Greyline Instruments PZ34 Specifications

Data Sheet
SENSOR MOUNTING
Ultrasonic Sensor Model PZ34
~ 4.75" (120 mm) OVERALL
3.5”
89 mm
25 ft (7.6 m) RG62AU COAXIAL CABLE (50 ft 15 m OPTIONAL)
3/4“ NPT
3/4" NPT
3.95”
100 mm
ISOLATION COUPLING (SUPPLIED)
General Specifications
Maximum Range:
Minimum Range (Deadband):
Operating Frequency:
Maximum Operating Pressure:
Exposed Materials:
Sensor Mounting:
Maximum Cable Length:
Optional Hazardous Rating:
Notes:
1.7”
43.2 mm
1. Shield from direct sunlight (temperature probe in sensor)
2. Use the "Isolation Coupling" supplied for mounting.
3. Use with Option ISB Intrinsic Safety Barrier for installation in hazardous locations.
4. Run Sensor cable in grounded metal conduit with no other conductors.
5. Extend Sensor cable up to 500 ft (152 m) with RG62AU coaxial only.
6. Refer to the Instruction Manual for complete installation and wiring instructions.
Beam Angle:
32 ft. (10 m) 16" (406.4 mm) 46 KHz 8°
-40° to 150° F (-40° to 65° C) 20 psi (1.35 bar) PVC 3/4" NPT 500 ft (150 m) CSA rated Intrinsically Safe Class I, Groups C,D, Class II, Groups E,F,G with optional Intrinsic Safety Barrier. Note: Max Range reduced to 25 ft. (7.8 m) with ISB option.
1 FT (300 mm) HORIZONTAL FROM SIDEWALL FOR EVERY
10 FT (3 m) VERTICAL
:
NOTE 2 FT (600 mm) FOR EVERY 10 FT (6 m) DEPTH IN APPLICATIONS WITH ROUGH SIDEWALLS, LADDERS, REINFORCING RINGS ETC.
Recommended Sensor Mounting
PREFERRED SENSOR
LOCATION
SENSOR FACE MUST BE HORIZONTAL ±1°
MAX. LIQUID LEVEL
6" SCHEDULE 40 PIPE IF EXTENSION REQUIRED