Glow-worm ENERGY 25c, ENERGY 30c, ENERGY 35c, Energy 15s, Energy 12s Installation And Maintenance Instructions Manual

...
Page 1
Installation and main­tenance instructions
ENERGY
25c 30c 35c
GB, IE
Page 2
Contents
Contents
1 Safety .................................................................... 4
1.1 Action-related warnings ......................................... 4
1.2 Risk caused by inadequate qualifications.............. 4
1.3 Intended use .......................................................... 4
1.4 General safety information .................................... 4
1.5 Regulations (directives, laws, standards).............. 6
2 Notes on the documentation .............................. 7
2.1 Observing other applicable documents ................. 7
2.2 Storing documents................................................. 7
2.3 Validity of the instructions...................................... 7
2.4 Benchmark............................................................. 7
3 Product description............................................. 7
3.1 Compartment Ventilation ....................................... 7
3.2 Information on the identification plate.................... 7
3.3 Functional elements: Combination unit ................. 8
3.4 CE label ................................................................. 8
4 Set-up.................................................................... 8
4.1 Transporting the unit .............................................. 8
4.2 Unpacking the product........................................... 8
4.3 Checking the scope of delivery.............................. 8
4.4 Dimensions............................................................ 9
4.5 Minimum clearances.............................................. 9
4.6 Using the mounting template................................. 9
4.7 Wall-mounting the product..................................... 9
4.8 Removing/installing the front casing.................... 10
4.9 Removing/installing the side section ................... 10
5 Installation.......................................................... 11
5.1 Checking the gas meter....................................... 11
5.2 Gas and water connections ................................. 11
5.3 Connecting the drain pipework for the
expansion relief valve .......................................... 12
5.4 Connecting the condensate discharge pipe ........ 12
5.5 Electrical installation ............................................ 13
6 Operation............................................................ 15
6.1 Using diagnostics codes ...................................... 15
6.2 Displaying the status codes................................. 15
6.3 Using check programmes .................................... 16
7 Start-up ............................................................... 16
7.1 Carrying out the initial start-up............................. 16
7.2 Checking the type of gas ..................................... 16
7.3 Checking the factory setting ................................ 16
7.4 Checking and treating the heating water/filling
and supplementary water .................................... 16
7.5 Avoiding danger arising from insufficient water
pressure............................................................... 17
7.6 Switching on the product ..................................... 18
7.7 Filling and purging the heating installation .......... 18
7.8 Filling the condensate siphon .............................. 18
7.9 Filling the hot water circuit ................................... 18
7.10 Checking and adjusting the gas settings ............. 18
7.11 Checking leak-tightness ...................................... 20
8 Adapting the unit to the heating
installation.......................................................... 21
8.1 Burner anti-cycling time ....................................... 21
8.2 Setting the pump output....................................... 21
8.3 Setting the bypass valve...................................... 22
8.4 Setting the hot water temperature ....................... 22
9 Handing the product over to the end user ...... 22
10 Inspection and maintenance ............................ 22
10.1 Using original seals.............................................. 22
10.2 Observing inspection and maintenance
intervals ............................................................... 22
10.3 Procuring spare parts .......................................... 23
10.4 Checking the COcontent ................................... 23
10.5 Setting the COcontent ....................................... 23
10.6 Removing the gas-air mixture unit ....................... 24
10.7 Cleaning the heat exchanger............................... 24
10.8 Checking the burner ............................................ 25
10.9 Checking the ignition electrode ........................... 25
10.10 Cleaning the condensate siphon ......................... 25
10.11 Cleaning the filter in the cold water inlet .............. 25
10.12 Cleaning the heating filter.................................... 25
10.13 Installing the gas-air mixture unit ......................... 26
10.14 Draining the product ............................................ 26
10.15 Checking the admission pressure of the
expansion vessel ................................................. 26
10.16 Completing inspection and maintenance work .... 26
10.17 Checking the product for leak-tightness .............. 26
11 Troubleshooting ................................................ 26
11.1 Rectifying faults ................................................... 26
11.2 Calling up the fault memory ................................. 26
11.3 Deleting the fault memory.................................... 26
11.4 Resetting parameters to factory settings ............. 26
11.5 Preparing the repair work .................................... 26
11.6 Replacing defective components......................... 26
11.7 Checking the product for leak-tightness .............. 29
12 Decommissioning the product ......................... 29
13 Customer service............................................... 29
Appendix ............................................................................30
A Check programmes – Overview ....................... 30
B Overview of diagnostics codes........................ 30
C Status codes – Overview .................................. 34
D Overview of fault codes .................................... 35
E Wiring diagram: Combi boiler .......................... 37
F Wiring diagram: Combi boiler (35 kW) ............ 38
G Inspection and maintenance work –
Overview............................................................. 39
H Position of the opening in the air/flue pipe ..... 40
H.1 Positioning of the opening of a fan-supported
flue gas pipe ........................................................ 40
H.2 Horizontal terminal positioning ............................ 41
I Commissioning Checklist................................. 42
Page 3
Contents
0020177746_03 ENERGY Installation and maintenance instructions 3
J Pipe lengths for the air/flue pipe ...................... 46
J.1 Length of the C13 type air/flue pipe..................... 46
J.2 Length of the C33 type air/flue pipe..................... 46
J.3 Length of the C43 type air/flue pipe..................... 46
K Technical data.................................................... 46
Index ...................................................................................49
Page 4
1 Safety
1 Safety
1.1 Action-related warnings
Classification of action-related warnings
The action-related warnings are classified in accordance with the severity of the possible danger using the following warning signs and signal words:
Warning symbols and signal words
Danger!
Imminent danger to life or risk of severe personal injury
Danger!
Risk of death from electric shock
Warning.
Risk of minor personal injury
Caution.
Risk of material or environmental damage
1.2 Risk caused by inadequate qualifications
Set-upDismantlingInstallationStart-upInspection and maintenanceRepairDecommissioning
Observe all instructions that are included
with the product.
Proceed in accordance with current tech-
nology.
Observe all applicable directives, stand-
ards, laws and other regulations.
1.3 Intended use
There is a risk of injury or death to the user or others, or of damage to the product and other property in the event of improper use or use for which it is not intended.
The product is intended as a heat generator for closed heating installations and for hot water generation.
Depending on the unit type, the products referred to in these instructions must only be installed and operated in conjunction with the
air/flue pipe accessories listed in the other applicable documents.
Intended use includes the following:
– observance of accompanying operating,
installation and servicing instructions for the product and any other system compon­ents
– installing and fitting the product in accord-
ance with the product and system approval
– compliance with all inspection and main-
tenance conditions listed in the instruc­tions.
Intended use also covers installation in ac­cordance with the IP code.
Any other use that is not specified in these in­structions, or use beyond that specified in this document shall be considered improper use. Any direct use in industrial or commercial processes is also deemed to be improper.
Caution.
Improper use of any kind is prohibited.
1.4 General safety information
1.4.1 Risk of death from escaping gas
What to do if you smell gas in the building:
Avoid rooms that smell of gas.If possible, open doors and windows fully
and ensure adequate ventilation.
Do not use naked flames (e.g. lighters,
matches).
Do not smoke.Do not use any electrical switches, mains
plugs, doorbells, telephones or other com­munication systems in the building.
If it is safe to do so, close the emergency
control valve or the main isolator.
If possible, close the gas isolator cock on
the product.
Warn other occupants in the building by
yelling or banging on doors or walls.
Leave the building immediately and ensure
that others do not enter the building.
Notify the gas supply company or the Na-
tional Grid +44 (0) 800 111999 by tele­phone once you are outside of the build­ing.
Page 5
Safety 1
0020177746_03 ENERGY Installation and maintenance instructions 5
1.4.2 Risk of death from escaping flue gas
If you operate the product with an empty con­densate trap / siphon, then flue gas may es­cape into the room air.
In order to operate the product, ensure that
the condensate trap / siphon is always full.
1.4.3 Risk of death due to blocked or leaking flue gas routes
Installation errors, damage, tampering, unau­thorised installation sites or similar can cause flue gas to escape and result in a risk of pois­oning.
What to do if you smell flue gas in the prop­erty:
Open all accessible doors and windows
fully to provide ventilation.
Switch off the product.Check the flue gas routes in the product
and the flue gas diversions.
1.4.4 Risk of death due to explosive and flammable materials
Do not use the product in storage rooms
that contain explosive or flammable sub­stances (such as petrol, paper or paint).
1.4.5 Risk of death from electric shock
There is a risk of death from electric shock if you touch live components.
Before commencing work on the product:
Unplug the mains plug.Or disconnect the product from the power
supply by switching off all power supplies (electrical partition with a contact gap of at least 3 mm, e.g. fuse or circuit breaker).
Secure against being switched back on
again.
Wait for at least 3 minutes until the capa-
citors have discharged.
Check that there is no voltage.
1.4.6 Risk of death due to lack of safety devices
The schematic drawings included in this doc­ument do not show all safety devices re­quired for correct installation.
Install the necessary safety devices in the
system.
Observe the applicable national and inter-
national laws, standards and guidelines.
1.4.7 Risk of poisoning and burns caused by escaping hot flue gases
Only operate the product if the air/flue pipe
has been completely installed.
With the exception of short periods for
testing purposes, only operate the product when the front casing is installed and closed.
1.4.8 Risk of being burned or scalded by hot components
Only carry out work on these components
once they have cooled down.
1.4.9 Risk of injury due to the heavy weight of the product
Make sure that the product is transported
by at least two people.
1.4.10 Risk of corrosion damage due to
unsuitable combustion and room air
Sprays, solvents, chlorinated cleaning agents, paint, adhesives, ammonia com­pounds, dust or similar substances may lead to corrosion on the product and in the flue system.
Ensure that the supply of combustion air is
always free of fluorine, chlorine, sulphur, dust, etc.
Ensure that no chemical substances are
stored at the installation site.
If you are installing the product in
hairdressing salons, painter's or joiner's workshops, cleaning businesses or similar locations, choose a separate installation room in which the room air is technically free of chemical substances.
1.4.11 Risk of material damage caused by
frost
Do not install the product in rooms prone
to frost.
Page 6
1 Safety
1.4.12 Risk of material damage caused by using an unsuitable tool
Use the correct tool to tighten or loosen
threaded connections.
1.5 Regulations (directives, laws,
standards)
Observe the national regulations, stand-
ards, guidelines and laws.
Page 7
Notes on the documentation 2
0020177746_03 ENERGY Installation and maintenance instructions 7
2 Notes on the documentation
2.1 Observing other applicable documents
You must observe all the operating and installation in-
structions included with the system components.
2.2 Storing documents
Pass these instructions and all other applicable docu-
ments on to the system operator.
2.3 Validity of the instructions
These instructions apply only to:
Product article number
Article number Gas Council
Number
ENERGY 25c -A (H­GB)
0010015652 47-019-24
ENERGY 30c -A (H­GB)
0010015653 47-019-25
ENERGY 35c -A (H­GB)
0010015654 47-019-26
2.4 Benchmark
Glow-worm is a licensed member of the Benchmark Scheme.
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instructions by a competent person approved at the time by the Health and Safety Executive and that it meets the requirements of the appropriate Building Regu­lations. The Benchmark Checklist can be used to demon­strate compliance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commission­ing and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme.
Benchmark is managed and promoted by the Heating and Hotwater Industry Council.
For more information visit www.centralheating.co.uk
3 Product description
3.1 Compartment Ventilation
The boilers are very high efficiency appliances.
As a consequence the heat loss from the appliance casing during operation is very low.
Compartment ventilation is not required as the products are only certified, and can only be fitted with a concentric flue system.
3.2 Information on the identification plate
The identification plate is mounted on the underside of the product in the factory.
The identification plate keeps record of the country in which the product is to be installed.
Information on the identification plate
Meaning
Barcode with serial number
Serial number For quality control purposes; 3rd and 4th
digits = year of production
For quality control purposes; 5th and 6th digits = week of production
For identification purposes; 7th to 16th digits = product article number
For quality control purposes; 17th to 20th digits = place of manufacture
ENERGY ..c Product description
2H, G20 – 2.0 kPa (20 mbar)
Factory setting for type of gas and gas connection pressure
Cat. Approved gas category
Condensing techno­logy
Efficiency class of the boiler in accord­ance with EC Directive 92/42/EEC
Type: Xx3(x) Permissible flue gas connections
PMS Maximum water pressure in heating
mode
PMW Maximum water pressure in hot water
handling mode
V/Hz Electric connection
W Max. electrical power consumption
IP Level of protection
Heating mode
Hot water generation
Pn Nominal heat output range in heating
mode
Pnc Nominal heat output range in heating
mode (condensing technology)
P Nominal heat output range in hot water
handling mode
Qn Nominal heating load range in heating
mode
Qnw Nominal heating load range in hot water
handling mode
T
max.
Max. flow temperature
NOx NOx class for the product
Code (DSN) Specific product code
Page 8
4 Set-up
Information on the identification plate
Meaning
Read the instructions.
GC no. Gas council number
3.3 Functional elements: Combination unit
15
12
11
10
8
9
7
5
6
4
3
2
1
18
17
20 19
14
16
13
1 Electronics box
2 Heating circuit expan-
sion relief valve
3 Plate heat exchanger
4 Condensate siphon
5 Flue gas pipe
6 Pressure sensor
7 Flue gas analysis point
(for rear flue gas con­nection)
8 Ignition transformer
9 Gas valve
10 Air intake pipe
11 Fan
12 Supply air measuring
stub pipe (for upper flue gas connection)
13 Flue gas analysis point
(for upper flue gas connection)
14 Primary heat exchanger
15 Heating expansion
vessel
16 Purge hose
17 Volume flow sensor
18 Heating pump
19 Bypass
20 3-way valve
3.4 CE label
The CE label shows that the products comply with the basic requirements of the applicable directives as stated on the identification plate.
The declaration of conformity can be viewed at the manufac­turer's site.
4 Set-up
4.1 Transporting the unit
Important: With regard to the regulations of 1992 concern-
ing the manual handling of loads, the unit exceeds the weight that can be lifted by a single person.
4.1.1 General
Hold the load as close as possible to your body. Avoid
rotational movements. Instead, reposition your feet.
If the unit is being lifted by two persons, ensure your
movements are coordinated during lifting.
Avoid bending your upper body – do not lean forwards or
to the side.
Wear suitable non-slip protective gloves in order to pro-
tect your hands against sharp edges. Ensure that you are carrying the load securely.
If required, get somebody to assist you in this.
4.1.2 Unloading the box from the delivery van
It is recommended that two people lift the unit together.Lift the box using the straps provided.Use safe lifting techniques – keep your back straight and
bend your legs at the knee.
Hold the load as close as possible to your body.If the unit is being lifted by two persons, ensure your
movements are coordinated during lifting.
If required, get somebody to assist you in this.
4.2 Unpacking the product
1. Remove the product from its box.
2. Remove the protective film from all of the product's components.
4.3 Checking the scope of delivery
Check that the scope of delivery is complete and intact.
Number Designation
1 Heat generator
1 Unit mounting bracket
1
Flexible condensate discharge pipe
6 3/4" seals
4 1/2" seals
1 Service valve
1 Gas stopcock
1 Filling device
Page 9
Set-up 4
0020177746_03 ENERGY Installation and maintenance instructions 9
Number Designation
2 Connection pipe (heating flow and return)
1 Cold water connection pipe
1 Domestic hot water connection pipe
1 Gas pipe
1 Expansion relief valve discharge pipe
1 Mounting template
1 Enclosed documentation
4.4 Dimensions
96
121
34
123
185
390
123
58 58
170
702
150
280
1 2 3 4 5
7
6
1 Heating flow
2 Hot water connection
3 Gas connection
4 Cold water connection
5 Heating return
6 Connection on the back
of the air/flue pipe
7 Connection on the top
of the air/flue pipe
4.5 Minimum clearances
CC
A
B
D
Minimum clearance
A 150 mm (top air/flue gas connection)
20 mm (air/flue gas connection on the rear)
B 150 mm
C 5 mm
(70 mm if the side panels ought to be removed)
D 600 mm
It is not necessary to maintain a clearance between the product and components made of combustible materials that go beyond the minimum clearances.
4.6 Using the mounting template
Use the mounting template to ascertain the locations at
which you need to drill holes.
4.7 Wall-mounting the product
Note
If you are using the rear air/flue gas connection, install the air/flue pipe before you wall-mount the product.
1. Check whether the wall has sufficient load-bearing ca­pacity to bear the operational weight of the product.
2. Check if the supplied fixing material may be used for the wall.
Page 10
4 Set-up
Conditions: The load-bearing capacity of the wall is sufficient, The fixing material may be used for the wall
Wall-mount the product as described.
Conditions: The load-bearing capacity of the wall is not sufficient
Ensure that wall-mounting apparatus on-site has a suf-
ficient load-bearing capacity. Use individual stands or primary walling, for example.
Do not wall-mount the product if you cannot provide
wall-mounting apparatus with a sufficient load-bearing capacity.
Conditions: The fixing material may not be used for the wall
Wall-mount the product as described using the permitted
fixing material provided on-site.
4.8 Removing/installing the front casing
4.8.1 Removing the front casing
B
C
A
1
1
1. Undo the two screws (1).
2. Gently press the front casing backwards in the centre so that the latching lug is released.
3. Pull the front casing forwards at the bottom edge.
4. Lift the front casing upwards from the bracket.
4.8.2 Installing the front casing
Refit the components in the reverse order.
4.9 Removing/installing the side section
4.9.1 Removing the side section
Caution. Risk of material damage caused by mech-
anical deformation.
Removing both side sections may cause mechanical distortion in the product, which may cause damage to the piping, for ex­ample, and potentially result in leaks.
Always remove only one side section –
never both side sections at the same time.
Note
If there is sufficient lateral clearance (at least 70 mm), you can remove the side section to fa­cilitate maintenance or repair work.
2x
1
A
B
C
D
1. Tilt the electronics box forward.
2. Hold on to the side section so that it cannot fall and unscrew both screws (1), one from the top and one from the bottom.
3. Tilt the side section to the outside and move it down­wards and out.
4.9.2 Installing the side section
Refit the components in the reverse order.
Page 11
Installation 5
0020177746_03 ENERGY Installation and maintenance instructions 11
5 Installation
Danger! Risk of scalding and/or damage due to
incorrect installation leading to escaping water.
Mechanical stresses in the connection pipes may lead to leaks.
Ensure that there is no mechanical stress
when installing the connection pipes.
Caution. Risk of material damage caused by
residues in the pipelines.
Welding remnants, sealing residues, dirt or other residues in the pipelines may damage the product.
Flush the heating installation thoroughly
before installing the product.
5.1 Checking the gas meter
Make sure that the existing gas meter is capable of
passing the rate of gas supply required.
5.2 Gas and water connections
Caution. Risk of damage caused by incorrect gas
connection installation.
Excess test pressure or operating pressure may cause damage to the gas valve.
Check the leak-tightness of the gas valve
using a maximum pressure of 11 kPa (110 mbar).
Caution. Risk of material damage caused by corro-
sion
Due to non-diffusion-tight plastic pipes in the heating installation, air gets into the heating water. Air in the heating water causes corro­sion in the heat generator circuit and in the product.
If you use non-diffusion-tight plastic pipes
in the heating installation, ensure that no air gets into the heat generator circuit.
Caution. Risk of material damage due to heat trans-
fer during soldering.
Only solder connectors if the connectors
are not yet screwed to the service valves.
Note
Apply heat insulation to the water pipes to the boiler outlet and to the installation.
Preliminary work
1. Check that the system volume and the volumetric capa­city of the expansion vessel are compatible.
If the volume of the expansion vessel is insufficient
for the installation.
Install an additional expansion vessel in the
heating return, as close to the product as pos­sible.
Install a non-return valve at the product's outlet
(heating flow).
2. Ensure that the installation has the following compon­ents:
A cold water stopcock for the unitA gas stopcock for the unitA filling and draining device in the heating installa-
tion
1
2
3
4
5
1 Heating flow connec-
tion, G3/4
2 Hot water connection,
G3/4
3 Gas connection, G1/2
4 Connection for the cold
water supply line, G3/4
5 Heating return connec-
tion, G3/4
1. Connect the water and gas connections in accordance with the applicable standards.
2. Purge the gas pipe before start-up.
3. Check whether the connections (Page 20) are leak­tight.
Page 12
5 Installation
5.3 Connecting the drain pipework for the expansion relief valve
1
Ensure that the pipeline is visible.The pipe must have a continuous fall and be routed to a
position so that any discharge of water, possibly boiling, or steam cannot create any danger to persons, damage to property or external electrical components and wiring.
The piping must be installed in such a way that you
can see when water drips out.
5.4 Connecting the condensate discharge pipe
1
2
Follow the instructions listed here and observe the legal
and local regulations on condensate discharge.
Use PVC or any other material that is suitable for drain-
ing the non-neutralised condensate.
If you cannot guarantee that the materials from which the
drain pipework is made are suitable, install a system for neutralising the condensate.
Note
The condensate drain pipework must have a continuous fall (45 mm per metre) and should whenever possible terminate at a suitable drain point within the heated envelope of the building that will remain frost free under long periods of low external temperatures.
Connect the condensate traps (1). Use the supplied drain
hose (2) for this.
Connect a condensate discharge pipe (21.5 mm, not
included in the scope of delivery) to the drain hose (2).
During installation remove all burrs from inside of cut pipe
work and avoid excessive adhesive which may trap small pockets of water close to the pipe wall which can freeze and build into a larger ice plug.
For any installation the condensate must be free flowing
and not be possible for air back-pressure to prevent wa­ter flow.
As with other pipe work insulate the condensate dis-
charge pipe to minimise any risk of freezing and beware when crossing cavities that the fall is maintained and the pipe sleeved.
You can find further information in specification "BS 6798" for installing and maintaining gas-fired boilers with a nominal heat input below 70 kW.
5.4.1 Condensate drainage systems
5.4.1.1 Internal soil and vent pipe
Ø19mm
min
5.4.1.2 External soil and vent pipe
L = 3m max
Ø19mm
min
Ø30mm
5.4.1.3 External termination into a gulley or hopper
L = 3m max
Ø19mm
min
Ø30mm
Page 13
Installation 5
0020177746_03 ENERGY Installation and maintenance instructions 13
5.4.1.4 Internal termination into combined sink waste
Ø30mm
Ø19mm
min
5.4.1.5 Internal termination downstream of sink waste
Ø30mm
Ø19mm
min
5.4.1.6 External termination into soakaway
400mm min
300mm
min
25mm
min
500mm min
Ø100mm
L = 3m max
Ø19mm
min
Ø30mm
5.4.1.7 External termination into rain water down pipe
Ø19mm
min
Ø30mm
5.5 Electrical installation
Danger! Risk of death from electric shock!
The power supply terminals L and N remain live even if the product is switched off:
Switch off the power supply.Secure the power supply against being
switched on again.
Only qualified electricians may carry out the electrical install­ation.
5.5.1 Opening the electronics box
B
B
A
Follow the instructions in the specified sequence.
Page 14
5 Installation
5.5.2 Closing the electronics box
Follow the instructions in the reverse order.
5.5.3 Cable route
1
2
1 24-V eBUS cable route 2 230-V eBUS cable route
5.5.4 Carrying out the wiring
30 mm max.
1. Shorten the connection cables to the appropriate lengths to prevent them from causing damage inside the electronics box.
2. Screw the plug to the connection cable.
3. Plug the plug into the slot provided on the PCB.
5.5.5 Establishing the power supply
1
1. Observe all valid regulations.
2. Make sure that the rated voltage of the mains is 230 V.
3. Provide one common electricity supply for the boiler and for the corresponding controller:
Power supply: Single-phase, 230 V, 50 HzFuse protection: 3 A
4. Open the electronics box. (Page 13)
5. Observe the routing of the power supply cable (1) in the electronics box in order to guarantee that there is no strain.
≤ 30 mm
NL
X1 230V~
RT
6. Carry out the wiring. (Page 14)
7. Close the electronics box. (Page 14)
8. Screw the supplied plug to a three-core power supply cable that complies with the relevant standards.
9. Connect the plug for the power supply cable.
10. Make sure that access to the power supply is always
freely available and is not covered or blocked by an obstruction.
Page 15
Operation 6
0020177746_03 ENERGY Installation and maintenance instructions 15
5.5.6 Connecting controllers to the electronic system
X2
X22
X41
+
24V=
RT BUS
Burner
off
X106
BUS24 V
BUSRTB.off
B ur ner
off
R T
24V
=
-
+
B U S
1
4
32
1 Safety thermostat for
floor-standing heating
2 24 V controller
3 eBUS controller or radio
receiver unit
4 Outside temperature
sensor, wired
1. Open the electronics box. (Page 13)
2. Carry out the wiring. (Page 14)
3. Connect the individual components depending on the
type of installation.
Conditions: If installing a multi-circuit controller.
Change the pump operating mode (d.18) from Eco (in-
termittent pump operating mode) to Comfort (continuous pump operating mode).
Conditions: If you are connecting a controller (230 V).
≤ 30 mm
NL
X1 230V~
RT
Connect the controller to the main plug.Remove the bridge from the plug 24V=RT.
4. Close the electronics box.
6 Operation
6.1 Using diagnostics codes
You can use the parameters marked as adjustable in the table of diagnostics codes to adapt the product to the system and customer requirements.
Overview of diagnostics codes (Page 30)
6.1.1 Activating diagnostics codes
1.
Press and hold the button for 7 seconds.
is shown in the display.
2.
Press the or button to set the value.
The access code (96) is reserved for the competent
person.
The access code (35) is reserved for the customer
service.
3.
Press the button to confirm.
is shown in the display.
6.1.2 Setting a diagnostics code
1.
Press the or button to select the diagnostics code.
2.
Press the button to confirm.
The value and/or status of the diagnostics code is
shown in the display.
3.
Press the or button to set the value.
4. If you allow the value to flash for three seconds, the setting is automatically confirmed.
is shown in the display for 1 second.
Note
You can manually confirm the setting at any time by pressing and holding the button for less than 3 seconds.
5. Proceed accordingly for all parameters that need to be changed.
6.
Press and hold the button for 3 seconds to finish configuring the diagnostics codes.
The display switches to the basic display.
6.2 Displaying the status codes
The status codes display the product's current operating status.
Status codes – Overview (Page 34)
6.2.1 Activating the status codes display
1.
Hold the button down for more than 7 seconds.
S.XX is shown on the display, followed by the heat-
ing flow temperature, the internal system pressure and the cylinder temperature (depending on the ver­sion).
2.
Press the button to exit this menu.
Page 16
7 Start-up
The display switches to the basic display.
6.3 Using check programmes
By activating various check programmes, you can trigger various special functions on the product.
Check programmes – Overview (Page 30)
6.3.1 Calling up the check programmes
1.
Hold the button down for more than 5 seconds.
All symbols are shown in the display.
is shown in the display.
2.
Press and hold the button for five seconds.
is shown in the display.
3.
Press the or button to select the check programme.
4.
Press the button to confirm.
on is shown in the display and the programme
starts.
5.
Press the and buttons at the same time whilst running a check programme.
The heating water temperature and the filling pres-
sure for the heating installation are shown altern­ately in the display.
6.
Press the button to return to the check programme.
The display shows the check programme.
7.
Press the button to finish the check programme.
OFF is shown in the display.
8.
Press and hold the button for 3 seconds to finish the check programmes.
End is shown in the display.The display switches to the basic display.
Note
If you do not press any button for 15 minutes, the current programme is automatically can­celled and the basic display is shown.
6.3.2 Displaying the pressure and temperature of the heating during a check programme
1.
Press the buttons simultaneously.
Display the filling pressure in the heating installation.Display the heating flow temperature.
2.
Press the button to display the check programme currently running.
7 Start-up
7.1 Carrying out the initial start-up
Initial start-up must be carried out by a customer service technician or an authorised competent person using the first­commissioning-checklist. The first-commissioning-checklist in the appendix (Page 42) of the installation instructions must be filled out and stored carefully along with the unit's documentation.
Carry out the initial start-up using the first-commission-
ing-checklist in the appendix.
Fill out and sign the first-commissioning-checklist.
7.2 Checking the type of gas
Make sure that the product is set up correctly by checking the type of gas. This ensures optimum combustion quality.
Check the type of gas as part of routine product mainten-
ance work when replacing components or carrying out work on the gas route.
7.3 Checking the factory setting
The product's combustion has been factory tested and is preset for operation with the gas group indicated on the iden­tification plate.
The product is only authorised to be operated with natural gas.
Check the information about the type of gas indicated on
the identification plate and compare this with the type of gas available at the installation location.
Conditions: The product design is not compatible with the local gas group
Do not start up the product.
Conditions: The product design is compatible with the local gas group
Proceed as described below.
7.4 Checking and treating the heating water/filling and supplementary water
Caution. Risk of material damage due to poor-qual-
ity heating water
Ensure that the heating water is of suffi-
cient quality.
Before filling or topping up the installation, check the
quality of the heating water.
Checking the quality of the heating water
Remove a little water from the heating circuit.Check the appearance of the heating water.If you ascertain that it contains sedimentary materials,
you must desludge the installation.
Use a magnetic rod to check whether it contains mag-
netite (iron oxide).
If you ascertain that it contains magnetite, clean the in-
stallation and apply suitable corrosion-protection meas­ures, or fit a magnetic filter.
Check the pH value of the removed water at 25 °C.
Page 17
Start-up 7
0020177746_03 ENERGY Installation and maintenance instructions 17
If the value is below 6.5 or above 8.5, clean the system
and treat the heating water.
Ensure that oxygen cannot get into the heating water.
Checking the filling and supplementary water
Before filling the installation, measure the hardness of the
filling and supplementary water.
Treating the filling and supplementary water
Observe all applicable national regulations and technical
standards when treating the filling and supplementary water.
Provided the national regulations and technical standards do not stipulate more stringent requirements, the following applies:
You must treat the heating water in the following cases:
– If the entire filling and supplementary water quantity dur-
ing the operating life of the system exceeds three times the nominal volume of the heating installation, or
– If the guideline values listed in the following table are not
met, or
– if the pH value of the heating water is less than 6.5 or
more than 8.5.
Total heating output
Water hardness at specific system volume
1)
20 l/kW
> 20 l/kW 50 l/kW
> 50 l/kW
kW
ppm
CaCO
mol/m³ppm
CaCO
mol/m³ppm
CaCO
mol/
m³
< 50 < 300 < 3 200 2 2 0.02
> 50 to 200
200 2 150 1.5 2 0.02
> 200 to 600
150 1.5 2 0.02 2 0.02
> 600 2 0.02 2 0.02 2 0.02
1) Nominal capacity in litres/heating output; in the case of multi­boiler systems, the smallest single heating output is to be used.
Caution. The use of unsuitable heating water may
cause aluminium corrosion and a result­ing lack of leak-tightness.
In contrast to steel, grey cast iron or copper, for example, aluminium reacts with alkaline heating water (pH value > 8.5) to produce substantial corrosion.
When using aluminium, make sure that
the pH value of the heating water is between 6.5 and a maximum of 8.5.
Caution. Risk of material damage if the heating
water is treated with unsuitable additives.
Unsuitable additives may cause changes in the components, noises in heating mode and possibly subsequent damage.
Do not use any unsuitable frost and cor-
rosion protection agents, biocides or seal­ants.
No incompatibility with our products has been detected to date with proper use of the following additives.
When using additives, follow the manufacturer's instruc-
tions without exception.
We accept no liability for the compatibility of any additive or its effectiveness in the rest of the heating system.
Additives for cleaning measures (subsequent flushing required)
Adey MC3+Adey MC5Fernox F3Sentinel X 300Sentinel X 400
Additives intended to remain permanently in the installation
Adey MC1+Fernox F1Fernox F2Sentinel X 100Sentinel X 200
Additives for frost protection intended to remain permanently in the installation
Adey MC ZEROFernox Antifreeze Alphi 11Sentinel X 500
If you have used the above-mentioned additives, inform
the end user about the measures that are required.
Inform the end user about the measures required for frost
protection.
7.5 Avoiding danger arising from insufficient water pressure
The filling pressure must be between 0.10 and 0.15 MPa (1.0 and 1.5 bar).
Note
If the heating flow temperature is shown in the display, press and hold the and buttons at the same time for longer than five seconds, or temporarily deactivate heating mode in order to display the pressure.
If the heating installation extends over several storeys, higher filling pressures may be required to avoid air entering the heating installation.
If the water pressure falls below 0.05 MPa (0.5 bar), the value flashes in the display.
If the water pressure falls below 0.03 MPa (0.3 bar), the product switches off. The display shows 0.0 MPa (0.0 bar). Fault F22 will be stored in the fault list.
Top up the water in the heating installation to start up the
product again.
Page 18
7 Start-up
The pressure value flashes in the display until a
pressure of 0.05 MPa (0.5 bar) or higher has been reached.
7.6 Switching on the product
Switch on the product via the main switch installed on-
site.
7.7 Filling and purging the heating installation
Preliminary work
Flush the heating installation through.
1
1
1. Check the silicone hose connection (1) between the pump's automatic air vent and the hydraulic console.
2. Fill with water until the required filling pressure is reached.
– Recommended filling pressure: 1 … 1.5 bar
The heating and hot water functions cannot be activ-
ated.
The pressure value flashes in the display until a
pressure of 0.05 MPa (0.5 bar) or higher has been reached.
An automatic air vent function is activated if the
pressure exceeds 0.05 MPa (0.5 bar) for longer than 15 seconds.
3. Purge each radiator until the water escapes normally, and then retighten the system's purging valves.
4. Check whether all connections are leak-tight.
Conditions: If the noise persists in the boiler
Purge the product again by activating check programme
(P.07) and then (P.06). Check programmes – Overview (Page 30)
7.8 Filling the condensate siphon
C
2
3
1
A
B
1. Unclip the lower section of the siphon (1) from the up­per section of the siphon (2).
2. Remove the float (3).
3. Fill the lower section of the siphon with water up to 10 mm below the upper edge of the condensate drain pipe­work.
4. Re-insert the float (3).
Note
Check that the float is present in the con­densate siphon.
5. Clip the lower section of the siphon (1) into the upper section of the siphon (2).
7.9 Filling the hot water circuit
1. Open the water tap to fill the hot water circuit.
2. Close the water tap once the appropriate volume of water has flowed out.
The hot water circuit is filled.
3. Check all connections and the entire system for leak­tightness.
7.10 Checking and adjusting the gas settings
Only a qualified competent person is authorised to imple­ment the settings on the gas valve assembly.
Each destroyed tamper-proof seal must be replaced.
The COadjusting screw must be sealed.
Never modify the factory setting of the gas pressure regu­lator of the gas valve assembly.
7.10.1 Checking the gas flow rate
The gas flow rate has been set during production and does not require adjustment. With the front casing fitted check the gas flow rate of the boiler as follows:
Start up the product with the check programme P.01.
Page 19
Start-up 7
0020177746_03 ENERGY Installation and maintenance instructions 19
In addition, ensure that maximum heat can be dissipated
into the heating system by turning up the room thermo­stat.
Wait at least 5 minutes until the boiler has reached its
operating temperature.
Ensure that all other gas appliances in the property are
turned off.
Measure the gas flow rate at the gas meter.Compare the measured values with the corresponding
values in the table.
Qnw from the data plate
H gas in m³/h
Nom. +5% 10%
15.3 1.62 1.70 1.46
18.4 1.95 2.05 1.76
24.7 2.61 2.74 2.35
25.7 2.72 2.86 2.45
28.6 3.03 3.18 2.73
30.6 3.24 3.40 2.92
35.7 3.78 3.97 3.40
Conditions: Gas flow rate not in the permissible range
Check all of the piping and ensure that the gas flow rates
are correct.
Only put the product into operation once the gas flow
rates have been corrected.
Conditions: Gas flow rate in the permissible range
End the check programme P.01.Allow the boiler to cool down by allowing pump overrun to
operate for a minimum of 2 minutes.
Record the boiler maximum gas flow rate onto the
Benchmark gas boiler commissioning checklist.
7.10.2 Checking the gas connection pressure (gas flow pressure)
1
2
1. Ensure that the gas inlet working pressure can be
obtained with all other gas appliances in the property working.
2. Close the gas stopcock (1).
3. Undo the sealing screw on the test nipple (2).
4. Connect a manometer to the test nipple (2).
5. Open the gas stopcock (1).
6. Start up the product with check programme P.01 (in-
stallation with eBUS control).
7. In addition, ensure that maximum heat can be dissip-
ated by fully opening one or more hot water taps.
8. With the boiler operating at full load check that the gas
inlet working pressure at the reference test point (2) complies with the requirements.
Permissible connection pressure
Great Bri­tain
Natural gas
G20
1.7 … 2 kPa
(17.0 … 20 mbar)
9. Should the pressure recorded at the reference test point in the boiler be lower than indicated check if there is any blockage in the pipework or if the pipework is un­dersized.
Conditions: Gas flow pressure not in the permissible range
Caution. Risk of material damage and operating
faults caused by incorrect gas connec­tion pressure.
If the gas connection pressure lies outside the permissible range, this can cause oper­ating faults in and damage to the product.
Do not make any adjustments to the
product.
Do not start up the product.
If you cannot correct the failure, notify the gas supply
company and proceed as follows:
End check programme P.01.Allow the boiler to cool down by allowing pump overrun
to operate for a minimum of two minutes.
Close the gas stopcock.Remove the pressure gauge and retighten the sealing
screw (2) for the measuring nipple.
Open the gas stopcock (1).Check the test nipple for gas tightness.Close the gas stopcock (1).Install the front casing. (Page 10)Disconnect the product from the electrical installation.You must not start up the boiler.
Conditions: Gas flow pressure in the permissible range
End the check programme P.01.Allow the boiler to cool down allowing pump overrun to
operate for a minimum of two minutes.
Close the gas stopcock (1).Remove the pressure gauge and retighten the sealing
screw (2) for the measuring nipple.
Open the gas stopcock (1).Check the test nipple for gas tightness.Install the front casing. (Page 10)Reset boiler controls for normal operation.Record the appliance gas inlet working pressure (kPa
resp. mbar) in the Benchmark gas boiler commissioning checklist.
Page 20
7 Start-up
7.10.3 Checking the leak-tightness of the flue gas installation and flue gas recirculation
1. Check the flue gas installation is intact in accordance
with the latest gas safe technical bulletin and informa­tion supplied in the installation instructions.
2. For extended flue gas installations check for flue gas
recirculation using the air analysis point.
3. Use a flue gas analyser.
4. If you discover CO or CO2in the supply air, search for
the leak in the flue gas installation or for signs of flue gas recirculation.
5. Eliminate the damage properly.
6. Check again whether the supply air contains any CO or
CO2.
7. If you cannot eliminate the damage, do not start up the
product.
7.10.4 Thoroughly flushing the heating installation ("hot")
1. Operate the appliance until the boiler and the heating
system are up to temperature.
2. Check the heating system for leaks.
3. Connect a hose to the drain valve located at the lowest
position of the heating system.
4. Shut off the boiler, open the drain valve and all purge
valves on the radiators and allow the water to flow out of the heating system and the boiler quickly and fully.
5. Close the drain valve.
6. Fill and purge the heating installation. (Page 18)
7. Re-fill the system until the system design pressure of
0,1 MPa (1,0 bar) is attained.
Note
The actual reading on the digital pressure gauge should ideally be 0,05 MPa (0,5 bar) plus an additional pressure corresponding to the highest point of the system above the base of the boiler – 10 m head equals an ad­ditional 1 bar reading on the pressure gauge. The minimum pressure should not be less than 0,1 MPa (1 bar) in any installation. If the system is to be treated with an inhibitor it should be applied at this stage in accordance with the manufacturer’s instructions. Further information can be obtained from Sentinel, Betz Dearborn Ltd., Tel: 0151 420 9595, or Fernox, Alpha– Fry technologies. Tel: 0870
8700362.
8. Install the front casing. (Page 10)
7.10.5 Checking the COcontent
1. Start up the product with the check programme (P.01)
and set the value. – Setting value for the programme P.01: 100 Check programmes – Overview (→ Page 30)
2. Wait until the value that is read is stable.
– Waiting period for reading a stable value: 5 min
1
3. Unscrew the cover from the flue gas analysis point (1).
4. Measure the COcontent at the flue gas analysis point
(1).
5. Compare the measured value with the corresponding value in the table.
Checking the COcontent
Great Britain
front casing on / front casing off
Natural gas
G20
9.2 ±1 %
The value is OK.The value is not OK; you cannot start up the
product.
Inform Customer Service.
7.11 Checking leak-tightness
Check the gas pipe, the heating circuit and the hot water
circuit for leak-tightness.
Check that the air/flue pipe has been installed correctly.
Conditions: Room-sealed operation
Check whether the vacuum chamber has been closed
tightly.
7.11.1 Checking the heating mode
1. Activate the heating mode on the user interface.
2. Turn all thermostatic radiator valves on the radiators until they are fully open.
3. Allow the product to operate for at least 15 minutes.
4. Fill and purge the heating installation. (Page 18)
5. Activate the display for the current operating status. (Page 15)
Status codes – Overview (Page 34)
If the product is working correctly, the display shows
S.04.
7.11.2 Checking the hot water generation
1. Activate the hot water handling mode on the user interface.
2. Open a hot water valve completely.
3. Activate the display for the current operating status. (Page 15)
Page 21
Adapting the unit to the heating installation 8
0020177746_03 ENERGY Installation and maintenance instructions 21
Status codes – Overview (Page 34)
If the product is working correctly, the display shows
S.14.
8 Adapting the unit to the heating
installation
You can reset/change the system parameters (section "Us­ing diagnostics codes").
Overview of diagnostics codes (Page 30)
8.1 Burner anti-cycling time
To prevent frequent switching on and off of the burner and thus prevent energy losses, an electronic restart lockout is activated for a specific period each time the burner is switched off. The burner anti-cycling time is only active for the heating mode. Hot water handling mode during a burner anti-cycling time does not affect the time function element.
8.1.1 Setting the maximum burner anti-cycling time
1. Set the diagnostics code. (Page 15)
Overview of diagnostics codes (Page 30)
2. If required, adjust the maximum burner anti-cycling time
using the diagnostics code d.02.
8.1.2 Resetting the remaining burner anti-cycling time
Hold the button down for more than 3 seconds.
is shown in the display.
8.2 Setting the pump output
The product is equipped with a speed-regulated high-effi­ciency pump, which adjusts independently to the hydraulic conditions of the heating installation.
If you have installed a low loss header in the heating install­ation, you should switch off the speed regulation and set the pump output to a fixed value.
If required, change the setting of the pump speed, which
depends on the operating mode, under diagnostics code d.14.
Set the diagnostics code. (Page 15)
Overview of diagnostics codes (Page 30)
Flow rate-pressure curves for 25 kW (pressure measured downstream of the valves)
A
B
0
10
20
30
40
50
60
0 200 400 600 800 1000 1200
1
2
3
4
1 Maximum speed (by-
pass closed)
2 Maximum speed (de-
fault setting for the by­pass)
3 Minimum speed (default
setting for the bypass)
4 Flow rate at maximum
output (ΔT = 20K)
A Throughput in circuit
(l/h)
B Available pressure
(kPa)
Flow rate-pressure curves for 30 kW (pressure measured downstream of the valves)
A
B
0
10
20
30
40
50
60
0 200 400 600 800 1000 1200
70
1
2
3
4
1 Maximum speed (by-
pass closed)
2 Maximum speed (de-
fault setting for the by­pass)
3 Minimum speed (default
setting for the bypass)
4 Flow rate at maximum
output (ΔT = 20K)
A Throughput in circuit
(l/h)
B Available pressure
(kPa)
Flow rate-pressure curves for 35 kW (pressure measured downstream of the valves)
A
B
0
10
20
30
40
50
60
0 200 400 600 800 1000 1200
70
1
2
3
4
1 Maximum speed (by-
pass closed)
2 Maximum speed (de-
fault setting for the by­pass)
3 Minimum speed (default
setting for the bypass)
Page 22
9 Handing the product over to the end user
4 Flow rate at maximum
output (ΔT = 20K)
A Throughput in circuit
(l/h)
B Available pressure
(kPa)
8.3 Setting the bypass valve
Caution. Risk of material damage caused by incor-
rect setting of the high-efficiency pump
If the pressure at the bypass valve is in­creased (by turning it clockwise) and the pump output is set to less than 100%, the product may not operate correctly.
In this case, set the pump output to
5 = 100% using diagnostics parameter
d.14.
Conditions: d.14 is set to 0 = auto
Do not change the factory settings.
Conditions: d.14 is set to 1 - 5
Remove the front casing. (Page 10)
1
Regulate the pressure using the adjusting screw (1).
Position of the adjusting screw
Notes/application
Right-hand stop (screwed all the way in)
If the radiators do not heat up sufficiently at the default setting. In this case, you must set the pump to the maximum speed.
Mid-position (six anti­clockwise rotations)
Default setting
Five further anti-clockwise rotations starting from the mid-position
If noises are produced in the radiators or radiator valves.
Install the front casing. (Page 10)
8.4 Setting the hot water temperature
Danger! Risk of death from legionella.
Legionella multiply at temperatures below 60 °C.
Ensure that the end user is familiar with
all of the Anti-legionella measures in order to comply with the applicable regulations regarding legionella prevention.
Set the hot water temperature.
Conditions: Water hardness: > 3.57 mol/m³
Hot water temperature: 50
9 Handing the product over to the end
user
When you have finished the installation, attach the sticker
supplied (in the end user's language) to the product cover.
Explain to the end user how the safety devices work and
where they are located.
Inform the end user how to handle the product.In particular, draw attention to the safety information
which the end user must follow.
Inform the end user that they must have the product
maintained in accordance with the specified intervals.
Instruct the end user about measures taken for routing
the combustion air supply and flue system.
10 Inspection and maintenance
10.1 Using original seals
If you replace components, use only the enclosed original seals; additional sealing materials are not required.
10.2 Observing inspection and maintenance intervals
Adhere to the minimum inspection and maintenance in-
tervals. The inspection may require maintenance to be carried out earlier, depending on the results.
Inspection and maintenance work – Overview (Page 39)
Page 23
Inspection and maintenance 10
0020177746_03 ENERGY Installation and maintenance instructions 23
10.3 Procuring spare parts
The original components of the product were also certified by the manufacturer as part of the declaration of conformity. If you use other, non-certified or unauthorised parts during maintenance or repair work, this may void the conformity of the product and it will therefore no longer comply with the applicable standards.
We strongly recommend that you use original spare parts from the manufacturer as this guarantees fault-free and safe operation of the product. To receive information about the available original spare parts, contact the contact address provided on the reverse of these instructions.
If you require spare parts for maintenance or repair
work, use only the spare parts that are permitted for the product.
10.4 Checking the COcontent
1. Start up the product with the check programme (P.01) and set the value.
– Setting value for the programme P.01: 100 Check programmes – Overview (→ Page 30)
2. Wait until the value that is read is stable. – Waiting period for reading a stable value: 5 min
1
3. Unscrew the cover from the flue gas analysis point (1).
4. Measure the COcontent at the flue gas analysis point (1).
5. Compare the measured value with the corresponding value in the table.
Checking the COcontent
Great Britain
front casing on / front casing off
Natural gas
G20
9.2 ±1 %
The value is OK.The value is not OK; you cannot start up the
product.
Set the COcontent. (Page 23)
10.5 Setting the COcontent
Conditions: The COcontent must be adjusted
1
A
B
Remove the sticker.Turn the screw (1) to set the COcontent (value with
front casing removed).
To increase the COcontent: Turn anti-clockwiseTo decrease the COcontent: Turn clockwise
Only carry out the adjustment in increments of 1/8 turn
and wait approximately 1 minute after each adjustment until the value has stabilised.
Compare the measured value with the corresponding
value in the table.
Setting the COvalue
Great Britain
front casing on / front casing off
Natural gas
G20
COat full load
9.2 ±0.2 %
Set for Wobbe index W
14.09 kWh/m³
Oat full load
4.5 ±1.8 vol. %
CO at full load
250 ppm
CO/CO
0.0027
If the setting is not in the specified adjustment range,
you must not start up the product.
Inform Customer Service.
Check whether the air-quality requirements with regard
to carbon monoxide are fulfilled.
Fit the front panel.
Page 24
10 Inspection and maintenance
10.6 Removing the gas-air mixture unit
Note
The gas-air mixture unit consists of three main components:
Fan
Gas valve,
Burner cover
1. Switch off the product via the main switch.
2. Close the gas isolator cock.
3. Remove the front casing. (Page 10)
C
A
B
1
D
2
4. Remove the screw (1).
5. Push the clip upwards.
6. Remove the flue gas pipe (2).
3
4
5
A
B
7. Remove the air intake pipe (3).
8. Remove the plugs from the gas valve (4) and from the fan (5).
A
C
D
B
6
9. Remove the gas-air mixture unit (6).
7
7
8
10. Remove the burner seals (7) and the burner (8).
11. Check the burner and the heat exchanger for damage and dirt.
12. If necessary, clean or replace the components accord­ing to the following sections.
13. Install the two new burner seals.
10.7 Cleaning the heat exchanger
1
1. Protect the folded down electronics box against sprayed
water.
2. Clean the ribs of the heat exchanger (1) with water.
The water runs out into the condensate tray.
Page 25
Inspection and maintenance 10
0020177746_03 ENERGY Installation and maintenance instructions 25
10.8 Checking the burner
1. Search the surface of the burner for possible damage. If you see any damage, replace the burner.
2. Install the two new burner seals.
10.9 Checking the ignition electrode
1
2
3 4 5
1. Disconnect the connection (2) and the earthing cable (1).
2. Remove the fixing screws (3).
3. Carefully remove the electrode from the combustion chamber.
4. Check that the electrode ends (4) are undamaged.
5. Check the electrode distance. – Clearance for the ignition electrodes: 3.5 … 4.5 mm
6. Make sure that the seal (5) is free from damage.
If necessary, replace the seal.
10.10 Cleaning the condensate siphon
C
2
3
1
A
B
1. Unclip the lower section of the siphon (1) from the up­per section of the siphon (2).
2. Remove the float (3).
3. Flush out the float and lower section of the siphon with water.
4. Fill the lower section of the siphon with water up to 10 mm below the upper edge of the condensate drain pipe­work.
5. Reinsert the float (3).
Note
Check whether the float is present in the condensate siphon.
6. Clip the lower section of the siphon (1) into the upper section of the siphon (2).
10.11 Cleaning the filter in the cold water inlet
1. Close the main cold water supply line.
2. Drain the product on the hot water side.
3. Remove the connection piece from the connection for the product's cold water supply.
4. Clean the filter in the cold water inlet without removing it.
10.12 Cleaning the heating filter
2
1
1. Remove the temperature sensor (1).
2. Remove the upper clip (2).
4
3
5
3. Remove the lower clip (3).
4. Remove the flow pipe (4).
5. Remove the heating filter (5) and clean it.
6. Reinstall the components in the reverse order.
Page 26
11 Troubleshooting
10.13 Installing the gas-air mixture unit
1. Install the burner.
2. Install two new burner seals in the burner hood.
3. Install the gas-air mixture unit.
4. Tighten the screws on the gas-air mixture unit.
– Ideally to 7 Nm if a torque spanner is available.
5. Install the flue pipe.
6. Install the air intake pipe.
10.14 Draining the product
1. Close the service valves of the product.
2. Start check programme P.05 (Page 16). Check programmes – Overview (Page 30)
3. Open the drain cock.
10.15 Checking the admission pressure of the
expansion vessel
1. Measure the pre-charge pressure of the expansion ves­sel at the vessel valve.
Conditions: Pre-charge pressure < 0.075 MPa (0.75 bar)
Top up the expansion vessel in accordance with the
static height of the heating installation, ideally with ni­trogen, otherwise with air. Ensure that the drain valve is open when topping up.
2. If water escapes from the expansion vessel's valve, you must replace the expansion vessel (Page 28).
3. Fill and purge the heating installation. (Page 18)
10.16 Completing inspection and maintenance
work
1. Check the COcontent.
10.17 Checking the product for leak-tightness
Check that the product is leak-tight. (Page 20)
11 Troubleshooting
11.1 Rectifying faults
If fault codes (F.XX) appear, refer to the table in the ap-
pendix or use the check programme(s). Overview of fault codes (Page 35) Check programmes – Overview (Page 30)
If several fault codes are generated at the same time, these are displayed alternately followed by the time at which the respective fault occurred.
Hold the button down for more than 3 seconds.
If you are unable to clear the fault code and it reappears
despite several fault clearance attempts, contact cus­tomer service.
11.2 Calling up the fault memory
The last 10 fault codes are stored in the fault memory (to­gether with the time at which the respective fault occurred and, after 24 hours, with the number of days).
Hold the button down for more than 7 seconds. Overview of fault codes (Page 35)
Press the button to exit this menu.
11.3 Deleting the fault memory
1. Delete the fault memory using the diagnostics code d.94.
2. Set the diagnostics code. (Page 15) Overview of diagnostics codes (Page 30)
11.4 Resetting parameters to factory settings
1. Reset all parameters to the factory settings using the diagnostics code d.96.
2. Set the diagnostics code. (Page 15) Overview of diagnostics codes (Page 30)
11.5 Preparing the repair work
1. Switch off the product.
2. Disconnect the product from the electrical installation.
3. Remove the front casing.
4. Close the gas stopcock.
5. Close the service valves in the heating flow and in the heating return.
6. Close the service valve in the cold water pipe.
7. Drain the product if you want to replace water-bearing components of the product.
8. Ensure that water does not drip on live components (e.g. the electronics box).
9. Use only new seals and O-rings. Do not use any addi­tional sealing materials.
11.6 Replacing defective components
11.6.1 Replacing the burner
1. Remove the gas-air mixture unit. (Page 24)
2. Remove the two burner seals.
3. Remove the burner.
4. Insert the new burner.
5. Insert two new burner seals in the burner cover.
6. Install the gas-air mixture unit. (Page 26)
11.6.2 Replacing the gas-air mixture unit
1. Remove the gas-air mixture unit. (Page 24)
2. Install the new gas-air mixture (Page 26).
11.6.3 Replacing the heat exchanger
1. Remove the front casing. (Page 10)
2. Remove the gas-air mixture unit. (Page 24)
Page 27
Troubleshooting 11
0020177746_03 ENERGY Installation and maintenance instructions 27
1
A
B
3. Remove the gas pipe (1).
1
2
3
2 4
A
B
4. Remove the temperature sensor (3).
5. Remove the upper clip (1).
6. Remove the lower clip (4).
7. Remove the supply pipe (2).
2
2 3
B
1
A
8. Remove the upper clip (1).
9. Remove the lower clip (3).
10. Remove the return pipe (2).
1
A
2
11. Remove the clip underneath the condensate tray (1).
12. Undo the four screws (2).
2
1
B
C
A
13. Remove the ignition electrode (1).
14. Lift the heat exchanger up slightly and remove it to­gether with the condensate tray.
15. Remove the ignition transformer (2).
16. Install the new heat exchanger in reverse order.
11.6.4 Replacing the pump head
1
2
1. Disconnect the pump cable from the electronics box.
2. Undo the four bolts (1).
3. Remove the pump head (2).
4. Replace the O-ring.
5. Use four screws to secure the new pump head.
6. Connect the pump cable to the electronics box.
Page 28
11 Troubleshooting
11.6.5 Replacing the expansion vessel
B
C
1
2
3
A
D
1. Undo the nut (3).
2. Remove both screws on the support plate (1).
3. Remove the support plate.
4. Pull out the expansion vessel (2) towards the front.
5. Insert the new expansion vessel into the product.
6. Screw the new expansion vessel to the water connec­tion. To do this, use a new seal.
7. Attach the support plate using both screws.
8. Fill and purge the product (Page 18) and, if required, the heating installation.
11.6.6 Replacing the main PCB
C
C
D
B
A
A
1. Open the electronics box.
2. Pull all of the plugs out from the PCB.
3. Undo the clips on the PCB.
4. Remove the PCB.
5. Install the new PCB in such a way that it clicks into the groove at the bottom and into the clip at the top.
6. Plug in the PCB plugs.
7. Close the electronics box.
11.6.7 Replacing the PCB for the user interface
B
C
C
D
A
A
1. Open the electronics box.
2. Pull the plug out of the PCB.
3. Undo the clips on the PCB.
4. Remove the PCB.
5. Install the new PCB in such a way that it clicks into the groove at the bottom and into the clip at the top.
6. Plug in the PCB plug.
7. Close the electronics box.
11.6.8 Replacing the expansion relief valve
1
2
1. Remove the clip (2).
2. Remove the expansion relief valve.
3. Fit the new expansion relief valve with a new O-ring.
4. Reattach the clip (2).
Page 29
Decommissioning the product 12
0020177746_03 ENERGY Installation and maintenance instructions 29
11.6.9 Replacing the volume flow sensor
1
B
A
1. Pull out the plug.
2. Remove the volume flow sensor (1).
3. Install the new volume flow sensor.
4. Plug in the plug.
11.6.10 Replace the pressure sensor
1
2
1. Pull out the plug.
2. Remove the clip (1).
3. Remove the pressure sensor (2).
4. Install the new pressure sensor.
5. Reattach the clip (1).
11.7 Checking the product for leak-tightness
Check that the product is leak-tight. (Page 20)
12 Decommissioning the product
Switch off the product.Disconnect the product from the power mains.Close the gas isolator cock.Close the cold water stop cock.
13 Customer service
For contact details for our customer service department, you can write to the address that is provided on the back page, or you can visit www.glow-worm.co.uk.
Page 30
Appendix
Appendix
A Check programmes – Overview
Note
Since the programme table is used for various products, some programmes may not be visible for the product in question.
Display Meaning
P.01 Burner operation on adjustable heat input:
The product operates after ignition with the heat input set between "0" (0% = Pmin) and "100" (100% = Pmax).
The function is active for 15 minutes.
P.02 Burner operation at ignition load:
After ignition, the product works at ignition load.
The function is active for 15 minutes.
P.03 The product runs in heating mode with the maximum heat input set using diagnostics code d.00.
P.04 Maximum output function:
If there is a hot water request, the product runs in hot water handling mode and at maximum heat load.
If there is no hot water request, the product runs with the heating partial load that is set via diagnostics code d.00 and in heating mode.
The function is active for 15 minutes.
P.05 Filling the product:
The diverter valve moves to the mid-position. The burner and pump switch off (to fill or drain the product).
If the pressure is lower than 0.03 MPa (0.3 bar) and then is above 0.05 MPa (0.5 bar) for longer than 15 seconds, the automatic purging function is activated.
The function is active for 15 minutes.
P.06 Purging the heating circuit:
The diverter valve is moved to the heating position.
The function is activated in the heating circuit for 15 minutes.
The pump runs and stops at regular intervals.
If required, this function can be manually switched off.
P.07 Purging the hot water circuit:
The function is activated in the small hot water circuit for 4 minutes and then in the heating circuit for 1 minute.
The pump runs and stops at regular intervals.
If required, this function can be manually switched off.
Automatic air vent function
Purging the product:
If the pressure is lower than 0.03 MPa (0.3 bar) and then is above 0.05 MPa (0.5 bar) for longer than 15 seconds, the automatic purging function is activated.
The function is activated in the small hot water circuit for 4 minutes and then in the heating circuit for 1 minute.
This function cannot be manually switched off.
B Overview of diagnostics codes
Note
Since the code table is used for various products, some codes may not be visible for the product in question.
Dia­gnostics code
Parameter
Values
Unit Increment, select, explanation
Default set­ting
Own setting
Min. Max.
d.00 Heating maximum output kW The maximum heating output
varies depending on the product. Section "Technical data"
Automatic: Unit automatically adjusts the maximum output to the current system demand
Section
"Technical
data"
Adjustable
d.01 Pump overrun in heating
mode
1 60 min 1 5 Adjustable
d.02 Maximum burner anti-
cycling time in heating mode
2 60 min 1 20 Adjustable
Page 31
Appendix
0020177746_03 ENERGY Installation and maintenance instructions 31
Dia­gnostics code
Parameter
Values
Unit Increment, select, explanation
Default set­ting
Own setting
Min. Max.
d.04 Water temperature in the
cylinder
Current value Not
adjustable
d.05 Determined heating flow
set target temperature
Current value
Not
adjustable
d.06 Hot water set target tem-
perature
Current value (Combination unit only) Not
adjustable
d.07 Set target temperature
for the domestic hot wa­ter cylinder
Current value Not
adjustable
d.08 Status of the 230 V ther-
mostat
Current value 0 = Room thermostat open (no
heat requirement)
1 = Room thermostat closed (heat requirement)
Not
adjustable
d.09 Heating flow set target
temperature that is set on the eBUS room ther­mostat
Current value Not
adjustable
d.10 Status of the internal
pump in the heating cir­cuit
Current value off / on Not
adjustable
d.11 Status of the heating
circuit's shunt pump
Current value off / on Not
adjustable
d.13 Status of the hot water
circuit's circulation pump
Current value off / on Not
adjustable
d.14 Operating mode of the
modulating pump
0 5 0 = variable rotational speed
(auto)
1; 2; 3; 4; 5 = Fixed rotational speeds Section "Setting the pump output"
0 Adjustable
d.15 Pump speed Current value % Not
adjustable
d.16 Status of the 24 V room
thermostat
Current value off = Heating off
on = Heating on
Not
adjustable
d.17 Heating control off = Flow temperature
on = Return temperature (ad­justment for underfloor heating. If you have activated the return temperature control, the auto­matic heating output determina­tion function is not active.)
0 Adjustable
d.18 Pump overrun operating
mode
1 3 1 = Continuous (pump runs per-
manently)
3 = Eco (intermittent pump mode – for the dissipation of the resid­ual heat after hot water gener­ation at an extremely low heat demand)
1 Adjustable
d.19 Pump operating mode, 2
stage pump
0 3 0 = Burner mode stage 2, pump
flow/overrun stage 1
1 = Heating mode and pump flow/overrun stage 1, hot water handling mode stage 2
2 = Automatic heating mode, pump flow/overrun stage 1, hot water handling mode stage 2
3 = Stage 2
3 Adjustable
d.20 Maximum hot water set
target temperature
50 60 1 60 Adjustable
d.21 Status of the warm start
for hot water
Current value off = Function deactivated
on = Function activated and available
Not
adjustable
Page 32
Appendix
Dia­gnostics code
Parameter
Values
Unit Increment, select, explanation
Default set­ting
Own setting
Min. Max.
d.22 Status of the hot water
request
Current value off = No current requirement
on = Current requirement
Not
adjustable
d.23 Status of the heating
demand
Current value off = Heating off (Summer mode)
on = Heating on
Not
adjustable
d.24 Status of the pressure
monitor
0 1 off = Not switched
on = Switched
Not
adjustable
d.25 Status of the requirement
to reheat the cylinder or for the hot water warm start from the eBUS ther­mostat
Current value off = Function deactivated
on = Function activated
Not
adjustable
d.27 Function of relay 1
(multi-functional module)
1 10 1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Extractor hood
5 = External solenoid valve
6 = Fault display
7 = Solar pump (omitted)
8 = eBUS remote control
9 = Legionella protection pump
10 = Solar valve
1 Adjustable
d.28 Function of relay 2
(multi-functional module)
1 10 1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Extractor hood
5 = External solenoid valve
6 = Fault display
7 = Solar pump (omitted)
8 = eBUS remote control
9 = Legionella protection pump
10 = Solar valve
2 Adjustable
d.31 Automatic filling device 0 2 0 = Manual
1 = Semi-automatic
2 = Automatic
0 Adjustable
d.33 Fan speed target value Current value rpm Fan speed = Display value x 100 Not
adjustable
d.34 Value for the fan speed Current value rpm Fan speed = Display value x 100 Not
adjustable
d.35 Position of the diverter
valve
Current value 0 = Heating
40 = Mid-position (parallel opera­tion)
100 = Domestic hot water
Not
adjustable
d.36 Value for the hot water
flow
Current value l/min Not
adjustable
d.39 Water temperature in the
solar circuit
Current value Not
adjustable
d.40 Heating flow temperature Current value Not
adjustable
d.41 Heating return temperat-
ure
Current value Not
adjustable
d.43 Heating curve 0.2 4 0.1 1.2 Adjustable
d.45 Value for the base point
of the heating curve
15 30 1 20 Adjustable
d.47 Outside temperature Current value Not
adjustable
d.50 Correction of the min-
imum fan speed
0 3000 rpm 1
Fan speed = Display value x 10
600 Adjustable
Page 33
Appendix
0020177746_03 ENERGY Installation and maintenance instructions 33
Dia­gnostics code
Parameter
Values
Unit Increment, select, explanation
Default set­ting
Own setting
Min. Max.
d.51 Correction of the max-
imum fan speed
-2500 0 rpm 1
Fan speed = Display value x 10
-1000 Adjustable
d.58 Solar circuit reheating 0 3 0 = Boiler's Legionella protection
function deactivated
3 = Hot water activated (min. target value 60 °C)
0 Adjustable
d.60 Number of blocks by the
temperature limiter
Current value Not
adjustable
d.61 Number of unsuccessful
ignitions
Current value Not
adjustable
d.62 Night set-back 0 30 1 0 Adjustable
d.64 Average burner ignition
time
Current value s Not
adjustable
d.65 Maximum burner ignition
time
Current value s Not
adjustable
d.66 Activation of the warm
start function for hot wa­ter
off = Function deactivated
on = Function activated
1 Adjustable
d.67 Remaining burner anti-
cycling time (setting un­der d.02)
Current value min Not
adjustable
d.68 Number of unsuccessful
ignitions at 1st attempt
Current value Not
adjustable
d.69 Number of unsuccessful
ignitions at 2nd attempt
Current value Not
adjustable
d.70 Operation of the diverter
valve
0 2 0 = Normal operating mode
(DHW and heating mode)
1 = Mid-position (parallel opera­tion)
2 = Permanent heating mode position
0 Adjustable
d.71 Maximum heating flow
set target temperature
45 80 1 Section
"Technical
data"
Adjustable
d.73 Correction of the hot wa-
ter warm start temperat­ure
-15 5 1 0 Adjustable
d.75 Maximum cylinder re-
heating time
20 90 min 1 45 Adjustable
d.77 Max. cylinder reheating kW 1
Section "Technical data"
Adjustable
d.80 Running time in heating
mode
Current value h Running time = Display value x
100
Not
adjustable
d.81 Running time in hot wa-
ter handling mode
Current value h Running time = Display value x
100
Not
adjustable
d.82 Number of burner igni-
tions in heating mode
Current value Number of ignitions = Display
value x 100
Not
adjustable
d.83 Number of burner igni-
tions in hot water hand­ling mode
Current value Number of ignitions = Display
value x 100
Not
adjustable
d.84 Maintenance in 0 3000 h Number of hours = Display value
x 10
300 Not
adjustable
d.85 Increase in the min. out-
put (heating and hot wa­ter handling mode)
kW 1 Adjustable
d.88 Flow rate limit value
for ignition in hot water handling mode
0 1 0 = 1.7 l/min (no delay)
1 = 3.7 l/min (2 s delay)
0 Adjustable
d.90 Status of the eBUS room
thermostat
Current value off = Not connected
on = Connected
Not
adjustable
Page 34
Appendix
Dia­gnostics code
Parameter
Values
Unit Increment, select, explanation
Default set­ting
Own setting
Min. Max.
d.91 Status DCF77 Current value Not
adjustable
d.93 Setting the product code 0 99 1
The Device Specific Number (DSN) can be found on the iden­tification plate.
Adjustable
d.94 Delete fault list 0 1 off = No
on = Yes
Adjustable
d.95 Software versions 1 = Main PCB
2 = Interface PCB
Adjustable
d.96 Default setting (reset) 0 = No
1 = Yes
Adjustable
C Status codes – Overview
Note
Since the code table is used for various products, some codes may not be visible for the product in question.
Status code Meaning
Displays in heating mode
S.0 Heating mode: No requirement
S.01 Heating mode: Advance fan operation
S.02 Heating mode: Pump pre-run
S.03 Heating mode: Burner ignition
S.04 Heating mode: Burner on
S.05 Heating mode: Pump/fan overrun
S.06 Heating mode: Fan overrun
S.07 Heating mode: Pump overrun
S.08 Heating mode: Temporary shutdown after heating procedure
Displays in hot water handling mode
S.10 Hot water handling mode: Requirement
S.11 Hot water handling mode: Advance fan operation
S.13 Hot water handling mode: Burner ignition
S.14 DHW mode: Burner on
S.15 DHW mode: Pump/fan overrun
S.16 DHW mode: Fan overrun
S.17 DHW mode: Pump overrun
Display in Comfort mode with warm start or hot water handling mode with cylinder
S.20 Hot water handling mode: Requirement
S.21 Hot water handling mode: Advance fan operation
S.22 Hot water handling mode: Pump pre-run
S.23 Hot water handling mode: Burner ignition
S.24 DHW mode: Burner on
S.25 DHW mode: Pump/fan overrun
S.26 DHW mode: Fan overrun
S.27 DHW mode: Pump overrun
S.28 Hot water handling mode: Temporary shutdown of the burner
Other displays
S.30 Room thermostat is blocking heating mode.
S.31 No heating demand: Summer mode, eBUS controller, waiting period
Page 35
Appendix
0020177746_03 ENERGY Installation and maintenance instructions 35
Status code Meaning
S.32 Fan waiting time: Fan speed outside of the tolerance values
S.33 Forced fan operation until the pressure monitor is switched
S.34 Frost protection active
S.39 Underfloor heating contact open
S.41 Water pressure too high
S.42 Flue non-return flap closed
S.46 Frost protection mode (Comfort): Minimum load
S.53 Product in waiting period/operation block function due to low water pressure (flow/return spread too large)
S.54 Waiting period: Low water pressure in the circuit (flow/return spread too large)
S.76 Maintenance message: Check the water pressure
S.88 Product purging active
S.91 Maintenance: Demo mode
S.96 Automatic test programme: Return temperature sensor, heating demands blocked.
S.97 Automatic test programme: Water pressure sensor, heating demands blocked.
S.98 Automatic test programme: Return temperature sensor, heating demands blocked.
S.99 Internal automatic test programmes
S.108 Purging the combustion chamber, fan in operation
S.109 Product's standby mode activated
D Overview of fault codes
Note
Since the code table is used for various products, some codes may not be visible for the product in question.
Fault code Meaning Possible cause
F.00 Fault: Flow temperature sensor NTC plug not plugged in or has come loose, multiple plug on the PCB not
plugged in correctly, interruption in cable harness, NTC sensor defective
F.01 Fault: Return temperature sensor NTC plug not plugged in or has come loose, multiple plug on the PCB not
plugged in correctly, interruption in cable harness, NTC sensor defective
F.10 Short circuit: Flow temperature sensor NTC sensor defective, short circuit in the cable harness, cable/casing
F.11 Short circuit: Return temperature sensor NTC sensor defective, short circuit in the cable harness, cable/casing
F.12 and
F.91
Short circuit: Cylinder temperature sensor
NTC sensor defective, short circuit in the cable harness, cable/casing
F.13 Short circuit: Domestic hot water cylinder
temperature sensor
NTC sensor defective, short circuit in the cable harness, cable/casing
F.20 Safety switch-off: Overheating temperat-
ure reached
Incorrect earth connection between cable harness and product, flow or return NTC defective (loose connection), stray spark via ignition cable, ignition plug or ignition electrode
F.22 Safety switch-off: Low water pressure in
the boiler
No or insufficient water in the product, water pressure sensor de­fective, cable to the pump or to the water pressure sensor loose/not connected/defective
F.23 Safety switch-off: Temperature difference
too great (NTC1/NTC2)
Pump blocked, insufficient pump output, air in product, flow and return NTC sensors connected the wrong way round
F.24 Safety switch-off: Temperature rise too
fast
Pump blocked, insufficient pump output, air in product, system pressure too low, non-return valve blocked/incorrectly installed
F.25 Safety switch-off: Flue gas temperature
too high
Break in plug connection for optional flue gas safety cut-out (STB), break in cable harness
F.27 Safety switch-off: Fault in flame detection Moisture on the electronics, electronics (flame monitor) defective, gas solen-
oid valve leaking
Page 36
Appendix
Fault code Meaning Possible cause
F.28 Fault: Ignition unsuccessful when startingupGas meter defective or gas pressure monitor has triggered, air in gas, gas
flow pressure too low, thermal isolator device (TAE) has triggered, incorrect gas restrictor, incorrect spare gas valve, fault on the gas valve, multiple plug on PCB incorrectly plugged in, break in cable harness, ignition system (ig­nition transformer, ignition cable, ignition plug, ignition electrode) defective, ionisation current interrupted (cable, electrode), incorrect earthing of product, electronics defective
F.29 Fault: Flame loss Gas supply temporarily stopped, flue gas recirculation, incorrect earthing of
product, ignition transformer has spark failure
F.32 Fan frost protection function active: Fan
speed outside the tolerance values
Plug on fan not correctly plugged in, multiple plug on PCB not correctly plugged in, break in cable harness, fan blocked, Hall sensor defective, elec­tronics defective
F.49 eBUS fault: Voltage too low Short circuit on eBUS, eBUS overload or two power supplies with different
polarities on the eBUS
F.61 Fault: Gas valve control system Short circuit/short to earth in cable harness for the gas valve, gas valve
defective (coils shorted to earth), electronics defective
F.62 Fault: Gas valve switch-off control Delayed switch-off of gas valve, delayed extinguishing of flame signal, gas
valve leaking, electronics defective
F.63 Fault: EEPROM Electronics defective
F.64 Fault: Electronics/sensor/analogue-to-
digital converter
Flow or return NTC short circuited, electronics defective
F.65 Fault: Electronics temperature too high Electronics overheating due to external influences, electronics defective
F.67 Value sent back by ASIC is incorrect
(flame signal)
Implausible flame signal, electronics defective
F.68 Fault: Unstable flame (analogue input) Air in gas, gas flow pressure too low, incorrect air ratio, incorrect gas re-
strictor, ionisation flow interruption (cable, electrode)
F.70 Invalid product code (DSN) Display and PCB replaced at same time and Device Specific Number not
reset, wrong or missing output range coding resistance
F.71 Fault: Flow/return temperature sensor Flow temperature sensor signalling constant value: Flow temperature sensor
incorrectly positioned on supply pipe, flow temperature sensor defective
F.72 Fault: Deviation in the water pressure
sensor/return temperature sensor
Flow/return NTC temperature difference too great flow and/or return tem­perature sensor defective
F.73 Fault: Water pressure sensor not con-
nected or has short-circuited
Interruption/short circuit of water pressure sensor, interruption/short circuit to GND in supply line to water pressure sensor or water pressure sensor defective
F.74 Fault: Electrical problem in the water
pressure sensor
Line to water pressure sensor has a short circuit to 5 V/24 V or internal fault in the water pressure sensor
F.75 Fault: Pressure sensor Pressure switch defective
F.76 The safety cut-out in the primary heat
exchanger is defective
Safety cut-out feedback does not match the gas valve feedback
F.77 Fault: Condensate or smoke No response, flue non-return flap defective
F.78 Interruption to DHW outlet sensor at
external controller
UK link box is connected, but hot water NTC not bridged
F.83 Fault: Dry fire When the burner starts, the temperature change registered at the flow or
return temperature sensor is non-existent or too small: Insufficient water in the product, the flow or return temperature sensor is not in the correct position on the pipe
F.84 Fault: Flow/return temperature sensor Values not consistent, difference < -6 K
Flow and return temperature sensors signalling implausible values: Flow and return temperature sensors have been inverted, flow and return temperature sensors have not been correctly installed
F.85 Fault: Temperature sensor The flow and/or return temperature sensors have been installed on the same
pipe/incorrect pipe
Temperature sensor not connected or is connected incorrectly
F.86 Fault: Underfloor heating contact Underfloor heating contact open, sensor disconnected or defective
F.87 Fault: Electrodes Electrodes not connected or they are connected incorrectly, short circuit in
the cable harness
F.88 Fault: Gas valve Gas valve not connected or it is connected incorrectly, short circuit in the
cable harness
F.89 Fault: Pump Pump not connected or it is connected incorrectly, incorrect pump connec-
ted, short circuit in the cable harness
Page 37
Appendix
0020177746_03 ENERGY Installation and maintenance instructions 37
Fault code Meaning Possible cause
Connection No communication between the PCB
and the user interface
Electronics defective
E Wiring diagram: Combi boiler
X2
X14
X21
L
N
19
10
20
2
6
3
11
13
14
18
7
17
8
X51
X51
X20
16
1 9
3
15
4
5
10
11
6
13
X51 X35
X20
X40 X51
X30
X2
X21
X41
X22
X14
L
N
+
24V=
RT BUS
Burner
off
RT
230Vac
X1
FUS
X106
X32
X90
X12
X35
X1
L
N
RT 230Vac
X35
4
1
3 2
eBUS
RT 24V
Burner off
X106
1
3
4
1
3
3
1
2
M
1
3
4
6
1
2
3
M
5
4
2
1
2
1
2
1
N
L
L
24V
230V~
24V
230V~
2
7
8
9
10
12
11
1
4
3
5
6
14
13
1 Main PCB
2 Interface PCB
3 Timer
4 Temperature sensor on the heating flow
5 Temperature sensor on the heating return
6 Fan
7 Gas valve assembly
8 3-port diverter valve
9 Pressure sensor
10 Flow rate sensor
11 External ignition transformer
12 Heating pump
13 Ionisation and ignition electrode
14 Main power supply and connection for 230 V control
Page 38
Appendix
F Wiring diagram: Combi boiler (35 kW)
X20
X40 X51
X30
X2
X21
X41
X22
X14
L
N
+
24V=
RT BUS
Burner
off
RT
230Vac
X1
FUS
X106
X32
X90
X12
X35
X2
X14
L
N
19
10
20
2
6
3
11
13
14
18
7
17
8
X12
L
N
X51
X51
X20
16
1 9
3
15
4
5
10
11
6
13
X51
X1
X21
L
N
RT 230Vac
4 3
1
2
eBUS
RT 24V
Burner off
X106
X35
1
3
4
1
3
3
1
2
M
1
3
4
6
1
2
3
M
4
3
2
1
5
4
2
1
5
6
7
8
2
1
2
1
N
L
L
X35
24V
230V~
24V
230V~
2
7
8
9
10
12
11
1
4
5
6
14
13
3
1 Main PCB
2 Interface PCB
3 Timer
4 Temperature sensor on the heating flow
5 Temperature sensor on the heating return
6 Fan
7 Gas valve assembly
8 3-port diverter valve
9 Pressure sensor
10 Flow rate sensor
11 External ignition transformer
12 Heating pump
13 Ionisation and ignition electrode
14 Main power supply and connection for 230 V control
Page 39
Appendix
0020177746_03 ENERGY Installation and maintenance instructions 39
G Inspection and maintenance work – Overview
The table below lists the manufacturer requirements with respect to minimum inspection and maintenance intervals. If na­tional regulations and directives require shorter inspection and maintenance intervals, you should observe these instead of the intervals listed in the table.
No. Work
Inspection
(annual)
Mainten-
ance
(must be
carried out
at regular
intervals)*
1
Check the air/flue pipe for leak-tightness and to ensure that it is fastened correctly. Make sure that it is not blocked or damaged and has been installed in accordance with the relevant Installa­tion Manual.
X X
2
Check the general condition of the product. Remove dirt from the product and from the vacuum chamber.
X X
3
Visually inspect the general condition of the heat exchanger. In doing so, pay particular attention to signs of corrosion, rust and other defects. If you notice any damage, carry out maintenance work.
X X
4
Check the gas connection pressure at maximum heat input. If the gas connection pressure is not within the correct range, carry out maintenance work.
X X
5
Check the COcontent (the air ratio) of the product and, if necessary, adjust it. Keep a record of this.
X X
6
Disconnect the product from the power mains. Check that the electrical plug connections and other connections are seated correctly and correct these if necessary.
X X
7
Close the gas isolator cock and the service valves.
X X
8
Drain the product on the water side. Check the admission pressure of the expansion vessel and top the vessel up if necessary (approx. 0.03 MPa/0.3 bar below the system filling pressure).
X
9
Remove the gas-air mixture unit.
X
10
Check the seals in the combustion area. If you see any damage, replace the seals. Replace both burner seals each time it is opened and accordingly each time maintenance work is carried out.
X
11
Clean the heat exchanger.
X
12
Check the burner for damage and replace it if necessary.
X
13
Check the condensate siphon in the product, clean and fill if necessary.
X X
14
Install the gas-air mixture unit. Caution: Replace the seals.
X
15
If the volume of water is insufficient or the outlet temperature is not reached, replace the second­ary heat exchanger if necessary.
X
16
Clean the filter in the cold water inlet. Replace the filter if impurities can no longer be removed or if the filter is damaged. In this case, also check the impeller sensor for dirt and damage, clean the sensor (do not use compressed air for this) and replace the sensor if it is damaged.
X
17
Open the gas isolator cock, reconnect the product to the power mains and switch the product on.
X X
18
Open the service valves, fill up the product/heating installation to 0.05-0.3 MPa/0.5-3.0 bar (de­pending on the static height of the heating installation) and start purging programme P.XX.
X
19
Perform a test operation of the product and heating installation, including hot water generation, and purge the system once more if necessary.
X X
20
Visually inspect the ignition and burner behaviour.
X X
21 Check the COcontent (the air ratio) of the product again.
X
22
Check the product for gas, flue gas, hot water and condensate leaks, and repair if necessary.
X X
23
Record the inspection/maintenance work carried out.
X X
*Note: For those appliances which are not part of an annual service agreement/policy, maintenance must be carried out at least every 5 years.
Page 40
Appendix
H Position of the opening in the air/flue pipe
G
N
N
MM
A
I
I
O
H
H
C
B
L
J
Q
Q
Q
Q
Q
K
P
D, E
F
I
S
R
T
H.1 Positioning of the opening of a fan-supported flue gas pipe
Installation site
Minimum dimen­sions
A
Directly below an opening, air bricks, opening windows, etc., that can be opened. 300 mm
B Above an opening, air bricks, opening windows, etc., that can be opened. 300 mm
C Horizontally to an opening, air bricks, opening windows, etc., that can be opened. 300 mm
D
Below temperature-sensitive building components, e.g. plastic gutters, down pipes or wastewater pipes
75 mm
E Below eaves 200 mm
F Below balconies or car port roofs 200 mm
G From vertical wastewater pipes or down pipes 150 mm
H From external or internal corners 200 mm
I Above floors, roofs or balconies 300 mm
J From a surface facing a terminal 600 mm
K From a terminal facing a terminal 1,200 mm
L From an opening in the car port (e.g. door, window) which leads into the dwelling 1,200 mm
M Vertical from a terminal on the same wall 1,500 mm
N Horizontal from a terminal on the same wall 300 mm
O From the wall on which the terminal has been installed 0 mm
P From a vertical structure on the roof 300 mm
Q Above the roof area 300 mm
R Horizontal from adjacent windows on pitched or flat roofs 600 mm
S Above adjacent windows on pitched or flat roofs 600 mm
T Below adjacent windows on pitched or flat roofs 2,000 mm
Page 41
Appendix
0020177746_03 ENERGY Installation and maintenance instructions 41
H.2 Horizontal terminal positioning
BS 5440-1 recommends that fanned flue chimney terminals should be positioned as follows:
a) at least 2 m from an opening in the building directly opposite, and
b) so that the products of combustion are not directed to discharge directly across a boundary if the products are likely to cause a nuisance to a neighbour or discharge over a walkway or patio.
For IE see current issue of IS 813.
For boilers covered within this manual.
1) Dimensions D, E, F and G:
These clearances may be reduced to 25 mm without affecting the performance of the boiler. In order to ensure that the con­densate plume does not affect adjacent surfaces the terminal should be extended as shown below.
Balcony/eaves
Gutter
Adequately secured air/flue gas pipe
The flue pipe must protrude beyond any overhang
2) Dimension H:
This clearance may be reduced to 25 mm without affecting the performance of the boiler. However, in order to ensure that the condensate plume does not affect adjacent surfaces a clearance of 300 mm is preferred.
For 1 and 2 above you can use a flue gas management kit to enable the termination point to be positioned and directed away from the building fabric.
Page 42
Appendix
I Commissioning Checklist
© Heating and Hotwater Industry Council (HHIC)
www.centralheating.co.uk
Benchmark Commissioning and Servicing Section
It is a requirement that the boiler is installed and commissioned to the
completed in full.
Page 43
Appendix
0020177746_03 ENERGY Installation and maintenance instructions 43
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
GAS BOILER SYSTEM COMMISSIONING CHECKLIST
CONTROLS
Optimum start control
Fitted
Fitted
Fitted
Fitted
ALL SYSTEMS
Yes
Yes
CENTRAL HEATING MODE
OR
mbar OR mbar
COMBINATION BOILERS ONLY
Yes
Yes
DOMESTIC HOT WATER MODE
OR
mbar OR mbar
Yes Temperature
CONDENSING BOILERS ONLY
Yes
ALL INSTALLATIONS
AND
²
Ratio
AND
²
Ratio
Yes
Yes
Yes
Yes
Page 44
Appendix
It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed.
Service Provider
SERVICE RECORD
SERVICE 01
AND
²
%
AND
²
%
SERVICE 02
AND
²
%
AND
²
%
SERVICE 03
AND
²
%
AND
²
%
SERVICE 04
AND
²
%
AND
²
%
SERVICE 05
AND
²
%
AND
²
%
SERVICE 06
AND
²
%
AND
²
%
SERVICE 07
AND
²
%
AND
²
%
SERVICE 08
AND
²
%
AND
²
%
SERVICE 09
AND
²
%
AND
²
%
SERVICE 10
AND
²
%
AND
²
%
Page 45
Appendix
0020177746_03 ENERGY Installation and maintenance instructions 45
PRIOR TO CO AND COMBUSTION RATIO CHECK
The boiler manufacturer’s installation instructions should have been followed, gas type verified and gas
supply pressure/rate checked as required prior to commissioning.
As part of the installation process, especially where a flue has been fitted by persons other than the
boiler installer, visually check the integrity of the whole flue system to confirm that all components are
correctly assembled, fixed and supported. Check that manufacturer’s max. flue lengths have not been
exceeded and all guidance has been followed (e.g. Gas Safe Technical Bulletin TB008).
The flue gas analyser should be of the correct type, as specified by BS 7967
Prior to its use, the flue gas analyser should have been maintained and calibrated as specified by the
manufacturer. The installer must have the relevant competence for use of the analyser.
Check and zero the analyser IN FRESH AIR as per analyser manufacturer’s instructions.
NOTE
THE AIR GAS RATIO VALVE IS FACTORY
SET AND MUST NOT BE ADJUSTED DURING COMMISSIONING UNLESS THIS ACTION IS RECOMMENDED FOLLOWING
CONTACT WITH THE MANUFACTURER. If any such adjustment is recommended and further checking of the boiler is required the
installer/service engineer must be competent
to carry out this work and to use the flue gas
analyser accordingly.
If the boiler requires conversion to operate with
a different gas family (e.g. conversion from
natural gas to LPG) separate guidance will be
provided by the boiler manufacturer
CARRY OUT FLUE INTEGRITY CHECK USING ANALYSER
Insert analyser probe into air inlet test point and allow readings to stabilise.
NOTE - where no air inlet test point is provided then a flue integrity check
with the analyser is not possible. The installer should verify that flue
integrity has been visually checked in accordance with the “Prior to
CO and combustion ratio check” box above before proceeding to the
“Check CO and combustion ratio at maximum rate” stage below.
SET BOILER TO MINIMUM RATE
In accordance with boiler instructions, set boiler to operate at minimum rate (to
minimum load condition). Allow sufficient time for combustion to stabilise.
NOTE - If manufacturer’s instructions do not specify how to set boiler to minimum
rate contact Technical Helpline for advice.
CHECK CO AND COMBUSTION RATIO AT MINIMUM RATE
With boiler still set at minimum rate, insert analyser probe into flue gas sampling
point. Allow readings to stabilise before recording.
NOTE - If no flue gas sampling point is present and the correct procedure is not
specified in the manual, consult boiler manufacturer for guidance.
CHECK CO AND COMBUSTION RATIO AT MAX. RATE
With boiler still set at maximum rate, insert analyser probe into flue gas
sampling point. Allow readings to stabilise before recording.
NOTE - If no flue gas sampling point is present and the correct procedure is
not specified in the manual, consult boiler manufacturer for guidance.
SET BOILER TO MAXIMUM RATE
In accordance with boiler instructions, set boiler to operate at max. rate
(full load condition). Allow sufficient time for combustion to stabilise.
NOTE - Do not insert analyser probe during this period to avoid
possible “flooding” of sensor.
Is CO less than 350ppm and CO/CO
2
ratio
less than 0.004
Is
O
2
20.6%
and
CO
2
< 0.2%
Is CO less than 350ppm and CO/CO
2
ratio
less than 0.004
BOILER IS OPERATING SATISFACTORILY
no further actions required.
Ensure test points are capped, boiler case is correctly replaced and
all other commissioning procedures are completed.
Complete Benchmark Checklist, recording CO and combustion ratio
readings as required.
TURN OFF APPLIANCE AND CALL
MANUFACTURER’S TECHNICAL HELPLINE
FOR ADVICE.
THE APPLIANCE MUST NOT BE
COMMISSIONED UNTIL PROBLEMS ARE
IDENTIFIED AND RESOLVED.
VERIFY FLUE INTEGRITY
Analyser readings indicate that combustion products
and inlet air must be mixing. Further investigation of
the flue is therefore required.
Check that flue components are assembled, fixed
and supported as per boiler/flue manufacturer’s
instructions.
Check that flue and flue terminal are not obstructed.
Is
CO
less than
335ppm
and
CO/CO
2
ratio less
than 0.004
Is
O
2
20.6%
and
CO
2
< 0.2%
Check all seals around the appliance burner,
internal flue seals, door and case seals.
Rectify where necessary.
TURN OFF APPLIANCE AND CALL
MANUFACTURER’S TECHNICAL HELPLINE
FOR ADVICE.
THE APPLIANCE MUST NOT BE
COMMISSIONED UNTIL PROBLEMS ARE
IDENTIFIED AND RESOLVED. IF
COMMISSIONING CANNOT BE FULLY
COMPLETED, THE APPLIANCE MUST BE
DISCONNECTED FROM THE GAS SUPPLY IN
ACCORDANCE WITH THE GSIUR.
NOTE: Check and record CO and combustion ratio
at both max. and min. rate before contacting the
manufacturer.
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
Page 46
Appendix
J Pipe lengths for the air/flue pipe
J.1 Length of the C13 type air/flue pipe
Applicability: C13 type air/flue pipe
Diameter of the air/flue pipe
Dia. 60/100 (L) Dia. 80/125 (L)
C13 type air/flue pipe
C13 type air/flue pipe
ENERGY 25c -A (H-GB)
10 m 25 m
ENERGY 30c -A (H-GB)
10 m 25 m
ENERGY 35c -A (H-GB)
10 m 25 m
J.2 Length of the C33 type air/flue pipe
Applicability: C33 type air/flue pipe
Diameter of the air/flue pipe
Dia. 60/100 (L) Dia. 80/125 (L)
C33 type air/flue pipe
C33 type air/flue pipe
ENERGY 25c -A (H-GB)
10 m 25 m
ENERGY 30c -A (H-GB)
10 m 25 m
ENERGY 35c -A (H-GB)
10 m 25 m
J.3 Length of the C43 type air/flue pipe
Applicability: C43 type air/flue pipe
Diameter of the air/flue pipe
Dia. 60/100 (L)
C43 type air/flue pipe
ENERGY 25c -A (H-GB)
5 m
ENERGY 30c -A (H-GB)
5 m
ENERGY 35c -A (H-GB)
5 m
K Technical data
Technical data – Heating
ENERGY 25c -A (H­GB)
ENERGY 30c -A (H­GB)
ENERGY 35c -A (H­GB)
Max. flow temperature adjustment range (default setting: 75 °C)
10 … 80 10 … 80 10 … 80
Maximum permissible pressure
0.3 MPa
(3.0 bar)
0.3 MPa
(3.0 bar)
0.3 MPa
(3.0 bar)
Nominal water flow (ΔT = 20 K)
788 l/h 1,094 l/h 1,102 l/h
Nominal water flow (ΔT = 30 K)
525 l/h 729 l/h 876 l/h
Page 47
Appendix
0020177746_03 ENERGY Installation and maintenance instructions 47
ENERGY 25c -A (H­GB)
ENERGY 30c -A (H­GB)
ENERGY 35c -A (H­GB)
Approximate value for the condensate volume (pH value between 3.5 and 4.0) at 50/30 °C
1.84 l/h 2.55 l/h 2.57 l/h
ΔP heating at nominal flow (ΔT = 20 K)
0.025 MPa
(0.250 bar)
0.025 MPa
(0.250 bar)
0.018 MPa
(0.180 bar)
Technical data – G20 power/loading G20
The lowest nominal heat output may be higher than the value in the technical data, depending on the design of the system and the current operating status.
ENERGY 25c -A (H­GB)
ENERGY 30c -A (H­GB)
ENERGY 35c -A (H­GB)
Maximum heat output
18 kW 25 kW 25 kW
Effective output range (P) at 40/30 °C
5.4 … 19.5 kW 6.5 … 27.0 kW 7.6 … 27.2 kW
Effective output range (P) at 50/30 °C
5.3 … 19.1 kW 6.3 … 26.5 kW 7.5 … 26.7 kW
Effective output range (P) at 80/60 °C
5.0 … 18.3 kW 6.1 … 25.4 kW 7.2 … 25.6 kW
Domestic hot water heat output (P)
5.0 … 25.2 kW 6.0 … 30.0 kW 7.1 … 35.0 kW
Maximum heat input – heating (Q max.)
18.4 kW 25.5 kW 25.7 kW
Minimum heat input – heat­ing (Q min.)
5.1 kW 6.1 kW 7.2 kW
Maximum heat input – hot water (Q max.)
25.7 kW 30.6 kW 35.7 kW
Minimum heat input – hot water (Q min.)
5.1 kW 6.1 kW 7.2 kW
Technical data – Domestic hot water
ENERGY 25c -A (H­GB)
ENERGY 30c -A (H­GB)
ENERGY 35c -A (H­GB)
Specific flow rate (D) (ΔT = 30 K) in accordance with EN 13203
12.1 l/min 14.2 l/min 16.5 l/min
Continuous flow rate (ΔT = 35 K)
622 l/h 730 l/h 849 l/h
Specific flow rate (ΔT = 35 K)
10.4 l/min 12.2 l/min 14.1 l/min
Minimum permissible pressure
0.03 MPa
(0.30 bar)
0.03 MPa
(0.30 bar)
0.03 MPa
(0.30 bar)
Maximum permissible pressure
1 MPa
(10 bar)
1 MPa
(10 bar)
1 MPa
(10 bar)
Recommended pressure
0.2 MPa
(2.0 bar)
0.2 MPa
(2.0 bar)
0.2 MPa
(2.0 bar)
Temperature range
35 … 60 35 … 60 35 … 60
Flow rate limiter
8.0 l/min 10.0 l/min 12.0 l/min
Technical data – General
ENERGY 25c -A (H­GB)
ENERGY 30c -A (H­GB)
ENERGY 35c -A (H­GB)
Gas category
I
2H
I
2H
I
2H
Diameter of the gas pipe
1/2 inch 1/2 inch 1/2 inch
Diameter of the heating connec­tions
3/4 inch 3/4 inch 3/4 inch
Expansion relief valve connector (min.)
15 mm 15 mm 15 mm
Condensate drain pipework (min.)
21.5 mm 21.5 mm 21.5 mm
G20 gas supply pressure
2.0 kPa
(20.0 mbar)
2.0 kPa
(20.0 mbar)
2.0 kPa
(20.0 mbar)
Page 48
Appendix
ENERGY 25c -A (H­GB)
ENERGY 30c -A (H­GB)
ENERGY 35c -A (H­GB)
Gas flow at P max. – hot water (G20)
2.7 m³/h 3.2 m³/h 3.8 m³/h
Gas flow at P max. – heating mode (G20)
1.9 m³/h 2.7 m³/h 2.7 m³/h
Gas flow at P min. (G20)
0.540 m³/h 0.646 m³/h 0.762 m³/h
CE number (PIN)
CE-0063CP3646 CE-0063CP3646 CE-0063CP3646
Flue gas mass rate in heating mode at P min.
2.34 g/s 2.80 g/s 3.30 g/s
Flue gas mass rate in heating mode at P max.
8.3 g/s 11.5 g/s 11.6 g/s
Flue gas mass rate in hot water handling mode at P max.
11.6 g/s 13.8 g/s 16.1 g/s
Flue gas temperature (80 °C/60 °C) at P max.
60 77 82
Flue gas temperature (80 °C/60 °C) at P min.
55 55 56
Flue gas temperature (50 °C/30 °C) at P max.
51 62 56
Flue gas temperature (50 °C/30 °C) at P min.
34 35 37
Flue gas temperature in hot water handling mode
69 68 75
Flue gas temperature when over­heating
105 95 104
Released system types
C13, C33, C43 C13, C33, C43 C13, C33, C43
Nominal efficiency at 80/60 °C
99.6 % 99.6 % 99.6 %
Nominal efficiency at 50/30 °C
104.0 % 104.0 % 104.0 %
Nominal efficiency at 40/30 °C
106.0 % 106.0 % 106.0 %
Nominal efficiency in partial load operation (30%) at 40/30 °C
108.5 % 108.5 % 108.5 %
NOx class
5 5 5
Product dimensions, width
390 mm 390 mm 390 mm
Product dimensions, depth
280 mm 280 mm 280 mm
Product dimensions, height
700 mm 700 mm 700 mm
Net weight
32 kg 33 kg 33 kg
Weight when filled with water
36 kg 38 kg 38 kg
Technical data – Electrics
ENERGY 25c -A (H­GB)
ENERGY 30c -A (H­GB)
ENERGY 35c -A (H­GB)
Electric connection
230 V / 50 Hz 230 V / 50 Hz 230 V / 50 Hz
Built-in fuse (slow-blow)
T2/2A, 250V T2/2A, 250V T2/2A, 250V
Max. electrical power consump­tion
66 W 75 W 60 W
Standby electrical power con­sumption
2 W 2 W 3 W
Level of protection
IPX4D IPX4D IPX4D
Page 49
Index
0020177746_03 ENERGY Installation and maintenance instructions 49
Index
A
Air/flue pipe, installed ............................................................ 5
B
Burner anti-cycling time ....................................................... 21
Bypass valve .......................................................................22
C
CE label .................................................................................8
Check programmes ........................................................... 30
Using..............................................................................16
Checking the burner ............................................................ 25
Checking the pre-charge pressure of the expansion
vessel .................................................................................. 26
Cleaning the condensate siphon.........................................25
Cleaning the heat exchanger ..............................................24
COcontent
Checking.................................................................. 20, 23
Competent person.................................................................4
Completing inspection work ................................................ 26
Completing maintenance work ............................................ 26
Condensate discharge pipe................................................. 12
Condensate siphon
Filling .............................................................................18
Controller............................................................................. 15
Corrosion............................................................................... 5
D
Decommissioning................................................................29
Decommissioning the product ............................................. 29
Diagnostics codes
Using..............................................................................15
Documents ............................................................................ 7
Draining the product ............................................................ 26
E
Electricity ...............................................................................5
Expansion relief valve ......................................................... 28
F
Fault codes ..........................................................................26
Fault memory ...................................................................... 26
Fault messages ................................................................... 26
Fault symbol ........................................................................ 16
Flow rate-pressure curves ...................................................21
Flue gas route .......................................................................5
Front casing, closed .............................................................. 5
Frost ...................................................................................... 5
G
Gas family check ................................................................. 16
Gas flow rate ....................................................................... 18
H
Handing over to the end user .............................................. 22
High-efficiency pump...........................................................21
High-efficiency pump output ................................................21
I
Identification plate ................................................................. 7
If you smell flue gas............................................................... 5
If you smell gas ..................................................................... 4
Inspection work ............................................................. 22, 39
Installation site....................................................................... 5
Intended use.......................................................................... 4
L
Leak-tightness .........................................................20, 26, 29
M
Maintenance work .........................................................22, 39
Minimum clearance ...............................................................9
P
Power supply .......................................................................14
Preparing the repair work ....................................................26
Preparing, repair work ......................................................... 26
Pressure sensor ..................................................................29
Pump head .......................................................................... 27
Q
Qualification...........................................................................4
R
Regulations ...........................................................................6
Removing the air intake pipe...............................................24
Removing the burner ...........................................................24
Removing the flue gas pipe.................................................24
Removing the front casing...................................................10
Removing the gas-air mixture unit....................................... 24
Removing the ignition transformer ......................................24
Removing the side section .................................................. 10
Replacing the burner ........................................................... 26
Replacing the expansion vessel.......................................... 28
Replacing the heat exchanger.............................................26
Replacing the main PCB ..................................................... 28
Replacing the PCB for the user interface............................28
Replacing, expansion vessel ...............................................28
Resetting the burner anti-cycling time ................................. 21
S
Safety device .........................................................................5
Schematic drawing ................................................................ 5
Setting the burner anti-cycling time ..................................... 21
Spare parts ..........................................................................23
Switching on the product .....................................................18
T
Tool .......................................................................................6
Transport ...............................................................................5
Transporting .......................................................................... 8
Treating the heating water .................................................. 16
U
Unloading the box ................................................................. 8
Unpacking the product .......................................................... 8
Using
Check programmes .......................................................16
Diagnostics codes..........................................................15
V
Voltage .................................................................................. 5
Volume flow sensor ............................................................. 29
W
Wall-mounting the product .................................................... 9
Weight ................................................................................... 9
Page 50
Page 51
Page 52
0020177746_03
Manufacturer/Supplier
Vaillant Group UK LTD
Nottingham Road ‒ Belper ‒ Derbyshire DE56 1JQ Telephone 01773 824639 ‒ Technical helpline 0330 100 7679 After sales service 0330 100 3142
www.glow-worm.co.uk
0020177746_03 16.11.2017
© These instructions, or parts thereof, are protected by copyright and may be repro­duced or distributed only with the manufacturer's written consent.
We reserve the right to make technical changes.
Loading...