Data Sheet February 2010
SLI Inverters
High-Efficiency, Low-Profile 1500 VA Inverters
Features
N+1 parallelable operation for
capacity or redundancy without additional hardware
Ultra compact 1U module size
Microprocessor controlled status
and monitoring ensures precise operation of all inverter functions
Tru e s in e wa ve o ut pu t
24 or 48 VDC input options
120 or 240 VAC 50 / 60 Hz outputs
Integrated static bypass switch option
High efficiency (93%) making it ideal for alternative energy
applications
LCD and LED status display
Serial or CANBUS communications
Accommodates harsh environments in excess of 40°C
DC noise filtering eliminates noise on DC bus (<2mV psophometric)
On-line or off-line mode selectable
Meets UL, cUL, and CE requirements
The SLI Family of “Slim Line” inverters represents an ideal solution for telecom and industrial applications. Thanks to innovative technology solutions like the patented “Compact coil” these inverters pack 1500 VA of power into a small and light package 19” or 23” rack mountable and just 1 rack unit high. The efficiency peaks 93%.
The family includes 4 models for different inputs (24Vdc and 48Vdc) and output (115Vac and 230Vac) voltage combinations. Several options are available for internal Static Transfer Switch
(STS), parallel hot-swap operation to realize flexible and scalable systems, grid connectivity for Distributed Generation systems with control of the power exchanged with the grid, and extended communication features.
The inverter carries on-board a powerful DSP (Digital Signal Processor) and allows easy programmability of the main parameters by means of an LCD display and keypad on the front panel. The unit can be interfaced with RS485 or optional CAN bus to an external controller.
Data Sheet SLI Inverters February 2010 High-Efficiency, Low-Profile 1500 VA Inverters
Specifications
Electrical
Input Voltage 48 VDC (40-72 VDC) or 24 VDC (20-36 VDC) Output Voltage 115 VAC (100-120 VAC) or 230 VA C (200- 240 VAC ) - sel ect 115 or 23 0 VAC
model Output Power 1500 W Output Waveform True sine wave Frequency 50/60 Hz (47-63 Hz) - select 50 or 60 Hz model Frequency (Stability) ±0.02% maximum Inverter Technology Pulse Width Modulation /High Frequency Switching Dielectric Strength 2,500 VAC minimum Inrush Current <10 A Operating Modes On-line (standard); Standby (selectable) Efficiency peak efficiency 93% Output Power Factor 0.33 lagging or leading To ta l Ha r mo n ic Di s to r ti o n 2 % m ax im um fo r li n ea r l oa ds /< 3% f o r n on -l in e ar lo ad s DC Noise Feedback < 30 dBrnc Transient Response <3% voltage change on instantaneous 0 to 100% load change Transfer Time (With Static Switch) < 2 msec Overload Capacity up to 125% continuous; 125% to 150% - 1800 cycles, 150% to 220% - 24
cycles, 220% to 300% - 4 cycles Load Voltage Regulation +3%/-1% Communications RS-485 or CANBUS communications interface and photo alarm relay Display 2 x 20 LCD display (optional) with LED status bar Input Overvoltage Protection 48 Vdc models: 74V; 24 Vdc Models: 37V Input Undervoltage Protection 48 Vdc models: 36V; 24 Vdc Models: 18V Input Overcurrent Protection 48 Vdc models: 70A; 24 Vdc models: 140A Overload 230 Vac models: 1800 VA; 115 Vac Models: 1650 VA Surge Capacity 230 Vac models: 2300 VA for 200 ms; 115 Vac Models: 1750 VA for 200 ms Electronic Overcurrent Protection 230 Vac Models: 1A to 8A (selectable); 115 VAC Models: 2A to 15A (selectable) AC Circuit Breaker 230 Vac Models: 10A; 115 Vac Models: 15A Electronic Short-circuit Protection: 230 Vac Models: 30A; 115 Vac Models: 60A Protection Mode Progammable for "latch" or "auto restart" after incident Isolation PRI-SEC: 3000 Vrms PRI-GND: 1000 Vrms SEC-GND: 1500 Vrms Signal-GND: 0
Vrms MTBF 200,000 hours at 40°C