SAVE THESE INSTRUCTIONS. This manual contains important SAFETY WARNINGS and
OPERATING INSTRUCTIONS for the PHCC Pro Series pumps. You will need to refer to it
before attempting any installation or maintenance.
ALWAYS keep these instructions with the unit so that they will be easily accessible.
Failure to read and follow these warnings and instructions could result in property
damage, serious injury, or death.
WARNING
• ALWAYS disconnect the pump from the power source before servicing or making
adjustments.
• NEVER handle the pump or motor with wet hands or when standing on a wet or damp
surface while the pump is plugged into the power source.
• MAKE SURE THERE IS A PROPERLY GROUNDED RECEPTACLE AVAILABLE. This pump is
wired with a 3-prong grounded plug. To reduce the risk of electric shock, be certain
that it is only connected to a properly grounded, 3-prong receptacle (preferably with
ground fault circuit interrupt). If you have a 2-prong receptacle, have a licensed
electrician replace it with a 3-prong receptacle according to local codes and ordinances.
• NEVER bypass grounding wires or remove the ground prong from the plug.
• DO NOT use an extension cord. The electrical outlet should be within the length of the
pump’s power cord, and at least 4 feet above the floor level to minimize potential
hazards from flood conditions.
• DO protect the electrical cord from sharp objects, hot surfaces, oil, and chemicals.
Avoid kinking the cord.
• MAKE SURE the supply circuit has a fuse or circuit breaker rated to handle the power
requirements noted on the nameplate of the pump.
Risk of electric shock. To reduce this risk, observe the
following precautions.
S5 Series
Dewatering Sump Pumps
5 Year Warranty
E7 Series
Sewage Pumps
3 Year Warranty
Specifications
ModelDischargeAmpsMax SolidMaxGPM / GPH
No.HPVoltsDiameter@ 10⬘HandlingHead@ 10⬘
S3033
S3050
S310011152⬙11.51
S5033
S5050
E7040
E7055
E710011152⬙12.82⬙23⬘114 6840
• DO NOT remove the power supply cord and strain relief or connect the pump directly to
the conduit.
• NEVER install the pump in locations classified as hazardous in accordance with the
National Electrical Code, ANSI/NFPA 70.
• ALWAYS install the pump in accordance with the National Electric Code and all
applicable local codes and ordinances. All wiring should be performed by a licensed
electrician.
• DO NOT use the power cord or strain relief to carry the pump. Use the pump handle.
• DO NOT expose the control unit to rain or snow.
• DO NOT operate the pump or control unit if it has been damaged in any way.
• DO drill an air bleed hole in the discharge pipe when a check valve is used. Drill
the hole angled toward the bottom of the sump to avoid splashing water outside
the sump pit. If a hole is not drilled above the pump, an air lock may prevent the
pump from operating. The hole must
check valve. The optimum size of the hole is different for different pumps. Drill a
1/80 (3.2mm) hole in the discharge pipe for the S3 Series and S5 Series pumps.
Drill a 3/16” (4.76mm) hole in the discharge pipe for the E7 Series pumps.
• DO NOT use sump pumps in pits handling raw sewage, salt water, or hazardous liquids.
S2, S3 & S5 Series pumps are not designed for this purpose. E7 Series pumps are
sewage pumps.
• DO NOT disassemble the pump or control unit. When service is required, contact
Glentronics technical support at 800-991-0466, option 3. Return the product to the
manufacturer for any repairs at the following address:
1
/
31151
1
/
21152⬙4.3
1
/
31151
1
/
21152⬙6.81
4
/
101152⬙6.32⬙22⬘74 4440
1
/
21152⬙7.02⬙23⬘89 5340
CAUTION
1
/
2⬙4.0
1
/
2⬙4.01
7
/
8⬙30⬘50 3000
7
/
8⬙33⬘65 3900
3
/
4⬙52⬘92 5520
1
/
2⬙26⬘59 3540
3
/
4⬙36⬘83 4980
To reduce the risk of hazards that can cause injury or
property damage, observe the following precautions.
be drilled above the water line but below the
Glentronics, Inc.
645 Heathrow Drive, Lincolnshire, IL 60069
1
NOTICES
• The control unit must receive 115V AC +/- 5% and 60 Hz from the AC outlet. Lower
voltage may cause the power failure alarm to activate.
• These primary pumps will not provide protection during a power outage. With the risk of
property damage from high water levels, the addition of a PHCC Pro Series battery back-up
sump pump system is highly recommended.
• After the initial installation, be sure to check the operation by filling the sump with water
and observing the pump operation through one full cycle.
• For continuous duty operation, the pump must be submerged at least 3/4 of the depth of
the pump at all times.
• In instances where the discharge line is exposed to freezing temperatures, the pipe must
be sloped downward so any remaining water will drain out. Failure to do so will prevent
water from exiting the sump and damage the pump if the line freezes.
Installation Instructions
Prior to Installation
1. Visually inspect your pump. Products may be damaged during shipping. If the product
has been damaged, contact your place of purchase or Glentronics, Inc. before installation.
2. Thoroughly read the instructions provided to learn specific details regarding installation
and use. This manual should be retained for future reference.
Installing the Pump
WARNING
1. Use a pit that conforms to all local codes and is large enough to accommodate the pump
and float switch. The minimum requirements for pumps with the double float assembly are
10⬙ in diameter and 14⬙ deep. However, larger sump pits are preferred, since they will
extend the discharge cycle and reduce the number of times the pump turns on.
2. Clean the pit of all debris. The pump’s intake screen must be kept clear.
3. The pump should not be set directly onto a clay, earthen, or sand base. You may install
bricks or blocks under the pump to
provide a solid base.
4. The pump should be level.
5. Install discharge plumbing according to
local, regional and state codes. Rigid
PVC pipe is recommended.
6. The sizes of the discharge outlets on the
pumps vary from 1
match the size of the discharge pipe to
the size of the outlet on the pump to
maintain the optimum pumping capacity.
If you are using a PHCC Pro Series pump
with a 20 discharge outlet to replace a
pump in a system that has been plumbed
with 11⁄2⬙ pipe, you may use the adapter
included with the system to reduce the
size of the discharge outlet to 11⁄ 2⬙.
However, this will reduce the capacity of
the pump.
7. An in-line check valve is recommended
to prevent back-flow. This check valve is
mandatory when sharing a discharge line
with another pump (i.e. a back-up pump
or a second primary pump). Note: When
using a check valve, an air bleed hole of
1
⁄8 ⬙ (3.2mm) for the S3 & S5 Series and
3
⁄16 ⬙ (4.76mm) for the E7 Series needs to be drilled in the discharge pipe. The hole must be
drilled above the water line but below the check valve. A small stream of water will escape
through this air bleed hole when the pump is running, so the hole should be drilled on an
angle toward the bottom of the sump pit.
8. Install a gate valve or ball valve as required by any codes.
9. Secure the power cord to the discharge pipe with wire ties or clamps to prevent
interference with the float assembly.
10. A pit cover is recommended for all installations as a safety measure, and to prevent
debris from falling into the pit.
11. A cover is required in all sewage pump installations with gas-tight seals to contain gases
and odors. A vent pipe should be added in any sewage installation.
12. In instances where the discharge line is exposed to freezing temperatures, the pipe must
be positioned in a downward slope so any remaining water will drain away. Failure to do
this will prevent water from exiting the pit and damage the pump if the line freezes.
This installation must be in accordance with the National
Electric Code and all applicable local codes and ordinances.
1
⁄2⬙ to 2⬙. Try to
Installing the Double Float
The PHCC Pro Series double float switch is easy to
install by using the enclosed metal hose clamp.
1. Hold the float switch to the discharge pipe so the
cage is below the bracket.
2. Secure the float to the pipe with the enclosed
hose clamp, but do not completely tighten the
clamp at this time.
3. Position the float switch to a level where the
bottom of the float cage is no lower than 3⬙ above
the bottom of the pump and no higher than 1⬙
below the top of the pit. To avoid debris pouring
into the float, it should be positioned on the side
of the discharge pipe opposite the drain tile. Note: It is important to mount the float
below the drain tile that empties into the pit. Mounting it above the drain tile would allow
water to fill the drain tile before the pump is activated to pump out the water.
4. Once the float switch is in the desired position, tighten the clamp.
Installing the Vertical Float
The vertical float switch contains a single large float.
Sewage will lift the float to the top of the lift rod
which will raise the lift rod and activate the pump.
As the pump evacuates the sewage from the pit the
float will drop, lowering the lift rod and turning off
the pump.
1. Fully open the metal hose clamp and insert it
through the slots in the mounting bracket of the
float switch.
2. Place the hose clamp over the discharge pipe so
that the gripping tabs are against the pipe and
select the desired activation level of the pump.
3. The pumping range can be adjusted by moving the float stop up or down the lift rod.
4. To avoid debris from pouring onto the float, it should be positioned on the side of the
discharge pipe opposite the drain tile.
5. Once the float switch is in the desired position, securely tighten the hose clamp. Note:
The cable from the switch must remain outside the hose clamp.
Connecting the Pump and Controller
WARNING
Deluxe Dual Float Controller Model # DFC2
1. Mount the controller to the foundation, drywall
or a stud through the 2 holes on the cabinet
using the proper mounting hardware for the
application. The controller should be mounted
at least 4⬘ from the floor and within 4’ of the
outlet.
2. Open the plastic door on the top of the unit and
using a small flat head screwdriver adjust the
dial to select the number of seconds that the
pump will run after the bottom float drops. The
timer can be adjusted from 5-45 seconds. The
manufacturer default is about 10 seconds.
Install a 9V battery and replace the door.
3. Plug the control box into a properly grounded,
3-prong receptacle (preferably with ground fault
circuit interrupt). Then, plug the pump into the
receptacle on the control box. Do not use an extension cord.
4. Make sure the Power Failure Alarm slide switch is in the ON position.
Vertical Float Switch Model # 1020012
The E7 Series pumps do not come with a controller.
1. Plug the vertical float switch cord into a properly grounded 3-prong receptacle (preferably
with a ground fault circuit intercept). Then, plug the pump into the receptacle on the
float switch cord. Do not use an extension cord.
Connecting to a Security System
The Deluxe Controller (Model DFC2) includes a terminal on
the right side of the control box to connect to a security
system or other alarm devices. There are (3) three positions
for wire connections on this terminal: N.O. – normally open,
N.C. – normally closed, and Common.
Make sure the outlet is single phase, 115V and 60HZ for all
the pump installations.
PUMP
WIRE
2
1. Check your security system to determine whether an open (no contact) or closed (making
contact) connection is needed to activate the alarm.
2. The security system will provide (2) two connection terminals to extend wires to the
control terminal. Strip two wires 1/4” each. Connect either wire to the common
terminal. To secure the wire into the terminal, insert the exposed wire into the hole on
the side of the terminal next to the screw marked common. Turn the screw a few turns to
lock-in the wire.
3. If the security system requires a closing of a contact to activate the alarm, secure the
other wire into the terminal hole labeled N.O. (normally open). If the security system
requires an opening of a contact, secure the wire into the terminal hole labeled N.C.
(normally closed). Note: Only the “AC power out” and ‘Float raised for 10 minutes” alarms
will activate the remote
terminal signal.
Completing the Installation (all models)
1. After the initial installation, be sure to check the pump operation by filling the sump with
water and observing the pump through one full cycle. When using the dual float the pump
should run for 10 seconds after the lower float drops. When using the tethered float the
pump should shut off when the float is tilted down. Note: When the pump activates, it
should have a “normal pumping” sound. Any abnormal sound, vibration, or lack of output is
the signal of a problem. Stop the pump and refer to the troubleshooting guide.
2. Replace the pit cover making sure not to pinch or crimp the pump wire with the cover.
The pit cover either has a ‘hole punch’ that will allow the cord to be passed through or
one can be drilled.
Product Operation
Dual Float Switch (included with controller models DFC1 and DFC2)
The dual float switch contains two large floating rings enclosed
within a protective cage. Water will lift the bottom float by a 1⁄4⬙,
which will activate the pump. If for any reason the lower float
does not activate the pump, the water will rise and activate the
second switch. As the pump evacuates the water from the pit the
floats will drop. The pump will run for an additional 10 seconds to
extend the cycle after the lower float drops. Note: When mounting
the float switch, position the bottom of the cage at the height you
want the pump to activate.
Deluxe Dual Float Controller Model # DFC2
The benefit of this controller is that it will sound an alarm
when problems exist regarding the ability of the sump pump
to keep the basement dry.
The PHCC Pro Series Deluxe Dual Float Controller features a
series of warnings (audible and visual) that pinpoint potential
problems with the pump, switch and power conditions. The
controller will sound an alarm when power has been
interrupted, when the pump has run for more than 10
minutes continuously, or when the 9V battery is low. The 9V
battery (sold separately) runs the controller during a power
outage, allowing it to sound an alarm if the circuit breaker
trips, the controller is not plugged in securely, or the homes
power is interrupted. Note: The 9V battery will only power theswitch, not the pump. The Deluxe Controller has a dial
(located in the battery compartment) to adjust the number of
seconds that the pump will run after the float drops. The
Deluxe Controller will also run the pump once a week for approximately four (4) seconds.
This test will exercise the pump and help ensure the pump is working properly.
Operating the Pump in a Continuous Duty Application
The PHCC Pro Series pumps are rated for continuous duty and may be used in applications
requiring continuous pumping including fountains, ponds, etc. For use in any continuous
duty application the pump should be plugged directly into the wall outlet without the use of
a controller. The outlet must be a single phase properly grounded 3-prong receptacle, 115V,
60HZ (preferably with ground fault circuit interrupt). For continuous duty operation, the
pump must be submerged at least 3/4 of the depth of the pump at all times.
DFC2
Understanding the Warnings and Alarms (Model # DFC2)
AC power is out
There are several causes for power failure.
The most common are a power outage by
the electric company or a tripped circuit
breaker. Although the deluxe controller
can not run the pump, it will sound an
alarm indicating the loss of power. This
will allow the homeowner to address the
problem. If this warning light and alarm
are on, the control box is not receiving
AC power for one of several reasons:
1. The control box is not plugged in.
2. The power to the house is out.
3. The circuit breaker to that outlet has been tripped.
4. The ground fault interrupter has been tripped for that outlet.
5. A power brownout is taking place.
Note: A PHCC Pro Series battery backup sump pump system can protect the basement during a
power outage. It will automatically activate a separate 12-volt battery powered pump, which
will keep the basement dry until power is restored.
Power Failure Alarm slide switch
When the controller is not receiving AC power, the monitoring features and the audible
alarms are powered by the 9-volt battery. This type of battery will power the controller for
many hours, but not indefinitely. Once the source of the AC power alarm is determined, it is
suggested that the Power Failure Alarm slide switch be turned to the OFF position until the
power is restored. This will preserve the battery and silence the alarm. When AC power is
restored, slide this switch back to the ON position. Note: If the AC power is restored and the
slide switch is in the OFF position, the alarm and light for the 9-volt battery warning will
activate, even if the battery is good. This is a reminder to reset the alarm. Slide the switch
to the ON position. If the battery is good, the light will go out. If the alarm continues to
sound, replace the battery.
The system is operating
This light should be ON and flashing at all times. It is included to indicate that the system
is monitoring the sump conditions. This light will not illuminate when:
1. The power is out and the Power Failure Alarm slide switch is in the OFF position.
2. The power is out and the 9V battery is discharged.
3. The controller is not functioning. Contact Glentronics service department.
The 9-volt battery is low
1. The 9-volt battery located in the top of the control box is coming to the end of its useful
life. Replace it with a new 9-volt alkaline battery.
2. The Power Failure Alarm switch is in the OFF position. It must be in the ON position at
all times, except when silencing an actual power failure condition.
Pump or float problem
This key feature monitors the time that the float switch is continuously up or in the
activated position. It is unusual for a pump run for 10 or more minutes continuously. This
can occur for many different reasons. Either the float is stuck in the up position, there is a
mechanical problem with the pump, or there is a problem with the plumbing connections.
Please refer to this manual’s Troubleshooting Guide on the following page.
Maintenance Check List
Maintenance should be performed 1-2 times per year.
1. Remove all debris from the bottom of the pit.
2. Remove all debris floating in the water.
3. Remove all debris from the float switch cage.
4. Fill the pit with water. Make sure pump turns on at the intended level.
5. While the pump is running, make sure pump is evacuating water at a good pace.
6. While the pump is running, make sure a stream of water is escaping from the air bleed
hole. If not, clear the hole of any deposits or debris.
7. Unplug the control box from the wall. Make sure the “AC power is out” light and alarm
sound (DFC2).
Backup Installation
When the power goes out, the
PHCC Pro Series AC sump pumps
will not operate. For protection
during a power outage, a PHCC Pro
Series battery backup system can
be installed. There are three
systems with matching batteries
that will provide protection. The
illustration at right is an example
of a typical battery backup
installation.
Visit our website
www.stopflooding.com for
more information about the
PHCC Pro Series AC pumps
and battery backup sump
pump products.
3
Warranty
GLENTRONICS, INC. warrants to the end purchaser that its pumps, switch and control unit products are free from defective materials and workmanship for the periods indicated below:
All parts and labor (excluding installation) for a period of:
• 3 years from the date of purchase, when purchased with the PHCC Pro Series S3 or E7 Series pumps
• 5 years from the date of purchase, when purchased with the PHCC Pro Series S5 Series pumps
• 1 year from the date of purchase, when used in continuous duty operations such as fountains or ponds
The defective product must be returned directly to the factory, postage prepaid with the original bill of sale or receipt to the address listed below. GLENTRONICS, INC., at its option, will
either repair or replace the product and return it postage prepaid.
Conditions
The unit must be shipped, freight prepaid, or delivered to GLENTRONICS, INC. to provide the services described hereunder in either its original carton and inserts, or a similar package
affording an equal degree of protection.
The unit must not have been previously altered, repaired or serviced by anyone other than GLENTRONICS, INC., or its agent; the serial number on the unit must not have been altered or
removed; the unit must not have been subject to accident, misuse, abuse or operated contrary to the instructions contained in the accompanying manual.
The dealer's dated bill of sale, or installers invoice must be retained as evidence of the date of purchase and to establish warranty eligibility.
This warranty does not cover product problems resulting from handling liquids hotter than 104 degrees Fahrenheit, handling inflammable liquids, solvents, strong chemicals or severe abrasive
solutions; user abuse; misuse, neglect, improper maintenance, commercial or industrial use; improper connection or installation, damages caused by lightning strikes; excessive surges in AC
line voltage; water damage to the controller; other acts of nature, or failure to operate in accordance with the enclosed written instructions.
GLENTRONICS, INC. WILL NOT BE LIABLE FOR ANY INCIDENTAL, SPECIAL OR CONSEQUENTIAL DAMAGES FOR BREACH OF ANY EXPRESS OR IMPLIED WARRANTIES ON THIS PRODUCT. SOME STATES
DO NOT ALLOW FOR THE EXCLUSION OR LIMITATION OF CONSEQUENTIAL OR INDIRECT DAMAGE. THE ABOVE LIMITATION MAY NOT APPLY TO YOU. THIS EXPRESS WARRANTY SHALL BE EXCLUSIVE
AND IS IN LIEU OF ALL OTHER WARRANTIES, WRITTEN OR ORAL, EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE. THIS CUSTOMER'S EXCLUSIVE REMEDY FOR BREACH OF THIS WARRANTY, OR OF ANY IMPLIED WARRANTY NOT EXCLUDED HEREIN, SHALL BE LIMITED TO REPAIR OR REPLACEMENT OF
THE PRODUCT.
For information or service contact:
Glentronics, Inc., 645 Heathrow Drive, Lincolnshire, IL 60069 800-991-0466
Model No. _________________________ Serial No. _________________________________________ Purchase Date _________________________