GE Industrial Solutions Spectra G-Frame MCCB with microEntelliGuard trip unit User Manual

GE Energy
Industrial Solutions
GEH-700 Installation Instructions
Spectra® RMS SG Frame Molded-Case Circuit Breaker
With microEntelliGuard
TM
Trip Units
Spectra microEntelliGuard overload and short-circuit protection for electrical equipment. Frame types SGHC, SGLC, SGPC, SGHH, SGLL, and SGPP are available with a selection of rating plugs to a maximum of 600 amperes, depending on the sensor rating.
SG Frame circuit breakers are listed per Underwriters Laboratories standard UL489 and Canadian Standards Association standard CSA22.2 No.5 and meet the requirements of the International Electrotechnical Commission standard IEC947-2.
WARNING: Danger of electrical shock or injury. Turn OFF the power ahead of equipment before installing this device or removing any other device.
IMPORTANT: Danger d’électrocution. Couper l’alimentation avant d’installer cet appareil ou avant de retirer un autre appareil.
®
RMS molded-case circuit breakers with
TM
trip units provide adjustable
CAUTION: This product is NOT suitable for use in equipment not specifically designed to accept it. Contact the equipment manufacturer for possible equipment modifications.
IMPORTANT: Cet appareil ne doit pas être employé dans un equipement qui n’est pas spécialement adapte a cet effet. Contactez le fabricant concernant les possibles modifications à apporter à l’équipement.
SG 600 amp Frame breaker with microEntelliGuard™ Trip Unit
Assembly
1. Unpack the circuit breaker and inspect it for any shipping damage. Ensure that the breaker has the proper ampere range, sensor rating, voltage rating, and interruption rating for the application. Since this breaker is available in a wide variety of configurations, compare the catalog number of your purchased breaker with the catalog number key in Table 1. Installation of an incorrect breaker could result in misapplication, lack of system coordination, or reduction in system functionality.
s
GEH-700 Installation Instructions
SG
PC
36
04
L4
R
6
Code Description Function
HC 35kA at 480Vac LC 65kA at 480Vac PC 100kA at 480 Vac HH 35kA at 480Vac LL 65kA at 480Vac PP 100kA at 480 Vac
01 150 Amps 04 400 Amps 06 600 Amps
L3 LSI
L4 LSIG
L5 LSIA
L7 LSI-CP X None
K Neutral Protection Z ZSI (ST/GF) T ZSI (ST/GF/INST) R RELT L ZSI (ST/GF) + REL M ZSI (ST/GF) + Neutral Protection N ZSI (ST/GF) + RELT + Neutral Protection V RELT + Neutral Protection P ZSI (ST/GF/INST) + RELT S ZSI (ST/GF/INST) + Neutral Protection W ZSI (ST/GF/INST) + RELT + Neutral Protection X Metering (Basic) 2 Metering (Basic) + Modbu 6 Metering (Adv) + Modbus + Waveform Capture 8 Metering (Adv) + Modbus + Waveform Capture + Protective Relays
Standard UL Rating
100% Continuous UL Rating
L = Long Time S = Short Time I = Instantaneous G = Ground Fault A = Ground Fault Alarm CP = Control Power
T
Interruption Rating
Max Amps
Standard Protection Functions
Advanced Protection Functions
Advanced Features & Communications
noitangiseD emarF006GSGS
egatloV LU xaM ,seloPcaV006 ,seloP 36 ,3
Table 1. Catalog numbering system for Spectra RMS™ SG Frame breakers with microEntelliGuard™ trip units
Example – a breaker with catalog number
Table 2. SG Frame Rating Plugs
SGPC3604L4R6 has the following features:
1 SG600 frame (SG) 2 100 kA at 480 Vac Standard UL rating (PC) 3 3 pole, 600 Vac maximum (36) 4 400 A sensors (04) 5 Long-time, Short-time, Instantaneous and Ground
Fault functions (L4) 6 RELT – Reduced Energy Let-Through (R) 7 Advance Metering, Modbus Communications, and
Waveform Capture (6)
2. Following the instructions supplied with the rating
plug, install the plug into the breaker body. Available rating plugs, with their catalog numbers, are listed in Table 2.
Catalog Numbers Trip Amps 150 400 600
GTP0060U0101 60 x GTP0080U0101 80 x GTP0100U0103 100 x GTP0125U0103 125 x GTP0150U0104 150 x x GTP0200U0204 200 x GTP0225U0306 225 x x GTP0250U0407 250 x x GTP0300U0408 300 x x GTP0350U0408 350 x x GTP0400U0410 400 x x GTP0450U0612 450 x GTP0500U0613 500 x GTP0600U0616 600 x
SG (Max Amps)
GEH-700 Installation Instructions
3. Install any internal accessories, following the instructions supplied with each accessory. Available accessories and their mounting locations are listed in Table 3. Check all accessories for proper installation and wire routing. Verify breaker operation with the installed accessories. Accessory leads can be routed along the side of the breaker and across the back. An auxiliary switch is required for the breaker status signal.
Table 3. Internal Accessories
Internal Accessory
Auxiliary Switch (SPDT or DPDT)
Bell Alarm Switch 1 Left Shunt Trip or
Undervoltage Release
Maximum
Number of
Accessories
1 Right
1 Left
Accessory
Installation
Location
4. Attach the terminal lugs, listed in Table 4, following the instructions supplied with the lug kit. Use one kit for either line or load end; two kits are required for both.
WARNING: It is important that the terminal covers are installed correctly to ensure proper circuit breaker operation.
IMPORTANT: Il est important de vérifier que tous couvercles ou caches de protection sont correctement installés afin d’assurer le bon fonctionnement de l’appareil.
6. Finally, connect all associated components that are required for the breaker to function properly, using the instructions supplied with each component. The following is a list of available associated components:
• Terminal board connector
• Neutral current sensor connector
• Control power connector
• Extension cable
• Control power module (control power transformer
may be required)
• Voltage conditioners (potential transformers may
be required)
• Voltage module
• Neutral current sensor
Table 4. Available Lug Kits
Catalog Number Description Wire Type Lug Material
TCLK265 2 Pole Lug Kit TCLK365 3 Pole Lug Kit TCOK265 2 Pole Lug Kit TCOK365 3 Pole Lug Kit
Cu/Al
Cu only
Tin-plated Aluminum
Tin-plated Copper
5. Ensure that all terminals are torqued to the proper value, as listed in the lug kit instruction sheet. Install the terminal covers, ensuring that they are firmly seated.
NOTE: Aluminum wire must be used with a joint compound recommended by the wire manufacturer.
IMPORTANT: Si un cable en aluminum est employé, utilisez le lubrifiant recommandé par le fabricant.
Mounting
®
All Spectra
RMS circuit breakers are suitable for reverse feed and have no line or load markings. Incoming power cables or busbars may be connected to either the upper or lower terminals as required by the application.
WARNING: Danger of electrical shock or injury. Turn OFF the power ahead of equipment before installing this device or removing any other device.
IMPORTANT: Danger de choc électrique ou de blessure. Couper l’alimentation entrant dans l’appareil avant de monter celui-ci ou de démonter d’autres appareils.
GEH-700 Installation Instructions
For individual front panel mounting:
1. Drill and tap all mounting holes and make any necessary front-panel escutcheon cutouts, as shown in Figure 1.
For individual mounting in a GE enclosure:
Install the breaker according to the instructions supplied with the enclosure. Available enclosures are listed in Table 7 (refer to the BuyLog for other accessories and/or any enclosure limitations).
Table 7. Enclosures
Enclosure Type 400A Catalog No. 600A Catalog No.
NEMA 1 (indoor)
NEMA 3R (outdoor) SG400R SG600R NEMA 12 (oil-tight and
dust-tight)
SG400F SG400S
SG400J SG600J
SG600F SG600S
Setup and Adjustment
TM
The Spectra RMS microEntelliGuard
trip units are digital, rms sensing, electronic trip units with an LCD and keypad for viewing and/or changing the various function settings. Refer to User’s Manual GEH-702 for detailed information concerning the operation, adjustment, and setting of the breaker trip unit.
You should record the overcurrent protection and protective relay set points for future reference.
Figure 1. Mounting Hole and Escutcheon Cutout Pattern in/(mm)
2. Mount the breaker with the hardware described in Table 5, following the instructions supplied with the kit.
Table 5. Breaker Mounting Screw Kits
Catalog Number Application Kit Description
Four #12-24x3-3/4 screws and lock washers Four #12-24x4-1/4 screws, nuts, and lock washers
SFGMSK1
SFGMSK2
Mounting plate with tapped holes
Mounting plate with clearance holes
For GE switchboard and panelboard mounting:
Install the breaker into the equipment according to the instructions supplied with the equipment. Available mounting hardware kits are listed in Table 6.
Table 6. Equipment Mounting Hardware Kits
Equipment Double Branch Single Branch
Panelboard-Spectra Series AMC6GBFP AMC3GMFP Switchboard – Spectra Series class 1 and 2 Switchboard – AV1, AV2 N/A N/A
Switchboard – AV3, AV5 N/A ContactFactory
AMC6GBFP AMC3GMFP
NOTE: Trip units as received may have settings that are undesirable for the specific application. Ensure that settings are appropriately adjusted before energizing the breaker.
Operation
The circuit breaker status is indicated by ON/OFF markings, universal I/O symbols, and an indicator window that shows red for ON, yellow for TRIP, and green for OFF. The corresponding handle positions are illustrated in Figure 2. To close the breaker from the OFF position, move the handle to the ON position. To close the breaker from the TRIP position, first move the handle to the OFF (reset) position, and then back to the ON position.
A Push-To-Trip button is provided for convenience in testing the mechanical operation of the breaker.
GEH-700 Installation Instructions
Figure 2. Handle Positions for ON, Tripped, OFF, and RESET
Maintenance
It is recommended that the following operations be performed annually:
External Accessories
The following external accessories are available for Spectra RMS SK Frame breakers. Catalog numbers and other ordering information for these external accessories may be obtained from your authorized GE distributor.
• Mounting kits
• Plug-in base, bolt-on base
• Back-connected studs
• Padlocking devices
• External Handle operator
• Motor operators
• Mechanical interlock
WARNING: Danger of electrical shock or injury. Turn off power ahead of equipment before attempting to service.
IMPORTANT: Danger d’électrocution. Couper l’alimentation avant d’affectuer toute action d’entretien.
1. Turn off the power to the equipment being serviced.
2. Clean the surfaces of the breaker and surrounding area of any dirt, soot, or other debris.
3. Inspect the breaker for any signs of damage.
4. Operate the push-to-trip button and toggle handle several times to exercise the mechanism and test the mechanical operation of the breaker.
5. Check all overcurrent protection and protective relay settings for correct values as established for the system.
6. If any sign of damage is found, or the mechanism has a sluggish or sticky operation, or the trip unit display designates an error status, replace the circuit breaker.
The circuit breaker is sealed and contains no user­serviceable parts. Opening the breaker will void any and all warranties.
GEH-700 Installation Instructions
Notes
GEH-700 Installation Instructions
Notes
Spectra and MicroVersaTrip are registered trademarks and EntelliGuard and microEntelliGuard are trademarks of the General Electric Company.
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE Company.
GE Energy
41 Woodford Avenue, Plainville, CT 06062 www.geelectrical.com © 2010 General Electric Company
imagination at work
GEH-700 Rev. 3 (07/10 M45)