Glentronics PHCC Pro Installation Manual

Page 1
PHCC Pro Series
Deluxe Float Switch & Controller
Instruction Manual & Safety Warnings
SAVE THESE INSTRUCTIONS. This manual contains important SAFETY
WARNINGS and OPERATING INSTRUCTIONS for the PHCC Pro Series Deluxe Float Controller with dual float (DFC2) and vertical float (VSC2). You will need to refer to it before attempting any installation or maintenance.
ALWAYS keep these instructions with the unit so that they will be easily accessible. Failure to read and follow these warnings and instructions could result in property damage, serious injury, or death.
WARNING
• ALWAYS disconnect the pump and float controller from the power source before servicing or making adjustments.
• NEVER handle the controller, float switch, pump or motor with wet hands or when standing on a wet or damp surface while the pump or controller is plugged into the power source.
• MAKE SURE THERE IS A PROPERLY GROUNDED RECEPTACLE AVAILABLE. This controller is wired with a 3-prong grounded plug. To reduce the risk of electric shock, be certain that it is only connected to a properly grounded, 3-prong receptacle. If you have a 2-prong receptacle, have a licensed electrician replace it with a 3-prong receptacle according to local codes and ordinances.
• NEVER bypass grounding wires or remove the ground prong from the controller.
• DO NOT use an extension cord. The electrical outlet should be within the length of the pump’s power cord, and at least 4 feet above the floor level to minimize potential hazards from flood conditions.
• DO protect the electrical cord from sharp objects, hot surfaces, oil, and chemicals. Avoid kinking the cord.
• MAKE SURE the supply circuit has a fuse or circuit breaker rated to handle the power requirements noted on the nameplate of the pump.
CAUTION
• DO NOT expose the control unit to any type of moisture, water, rain or snow.
• DO NOT operate the pump or control unit if it has been damaged in any way.
• DO NOT use the caged dual float switch with pumps in pits handling raw sewage, salt water or hazardous liquids. This product is for ground water applications only.
• DO NOT use the vertical float switch with pumps in pits handling salt water or other hazardous liquids.
• DO NOT use in continuous duty applications such as fountains or ponds.
• DO NOT disassemble the pump or control unit. When service is required, contact Glentronics technical support at 800-991-0466, option 3. Return the product to the manufacturer for any repairs at the following address:
Glentronics, Inc., 645 Heathrow Drive, Lincolnshire, IL 60069
NOTICES
• The control unit must receive 115V AC +/- 5% and 60 Hz from the AC outlet.
• The controller will not provide protection during a power outage. With the risk of property damage from high water levels, the addition of a PHCC Pro Series battery backup sump pump system is highly recommended.
• After the initial installation, be sure to check the operation by filling the sump with water and observing the pump operation through one full cycle.
Risk of electric shock. To reduce this risk, observe the following precautions
To reduce the risk of hazards that can cause injury or property damage, observe the following precautions
Installation
FLOOR JOIST
MOUNTED DELUXE
FLOAT CONTROLLER
PLUGGED INTO
AC OUTLET
WATER SENSOR WIRE
FLOAT WIRE
WATER SENSOR
AIR BLEED
HOLE
DUAL
FLOAT
SUMP FOOT
SLOPE
PIPE
DOWN
DISCHARGE
PIPE
VALVE
PUMP WIRE
UNION/CHECK
VALVE
GAT E
PIT COVER
DRAIN TILE
PRO SERIES PUMP
Dual Float Switch (Model DFC2)
The dual float switch contains two large floating rings enclosed within a protective cage. Water will lift the bottom float by a
1
⁄4”, which will activate the pump. If for any reason the lower float does not activate the pump, the water will rise and activate the second switch. As the pump evacuates the water from the pit, the floats will drop. The pump will run for an additional 10 seconds to evacuate the pit completely after the float drops. The float switch wire includes a connector that can be separated from the controller when the wire needs to be threaded through small openings. Note: When mounting the float switch, position the
bottom of the cage at the height you want the pump to activate.
Installing the Dual Float
The PHCC Pro Series dual float switch is easy to install by using the enclosed stainless steel hose clamp.
1. Hold the float switch to the discharge pipe so the cage is below the bracket.
2. Secure the float to the pipe with the enclosed hose clamp, but do not completely tighten the clamp at this time.
3. Position the float switch to a level where the bottom of the float cage is no lower than 3” above the bottom of the pump. To avoid debris pouring onto the float, it should be positioned on the side of the discharge pipe opposite the drain tile. Note: It is important to mount
the float below the drain tile that empties into the pit. Mounting it above the drain tile would allow water to fill the drain tile before the pump is activated to pump out the water.
4. Once the float switch is in the desired position, tighten the clamp.
Vertical Float Switch (Model VSC2)
The vertical float switch contains a single large float. Water will lift the float by a
1
⁄2”, which will activate the pump. As the pump evacuates the water from the pit, the float will drop. The pump will run for an additional 10 seconds to evacuate the pit completely after the float drops. Note: There are two rubber stoppers on the float
switch rod. Do not remove or alter their position as it will disrupt the timing of the controller and how long the pump runs. The float switch wire includes a connector that can
be separated from the controller when the wire needs to be threaded through small openings. Note: When mounting
the float switch, position the bottom of the float at the height you want the pump to activate.
Instructions
Prior to Installation
1. Visually inspect the product. Products may be damaged during shipping. If the product has been damaged, contact your place of purchase or Glentronics, Inc. before installation.
2. Thoroughly read the instructions provided to learn specific details regarding installation and use. This manual should be retained for future reference.
Page 2
Installing the Vertical Float
The PHCC Pro Series float switch is easy to install by using the enclosed stainless steel hose clamp.
1. Hold the float switch to the discharge pipe so the float is below the bracket.
2. Secure the float to the pipe with the enclosed hose clamp, but do not completely tighten the clamp at this time.
3. Position the float switch to a level where the bottom of the float is no lower than 3” above the bottom of the pump. To avoid debris pouring onto the float, it should be positioned on the side of the discharge pipe opposite the drain tile. Note: It is important to mount the float
below the drain tile that empties into the pit. Mounting it above the drain tile would allow water to fill the drain tile before the pump is activated to pump out the water.
4. Once the float switch is in the desired position, tighten the clamp.
Deluxe Float Controller
The benefit of this controller is that it will sound an alarm when problems exist or maintenance is needed. The controller will also run the pump once a week for approximately four (4) seconds. This test will exercise the pump and help ensure the pump is working properly.
The PHCC Pro Series Deluxe Float Controller features a series of warnings (audible and visual) that pinpoint potential problems with the pump, switch and power conditions. The controller will sound an alarm when power has been interrupted, when the pump has run for more than 10 minutes continuously, or when the 9V battery is low. The 9V battery (sold separately) runs the controller during a power outage, allowing it to sound an alarm if the circuit breaker trips, the controller is not plugged in securely, or the home’s power is interrupted.
Note: The 9V battery will only power the switch, not the pump.
Installing the Deluxe Float Controller
1. Mount the controller to the wall through the 2 holes on the cabinet using the proper mounting hardware for the application. The controller should be mounted at least 4‘ from the floor and within 4’ of the outlet.
2. Open the plastic door on the top of the unit and using a flat head screwdriver adjust the dial to select the number of seconds that the pump will run after the float drops. The dial can be adjusted from 5-45 seconds. The manufacturer default is about 10 seconds. Install a 9V alkaline battery and replace the plastic door.
3. Plug the control box into a properly grounded, 3-prong receptacle. Then, plug the pump into the receptacle on the control box. Do not use an extension cord.
4. Make sure the Power Failure Alarm slide switch is in the ON position.
5. Plug the float switch into the bottom of the controller.
Completing the Installation
1. After the initial installation, be sure to check the pump operation by filling the sump with water and observing the pump through one full cycle. The pump should run for 10 seconds after the float drops to its original position.
2. Replace the pit cover making sure not to pinch or crimp the pump wire with the cover. The pit cover either has a ‘hole punch’ that will allow the cord to be passed through it, or a hole can be drilled in the cover.
High Water Alarm ­Accessory for the Deluxe Controller
(Requires the additional purchase of model PS-WS)
Water Sensor
The water sensor is designed to warn you of a potential flood. If you are installing it in the sump pit, it must to be installed between the basement floor and the primary float switch. If there is a failure with either the main pump or the plumbing system, the water level will rise past the primary float switch and activate the water sensor. When the water sensor is activated, it will trigger a warning light, an audible alarm, and the remote terminal on the controller.
This water sensor is only designed to give you a warning of a potential problem; it will not activate the primary pump.
Installing the Water Sensor
The water sensor should be mounted near the top of the pit or where it is appropriate for your installation (see diagram). Attach the water sensor very securely with the included plastic wire tie. Be sure the water sensor is positioned vertically with the mounting bracket at the top. Plug the water sensor into the bottom of the controller. Do not tilt the water
sensor. Do not position the water sensor on the side of the discharge pipe facing the drain tile or any incoming rush of water.
Testing the Water Sensor
Lift up the float on the water sensor with your fingers. As long it is up, the high water alarm warning light and the audible alarm should be on. When the float is down, the warning light and audible alarm will turn off.
Understanding the Warnings & Alarms
AC power is out
There are several causes for power failure. The most common causes are a power outage by the electric company or a tripped circuit breaker. Although the deluxe controller can not run the pump, it will sound an alarm indicating the loss of power. This will allow the homeowner to address the problem.
If this warning light and alarm are on, the control box is not receiving AC power for one of many reasons:
1. The control box is not plugged in
2. The power to the house is out
3. The circuit breaker to that outlet has been tripped
4. A power brownout is taking place
Power Failure Alarm slide switch
When the controller is not receiving AC power, the monitoring features and the audible alarms are powered by the 9-volt battery. This type of battery will power the controller for many hours, but not indefinitely. Once the source of the AC power alarm is determined, it is suggested that the Power Failure Alarm slide switch be turned to the OFF position until the power is restored. This will preserve the battery and silence the alarm. When AC power is restored, slide this switch back to the ON position.
Note: If the AC power is restored and the slide switch is in the OFF position, the alarm and light for the 9-volt battery warning will activate, even if the battery is good. This is a reminder to reset the alarm. Slide the switch to the ON position. If the battery is good, the light will go out. If the alarm continues to sound, replace the battery.
The system is operating
This light should be ON and flashing at all times. It is included to indicate that the system is monitoring the sump conditions. This light will not illuminate when:
1. The power is out and the Power Failure Alarm slide switch is in the OFF position
2. The power is out and the 9V battery is discharged
3. The controller is not functioning. Contact the Glentronics service department
The 9-volt battery is low
1. The 9-volt battery located in the top of the control box is coming to the end of its useful life. Replace it with a new 9-volt alkaline battery.
2. The Power Failure Alarm switch is in the OFF position. It must be in the ON position at all times, except when silencing an actual power failure condition.
Pump or float problem
This key feature monitors the time that the float switch is up continuously or in the activated position. It is unusual for a pump run
Power Failure Alarm
On Off
Slide switch to OFF during power failures
to conserve battery energy and silence alarm
AC power is out
Make sure this controller is plugged into the wall outlet Check the circuit breaker
The system is operating
Light should be flashing
9 volt battery low or slide switch is OFF
Replace 9 volt alkaline battery or move switch to ON
Pump or float problem
The pump has run continuously for 10 minutes Refer to the instructions for possible causes
High water alarm (optional feature)
Water has reached the high water sensor
www.stopflooding.com
12 Amps maximum
Model No. DFC2
Glentronics, Inc.
800.991.0466
Common
Deluxe
Float
Controller
Consider a Pro Series
Battery Backup
Sump Pump
System
Remote
Connection
N.C.
N.O.
Page 3
for 10 or more minutes continuously. This can occur for many different reasons. Either the float is stuck in the up position, there is a mechanical problem with the pump, or there is a problem with the plumbing connections. Please refer to the Troubleshooting Guide on the last page.
High water alarm (optional feature*)
When water reaches the optional water sensor, it will activate the warning light, audible alarm, and remote terminal. The activation of the water
sensor could indicate that there is a failure of the main pump or plumbing problem. Please refer to the Troubleshooting Guide on the last page.
*This feature requires the additional purchase of the water sensor (Model # PS-WS).
Glentronics, Inc., Lincolnshire, IL 60069
800-991-0466
www.stopflooding.com
LIMITED WARRANTY
By opening this package and using this GLENTRONICS, INC. product, you are agreeing to be bound by the terms of the GLENTRONICS, INC. limited warranty (“warranty”) as set out below. Do not use your product until you have read the terms of the warranty. If you do not agree to the terms of the warranty, do not use the product and return it within the return period stated on your purchase receipt from the retail store or authorized distributor where you purchased it for a refund.
To the extent permitted by law, this warranty and the remedies set forth are exclusive and in lieu of all other warranties, remedies and conditions, whether oral, written, statutory, express or implied. GLENTRONICS, INC. disclaims all statutory and implied warranties, including without limitation, warranties of merchantability and fitness for a particular purpose and warranties against hidden or latent defects, to the extent permitted by law. GLENTRONICS, INC. will not be liable for any incidental, special or consequential damages for breach of any express or implied warranties on this product. In so far as such warranties cannot be disclaimed, GLENTRONICS, INC. limits the duration and remedies of such warranties to the duration of this express warranty and, AT GLENTRONICS, INC.'s option, the repair or replacement services described below. Some states (countries and provinces) do not allow limitations on how long an implied warranty (or condition) may last, so the limitation described above may not apply to you.
Any and all causes of action arising from, filed as a result of or in reference to, this warranty or the products described under this warranty shall be governed by and construed under the laws of the State of Illinois. Any cause of action arising from, filed as a result of or in reference to, this warranty or the products described under this warranty shall be filed only in the Circuit Court of the 18th Judicial District, Lake County, Waukegan, Illinois, or in the Northern District of Illinois if filed in Federal Court. The maximum liability for any product described in this warranty shall be the cost of product replacement only.
If any term is held to be illegal or unenforceable, the legality or enforceability of the remaining terms shall not be affected or impaired.
What is Covered by this Warranty?
GLENTRONICS, INC. warrants to the end purchaser that its pumps, switch and control unit products are free from defective materials and workmanship for the periods indicated below:
All parts and labor (excluding installation) for a period of:
• 1 year from the date of purchase, when purchased individually for use with another brand of sump pump
• When purchased with a PHCC Pro series pump, the Deluxe Float Controller and float switch are covered under the pump’s warranty
The defective product must be returned directly to the factory, postage prepaid with the original bill of sale or receipt to the address listed below. GLENTRONICS, INC., at its option, will either repair or replace the product and return it postage prepaid.
What is NOT Covered by this Warranty?
This warranty does not cover the cost or value of damaged property, including expressly any property that has been affected by water overflow, seepage or flooding. If GLENTRONICS, INC. determines that a product is deemed defective under this warranty agreement, it will repair or replace the PRODUCT ONLY. GLENTRONICS, INC. will not cover the cost to reinstall the product, nor will GLENTRONICS, INC. pay the cost of having a plumber or contractor repair or replace the product.
GLENTRONICS, INC. will not repair or replace a product that was installed incorrectly. A product shall be considered “installed incorrectly” when it deviates in any way from the instructions described in this manual.
This warranty does not cover product problems resulting from handling liquids hotter than 104 degrees Fahrenheit, handling inflammable liquids, solvents, strong chemicals or severe abrasive solutions; user abuse; misuse, neglect, improper maintenance, commercial or industrial use; improper connection or installation, damages caused by lightning strikes; excessive surges in AC line voltage; water damage to the controller; other acts of nature, or failure to operate in accordance with the enclosed written instructions.
How to Obtain Warranty Service
Within thirty (30) days of the product’s defective performance, the unit must be shipped, freight prepaid, or delivered to GLENTRONICS, INC. to provide the services described hereunder in either its original carton and inserts, or a similar package affording an equal degree of protection. Products not received by GLENTRONICS, INC. at the address indicated below within thirty (30) days of the product’s defective performance will not be considered for warranty service. Products received after one (1) year from the date of purchase, fall outside of the timeframe for warranty service and will not be eligible for warranty service. The product must be returned to GLENTRONICS, INC. for inspection in order to be considered for warranty service. If the product is not returned to GLENTRONICS, INC. or the product is inspected by any person, plumber, contractor or business other than GLENTRONICS, INC., this warranty shall no longer be valid. Prior to defective operation, the unit must not have been previously altered, repaired or serviced by anyone other than GLENTRONICS, INC., or its agent; the serial number on the unit must not have been altered or removed; the unit must not have been subject to accident, misuse, abuse or operated contrary to the instructions contained in the accompanying manual. The dealer's dated bill of sale, or installer’s invoice must be retained as evidence of the date of purchase and to establish warranty eligibility.
Where are Products Sent for Warranty Service?
Glentronics, Inc., 645 Heathrow Drive, Lincolnshire, IL 60069
How Can I Obtain More Information?
By calling 800-991-0466.
Page 4
Troubleshooting Guide
The pump will not start or run
Thermal protector tripping or not functioning
Pump starts and stops too frequently
Pump will not shut off
Insufficient or no water volume
Abnormal sound or vibration
Pump unexpectedly turns off for 5 seconds
*Consult a licensed electrician. If the above solutions do not solve the problem, contact Glentronics customer service 800-991-0466, option 3.
(Always unplug the pump from the controller before performing any maintenance)
Pump is not plugged in Water is not high enough to activate the pump Open circuit Poor power source Low voltage Bad power cable Locked impeller Defective float switch Defective pump Locked impeller Incorrect power supply Overburdened due to heavy sand content in the water Pump running continuously with no water present Float switch mounted too low Water flowing back from pipe Malfunctioning float switch Clogged or frozen discharge Blocked intake strainer
One or both of the floats is obstructed and cannot drop down
Defective float switch Check valve installed with no air bleed hole in
pipe or pump
Check valve is stuck or installed upside down
Check valve on secondary pump will not close and water re-circulates within the system
Worn impeller Partially blocked impeller Clogged or frozen discharge Broken or leaking pipe Low power voltage Check valve installed with no air bleed hole in
pipe or pump
Check valve is stuck or installed upside down
Pump is air locked Check valve on secondary pump will not close
and water re-circulates within the system Blocked intake screen Broken impeller
Pump is experiencing an anti air lock safety feature
Plug pump in properly (see instructions) Make sure float switch is positioned properly Check circuit breaker or fuse Check circuit line wires and cable* Check line wires and source voltage* Replace with new cable* Remove strainer and clear obstruction Replace float switch with new float switch Replace pump with new pump Remove strainer and clear obstruction Check power supply source and voltage Use water filter or replace with a higher wattage pump Check float switch Raise float switch Install or replace check valve Replace float switch with new float switch Clear blockage or thaw frozen line Clear debris from intake strainer Clear debris from inside the float cage (Loosen nut on top of float, then
remove c-clip on bottom of float. Remove debris. Tighten nut on top of float, then replace c-clip on bottom of float.) When reassembling the float, the magnetic strip on the inside of the float should be facing down.
Replace float switch with new float switch An air bleed hole of 3/16” (4.76mm) needs to be drilled in the discharge
pipe below the check valve and pit cover Reverse or replace check valve. Make sure the check valve is installed with
the flow arrow pointing up and out of the pit.
Replace the check valve on the secondary pump
Replace impeller & adjust spacing between impeller and cover Remove strainer and clear obstruction Clear blockage or thaw frozen line Repair piping Check power voltage, wires and cable condition An air bleed hole of 3/16” (4.76mm) needs to be drilled in the discharge
pipe below the check valve and pit cover Reverse or replace the check valve. Be sure check valve is installed with
flow arrow pointing up and out of the pit Remove debris from the air bleed hole
Replace the check valve on the secondary pump
Clear debris from intake screen Replace impeller with new one Pump is frequently cycling on and off. The controller has a safety feature
that turns the pump off for 5 seconds if it detects a possible air lock. This is normal. No action is required.
1806103 02/16
Loading...