Please read these instructions and follow them carefully for the
safe and economical use of your boiler.
The boiler is automatic in operation, once the pilot is lit and the
controls have been set.
Glow-worm Hideaways’ are central heating boilers, to provide
heating and if required an indirect domestic hot water supply.
Gas Safety (Installation and Use) Regulations
In your own interests and that of safety, it is the Law that ALL gas
appliances are installed by a competent person in accordance
with the current issue of the above regulations.
CE Mark
This boiler meets the requirements of Statutory Instrument, No.
3083 The Boiler Efficiency Regulations, and therefore is deemed
to meet the requirements of Directive 92/42/EEC on the efficiency
requirements for new hot water boilers fired with liquid or
gaseous fuels.
Type test for purposes of Regulation 5 certified by:
Notified body 0086.
Product/production certified:
Notified body 0086.
The CE Mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the Laws of
the Member States relating to appliances burning gaseous
fuels.
2. Directive 73/23/EEC on the harmonization of the Laws of the
Member States relating to electrical equipment designed for
use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of
the Members States relating to electromagnetic
compatibility.Information for the Installer and Service Engineer.
Control of Substances Hazardous to Health
Under Section 6 of The Health and Safety at Work Act 1974, we
are required to provide information on substances hazardous to
health.
The adhesives and sealants used in this appliance are cured
and give no known hazard in this state.
Insulation Pads/Ceramic Fibre, Glassyarn
These can cause irritation to skin, eyes and the respiratory tract.
If you have a history of skin complaint you may be susceptible
to irritation. High dust levels are usual only if the material is
broken.
Normal handling should not cause discomfort, but follow normal
good hygiene and wash your hands before eating, drinking or
going to the lavatory.
If you do suffer irritation to the eyes or severe irritation to the skin
seek medical attention.
Boiler Thermostat
These contain very small amounts of xylene in the sealed phial
and capillary. If broken, under normal circumstances the fluid
does not cause a problem, but in cases of skin contact, wash
with cold water.
If swallowed drink plenty of water and seek medical attention.
CONTENTS DESCRIPTION SECTION PAGE No.
INSTRUCTIONS
FOR USE
Introduction3
Lighting the Boiler4
INSTALLATION
INSTRUCTIONS
General Data15
Water Systems27
Flue and Ventilation38
Installation49
Casing Location511
Electrical Wiring612
Commissioning713
Make sure that nothing obstructs the rear side grilles or
clearances. See diagram 1.2 and 1.3 for minimum clearances.
Boilers Installed in a Compartment
If the boiler is fitted in a compartment, cupboard etc., do not
obstruct the purpose built compartment vents or grille on the
boiler.
Do not use the compartment for storage purposes.
Maintenance
To ensure the continued efficient and safe operation of the
boiler it is recommended that it is checked and serviced at
regular intervals. The frequency of servicing will depend upon
the particular installation conditions and usage, but in general
once a year should be enough.
If this appliance is installed in a rented property there is a duty
of care imposed on the owner of the property by the current
issue of the Gas Safety (Installation and Use) Regulations,
Section 35.
It is the law that servicing is carried out by a competent person.
To obtain service please call your installer or Heatcall (Glow-
worm’s own service organisation) using the telephone number
given on the inside of the front panel.
Please be advised that the ‘Benchmark’ logbook should be
completed by the installation engineer on completion of
commissioning and servicing.
All CORGI Registered Installers carry a CORGI ID card, and
have a registration number. Both should be recorded in your
boiler Logbook. You can check your installer is CORGI registered
by calling CORGI direct on :- 01256 372300.
FLUE
BLOCKAGE
SAFETY DEVICE
RESET BUTTON
SETTING
POINTS
E
PIEZO
IGNITION
BUTTON 'C'
GAS
CONTROL
KNOB 'A'
7991
THERMOSTAT
CONTROL
KNOB 'B'
SETTING
POINT
Boiler Electrical Supply
WARNING. This boiler must be earthed.
The boiler must only be connected to a 230V~50Hz supply,
protected by a 3A fuse, maximum.
All wiring must be in accordance with the current issue of
BS7671.
2
Heat resistant cable having a conductor size of 0.75mm
0.22mm), to BS6500 Table 16 must be used.
, (24/
To Connect an Electrical Plug
The colours of three core flexible cable are, Brown - live, Blue
- neutral, Green and yellow - earth.
As the markings on your plug may not correspond with these
colours continue as follows:
The wire coloured brown must be connected to the terminal
marked “L” or Red.
The wire coloured blue must be connected to the terminal
marked “N” or Black.
The wire coloured green and yellow must be connected to the
terminal marked “E”, Green or the earth symbol
.
GAS CONTROL KNOB
= OFF
= PILOT/IGNITION
= MAIN BURNER
Diagram 1
Safety Device
This appliance is fitted with a flue blockage safety device which
will shut down the appliance in the event of abnormal flue
conditions. This device is NOT a substitute for an independently
mounted Carbon Monoxide detector.
The safety device is reset, after three minutes, by pushing in the
button shown in diagram 1.
Shut down can occur during certain climate conditions, but if it
recurs the chimney flue and air inlet into the room must be
checked and any problems found corrected by a competent
person, before the boiler is used again.
3221756A
Instructions for Use
To Light the Boiler
WARNING. If the pilot light goes out for any reason, do not
attempt to relight until three minutes have gone by.
Remove the door by pulling forwards with the fascia at the top.
Lift up to free from bottom side lugs.
Refer to diagram 1 to identify the controls.
Check that the mains electrical supply to the boiler is switched
OFF.
Check that the Flue Blockage Safety Device has not operated,
that is, the button is in. Refer to Safety Device instructions.
Push in slightly and turn gas control knob “A” clockwise until
'is against its setting point.
'
Turn thermostat control knob “B” anticlockwise until “O” is
against its setting point.
Push in slightly and turn gas control knob “A” anticlockwise until
' is against its setting point, then push fully and hold in.
'
Push and release piezo ignition button “C” until the pilot burner
lights.
Air may be present in the supply pipe so the lighting of the pilot
may need to be repeated until all the air has been expelled.
When the pilot is alight, view through window “E”, keep gas
control knob “A” fully pushed in for about 15 seconds, then
release.
If the burner fails to stay alight, wait three minutes, then repeat
the lighting procedure only now keep control knob “A” depressed
for a little longer before releasing. The Flue Blockage Safety
Device may also need resetting, refer to instructions above.
If the gas control knob “A” is turned to '
prevents it being turned on again for a short period. No attempt
should be made to relight the pilot for at least three minutes.
Make sure that the pilot is alight and stable, then switch on the
electrical supply.
Press in and turn gas control knob “A” anticlockwise until '
is against its setting point.
Set any remote controls to call for heat.
Turn the boiler thermostat knob “B” clockwise until “MAX” is
against its setting point and the main burner will light. Adjust
thermostat to required setting between “MIN” and “MAX”.
“MAX” is about 82
Refit the door by fitting the hooked runner at the bottom into the
slot in the side panels and pushing onto the studs.
o
C (180oF).
', a safety lock
To Turn the Boiler Off
For short periods. Turn the boiler thermostat control knob “B”
anticlockwise to “O”. The pilot will remain alight. To relight the
main burner turn the thermostat control knob “B” clockwise to
the desired setting between “MIN” and “MAX”.
For longer periods. Push in slightly and turn gas control knob
“A” fully clockwise until “
thermostat control knob “B” anticlockwise to “O”. Isolate the
boiler from the electrical supply. Follow the full lighting procedure
to relight.
Refer also to “Protection Against Freezing”.
” is against its setting point. Turn
Gas Leak or Fault
If a gas leak or fault exists or is suspected the boiler must be
turned off, including the electrical supply and must not be used
until the fault has been put right. Advice/help should be obtained
from the local gas undertaking or your installation/servicing
company.
Protection Against Freezing
If the boiler is to be out of use for any long period of time during
severe weather conditions we recommend that the whole of the
system including the boiler, be drained off to avoid the risk of
freezing up. If an immersion heater is fitted in the domestic hot
water cylinder make sure it is switched off.
Sheet Metal Parts
WARNING. This appliance contains metal parts (component)
and care should be taken when handling and cleaning, with
particular regard to edges.
Cleaning
Keep the casing clean by wiping it over occasionally with a
damp soapy cloth and dry with a polishing cloth.
'
Do not use abrasive cleaners.
Replacement Parts/Boiler Identification
If replacement parts are required apply to your local supplier or
gas undertaking. Please quote the name of the boiler and its
serial number which can be found on the data label positioned
on the boiler top, to the rear of the inclined flueway cleaning
door.
221756A
Clearance
Minimum clearances must be left around the boiler as shown in
diagram 1.2 and 1.3.
4
A
N
*
C
L
FLUE
1 General
F (MIN)
L (MIN)
H
C
L
FLUE
G
(MIN)
✝A SPECIAL TOP CASING
TO SUIT 600mm (23
5
/
in.)
8
WORKTOPS IS AVAILABLE
GAS CONNECTION
1
Rc
1
/
(
/
2
2
in. B.S.P.T.)
WATER CONNECTIONS
Rc1 (1in. B.S.P.T.)
1177
C
M
E
L
B
D
J (MIN)
K
(MIN)
C
WATER CONNECTIONS Rc1
reduced with DISTRIBUTOR
TUBE to Rc
(pumped return)
✽INSIDE DIAMETER OF
SOCKET FOR 125mm (5in.)
NOMINAL DIAMETER FLUE
TO BS567
GENERAL DIMENSIONS - given in millimetres (Approx. inches)
Warning. When installing or servicing this boiler care should be
taken when handling sheet metal parts, to avoid the possibility
of personal injury.
Important Notice
This boiler is for use only on G20 gas.
Wherever possible, all materials, appliances and components
to be used shall comply with the requirements of British
Standards.
Where no British Standards exist, materials and equipment
should be fit for their purpose and of suitable quality and
workmanship.
1.1 Data
Approx.weight of boiler:98.5kg (217 lb)
RANGE RATING
NOMINAL
HEAT INPUT
(GROSS)
NOMINAL
HEAT
OUTPUT
BURNER
SETTING
PRESSURE
(HOT)
INJECTOR
HIDEAWAY 80
kW
26.0227.929.68
Btu/h
Btu/h
mbar
88,78095,200 101,270
kW
20.5221.9823.45
70,00075,00080,000
11.513.215.2
in.w.g
3
3
/
(
/
in. B.S.P.T.)
4
4
Diagram 1.1
4
minmediummax
4.65.36.1
205753
Water content:8.64litre (1.9 gal)
Gas connection:Rc1/2(1/2 BSP)
Water connection:Rc1 (1inch BSP)
Electrical supply:230V - 50Hz fused at 3A
Burner:Aeromatic
The Seasonal Efficiency Domestic Boilers UK (SEDBUK) is
71.7%.
The value is used in the UK Government’s Standard Assessment
Procedure (SAP) for energy rating of dwellings. The test data
from which it has been calculated have been certified by B.S.I.
1.2 Range Rating
This boiler is range rated and may be adjusted to suit individual
systems. The table gives settings and outputs.
The boiler input is supplied preset to maximum and should be
adjusted to suit system requirements.
1.3 Statutory Requirements
The installation of this boiler must be carried out by a competent
person in accordance with the relevant requirements of the
current issue of:
Manufacturer’s instructions, supplied.
The Gas Safety (Installation and Use) Regulations, The Building
Regulations, Local Water Company Byelaws, The Building
Standards (Scotland) Regulations, applicable in Scotland, The
Health and Safety at Work Act, The Control of Substances
Hazardous to Health, The Electricity at Work Regulations and
any applicable local regulations.
Detailed recommendations are contained in the current issue of
the following British Standards and Codes of Practice:
BS6798, BS5440 Part 1 and 2, BS5449, BS6700, BS6891,
BS5546, BS7478, BS7593, BS7671.
Manufacturer’s instructions must not be taken as overriding
statutory requirements.
5221756A
1 General
1.4 B.S.I. Certification
This boiler is certificated by B.S.I. for safety and performance.
It is, therefore, important that no alteration is made to the boiler
unless approved, in writing, by Hepworth Heating Ltd.
Any alteration not approved by Hepworth Heating Ltd., could
invalidate the B.S.I. certification, boiler warranty and could also
infringe the statutory requirements.
1.5 Gas Supply
The gas installation shall be in accordance with the current
issue of BS6891.
The supply from the governed meter must be of adequate size
to provide a steady inlet working pressure of 20mbar (8in wg) at
the boiler.
On completion test the gas installation using the pressure drop
method and suitable leak detection fluid, purge in accordance
with the current issue of BS6891.
1.6 Electrical
Warning. This boiler must be earthed.
The electrical installation must be carried out by a competent
person. All external components must be of the approved type
and must be connected in accordance with the current issue of
BS7671 and any local regulations which may apply.
Connection of the boiler and any system controls to the mains
supply should be through a 3A fused double pole isolating
switch, having a minimum double pole contact separation of
3mm, serving only the boiler and system controls.
2
Heat resistant flexible cable of at least 0.75mm
issue of BS6500 Table 16 must be used for all connections
within the boiler casing.
, to the current
1.7 Boiler Location
The boiler must not be installed in a room used or intended to
be used as sleeping accommodation or a room containing a
bath or shower.
This boiler is not suitable for installation out of doors.
The boiler must stand on a level floor, conforming with local
authority requirements and building regulations. The base
temperature is within the requirements of the current issue of
BS5258. The boiler may be stood on a wooden floor but a metal
plate is required to protect plastic tiles and similar floor coverings.
Suitable clearance needs to be available at the sides of the
boiler to ease connection of pipework. The actual clearances
will vary according to site conditions.
When the boiler is to be installed level with work surfaces,
minimum clearances to fixtures, walls and the like should be
provided, see diagram 1.2.
To ease minimum clearances it may be necessary to modify
units or fixtures.
A front access clearance should be provided as shown in
diagram 1.3.
The minimum gap behind the top casing is dimension “G” in
diagram1.1. The boiler can be sited further away from the wall
if required to align with kitchen units.
Combustible wall material must be 25mm (1in) away from flue
components.
A special top casing, part number 425562 can be bought, to
enable boiler casings to be arranged flush with 600mm (23
deep worktops.
Where the installation of the boiler will be in an unusual location,
special procedures may be necessary, the current issue of
BS6798 gives detailed guidance on this aspect.
5
/8in)
A compartment used to enclose the boiler must be designed
and constructed specifically for this purpose. An existing
cupboard or compartment modified for the purpose may be
used. Details of essential features of cupboard and compartment
design are given in the current issue of BS6798.
Make sure that nothing will obstruct the side clearances or side
grilles. If installing the boiler in a compartment make sure that
openings and vents are not obstructed.
1.8 Heating System Controls
The heating system should have installed: a programmer and
room thermostat controlling the boiler.
Thermostatic radiator valves may be installed in addition to the
room thermostat.
Note: For further information, see The Building Regulations
1991 - Conservation of fuel and power, 1995 edition - Appendix
G, table 4b.
WORKTOP
254
W
(10 in.)
BOILER
Y
BOILER
Diagram 1.2
Diagram 1.3
Z
8
0911
X
W
MODEL
80
70 - 80
BOILER
W(MIN) X(MIN) Y(MIN) Z(MIN)
mm in mm in mm in mm in
40 1
X
5
/8 6 1/4 437 171/4 10 3/
TOP & SIDE CLEARANCES
WALL OR
FIXTURE
530 (21in.)
FRONT CLEARANCE
1529
221756A
6
2 Water Systems
2.1 Water Pressure Head
This boiler must not be connected to a sealed water system.
This boiler shall only be connected to an open vented cistern
water supply, with a minimum head of 1metre (39in) and a
maximum of 27metre (90ft).
2.2 Inhibitor
Attention is drawn to the current issue of BS5449 and BS7593
on the use of inhibitors in central heating systems.
If an inhibitor is to be used in the system contact should be made
with a manufacturer so that they can recommend their most
suitable product.
If using in an existing system take special care to drain the entire
system, including the radiators, then thoroughly cleaning out
before fitting the boiler, whether or not adding an inhibitor.
2.3 Gravity Domestic Hot Water and Pumped
Central Heating
It is recommended that a cylinder thermostat is used to prevent
the stored water temperature becoming too high when the
heating pump is off.
The domestic hot water primary flow and return must be 28mm
od. The installation must comply with the current issue of
BS5546 and BS6700, see diagram 2.1.
If the above conditions cannot be met, it is suggested that a fully
pumped system is used.
2.4 Pumped Central Heating and Domestic Hot
Water
Where a single flow and return is taken from the boiler, a
minimum static head of 1metre (39in) must be provided between
the water level in the cold water cistern and the centre of the
waterway, see diagram 2.2.
2.5 Circulation Pump
Normally the pump should be set to give a temperature difference
oC
(20oF), across the boiler. At the appropriate flow rate the
of 11
resistance through the boiler can be found by reference to the
pressure loss graph, diagram 2.3.
Use a pump with integral valves or fit valves as close to the
pump as possible.
REFER TO BS 5546
22mm VENT
15mm COLD FEED
INDIRECT
CYLINDER
(Shown with
27metres
Max.
DRAIN OFF
COCK
recommended
thermostat and valve).
28mm
PUMP
BOILER
C
Distributor tube in
pumped return
connection
L
PUMPED HEATING AND GRAVITY
DOMESTIC (DIAGRAMMATIC)
22mm VENT
15mm
COLD FEED
1 metre
MIN.
27metres
MAX.
DRAIN OFF
COCK
TO INDIRECT
CYLINDER
PUMP
BOILER
C
L
Distributor tube in
pumped return
connection
FULLY PUMPED SYSTEM
(DIAGRAMMATIC)
0869
To Heating
Circuit
Diagram 2.1
0870
To Heating
Circuit
Diagram 2.2
2.6 Domestic Hot Water Cylinder
For all systems supplying domestic hot water the cylinder must
be indirect.
2.7 Safety Valve
A safety valve need not be fitted to an open vented system.
2.8 Draining Tap
A drain tap must be fitted at the lowest points of the system
which will allow the draining of the entire system, including the
boiler and domestic hot water cylinder.
FLOW RATE (GALLON/MINUTE)
0123456789
2.00
1.75
1.50
1.25
1.00
0.75
0.50
WATER PRESSURE LOSS
(metre HEAD OF WATER)
0.25
0
6
0
FLOW RATE (LITRES/MINUTE)
12 18
24 30 36 42
PRESSURE LOSS OF BOILER
70
60
50
40
30
20
WATER PRESSURE LOSS
10
0
(INCHES HEAD OF WATER)
Diagram 2.3
7221756A
1074
3 Flue and Ventilation
Important Note
The boiler is fitted with a Flue Blockage Safety Device, which
will shut down the boiler if there is an unacceptable spillage of
products at the draught diverter.
This safety device MUST NOT under any circumstances be
interferred with or put out of action. The safety device must only
be replaced with the Glow-worm parts.
3.1 Flue
The integral draught diverter on the Hideaway range of boilers
makes the combustion performance independent of conditions
in the secondary flue, but in common with other fuels an efficient
flue is necessary to make sure of a trouble free installation.
The flue must be at least equivalent to 1m vertical.
The boiler flue socket is designed to take flue pipes to the
current issue of BS567. If a flue pipe to BS715 is to be used, an
adapter must be fitted to the boiler flue socket, as diagram 1.1.
The flue must be in accordance with the current issue of
BS5440 Part 1.
3.2 Flue Guidelines
The flue should be kept as short as possible. Horizontal or very
shallow runs of the flue should be avoided as they encourage
local cooling.
Always choose a flue route which will cause the least cooling of
the flue.
There should be a vertical rise of at least 600mm (2ft) before
using a bend. 90
End with a certificated flue terminal, preferably above ridge
height, but at least above the eaves of a pitched roof.
An existing chimney must be thoroughly swept and all debris
cleared away before lining.
o
elbows should not be used.
3.3 Timber Frame Buildings
If the boiler is to be installed in a timber frame building it should
be fitted in accordance with the Institute of Gas Engineers
document IGE/UP/7/1998. If in doubt seek advice from the local
gas undertaking or Hepworth Heating Ltd.
3.5 Ventilation for Boilers Installed in a
Cupboard or Compartment
When the boiler is fitted in a cupboard or compartment, high and
low level purpose designed, permanent openings must be
provided to supply air for combustion and compartment
ventilation.
The air vents must have minimum areas in accordance with
“Compartment Air Vent B”. The figures quoted refer to the
minimum acceptable effective area.
Both the high and low level openings must communicate with
the same room, or must both be on the same wall to outside air.
If air vent grilles are fitted to a cavity wall, the opening through
the wall must be ducted.
Where ventilation air to a compartment is taken from a room or
space, then the room or space must be fitted with a ventilation
opening as specified in “Air Vent Table A”.
For information regarding compartment requirements refer to
the appropriate section of the current issue of BS6798.
AIR VENT TABLE 'A' FOR
ROOM/SPACE INSTALLATIONS
2
EFFECTIVE
AREA OF VENT
COMPARTMENT AIR VENT TABLE 'B'
COMPARTMENT
VENTILATION
REQUIREMENTS
VENTILATION
FROM ROOM
OR SPACE
FROM
OUTSIDE
cm
in
104
2
16
HIGH LEVELLOW LEVEL
VENT AREAVENT AREA
272cm242in2544cm284in
136cm221in2272cm242in
2
2
3.4 Ventilation for Boiler Installed in a Room
or Space
If the boiler is to be installed in a room or space a purpose
designed permanent ventilation opening, to supply air for
combustion, must be provided on an outside wall to external air,
refer to the current issue of BS5440 Part 2 for details.
The opening may be directly into the room or the space
containing the boiler, or an outside wall of an adjacent room or
space which has an internal permanent air vent, of the same
size, into the room or space containing the boiler.
Do not ventilate through a bedroom, bedsitting room, private
garage or a room containing a bath or shower.
When the boiler is installed in a room or internal space already
containing other fuel burning appliances then the air supply of
such appliances must be taken into account.
The ventilation opening areas are given in “Air Vent Table A”.
The figures quoted refer to the minimum acceptable effective
area.
221756A
3.6 Extract Fans
If an extract fan is fitted in the premises, there is a possibility that
if adequate inlet openings are not provided, spillage of the
products from the boiler could occur.
When openings are fitted in accordance with the current issue
of BS5440 Part 2 and this section, extract fans should not cause
down draught, but where such fan installations are found, a
spillage test must be carried out in accordance with the current
issue of BS5440 Part 1 and any corrective work done.
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.