IMPORTANT NOTE: This instrument is manufactured and calibrated to meet product specifications.
Please read this manual carefully before installation and operation. Any unauthorized repairs or
modifications may result in a suspension of the warranty.
If this product is not used as specified by the manufacturer, protection may be impaired.
Available in Adobe Acrobat pdf format
Page 3
SFM 6.1 Slurry Flow Meter
CONNECTIONS:
POWER INPUT: The standard model requires AC power input between 100 to 240 VAC 50/60Hz. No
adjustments are necessary for voltages within this range. Connect L (Live) N (Neutral) and AC Ground.
Optional DC input model requires 9-32 VDC/9 Watts. Connect to + and - terminals.
Optional Thermostat and Heater modules are available rated for 115 VAC or 230 VAC.
IMPORTANT NOTE: To comply with electrical safety standards, AC power input and relay connection
wires must have conduit entry to the instrument enclosure. Installation requires a switch, overcurrent
fuse or circuit breaker in the building (in close proximity to the equipment) that is marked as the
disconnect switch.
Risk of electric shock. Loosen cover screw to access connections. Only qualified personnel
should access connections.
Note: Use of instrumentation over 40°C ambient requires special field wiring.
Note: User replaceable fuse is 2 Amp 250V (T2AL250V).
Page 4
CONNECTIONS
SFM 6.1 Slurry Flow Meter
Page 5
SFM 6.1 Slurry Flow Meter
KEYPAD SYSTEM
The following diagram shows the SFM 6.1 menu system. Arrows show the four directions to leave a
menu box. Pressing a corresponding keypad arrow will move to the next item in the direction shown.
Move the cursor (highlighted) under numerals and increase or decrease numerals with the and
keys.
To store calibration values permanently (even through power interruptions), press the .
Page 6
CALIBRATION MENU
SFM 6.1 Slurry Flow Meter
Page 7
ICONS
SFM 6.1 Slurry Flow Meter
Page 8
SFM 6.1 Slurry Flow Meter
MAIN DISPLAY
The main display shows the units selected from the Units/Mode menu, Flow or
Velocity rate being measured, TOTALIZER and RELAY states. The SFM 6.1
will start-up with this display.
MESSAGE ICON
Press from the main display to view status of the data logger and error/warning
messages provided by the instrument. The Message Icon will appear on the main
display if error messages are being generated by the instrument. Press to return
to the main display.
STATUS
Press from the main display to view instrument status. Velocity will be
displayed in ft/sec or m/sec.
Tot
Signal Cutoff
Signal Strength
Relays
20mA at
Displays the current totalizer reading.
Adjust the setting in percent to suppress flow
readings at zero flow when fluid swirling or pipe
vibration may cause the instrument to continue
reading. Example: Signal Cutoff at 5% will force the
display and outputs to zero when signal strength
drops below 5%.
Displays percentage of signal being received by the
ultrasonic sensor.
Energized relays will display as a white character on
a black background.
Displays the flow rate set as 20mA in the Calibration
menu. Press to return to the main display.
Page 9
SFM 6.1 Slurry Flow Meter
24 HR LOG (Data Logging option only)
Press from the main display to view a formatted flow report from instruments
with a built-in data logger. Press to scroll down one day or repeatedly to scroll
to a specific date. Up to 365 days can be stored. Newest date will overwrite the
oldest. Press to return to the main display.
PASSWORD
The password (a number from 0000 to 9999) prevents unauthorized access to the
Calibration menu.
From the main display press the key to get to Password.Factory default
password is 0000 and if it has not been changed press the to proceed to the
Menu Selections screen.
If a password is required, press to place the cursor under the first digit and or
to set the number, then to the second digit, etc. Press or to proceed to
the Menu Selections screen.
A new password can be stored by going to Special Functions/New Password.
Page 10
SFM 6.1 Slurry Flow Meter
UNITS/MODE
From Mode press the and then the or to select Flow or Velocity.
Flow mode displays the flow rate in engineering units (e.g. gpm, litres/sec, etc.)
Press the to store your selection then the to the next menu item and to
enter.
From Linear press the key and then the or to select your units of
measurement. Press the to store your selection.
Press the key to move the symbol to each subsequent menu item and the to
save your selections.
Note: the volume selection "bbl" denotes U.S. oil barrel.
Press or to return to the Menu Selections screen.
Page 11
SFM 6.1 Slurry Flow Meter
CALIBRATION
Press the to Calibration and to enter. Use or to position before
each menu item and to enter. When settings are completed press to store and
return to the Calibration menu.
20mA at
(5V Flo)
4mA at
(0V Flo)
Min Vel
Pipe ID
Damping
Pressthenorto change the numbers and decimal point.
Use this menu to set the corresponding flow rate that will be
represented by 20mA analog output. If maximum flow is
unknown, enter an estimated flow rate and observe actual flow
to determine the correct maximum value. Any velocity or flow
rate up to +40 ft/sec (12.2 m/sec) may be selected.
Pressorto set the flow rate corresponding to 4mA analog
output. This setting may be left at zero flow (or velocity or can
be raised to any value less than the 20mA setting, or lowered to
any velocity or corresponding flow rate down to -40 ft/sec
(-12.2 m/sec).
Pressand enter a minimum velocity cutoff. Forward and
reverse velocities less than Min Vel will be forced to zero.
Place the cursor under the digits and thenorto change the
numbers and decimal point. Pipe ID should be entered as the
exact inside diameter of the pipe where the sensor is mounted.
Refer to the Pipe Charts Appendix in this manual for inside
diameter of common pipe types and sizes.
Increase damping to stabilize readings under turbulent flow
conditions. Decrease for fast response to small changes in flow.
Damping is shown in percentage (maximum is 99%). Factory
default is 10%.
Press to return to Menu Selections screen.
Page 12
RELAY PARAMETERS
SFM 6.1 Slurry Flow Meter
Relay
Function
Flow
Pressandorto select a corresponding relay number (2
relays are standard, 4 additional are optional).
Pressorto select Off, Pulse or Flow.
Mode Select Pump, Low Alarm or Hi Alarm.
Pumpmode provides separate On/Off settings where the
relay will energize at one flow rate and de-energize at another.
On Position the cursor under the numerals and press or
to set digits to the required relay On set point.
Off set digits to the required Off set point.
Low Alarm mode relay will energize at a programmable flow
rate and remain energized with flow below the set point. When
flow rises above the set point, the relay will de-energize.
Hi Alarm mode relay will energize at a programmable flow
rate and remain energized with flow above the set point. When
flow falls below the set point, the relay will de-energize.
Pulse
Pressand set digits to the flow volume increment required
between relay pulses. Use this feature for remote samplers,
chlorinators or totalizers. Minimum time between pulses is
2.25 seconds and pulse duration is 350 milliseconds.
Return to Relay and change settings for each relay number.
Press to return to Menu Selections.
Page 13
DATA LOGGING (OPTIONAL)
Refer to Options section of this manual.
SPECIAL FUNCTIONS
SFM 6.1 Slurry Flow Meter
Language
Analog Out
Backlight
Reset Totalizer
Negative Totals
Select English, French or Spanish
Select 4-20mA or 0-5V mode for the analog
output.
Select High, Medium or Low for continuous
backlight.
Select Key Hi/Lo for high backlight for 1 minute
after a keypress and then Lo backlight until a key is
pressed again.
Select Key High, Med or Low for backlight
for 1 minute after a keypress and then backlight off
until a key is pressed again.
Pressand select Yes to erase and restart the
totalizer at zero.
Select Yes to have reverse flow readings
deducted from the totalizer. Select No to totalize
forward flow only and ignore reverse flow.
Flo Direction
Cal Constant
Restore Defaults
New Password
Press to return to Menu Selections.
Select On to enable flow direction measurement.
Select Off to disable flow direction
measurement. Select Invert to invert the sense of
the flow measurement.
Scales the velocity reading. Factory value is close
to 1.000 for a SE4-A sensor.
Select Yes and press to erase all user settings
and return the instrument to factory default
settings.
Select any number from 0000 to 9999 and press .
Default setting of 0000 will allow direct access to
the calibration menus. Setting of any password
greater than 0000 will require the password to be
entered to access the calibration menus.
Page 14
SFM 6.1 Slurry Flow Meter
SIMULATION
Exercises the 4-20mA (0-5V) output, digital display and control relays.
TestSelect Maximum and press to simulate maximum Flow or Velocity and
to output 20mA (5V) to the analog channel.
Select Minimum and press to simulate minimum Flow or Velocity and
to output 4mA (0V) to the analog channel.
To simulate measurements between minimum and maximum set Test to
Actual and then enter for the flow measurement. The analog output and
control relays will respond to the simulated value.
Page 15
SFM 6.1 Slurry Flow Meter
SENSOR MOUNTING LOCATION
The position of the sensor is one of the most important considerations for accurate slurry flow
measurement. The same location guidelines apply to slurry as most other types of flow meters.
Before permanently mounting a slurry sensor onsite testing is recommended to determine optimum
mounting position. Use the sensor coupling compound (supplied with each Greyline flow meter, or
petroleum gel, acoustic compound or electrocardiograph gel). Take several readings around the axis of
the pipe and then at several points upstream and downstream from the selected position, checking for
consistent readings. Avoid high or low reading areas. Mount the sensor where consistent (average)
readings were obtained or continue testing on another pipe section.
VERTICAL OR HORIZONTAL PIPE - Vertical pipe
runs generally provide evenly distributed flow. On
Horizontal pipes and liquids with high concentrations
of gas or solids, the sensor should be mounted on the
side (3 or 9 o’clock position) to avoid concentrations of
gas at the top of the pipe, or solids at the bottom. For
liquids with minimal gas bubbles (e.g. potable water)
the sensor should be mounted on the top of a horizontal
pipe (12 o’clock position) to obtain the best signal
strength.
VELOCITY INCREASING DEVICES: Generally the sensor must be mounted away from flow
disturbances such as valves, pumps, orifice plates, venturis or pipe inlets and discharges which tend to
increase flow velocity. Velocity increasing devices often cause cavitation, or rapid release of gas
bubbles, and readings both up and downstream may show much higher velocity. As a guideline, mount
the sensor at least 20 diameters upstream or 30 diameters downstream from velocity increasing devices.
Required distance from a velocity increasing device will vary in applications depending on the flow
velocity and the characteristics of the liquid itself.
TURBULENCE INCREASING DEVICES: Elbows,
flanged connections and tees tend to introduce
desirable conditions of an evenly distributed flow
profile with some air or gases entrained in the flow.
Sensor mounting 6 pipe diameters upstream and 10
diameters downstream from these disturbances is
generally optimum.
The sensor is designed to mount longitudinally on a straight section of pipe. Do not attempt to mount it
on bends, elbows or fittings.
Page 16
SFM 6.1 Slurry Flow Meter
SENSOR MOUNTING
Prepare an area 2" wide by 4" long (50mm x 100mm) for sensor bonding by removing loose paint, scale
and rust. The objective of site preparation is to eliminate any discontinuity between the sensor and the
pipe wall, which would prevent acoustical coupling.
A PC4 Sensor Mounting Kit is supplied with each Greyline flow meter. It includes recommended
coupling compound in a plastic applicator and a stainless steel mounting bracket with adjustable pipe
straps.
Page 17
SENSOR COUPLING
For permanent or temporary bonding, the following are recommended:
a)Dow Corning silicon compound #4 (supplied)
Additional supply: order Greyline Option CC
b)High Temperature compound
Additional supply: order Greyline Option AP-1W
c)Water-based sonic compound: Order Greyline Option CC30
d)Electrocardiograph gel
e)Petroleum gel (Vaseline)
The above are arranged in their order of preferred application.
d & e are only good for temporary bonding at room temperature.
DO NOT USE: Silicon RTV caulking compound (silicon rubber).
SFM 6.1 Slurry Flow Meter
Use the PC4 pipe clamp (supplied) as illustrated above or
use a loop of electrical tape for temporary mounting. Apply
silicon coupling compound #4 to the coloured face of the
sensor. A bead, similar to toothpaste on a toothbrush, is
ideal. Do not overtighten (crush the sensor).
The sensor must be fixed securely to the pipe with coupling material
between the sensor face and the pipe. Sensor installation with
excessive coupling compound can result in gaps or voids in the
coupling and cause errors or loss of signal. Insufficient coupling
compound will create similar conditions.
Over time temporary coupling compounds (e.g. Petroleum Gel) may gradually sag away from the sensor
resulting in reduced signal strength and finally complete loss of signal. Warm temperatures, moisture
and vibration will accelerate this process. Dow Corning Silicone Compound #4 as supplied with the
SFM 6.1 (and available from Greyline Instruments) is recommended for semi-permanent installations.
Page 18
SFM 6.1 Slurry Flow Meter
SENSOR MOUNTING/COUPLING RECOMMENDATIONS
Page 19
SFM 6.1 Slurry Flow Meter
ENCLOSURE INSTALLATION
Locate the enclosure within 20 ft (6 m) of the sensor (500 ft -150 m optional). The enclosure can be wall
mounted with the four mounting screws (included).
Avoid mounting the enclosure in direct sunlight to protect the electronics from damage due to
overheating and condensate. In high humidity atmospheres, or where temperatures fall below freezing,
Option TH Enclosure Heater and Thermostat is recommended. Seal conduit entries to prevent moisture
from entering enclosure.
NEMA4X STAINLESS STEEL
Insert #14 screws (supplied) through the four enclosure mounting
holes to secure the enclosure to the wall or mounting stand.
Additional conduit holes can be cut in the bottom of the enclosure
when required. Use a carbide tipped hole cutter to cut the required
holes.
DO NOT make conduit/wiring entries into the top of the enclosure.
Note: Grounding must be provided as part of the installation. Ground
in accordance with the requirements of the National Electrical Code.
System grounding is provided by connecting grounding wires from
all conduit entries to the steel mounting plate or another point which
provides continuity.
CLEANING
Cleaning is not required as a part of normal maintenance.
Page 20
FUSE REPLACEMENT
1. Turn OFF power.
2. Loosen cover screw and open.
3. Remove power module.
4. Locate fuse on Power Board.
5. Replace fuse with 2 AMP/ 250V, 5 x 20mm fuse.
6. Reinstall power module into chassis.
SFM 6.1 Slurry Flow Meter
Page 21
FIELD TROUBLESHOOTING
SFM 6.1 Slurry Flow Meter
Possible Causes:
METER READING LOWER THAN EXPECTED
Calibration Error
Lower flow rate than expected
Signal not penetrating far enough into the flow stream
Improper mounting of sensor
Pipe is not full
METER READING WHEN THERE IS NO FLOW
Corrective Action:
Review UNITS/MODE menu and Pipe ID
Investigate pump/valves. Compare velocity
with alternate instrument
Relocate sensor closer to elbows or flow
disturbances
Reinstall Sensor with careful application of
Coupling Compound
Remount Sensor on vertical pipe
Vibration on pipe
Local electrical noise
Cross talk between two or more SFM 6.1 flowmeters
on same pipe
Variable Speed Drive interference
Sensor cable connections incorrect or loose
Adjust Status / Signal Cutoff setting
Install in another location
Ensure all Flowmeter wiring is in METAL
conduit and sensor shield is properly grounded.
Ensure correct power input Ground connection
(<1 ohm resistance).
Ensure 4-20mA Shield connected to Instrument
Ground stud.
Refer to Synchronization instructions
Follow Drive manufacturers wiring and
Grounding instructions
Relocate Flowmeter electronics, Sensor and
wiring away from VSD
Refer to Connections diagram. Disconnect and
reconnect sensor cables ensuring that cable is
properly inserted into terminals and tightened.
Page 22
SFM 6.1 Slurry Flow Meter
Possible Causes:
METER READING ERRATIC
Sensor mounted too close to valve, pump or elbow
NO FLOW INDICATION
Not enough suspended particles or gases in the fluid
Coupling compound washed out, or sensor loose on
pipe
Power interruption. No flow.
Corrective Action:
Change sensor placement. Recommended 6-10
diameters from elbows, and 30 diameters from
pumps, controlling valves, orifice plates,
nozzles or open pipe discharge
Relocate sensor in more turbulent pipe section.
Mount sensor at 12 o'clock position on
horizontal pipe
Relocate sensor >30 pipe diameters from
velocity increasing device
Ensure all Flowmeter wiring is in METAL
conduit and sensor cable shield is connected to
Ground stud
Follow Drive manufacturers wiring and
Grounding instructions
Relocate Flowmeter electronics, Sensor and
wiring away from VSD
Page 23
SFM 6.1 Slurry Flow Meter
Possible Causes:
METER READING DOES NOT TRACK FLOW
Sensor and GND wires reversed or not properly
connected
Improper AC power input Ground
Corrective Action:
Check Sensor connections
Use direct connection with 12 AWG wire to
nearest Ground pole (<1 ohm resistance).
SENSOR CABLE RESISTANCE TEST
Unplug the green sensor terminal from the slurry board and connect the sensor wires as shown. With a
multimeter, perform resistance checks for each set of wires. One single loose terminal may cause false
readings.
Test across shield and core of each wire: TMTR (black/white) and RCVR (black). Resistance should be
around 82.5K ohms for any cable length. High readings indicate an open circuit and low readings
indicate a short or partial short in the sensor cable.
Page 24
SFM 6.1 Slurry Flow Meter
COMMON QUESTIONS AND ANSWERS
The pipe vibrates. Will it affect the flow meter?
Common vibration frequencies are far lower than the sonic frequencies used by the Greyline flow meter,
and will not normally affect accuracy or performance. However, applications where very weak
ultrasonic signal is present (when sensitivity is adjusted to maximum and signal strength is low),
accuracy may be affected by pipe vibration, or the flow meter may show readings under no-flow
conditions. Attempt to relocate the sensor on a pipe section where vibration is reduced, or arrange pipe
mounting brackets to reduce vibration at the sensor mounting location.
The flow meter must be installed in a high noise environment. Will this affect operation?
Greyline flow meters are designed to discriminate between environmental noise and the ultrasonic
signal. High noise environments may affect the flow meter’s performance where low signal strength
and/or low flow velocities are being measured. Relocate the sensor in a more quiet environment if
possible.
Will pipe corrosion affect accuracy of the flow meter?
Yes. Rust, loose paint etc. must be removed from the outside of the pipe to provide a clean mounting
position when installing a slurry sensor. Severe corrosion/oxidation on the inside of the pipe may
prevent the ultrasonic signal from penetrating into the flow. If the pipe cannot be cleaned, a spool piece
(PVC recommended) should be installed for sensor mounting.
What effect do pipe liners have on the flow meter?
The air gap between loose insertion liners and the pipe wall prevent the ultrasonic signal from entering
the flow. Better results can be expected with bonded liners such as cement, epoxy or tar, however an on
site test is recommended to determine if the application is suitable for a slurry flow meter.
Why is Doppler ultrasonic only recommended for liquids containing suspended solids or gases?
The slurry sensor transmits sound into the flow stream which must be reflected back to the sensor to
indicate flow velocity. Gas bubbles or suspended solids act as reflectors for the ultrasonic signal. As a
guideline, Greyline slurry flow meters are recommended for liquids containing solids or bubbles with a
minimum size of 100 microns and a minimum concentration of 75 ppm. Most applications (except
potable, distilled or deionized water) will meet this minimum requirement.
Can the sensor be submerged in water?
Yes, for short periods of time or by accident, but it is not recommended for continuous operation. The
sensor is constructed to withstand submersion to 10 psi without damage, but external liquid moving in
contact with the sensor can be interpreted as flow and cause false readings.
What is the purpose of the Signal Strength Display?
Ultrasonic signals of very low strength are not accepted or processed by the instrument. This feature
assists in rejection of environmental noise and vibration. Use the display to evaluate signal strength in
your application. Strong signals will increase in percentage to a maximum of 100% or greater.
Page 25
SFM 6.1 Slurry Flow Meter
Can I change the length of the sensor cable?
Yes. Technological advances in Greyline ultrasonic design allow cable lengths up to 500 ft (152 m) with
no loss of signal strength. Extended cable (Greyline Option DXC) should be installed in rigid or flexible
conduit for mechanical protection. Use only Greyline shielded coaxial pair (RG174U) cable. Cable
junctions should be made through a terminal block and housed in a watertight metal junction box
(Greyline Option DJB). BNC coaxial connectors (TV cable type) are not recommended for cable splices.
Does the SFM 6.1 require periodic recalibration?
SFM 6.1 calibration does not drift over time. The solid state sensor has no moving parts to wear and
affect calibration. The ultrasonic flow technique generates an ultrasonic signal proportional to the
velocity of flow. All Greyline timing/counting circuits use crystal-controlled frequency references to
eliminate any drift in the processing circuitry.
ISO 9000 or similar quality management systems may require periodic and verifiable recalibration of
flow meters. SFM 6.1 Slurry Flow Meters may be returned to Greyline for factory calibration and issue
of a new NIST traceable certificate. Refer to the ‘Product Return Procedure’ section of this manual for
return instructions.
Page 26
SFM 6.1 Slurry Flow Meter
APPLICATIONS HOTLINE
For applications assistance, advice or information on any Greyline Instrument contact your Sales Representative,
write to Greyline or phone the Applications Hotline below:
United States:Tel: 315-788-9500Fax: 315-764-0419
Canada:Tel: 613-938-8956Fax: 613-938-4857
Toll Free:888-473-9546
Email:info@greyline.com
Web Site:www.greyline.com
Greyline Instruments Inc.
CanadaUSA:
16456 Sixsmith Drive11451 Belcher Road South
Long Sault, Ont. K0C 1P0Largo, FL 33773
PRODUCT RETURN PROCEDURE
Instruments may be returned to Greyline for service or warranty repair.
1Obtain an RMA Number from Greyline -
Before shipping a product to the factory please contact Greyline by telephone, fax or email to obtain an
RMA number (Returned Merchandise Authorization). This ensures fast service and correct billing or
credit.
When you contact Greyline please have the following information available:
1.Model number / Software Version
2.Serial number
3.Date of Purchase
4.Reason for return (description of fault or modification required)
5.Your name, company name, address and phone number
2Clean the Sensor/Product -
Important: unclean products will not be serviced and will be returned to the sender at their expense.
1. Rinse sensor and cable to remove debris.
2. If the sensor has been exposed to sewage, immerse both sensor and cable in a solution of 1 part
household bleach (Javex, Clorox etc.) to 20 parts water for 5 minutes. Important: do not immerse
open end of sensor cable.
3. Dry with paper towels and pack sensor and cable in a sealed plastic bag.
4. Wipe the outside of the enclosure to remove dirt or deposits.
5. Return to Greyline for service.
Page 27
FLOW METER DATA SHEET
SFM 6.1 Slurry Flow Meter
Page 28
SFM 6.1 Slurry Flow Meter
LIMITED WARRANTY
_____________________________________
Greyline Instruments warrants, to the original purchaser, its
products to be free from defects in material and workmanship for a
period of one year from date of invoice. Greyline will replace or
repair, free of charge, any Greyline product if it has been proven to
be defective within the warranty period. This warranty does not
cover any expenses incurred in the removal and re-installation of
the product.
If a product manufactured by Greyline should prove defective
within the first year, return it freight prepaid to Greyline
Instruments along with a copy of your invoice.
This warranty does not cover damages due to improper installation
or handling, acts of nature, or unauthorized service. Modifications
to or tampering with any part shall void this warranty. This
warranty does not cover any equipment used in connection with the
product or consequential damages due to a defect in the product.
All implied warranties are limited to the duration of this warranty.
This is the complete warranty by Greyline and no other warranty is
valid against Greyline. Some states do not allow limitations on how
long an implied warranty lasts or limitation of incidental or
consequential damages, so the above limitations or exclusions may
not apply to you.
This warranty gives you specific legal rights, and you may also
have other rights which vary from state to state.
Greyline Instruments Inc.
Page 29
SFM 6.1 Slurry Flow Meter
APPENDIX A – OPTIONS
EXTRA SENSOR CABLE
(OPTION DXC)
Each Greyline flow meter includes 20 ft / 6m (or 50 ft / 15 m optional) continuous shielded coaxial pair
cable. Additional cable and Cable Junction Box (Option JB2X) may be ordered with the Flow Meter, or
the cable may be spliced and extended up to 500 ft (152m) as required during installation. No
adjustment is required when the sensor cable is extended or shortened. Use only Greyline shielded
coaxial pair (RG174U) cable.
Extended sensor cable should be installed in conduit for mechanical protection. Recommended
installation is illustrated below:
COAXIAL CABLE PREPARATION
DXC ultrasonic sensor cable can be cut and spliced up to a maximum length of 500 ft (152 m). Cable
ends must be prepared as illustrated below.
Page 30
SFM 6.1 Slurry Flow Meter
QZ02L-B VELOCITY SENSOR
38.1mm
MB-QZ- MOUNTINGBRACKET
SENSOR CABLE JUNCTION BOX
(OPTION JB2X)
Optional Watertight steel NEMA4 Junction Boxes with terminal strips are available from Greyline
Instruments.
Sensor Cable:25 ft. (7.6 m) submersible polyurethane jacket, shielded, 3 coaxial
Hazardous Rating:CSA rated Intrinsically Safe Class I, Groups C,D, Class II, Groups E,F,G
1.62"
41.2 mm
3.00"
76.2 mm
0.56"
4.2 mm
with optional Intrinsic Safety Barrier
25 ft (7.6 m)
Sensor Cable
SIDE VIEW
5.00”
127mm
1.50"
0.63"
0.50"
12.7mm
16 mm
Page 31
SFM 6.1 Slurry Flow Meter
ENCLOSURE HEATER AND THERMOSTAT - Option TH
Instruments can be factory-equipped with an Enclosure Heater and Thermostat or the module can be
customer-installed. The Thermostat is factory set to turn ON at 40°F (4.5°C) and OFF at 60°F (15.5°C).
Power consumption is 15 Watts.
Page 32
SFM 6.1 Slurry Flow Meter
POWER INPUT OPTION
9-32VDC
SFM 6.1 Flow Meters may be ordered factory-configured for 9-32VDC power input.
QUICK BENCH TEST:
Connect Sensor as shown below, then Power. Test operation of the SFM 6.1 by holding the sensor in
one hand and rubbing your thumb or fingers briskly across the face (plastic surface) of the sensor.
Allow 15 seconds for the SFM 6.1 to process the signal and display a flow value.
CONNECTIONS:
POWER INPUT: Connect 9-32VDC to the + and - terminals. The Power Input GND terminal must be
connected to the nearest Ground pole. A 1 amp fuse in line is recommended.
Page 33
SFM 6.1 Slurry Flow Meter
Note:
DATA LOGGING (Optional)
Setup
Select Data Logging from Menu Selections.
Log Site IDEnter a number from 00 to 99. The site ID will become part
of the downloaded file name to help distinguish downloads
from different instruments. Press to store the setting.
ModeSelect Velocity (e.g. ft/sec or m/sec). Flow (e.g. USGPM or
l/sec). Press to store the setting.
Set DatePress or to scroll and select Month, Day and Year.
Press to store the setting.
Set TimePress or to select the current time in Hours, Minutes and
Seconds. Press to store the setting.
IntervalPress or to select the logging interval.
Press to store the setting.
LogStop, Start or Delete the log file.
Press or to Delete and to delete the log file.
Press or to Start and to start the logger.
You MUST delete old log and start a new log AFTER having set
changes to Log Site ID, Mode and/or Interval for those changes to be
applied to the log file.
RETRIEVE LOG FILE
Plug a USB Flash Memory Drive (not supplied by Greyline) into the USB output
cable from the instrument. The instrument display will show the USB file
download icon until the log file is transferred to the memory card and then display
file download completed icon. The USB flash drive may be removed.
Download file names will appear in this format:
Tag is set according to the Log Site ID entered in the instrument Data Logging
menu.
Page 34
SFM 6.1 Slurry Flow Meter
Download letter will be A for the first download from an instrument. B for the
second, then C etc. At the letter Z a - character will appear indicating that the
maximum number of downloads for that instrument are on the USB flash drive.
Older files can be erased or moved from the flash memory drive or a new memory
drive can be used.
OPENING LOG FILES
Install Greyline Logger on your PC or laptop. Refer to the Help menu in the
program for detailed instructions.
Select File/Open/Instrument Log (.log) to open the log file from your USB flash
drive.
Page 35
SPECIFICATIONS
Flow Rate Range:-40 to -0.25 ft/sec, +0.25
to +40 ft/sec (-12.2 to -
0.076 m/sec, +0.076 to
+12.2 m/sec,) in most
applications
Pipe Size:Any pipe ID from ½ " to
180" (12.7 mm to 4.5 m)
Accuracy:±2% of full scale.
Requires solids or
bubbles minimum size of
100 microns, minimum
concentration 75 ppm.
Repeatability: ±0.1%,
Linearity ±0.5% of full
scale
Displays:White, backlit matrix -
displays flow rate, totalizer, relay states, operating mode and calibration
menu
Calibration:built-in 5-key calibrator with English, French or Spanish language
selection
Power Input:100-240VAC, 50/60Hz, 30 Watts or
Optional 9-32VDC, rated 9W (typical 3.7W with standard features)