GUIDE
APPENDIX B - CONVERSION TABLE
FROMTOMULTIPLY BY
US GALLONSCUBIC FEET0.1337
US GALLONSIMPERIAL GALS0.8327
US GALLONSLITRES3.785
US GALLONSCUBIC METERS0.003785
LITRES/SECGPM15.85
LITRESCUBIC METERS0.001
BARRELSUS GALLONS42
BARRELSIMPERIAL GALS34.9726
BARRELSLITRES158.9886
INCHESMM25.4
DEGREES FDEGREES C(°F-32) x 0.556
POUNDSKILOGRAMS0.453
PSIBAR0.0676
FOOT²METER²0.0929