IMPORTANT NOTE: This instrument is manufactured and calibrated to meet product specifications.
Please read this manual carefully before installation and operation. Any unauthorized repairs or
modifications may result in a suspension of the warranty.
If this product is not used as specified by the manufacturer, protection may be impaired.
Available in Adobe Acrobat pdf format
Page 3
DFM 5.0 Doppler Flow Meter
CONNECTIONS:
POWER INPUT: The standard model requires AC power input between 100 to 240 VAC 50/60Hz . No
adjustments are necessary for voltages within this range.
Optional DC input model requires 9-32 VDC/7 Watts. Connect to + and − terminals. Connect L (Live)
N (Neutral) and AC Ground.
Optional Thermostat and Heater modules are available rated for 115 VAC or 230 VAC.
IMPORTANT NOTE: To comply with CSA/UL electrical safety standards, AC power input and relay
connection wires must have conduit entry to the instrument enclosure. Installation requires a switch,
overcurrent fuse or circuit breaker in the building (in close proximity to the equipment) that is marked
as the disconnect switch.
Risk of electric shock. Loosen cover screw to access connections. Only qualified personnel
!
should access connections.
Note: Use of instrumentation over 40°C ambient requires special field wiring.
Note: User replaceable fuse is 2 Amp 250V (T2AL250V).
Page 4
CONNECTIONS
DFM 5.0 Doppler Flow Meter
–+
SYNC
GND
GND
TMTR
RCVR
4-20mA (1)
RLY2
RLY1
–
+
NO
C
NC
NO
C
NC
EXTRA RELAYS OPTION
NC
RLY3
AC
LN
AC
GROUND
NC
C
L
N
C
NO
POWER
INPUT
NO
RLY4
HEATER OPTION
NC
C
NO
RLY5
RLY6
TRANSDUCER
NC
C
NO
GND
Page 5
DFM 5.0 Doppler Flow Meter
KEYPAD SYSTEM
The following diagram shows the DFM 5.0 menu system. Arrows show the four directions to leave a
menu box. Pressing a corresponding keypad arrow will move to the next item in the direction shown.
Move the cursor (underline) under numerals and increase or decrease numerals with the Ç and Èkeys.
To store calibration values permanently (even through power interruptions), press the ü.
Page 6
CALIBRATION MENU
DFM 5.0 Doppler Flow Meter
Linearin
VolumeUSG
Timemin
--Units/Mode--------
>ModeFlow
--Calibration-------
4mA at0.000 USG/m
Pipe ID12.00in
>20mA at 2500.0 USG/m
Damping20%
FunctionFlow
ModePump
On1000 USG
--Relay Parameters--
Off0.000 USG
>Relay1
ModeFlow
Set Date Feb 18/2007
Set Time11:27:40
Interval10sec
Reset LogNO
--Data Logging-------
>Log Site ID0
Calibration
Relay Parameters
Data Logging
>Units / Mode
Password0000
Special Functions
--Menu Selections----
--Password----------
--Special Functions-
Simulation
Configuration
BacklightOn High
Reset TotalizerNO
Negative TotalsNO
>LanguageEnglish
Reverse FlowNO
Cal Constant1.000
Restore Defaults NO
4-20mA5.60mA
New Password0000
Relays 1 23456
--Simulation--------
>Output250USG
Doppler1.02
Logger1.03T
Relays2
>Utility Board1.01
4-20 Outputs1
--Configuration-----
Data logLogging
Log Use0%
--Message-----------
SensorGood
USG/min
0.000
Total0.000ft/s
Average0.000ft/s
Maximum0.000ft/s
Max Time01:57:00
>DateFeb. 12/2008
Minimum-1.046ft/s
--24 hr log----------
Page 7
Tot20130.8 USG
Relays123456
Min Time02:35:00
Tot0.000USG
Signal Cutoff5%
Signal Strength0%
Sig Confidence0
Relays123456
--Status------------
>Velocity0.00ft/s
20mA at
OPTIONAL FEATURES
DFM 5.0 Doppler Flow Meter
USG/min
0.000
Tot20130.8 USG
Relays123456
--Message----------Data logLogging
Log Use0%
SensorGood
--Status------------
>Velocity0.00ft/s
Tot0.000USG
Signal Cutoff5%
Signal Strength0%
Sig Confidence0
Relays123456
20mA at
RUN
The main display shows the units selected from the Units/Mode menu,
Flow or Velocity rate being measured, TOTALIZER and RELAY states.
The DFM 5.0 will start-up with this display and will return to this screen
after a timeout if keys are not pressed in other menus.
MESSAGE
Press Ç from the RUN display to view status of the data logger and
error/warning messages provided by the instrument. The word Message
will appear on the RUN display if error messages are being generated by
the instrument. Refer to the manual section Error/Warning Messages for a
description. Press ü to return to the main display.
STATUS
Press È from the RUN display to view instrument status. Velocity will be
displayed in ft/sec or m/sec.
Tot Displays the current totalizer reading.
Signal Cutoff Adjust the setting in percent to suppress flow readings
at zero flow when fluid swirling or pipe vibration may cause the
instrument to continue reading. Example: Signal Cutoff at 5% will force
the display and outputs to zero when signal strength drops below 5%.
Signal Strength Displays percentage of signal being received by the
ultrasonic sensor.
Sig Confidence This indicates consistent or widely varying flow rates
and helps gauge the quality of the velocity signal in the application.
Relays Energized relays will display as a white character on a black
background.
20mA at Displays the flow rate set as 20mA in the Calibration menu.
Press ü to return to the main display.
Page 8
DFM 5.0 Doppler Flow Meter
--24 hr log----------
>DateFeb. 12/2008
Total0.000ft/s
Average0.000ft/s
Maximum0.000ft/s
Max Time01:57:00
Minimum-1.046ft/s
Min Time02:35:00
--Password----------
Password0000
24 HR LOG (Data Logging option only)
Press Å from the RUN display to view a formatted flow report from
instruments with a built-in data logger. Press È to scroll down one day or
repeatedly to scroll to a specific date. Up to 365 days can be stored.
Newest date will overwrite the oldest. Press ü to return to the main
display.
PASSWORD
The password (a number from 0000 to 9999) prevents unauthorized access
to the Calibration menu.
From the Run display press the Æ key to get to
Password. Factory
default password is 0000 and if it has not been changed press the ü to
proceed to the Menu Selections screen.
If a password is required, press Æ to place the cursor under the first digit
and È or Ç to set the number, then Æ to the second digit, etc. Press Æ or
ü to proceed to the Menu Selections screen.
A new password can be stored by going to
Password
.
Special Functions/New
Page 9
DFM 5.0 Doppler Flow Meter
--Units/Mode--------
>ModeFlow
Linearin
VolumeUSG
Timemin
--Units/Mode-------ModeFlow
>Lineari
--Units/Mode--------
>VolumeUS
ft
mm
ft3
bbl
m3
IMG
IG
USMG
UNITS/MODE
>Mode press the Æ and then the Ç or È to select Flow or
From
Velocity. Flow mode displays the flow rate in engineering units (e.g.
gpm, litres/sec, etc.) Press the ü to store your selection then the È to the
next menu item and Æ to enter.
>Linear press the Æ key and then the Ç or È to select your units
From
of measurement. Press the ü to store your selection.
n
m
Press the È key to move the
> symbol to each subsequent menu item and
the ü to save your selections.
Note: the volume selection "bbl" denotes U.S. oil barrel.
Press Å or ü to return to the Menu Selections screen.
G
L
--Units/Mode-------ModeFlow
Linearin
VolumeUSG
>Timese
day
hr
min
c
Page 10
DFM 5.0 Doppler Flow Meter
--Calibration-------
>20mA at 2500.0 USG/m
4mA at0.000 USG/m
Pipe ID12.00in
Damping20%
CALIBRATION
Press the È to
> before each menu item and Æ to enter. When settings are completed
>Calibration and Æ to enter. Use È or Ç to position
press ü to store and return to the Calibration menu
20mA at Press Æ then È or Ç to change the numbers and decimal point.
Use this menu to set the corresponding flow rate that will be represented
by 20mA analog output. If maximum flow is unknown, enter an estimated
flow rate and observe actual flow to determine the correct maximum
value. Any velocity or flow rate up to +40 ft/sec (12.2 m/sec) may be
selected.
4mA at Press È or Ç to set the flow rate corresponding to 4mA analog
output. This setting may be left at zero flow (or velocity or can be raised
to any value less than the 20mA setting, or lowered to any velocity or
corresponding flow rate down to -40 ft/sec (-12.2 m/sec).
Pipe ID Place the cursor under the digits and then È or Ç to change the
numbers and decimal point.
Pipe ID should be entered as the exact
inside diameter of the pipe where the sensor is mounted. Refer to the Pipe
Charts Appendix in this manual for inside diameter of common pipe types
and sizes.
Damping - Increase damping to stabilize readings under turbulent flow
conditions. Decrease for fast response to small changes in flow.
Damping
is shown in percentage (maximum is 99%). Factory default is 20%.
Press ü from the Units/Mode display to return to Menu Selections.
Page 11
DFM 5.0 Doppler Flow Meter
--Relay Parameters--
>Relay1
FunctionFlow
ModePump
On1000 USG
Off0.000 USG
RELAY PARAMETERS
Relay
Press Æ and È or Ç to select a corresponding relay
number (2 relays are standard, 4 additional are optional).
Function
FlowMode Select Pump, Low Alarm or Hi Alarm.
Press È or Ç to select Off, Pulse or Flow.
Pump mode provides separate On/Off settings where the
relay will energize at one flow rate and de-energize at
another.
On Position the cursor under the numerals and press È or
Ç to set digits to the required relay
Off set digits to the required Off set point.
Low Alarm mode relay will energize at a programmable
On set point.
flow rate and remain energized with flow below the set
point. When flow rises above the set point, the relay will
de-energize.
Pulse
Hi Alarm mode relay will energize at a programmable
flow rate and remain energized with flow above the set
point. When flow falls below the set point, the relay will
de-energize.
Press È and set digits to the flow volume increment
required between relay pulses. Use this feature for remote
samplers, chlorinators or totalizers. Minimum time
between pulses is 2.25 seconds and pulse duration is 350
milliseconds.
Return to
Relay and change settings for each relay
number.
Press ü to return to
Menu Selections.
Page 12
DATA LOGGING (OPTIONAL)
Refer to Options section of this manual.
DFM 5.0 Doppler Flow Meter
--Special Functions-
>LanguageEnglish
BacklightOn High
Reset TotalizerNO
Negative TotalsNO
Reverse FlowNO
Cal Constant1.000
Restore DefaultsNO
New Password0000
--Special FunctionsLanguageEnglish
>BacklightOn Hig
On Med
On Low
Key Hi/Lo
Key High
Key Med
Key Lo
Off
SPECIAL FUNCTIONS
Language Select English, French or Spanish
Backlight
Select On High, Medium or Low for continuous
backlight.
Select Key
Lo backlight until a key is pressed again.
then
h
Select Key High, Med or Low for backlight for 1 minute after a keypress
Hi/Lo for high backlight for 1 minute after a keypress and
and then backlight off until a key is pressed again.
Reset Totalizer Press Æ and select Yes to erase and restart the
totalizer at zero.
Negative Totals Select Yes to have reverse flow readings deducted
from the totalizer. Select
No to totalize forward flow only and ignore
reverse flow.
Reverse Flow Select Yes to change the display from positive or
negative values (e.g. sensor mounted in a direction that shows normal flow
as negative values. Use
Reverse Flow to change readings to positive
values.)
Cal Constant Set to 1.000 for SE4-A transducer. (Note: Different
transducer models require specific Cal Constants.)
Restore Defaults Select Yes and press ü to erase all user settings
and return the instrument to factory default settings.
New Password Select any number from 0000 to 9999 and press ü.
Default setting of 0000 will allow direct access to the calibration menus.
Setting of any password greater than 0000 will require the password to be
entered to access the calibration menus.
Press ü to return to
Menu Selections.
Page 13
DFM 5.0 Doppler Flow Meter
--Simulation------->Output250USG
4-20mA5.60mA
Relays 1 23456
SIMULATION
Exercises the 4-20mA output, digital display and control relays (does not
affect the totalizer or optional data logger).
Output Press Æ and then È or Ç to change the simulated output. Press
ü to begin simulation. The 4-20mA output and relay states will be
displayed on the screen below.
Press the ü to terminate simulation and return to the Menu
Selections
screen.
Page 14
DFM 5.0 Doppler Flow Meter
SENSOR MOUNTING LOCATION
The position of the sensor is one of the most important considerations for accurate Doppler flow
measurement. The same location guidelines apply to Doppler as most other types of flow meters.
Before permanently mounting a Doppler sensor onsite testing is recommended to determine optimum
mounting position. Use the sensor coupling compound (supplied with each Greyline flow meter, or
petroleum gel, acoustic compound or electrocardiograph gel). Take several readings around the axis of
the pipe and then at several points upstream and downstream from the selected position, checking for
consistent readings. Avoid high or low reading areas. Mount the sensor where consistent (average)
readings were obtained or continue testing on another pipe section.
12 O'CLOCK POSITION WITH
VERTICAL OR HORIZONTAL PIPE - Vertical pipe
LOW GAS CONTENT
runs generally provide evenly distributed flow. On
Horizontal pipes and liquids with high concentrations
of gas or solids, the sensor should be mounted on the
side (3 or 9 o’clock position) to avoid concentrations
3 O'CLOCK POSITION WITH HIGH
GAS OR SOLIDS CONTENT
of gas at the top of the pipe, or solids at the bottom.
For liquids with minimal gas bubbles (e.g. potable
water) the sensor should be mounted on the top of a
HAS EVENLY DISTRIBUTED FLOW
VERTICAL PIPE USUALLY
horizontal pipe (12 o’clock position) to obtain the best
signal strength.
VELOCITY INCREASING DEVICES: Generally the sensor must be mounted away from flow
disturbances such as valves, pumps, orifice plates, venturis or pipe inlets and discharges which tend to
increase flow velocity. Velocity increasing devices often cause cavitation, or rapid release of gas
bubbles, and readings both up and downstream may show much higher velocity. As a guideline, mount
the sensor at least 20 diameters upstream or 30 diameters downstream from velocity increasing devices.
Required distance from a velocity increasing device will vary in applications depending on the flow
velocity and the characteristics of the liquid itself.
TURBULENCE INCREASING DEVICES: Elbows,
SENSOR MOUNTS 6 DIAMETERS
UPSTREAM OR 10 DOWNSTREAM
FROM AN ELBOW
flanged connections and tees tend to introduce
desirable conditions of an evenly distributed flow
profile with some air or gases entrained in the flow.
Sensor mounting 6 pipe diameters upstream and 10
FLOW
diameters downstream from these disturbances is
generally optimum.
The sensor is designed to mount longitudinally on a straight section of pipe. Do not attempt to mount it
on bends, elbows or fittings.
Page 15
DFM 5.0 Doppler Flow Meter
SENSOR MOUNTING
Prepare an area 2" wide by 4" long (50mm x 100mm) for sensor bonding by removing loose paint, scale
and rust. The objective of site preparation is to eliminate any discontinuity between the sensor and the
pipe wall, which would prevent acoustical coupling.
A PC4 Sensor Mounting Kit is supplied with each Greyline flow meter. It includes recommended
coupling compound in a plastic applicator and a stainless steel mounting bracket with adjustable pipe
straps.
SENSOR
PIPE
END VIEW
PIPE
Mount the PC4 pipe clamp as illustrated on pipes
0.6" / 15 mm OD or larger. Stainless steel bands are
included for mounting on pipes up to 32" / 81 cm OD.
Additional stainless steel bands (by customer) may be
combined to mount on pipes up to 180" / 4.5 m OD.
SENSOR
ADJUSTABLE
STAINLESS
STEEL STRAP
PIPE
PIPE
Page 16
SENSOR COUPLING
For permanent or temporary bonding, the following are recommended:
a)Dow Corning silicon compound #4 (supplied)
Additional supply: order Greyline Option CC
b)High Temperature compound (supplied with Sensor Option SE3H)
Additional supply: order Greyline Option AP-1W
c)Water-based sonic compound: Order Greyline Option CC30
d)Electrocardiograph gel
e)Petroleum gel (Vaseline)
The above are arranged in their order of preferred application.
d & e are only good for temporary bonding at room temperature.
DO NOT USE: Silicon RTV caulking compound (silicon rubber).
DFM 5.0 Doppler Flow Meter
Use the PC4 pipe clamp (supplied) as illustrated above or
COMPOUND
use a loop of electrical tape for temporary mounting.
Apply silicon coupling compound #4 to the coloured face
of the sensor. A bead, similar to toothpaste on a
toothbrush, is ideal. Do not overtighten (crush the
SENSOR
The sensor must be fixed securely to the pipe with coupling material
sensor).
COMPOUND
between the sensor face and the pipe. Sensor installation with
excessive coupling compound can result in gaps or voids in the
coupling and cause errors or loss of signal. Insufficient coupling
SENSOR
PIPE
compound will create similar conditions.
TAPE OR
Over time temporary coupling compounds (e.g. Petroleum Gel) may
CLAMP
gradually sag away from the sensor resulting in reduced signal
strength and finally complete loss of signal. Warm temperatures, moisture and vibration will accelerate
this process. Dow Corning Silicone Compound #4 as supplied with the DFM 5.0 (and available from
Greyline Instruments) is recommended for semi-permanent installations.
Page 17
DFM 5.0 Doppler Flow Meter
OO
SENSOR MOUNTING/COUPLING RECOMMENDATIONS
BAD
G
D
Page 18
DFM 5.0 Doppler Flow Meter
ENCLOSURE INSTALLATION
Locate the enclosure within 20 ft (6 m) of the sensor (500 ft -150 m optional). The enclosure can be wall
mounted with the four mounting screws (included) or panel mounted with Option PM Panel Mount kit
from Greyline Instruments.
Avoid mounting the enclosure in direct sunlight to protect the electronics from damage due to
overheating and condensate. In high humidity atmospheres, or where temperatures fall below freezing,
Option TH Enclosure Heater and Thermostat is recommended. Seal conduit entries to prevent moisture
from entering enclosure.
NEMA4X (IP66) WITH CLEAR COVER
1. Open hinged enclosure cover.
COVER
2. Insert #8 screws (supplied) through the four enclosure mounting holes
to secure the enclosure to the wall or mounting stand.
Additional conduit holes can be cut in the bottom of the enclosure when
ENCLOSURE
MOUNTING
HOLES
required. Use a hole saw or Greenlee-type hole cutter to cut the required
holes.
ENCLOSURE
DO NOT make conduit/wiring entries into the top of the enclosure.
END VIEW
Note: This non-metallic enclosure does not automatically provide grounding between conduit
connections. Grounding must be provided as part of the installation. Ground in accordance with the
requirements of the National Electrical Code. System grounding is provided by connecting grounding
wires from all conduit entries to the steel mounting plate or another point which provides continuity.
CLEANING
Cleaning is not required as a part of normal maintenance.
Page 19
DFM 5.0 Doppler Flow Meter
SYNCHRONIZATION
Synchronization may be required to prevent interference (readings with no flow or "cross talk") in
applications where more than one DFM 5.0 Doppler sensor is used in close proximity. Synchronize
DFM 5.0 flow meters only if sensors from separate DFM 5.0 flow meters are mounted on the same pipe.
To synchronize one or more DFM 5.0 flow meters use twisted, shielded pair cable, 22AWG or heavier.
Connect SYNC + of one DFM 5.0 to the SYNC + of the next unit. And connect SYNC - of one DFM
5.0 to the SYNC - of the next unit, etc. Connect shield to Transducer GND on all units as illustrated
below.
No changes in DFM 5.0 hardware setup or software are required. The instruments manage
synchronization connections automatically.
TRANSDUCER
GND
SYNC
–+
TRANSDUCER
GND
SYNC
–+
TRANSDUCER
GND
SYNC
–+
Page 20
FIELD TROUBLESHOOTING
Possible Causes:Corrective Action:
METER READING LOWER THAN EXPECTED
DFM 5.0 Doppler Flow Meter
Calibration Error
Lower flow rate than expected
Review
•
Investigate pump/valves. Compare velocity
•
UNITS/MODE menu and Pipe ID
with alternate instrument
Signal not penetrating far enough into the flow
stream
Relocate sensor closer to elbows or flow
•
disturbances
Improper mounting of sensor• Reinstall Sensor with careful application of
Coupling Compound
Pipe is not full• Remount Sensor on vertical pipe
METER READING WHEN THERE IS NO FLOW
Vibration on pipe• Adjust Status / Signal Cutoff setting
• Install in another location
Local electrical noise• Ensure all Flowmeter wiring is in METAL
conduit and sensor shield is properly grounded.
•
Ensure correct power input Ground connection
(<1 ohm resistance).
Cross talk between two or more DFM 5.0
flowmeters on same pipe
Variable Speed Drive interference
Sensor connections incorrect
Page 21
•
Ensure 4-20mA Shield connected to
Instrument Ground stud.
•
Refer to Synchronization instructions
•
Follow Drive manufacturers wiring and
Grounding instructions
•
Relocate Flowmeter electronics, Sensor and
wiring away from VSD
•
Refer to Connections diagram
Possible Causes:Corrective Action:
METER READING ERRATIC
DFM 5.0 Doppler Flow Meter
Sensor mounted too close to valve, pump or
elbow
Change sensor placement. Recommended 6-10
•
diameters from elbows, and 30 diameters from
pumps, controlling valves, orifice plates,
nozzles or open pipe discharge
NO FLOW INDICATION
Not enough suspended particles or gases in the
fluid
Relocate sensor in more turbulent pipe section.
•
Mount sensor at 12 o'clock position on
horizontal pipe
Coupling compound washed out, or sensor loose
on pipe
• Remount sensor
• Use Dow Corning Silicone #4
Power interruption. No flow.• Check fuse/breaker. Confirm flow
Relocate sensor >30 pipe diameters from
velocity increasing device
•
Ensure all Flowmeter wiring is in METAL
conduit and sensor cable shield is connected to
Ground stud
•
Follow Drive manufacturers wiring and
Grounding instructions
•
Relocate Flowmeter electronics, Sensor and
wiring away from VSD
Possible Causes:Corrective Action:
METER READING DOES NOT TRACK FLOW
DFM 5.0 Doppler Flow Meter
Sensor and GND wires reversed or not properly
connected
Improper AC power input Ground
Check Sensor connections
•
Use direct connection with 12 AWG wire to
•
nearest Ground pole (<1 ohm resistance).
Page 23
DFM 5.0 Doppler Flow Meter
COMMON QUESTIONS AND ANSWERS
The pipe vibrates. Will it affect the flow meter?
Common vibration frequencies are far lower than the sonic frequencies used by the Greyline flow meter,
and will not normally affect accuracy or performance. However, applications where very weak Doppler
signal is present (when sensitivity is adjusted to maximum and signal strength is low), accuracy may be
affected by pipe vibration, or the flow meter may show readings under no-flow conditions. Attempt to
relocate the sensor on a pipe section where vibration is reduced, or arrange pipe mounting brackets to
reduce vibration at the sensor mounting location.
The flow meter must be installed in a high noise environment. Will this affect operation?
Greyline flow meters are designed to discriminate between environmental noise and the Doppler signal.
High noise environments may affect the flow meter’s performance where low signal strength and/or low
flow velocities are being measured. Relocate the sensor in a more quiet environment if possible.
Will pipe corrosion affect accuracy of the flow meter?
Yes. Rust, loose paint etc. must be removed from the outside of the pipe to provide a clean mounting
position when installing a Doppler sensor. Severe corrosion/oxidation on the inside of the pipe may
prevent the Doppler signal from penetrating into the flow. If the pipe cannot be cleaned, a spool piece
(PVC recommended) should be installed for sensor mounting.
What effect do pipe liners have on the flow meter?
The air gap between loose insertion liners and the pipe wall prevent the Doppler signal from entering the
flow. Better results can be expected with bonded liners such as cement, epoxy or tar, however an on site
test is recommended to determine if the application is suitable for a Doppler flow meter.
Why is Doppler only recommended for liquids containing suspended solids or gases?
The Doppler sensor transmits sound into the flow stream which must be reflected back to the sensor to
indicate flow velocity. Gas bubbles or suspended solids act as reflectors for the Doppler signal. As a
guideline, Greyline Doppler flow meters are recommended for liquids containing solids or bubbles with
a minimum size of 100 microns and a minimum concentration of 75 ppm. Most applications (except
potable, distilled or deionized water) will meet this minimum requirement.
Can the sensor be submerged in water?
Yes, for short periods of time or by accident, but it is not recommended for continuous operation. The
sensor is constructed to withstand submersion to 10 psi without damage, but external liquid moving in
contact with the sensor can be interpreted as flow and cause false readings.
Page 24
DFM 5.0 Doppler Flow Meter
What is the purpose of the Signal Strength Display?
Doppler signals of very low strength are not accepted or processed by the instrument. This feature
assists in rejection of environmental noise and vibration. Use the display to evaluate signal strength in
your application. Strong signals will increase in percentage to a maximum of 100% or greater.
Can I change the length of the sensor cable?
Yes. Technological advances in Greyline Doppler design allow cable lengths up to 500 ft (152 m) with
no loss of signal strength. Extended cable (Greyline Option DXC) should be installed in rigid or flexible
conduit for mechanical protection. Use only Greyline shielded coaxial pair (RG174U) cable. Cable
junctions should be made through a terminal block and housed in a watertight metal junction box
(Greyline Option DJB). BNC coaxial connectors (TV cable type) are not recommended for cable
splices.
Does the DFM 5.0 require periodic recalibration?
No. DFM 5.0 calibration does not drift over time. The solid state sensor has no moving parts to wear and
affect calibration. The Doppler flow technique generates an ultrasonic signal proportional to the velocity
of flow. All Greyline timing/counting circuits use crystal-controlled frequency references to eliminate
any drift in the processing circuitry.
Page 25
DFM 5.0 Doppler Flow Meter
APPLICATIONS HOTLINE
For applications assistance, advice or information on any Greyline Instrument contact your Sales
Representative, write to Greyline or phone the Applications Hotline below:
United States:Tel: 315-788-9500Fax: 315-764-0419
Canada:Tel: 613-938-8956Fax: 613-938-4857
Toll Free:888-473-9546
Email:info@greyline.com
Web Site:www.greyline.com
Greyline Instruments Inc.
CanadaUSA:
16456 Sixsmith Drive105 Water Street
Long Sault, Ont. K0C 1P0Massena, NY 13662
Page 26
DFM 5.0 Doppler Flow Meter
PRODUCT RETURN PROCEDURE
Instruments may be returned to Greyline for service or warranty repair.
Obtain an RMA Number from Greyline -
1
Before shipping a product to the factory please contact Greyline by telephone, fax or email to obtain an
RMA number (Returned Merchandise Authorization). This ensures fast service and correct billing or
credit.
When you contact Greyline please have the following information available:
1. Model number / Software Version
2. Serial number
3. Date of Purchase
4. Reason for return (description of fault or modification required)
5. Your name, company name, address and phone number
Clean the Sensor/Product -
2
Important
1. Rinse sensor and cable to remove debris.
2. If the sensor has been exposed to sewage, immerse both sensor and cable in a solution of 1 part
household bleach (Javex, Clorox etc.) to 20 parts water for 5 minutes. Important: do not immerse open
end of sensor cable.
3. Dry with paper towels and pack sensor and cable in a sealed plastic bag.
4. Wipe the outside of the enclosure to remove dirt or deposits.
5. Return to Greyline for service.
3
Ship to Greyline -
After obtaining an RMA number please ship the product to the appropriate address below:
: unclean products will not be serviced and will be returned to the sender at their expense.
Canadian and InternationalUSA
Customers:Customers:
Greyline Instruments Inc.Greyline Instruments Inc.
16456 Sixsmith Drive204 150th Avenue
Long Sault, Ont. K0C 1P0Madeira Beach, FL 33708
Please complete and return this form to Greyline. It is
important. We use this information to check our database
for performance of Greyline flow meters in similar
applications, and to provide advice and recommendations
to you. Thanks for your cooperation.
Greyline Instruments warrants, to the original purchaser, its
products to be free from defects in material and workmanship for
a period of one year from date of invoice. Greyline will replace
or repair, free of charge, any Greyline product if it has been
proven to be defective within the warranty period. This warranty
does not cover any expenses incurred in the removal and
re-installation of the product.
If a product manufactured by Greyline should prove defective
within the first year, return it freight prepaid to Greyline
Instruments along with a copy of your invoice.
This warranty does not cover damages due to improper
installation or handling, acts of nature, or unauthorized service.
Modifications to or tampering with any part shall void this
warranty. This warranty does not cover any equipment used in
connection with the product or consequential damages due to a
defect in the product.
All implied warranties are limited to the duration of this
warranty. This is the complete warranty by Greyline and no
other warranty is valid against Greyline.Some states do not
allow limitations on how long an implied warranty lasts or
limitation of incidental or consequential damages, so the above
limitations or exclusions may not apply to you.
This warranty gives you specific legal rights, and you may also
have other rights which vary from state to state.
Greyline Instruments Inc.
Page 29
DFM 5.0 Doppler Flow Meter
APPENDIX A – OPTIONS
EXTRA SENSOR CABLE
(OPTION DXC)
Each Greyline flow meter includes 20 ft / 6m (or 50 ft / 15 m optional) continuous shielded coaxial pair
cable. Additional cable and Cable Junction Box (Option DJB) may be ordered with the Flow Meter, or
the cable may be spliced and extended up to 500 ft (152m) as required during installation. No
adjustment is required when the sensor cable is extended or shortened. Use only Greyline shielded
coaxial pair (RG174U) cable.
Extended sensor cable should be installed in conduit for mechanical protection. Recommended
installation with a metal junction box (Option DJB) is illustrated below:
EXTENDED SENSOR
CABLE TO ELECTRONICS
ENCLOSURE
CONDUIT (BY CUSTOMER)
If Required For Mechanical Protection
MAX. LENGTH
500 ft (152m)
GREYLINE SHIELDED
COAXIAL PAIR
CORE
SHIELD
CORE
GREEN
TERMINAL BLOCK
GND
GREEN WIRES
MUST BE CONNECTED
TO GND TERMINAL
SENSOR CABLE
20 ft (6m) SHIELDED
COAXIAL PAIR
SENSOR
COAXIAL CABLE PREPARATION
DXC Doppler sensor cable can be cut and spliced up to a maximum length of 500 ft (152 m). Cable ends
must be prepared as illustrated below.
GOOD
BLACK
INSULATION
HAS BEEN
REMOVED
BAD
BLACK
INSULATION
HAS NOT
BEEN
REMOVED
Page 30
DFM 5.0 Doppler Flow Meter
SENSOR CABLE JUNCTION BOX
(OPTION DJB)
Optional Watertight steel NEMA4 Junction Boxes with terminal strips are available from Greyline
Instruments.
DIMENSIONS
OPTION DJB - JUNCTION BOX
Page 31
DFM 5.0 Doppler Flow Meter
SENSOR INTRINSIC SAFETY
(OPTION 2ISB)
When connected through Intrinsic
Safety Barriers, the Greyline Sensor
Model SE4 is CSA certified for
installation in a hazardous location
rated:
Class I, Groups C,D
Class II, Groups E,F,G
Class III
Intrinsic Safety Barriers may be ordered
with the Greyline instrument and are
supplied mounted in the Greyline
instrument enclosure. Replacement
barrier fuses (Part No. ISB- 011239)
may be purchased separately. The
instrument enclosure containing the
2ISB Intrinsic Safety Barriers must be
installed in a non-hazardous location.
Refer to SESPEC-INST-01 for complete
installation instructions.
DRAWINGNO:GN3SPEC-INST-02
TRANSDUCER
DFM 5.0
GND
1
2
(rated 9.6V, 27 ohms)
STAHL 9001/02-093-390-101
STAHL 9001/02-093-390-101
313
424
WHT
BLK
NOTE:
BARRIER-EQUIPPED UNITS ARE
FACTORY-WIRED WITH GROUND
THROUGH THE INSTRUMENT CHASSIS.
Page 32
SIDE VIEW
NON-HAZARDOUS LOCATION
HAZARDOUS LOCATION
CLASS I, GROUPS C,D
CLASS II, GROUPS E,F,G
CLASS III
DFM 5.0 Doppler Flow Meter
NON-INCENDIVE
With SE4 sensor installed in hazardous
locations rated:
Class I, Division 2,
Groups A,B,C&D
Intrinsic Safety Barriers are not required
for SE4 sensor installation in Div 2.
locations when properly connected to a
DFM 5.0. The DFM 5.0 instrument
enclosure must be installed in a
non-hazardous location.
DRAWING NO: SESPEC-INST-02
GND
GND
RCVR
BLK
TRANSDUCER
GND
SYNC
TMTR
WHT
–+
DFM 5.0
SIDE VIEW
NON-HAZARDOUS LOCATION
HAZARDOUS LOCATION
CLASS I, DIVISION 2, GROUPS A,B,C&D
CABLE:
CWPT-13129 500 ft max.
CONTAINS
: Shield, 2 of RG174 (32pf/ft, 77nH/ft)
Page 33
DFM 5.0 Doppler Flow Meter
ENCLOSURE HEATER AND THERMOSTAT - Option TH
Instruments can be factory-equipped with an Enclosure Heater and Thermostat or the module can be
customer-installed. The Thermostat is factory set to turn ON at 40°F (4.5°C) and OFF at 60°F (15.5°C).
Power consumption is 15 Watts.
TO AC POWER SUPPLY
ENCLOSURE SUNSCREEN - Option SCR
Do not mount instrument electronics in direct sunlight. Overheating will reduce the life of electronic
components and condensate may form during the heat/cool cycles and cause electrical shorts.
11"/280 mm
Note:
Exposure to direct sunlight can cause
overheating and moisture condensation
which will reduce the operating life of
electronics.
Protect Instruments from direct sunlight
with this iridite finished aluminum sun
screen (Greyline Option SCR).
Seal conduit entries with caulking
compound to further reduce moisture
condensation.
11"
280 mm
5"
127 mm
Page 34
DFM 5.0 Doppler Flow Meter
POWER INPUT OPTION
9-32VDC
DFM 5.0 Flow Meters may be ordered factory-configured for 9-32VDC power input.
QUICK BENCH TEST:
Connect Sensor as shown below, then Power. Test operation of the DFM 5.0 by holding the sensor in
one hand and rubbing your thumb or fingers briskly across the face (plastic surface) of the sensor.
Allow 15 seconds for the DFM 5.0 to process the signal and display a flow value.
CONNECTIONS:
POWER INPUT: Connect 9-32VDC to the + and − terminals. The Power Input GND terminal must be
connected to the nearest Ground pole. A 1 amp fuse in line is recommended. Power Consumption is 6.5
W continuous.
4-20mA (1)
RLY2
RLY1
NO
C
NC
NO
C
NC
–
+
EXTRA RELAYS OPTION
NC
NC
C
NO
RLY3
RLY4
9-32VDC
+–
GND
C
NO
NC
C
NO
RLY5
RLY6
TRANSDUCER
NC
–+
SYNC
GND
GND
TMTR
RCVR
C
NO
GND
Page 35
DFM 5.0 Doppler Flow Meter
D
--Data Logging------>Log Site ID00
ModeFlow
Set Date Feb 18/2008
Set Time11:27:40
Interval10sec
Reset LogNO
Velocity
Mar 19/2009
12:28:41
99
60min
30min
10min
5min
2min
1min
30sec
YES
DATA LOGGING (Optional)
Setup
Select
Data Logging from Menu Selections.
Log Site IDEnter a number from 00 to 99. The site ID will
become part of the downloaded file name to help
distinguish downloads from different instruments.
Press ü to store the setting.
ModeSelect Velocity (e.g. ft/sec or m/sec). Flow (e.g.
USGPM or l/sec). Press ü to store the setting.
Set Date
Press Ç or È to scroll and select Month, Day and
Year. Press ü to store the setting.
Set Time
Press Ç or È to select the current time in Hours,
Minutes and Seconds. Press ü to store the setting.
Interval
Press Ç or È to select the logging interval. Flow rate
reading will be stored at each time interval. Press ü to
store the setting.
Reset LogSelect Yes to apply any changes that have been made
to the logger
Interval or Mode. The current log file
will be erased from memory and a new log file will
start.
RETRIEVE LOG FILE
Plug a USB Flash Memory Drive (not supplied by Greyline) into the USB
output cable from the instrument. The instrument display will show the
message
card and then display
Downloading until the log file is transferred to the memory
Completed. The USB flash drive may be
removed.
Download file names will appear in this format:
DFM_ _00A.LOG
MODELTAG DOWNLOA
Tag is set according to the
Logging
menu.
Log Site ID entered in the instrument Data
Page 36
DFM 5.0 Doppler Flow Meter
Download letter will be A for the first download from an instrument. B for
the second, then
C etc. At the letter Z a - character will appear indicating
that the maximum number of downloads for that instrument are on the
USB flash drive. Older files can be erased or moved from the flash
memory drive or a new memory drive can be used.
OPENING LOG FILES
Install Greyline Logger on your PC or laptop. Refer to the Help menu in
the program for detailed instructions.
Select File/Open/Instrument Log (.log) to open the log file from your USB
flash drive.
Page 37
DFM 5.0 Doppler Flow Meter
O
SPECIFICATIONS
7.4 / 188 mm"
Flow Rate Range:-40 to -0.25 ft/sec, +0.25 to
+40 ft/sec (-12.2 to -0.076
m/sec, +0.076 to +12.2
m/sec,) in most applications
Pipe Size:Any pipe ID from½"to180"
(12.7 mm to 4.5 m)
Accuracy:±2% of full scale. Requires
solids or bubbles minimum
size of 100 microns, minimum
concentration 75 ppm.
Repeatability: ±0.1%,
Linearity ±0.5% of full scale
Displays:White, backlit matrix -
displays flow rate, totalizer,
relay states, operating mode
and calibration menu
Calibration:built-in 5-key calibrator with English, French or Spanish language selection
Power Input:100-240Vac, 50/60Hz, 30 Watts or 115Vac, 50/60Hz, 30 Watts or 230Vac,