Read all warnings and instructions in this manual.
Save these instructions.
CAUTION
D This dispense valve is designed to dispense
petroleum-based lubricants and antifreeze only.
Do not dispense windshield washer solvent with
this dispense valve.
D This dispense valve is designed for indoor use
only.
D This dispense valve is not designed for in-line
installation. Do not install with a shutoff valve on
the outlet side of the meter. Such installation
could result in damage to the meter housing
cover.
GRACO INC. P.O. BOX 1441 MINNEAPOLIS, MN 55440- 1441
Copyright 2001, Graco Inc. is registered to I.S. EN ISO 9001
Equipment misuse can cause the equipment to rupture or malfunction and result in serious injury.
INSTRUCTIONS
D This equipment is for professional use only.
Symbols
Warning Symbol
WARNING
This symbol alerts you to the possibility of serious
injury or death if you do not follow the instructions.
Caution Symbol
CAUTION
This symbol alerts you to the possibility of damage to
or destruction of equipment if you do not follow the
instructions.
D Read all instruction manuals, tags, and labels before you operate this equipment.
D Use the equipment only for its intended purpose. If you are not sure, call your Graco distributor
for assistance.
D Do not alter or modify this equipment. Use only genuine Graco parts and accessories.
D Do not leave this dispense valve unattended while it is dispensing.
D Check equipment daily. Repair or replace worn or damaged parts immediately.
D Do not exceed the maximum working pressure of the lowest rated system component. See the
Technical Data on page 20 for the maximum working pressure of this component.
D Use fluids and solvents that are compatible with the equipment wetted parts. See the Technical
Data section of all equipment manuals. Read the fluid and solvent manufacturer’s warnings.
D Route hoses away from traffic areas, sharp edges, moving parts, and hot surfaces. Do not
expose Graco hoses to temperatures above 180_ F(82_ C) or below --40_ F(--40_ C).
D Comply with all applicable local, state, and national fire, electrical, and safety regulations.
D Do not point the dispense valve at anyone or at any part of the body.
D Do not put your hand or fingers over the end of the dispense valve.
D Do not stop or deflect leaks with your hand, body , glove, or rag.
D Use only extensions and nozzles that are designed for use with this dispense valve.
D Follow the Pressure Relief Procedure on page 5 before you clean, check, or service this
D Tighten all fluid connections before you operate this equipment.
D Check the hoses, tubes, and couplings daily. Replace worn or damaged parts immediately. Do
2309377
equipment.
not repair high pressure couplings; you must replace the entire hose.
WARNINGWARNING
FIRE AND EXPLOSION HAZARD
Improper grounding, poor ventilation, open flames, or sparks can cause a hazardous condition and
result in a fire or explosion and serious injury.
D Be sure the entire fluid system is properly grounded. Refer to your pump instruction manual for
complete details. See Grounding on page 6.
D If there is any static sparking or you feel an electric shock while using this equipment, stop
dispensing immediately. Do not use the equipment until you identify and correct the problem.
D Provide fresh air ventilation to avoid the buildup of flammable fumes from solvents or the fluid
being dispensed.
D Keep the dispensing area free of debris, including solvent, rags, and spilled gasoline.
D Do not smoke while flammable fluids or fumes are in the dispensing area.
3309377
Installation
Typical Installations
Fig. 1 shows a typical hose reel installation. These
dispense valves can also be installed on a console, as
showninFig.2.
CAUTION
Do not use this dispense valve on non-Graco
consoles. Such use could result in the trigger
becoming inadvertently pressed while the dispense valve is stowed.
J
L
H
The typical installation shown in Fig. 1 is only a guide.
The components shown are typical; however, it is not a
complete system design. Contact your Graco distributor for assistance in designing a system to suit your
particular needs.
CAUTION
This dispense valve is not designed for in-line
installation. Do not install with a shut-off valve
on the outlet side of the meter. Such installation
could result in damage to the meter housing
cover.
Mounting Bracket
Mounting bracket 196471 is available for resting a PM5
dispense valve on a console. See Fig. 2.
CAUTION
Do not obstruct the trigger of this dispense
valve, and do not set the unit down resting on its
trigger, or it might not stop dispensing.
M
K
N
Fig. 1
KEY DESCRIPTION
HThermal relief kit (required) Part No. 235998
Install downstream from pump.
JFluid shut-off valve
KHose
LHose reel fluid inlet hose
MHose reel
NPM5 electronic metered dispense valve
4309377
06174B
mounting bracket
196471
Fig. 2
TI0334
Installation
WARNING
PRESSURIZED EQUIPMENT HAZARD
The equipment stays pressurized until pressure is
manually relieved. To reduce the risk of serious
injury from pressurized fluid, accidental spray from
the dispense valve, or splashing fluid, follow the
Pressure Relief Procedure when you
D Are instructed to relieve pressure
D Check, clean, or service any system equipment
D Install or clean fluid nozzles or filter
Pressure Relief Procedure
1. Turn off the power supply to the pump.
2. Trigger the dispense valve into a waste container
to relieve pressure.
3. Open any bleed-type master air valves and fluid
drain valves in the system.
4. Leave the drain valve open until you are ready to
pressurize the system.
WARNING
FIRE AND EXPLOSION HAZARD
The movement of fluids through the
dispensing system generates static
electricity. The static electricity can
cause volatile fumes to ignite, resulting in explosion
and fire. The dispensing system must grounded.
See Grounding on page 6.
Installation Procedure
CAUTION
If this is a new installation, or if the fluid in the
lines is contaminated, flush the lines before you
install the metered valve. Contaminated lines
could cause the valve to leak.
1. If this is an existing installation, go to step 7.
Steps 2 through 6 are the Flushing Procedure.
2. Close the fluid shut-off valve (J) at each dispense
position.
3. Make sure the main fluid outlet valve at the pump
is closed, the air pressure to the pump motor is
adjusted, and the air valve is open. Slowly open
the main fluid valve.
4. Place the hose end (with no dispense valve connected) into a container for waste oil. Secure the
hose in the container so it will not come out during
flushing. If you have multiple dispense positions,
first flush the dispense position farthest from the
pump, and work your way toward the pump.
5. Slowly open the shut-off valve (J) at the dispense
position. Flush out a sufficient amount of oil to
ensure that the entire system is clean, and close
the valve.
6. Repeat step 5 at all other dispense positions.
7. Relieve the pressure.
Pre-Installation Procedure
1. Relieve the pressure.
WARNING
To reduce the risk of serious injury whenever you
are instructed to relieve pressure, always follow the
Pressure Relief Procedure above.
2. Close the shut-off valve (item J in Fig. 1).
3. Ground the hose and reel or console. See
Grounding on page 6. Leave a minimum two
engaged threads bare when using PTFE tape. The
bare threads ensure a ground is maintained.
WARNING
To reduce the risk of serious injury, whenever you
are instructed to relieve pressure, always follow the
Pressure Relief Procedure at left.
8. Slide the swivel cover (4) of the PM5 onto the
hose, small end first. See Fig. 3.
9. Apply thread sealant to the male threads of the
hose fitting, thread the hose fitting into the swivel
(3) of the PM5, and tighten it firmly. See Fig. 3.
NOTE: Make sure you let the sealant cure to the
manufacturer’s recommendations before you let
fluid into the system.
5309377
Installation
10. Thread the sealing nut (5c, 6c, or 7c) onto the
extension (5a) or street elbow (6d or 7d), thread
the extension or elbow in at least three full turns,
position it for proper alignment, and tighten the
sealing nut. The PTFE seal on the sealing nut
must face the valve housing. See Fig. 4.
NOTE: Theflexibleextension(6a)canalsobe
threaded directly into the meter outlet without the
street elbow or sealing nut. See the note in the
Parts Drawing on page 19.
1 1. Thread the new nozzle (5b, 6b, or 7b) onto the
extension, and, with an open-end adjustable
wrench, tighten it firmly. See Fig. 4.
NOTE: Only tighten the nozzle with the wrench
on the flats of the nozzle bushing. Do not disas-semble the bushing from the nozzle. Disassembly will affect the performance of the nozzle.
WARNING
Model shown has
75_ bend rigid
extension
5b
Fig. 4
hose
4
5c
5a
nozzle bushing
Nozzle is not serviceable.
TI0327
Do not use Graco’s old nozzle (Part No. 203655) or
any other manual shut-off nozzle on the PM5
extension. You must use the new automatic nozzle
that is provided with the PM5, or the meter could
be damaged. Do not use any sealant material.
12. Open all dispense position shut-off valves, and
start the pump to pressurize the system. See the
Operation section for proper operation of meter.
13. T o ensure dispensing accuracy, purge all air from
the fluid lines and dispense valve before you use
it. Set the system flow to the desired flow rate,
which is typically 1.5 gpm. Do not exceed a 5-gpm
flow rate.
Slide onto
hose before
connecting.
hose fitting
3
4
Grounding
Proper grounding is an essential part of maintaining a
safe system.
To reduce the risk of static sparking, ground all system
components according to local and national electrical
codes. Refer to the user manuals for the pump and
other system components, and ground the following:
D Pump: Follow the manufacturer’s recommend-
ations.
D Air and Fluid hoses: Use only grounded hoses.
D Air compressor: Follow the manufacturer’s recom-
mendations.
Fig. 3
6309377
TI0328
D Fluid supply container: Follow the local code.
To maintain grounding continuity when flushing or
relieving pressure, always hold a metal part of the
valve firmly to the side of a grounded metal pail, then
trigger the valve.
Setup
T erms
The following terms are shown on the display and/or
used often in this instruction manual.
D R--TOTAL: resettable total
Displayed to show the cumulative amount that the
dispense valve has dispensed in all modes. It can
be reset to zero.
D TOTAL: non-resettable total
Displayed to show the cumulative amount that the
dispense valve has dispensed in all modes for the
history of the unit. It cannot be reset.
D MANUAL mode
Dispense mode in which the display counts up from
zero to show the dispensed amount. In this mode,
you may lock the trigger, but you must manually
unlock it when the desired amount is dispensed.
Memory setting also unlocks the trigger.
D AUTO mode
Dispense mode in which a preset, user-entered
amount is dispensed. When the preset amount is
dispensed, a beep sounds, the trigger unlocks to
stop the unit from dispensing, and the amount
dispensed is displayed. At this point, you may
dispense more by pulling back the trigger, and the
display resumes counting up in Manual mode.
D Asleep / Awake
Asleep is a battery-saving mode in which the display goes blank after 45 seconds of inactivity during
normal operation and 2 minutes when in the options
menu. The display comes awake from sleep mode
when you press the Manual/Reset or Auto/Reset
button, but not when you squeeze the trigger to
dispense fluid. The unit does keep track of the
amount dispensed while the display is asleep.
NOTE: If the unit falls asleep after any dispense
cycle, and you do wake it up by pressing the Auto/
Reset button, the previously dispensed amount is
cleared, and the Auto mode dispense amount
stored in memory is displayed. You will be at the
beginning of an Auto mode dispense cycle.
Keypad Buttons
The buttons on the keypad and their functions are as
follows (see the figure below):
D 10, 1.0, and 0.1
Used in Auto mode and during setup to enter
dispense amounts.
D MANUAL / RESET and AUTO / RESET
Used individually to select Manual mode and Auto
mode. Used together (pressed simultaneously) to
access the setup menus.
For both of these buttons, the first push selects the
mode, and the second push resets the display to
zero.
D TOTAL
Used in any mode to see the resettable total and
the non-resettable total.
NOTE: All buttons are disabled while fluid is being
dispensed.
GAL
AUTO
If the unit falls asleep after any dispense cycle, and
you do not wake it up by pressing the Manual/Reset or Auto/Reset button, it will default to manual
mode. When dispensing begins you will be at the
beginning of a manual mode dispense cycle.
06044A
7309377
Loading...
+ 15 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.