The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be
reproduced, either in part or in its entirety, without the prior written consent of GE.
The illustrations and plans describing the equipment are intended as general reference only and are
not necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.
Modifications reserved Page 2/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50 & 60 kVA
f
t
Dear Customer,
We thank you for selecting our products and are
pleased to count you amongst our very valued
customers at GE.
We trust that the use of the LP 33 Series
Uninterruptible Power Supply system, developed
and produced to the highest standards o
quality, will give you complete satisfaction.
Please carefully read the Installation Guide.
It contains all the necessary information abou
the installation of the UPS.
Thank you for choosing GE !
START UP AND COMMISSIONING
A GE Global Services Field Engineer must perform start-up and commissioning of the
UPS. Please Contact G.E. Global Services at least two weeks prior to schedule start-up
and commissioning at 1-800-637-1738, or by E-mail at gedeservices@indsys.ge.com
g
GE Consumer & Industrial SA
General Electric Company
CH – 6595 Riazzino (Locarno)
Switzerland
www.gedigitalenergy.com
Distributed in the USA by:
g
GE Zenith Controls
General Electric Company
2501 Pecan Street
Bonham, Texas 75418
T 903 640 7900
T 903 640 7900
www.geindustrial.com/cwc/home
Your service contact:
Modifications reserved Page 3/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
Preface
Congratulations on your choice of a LP 33 Series Uninterruptible Power Supply (UPS).
It will help eliminate load disturbances due to unexpected power problem.
This Installation Guide describes how to prepare the installation site, and it provides
weight and dimensions and procedures for moving, installing and connecting the UPS.
While every care has been taken to ensure the completeness and accuracy of this
manual, GE assumes no responsibility or liability for any losses or damages resulting from
the use of the information contained in this document.
WARNING !
LP 33 Series / 50 & 60 kVA, is a product that needs to be installed by a licensed and
knowledgeable contractor.
We recommend that this manual be kept next to the UPS for future references.
If any problems are encountered with the procedures contained in this manual, please
contact your Service Center before you proceed.
This document shall not be copied or reproduced without the permission of GE.
Some of the information contained in this manual may be changed without notice to
reflect technical improvements.
Safety instructions
Read the safety instructions contained on the following pages carefully before the
installation of the UPS, options and battery system.
Pay attention to the rectangular boxes included in the text:
They contain important information and warning concerning electrical connections and
personnel safety.
Parallel version secured with RPA
When included in the text, this symbol refers to operation needed
only for parallel system.
Modifications reserved Page 4/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
3.1.1Dimensions and weight ............................................................................................................................ 13
3.3.1Storage of the UPS ...................................................................................................................................... 14
3.3.2Storage of the battery............................................................................................................................... 15
3.4PLACE OF INSTALLATION.......................................................................................................................................... 16
3.5VENTILATION AND COOLING.................................................................................................................................. 19
4.3EPO (EMERGENCY POWER OFF)............................................................................................................................. 38
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
1 SAFETY RULES
With this document, GE gives to the user all the necessary information about the correct use of the UPS.
Please read carefully this Installation Guide before installing or operating the UPS.
We recommend that this manual be kept next to the UPS for future references.
If any problems are encountered with the procedures contained in this manual, please contact the
nearest Service Center before you proceed.
All UPS installation, maintenance and service work should be performed by qualified service personnel
only.
The KNOWLEDGE and the FULLY compliance of the safety instructions and the warning
contained in this manual are
THE ONLY CONDITION
to avoid any dangerous situations during installation, operation, maintenance work,
and to preserve the maximum reliability of the UPS system.
NOTE !
LP 33 Series / 50 & 60 kVA is a FCC Class A-UPS Product.
While every care has been taken to ensure the completeness and
accuracy of this manual, GE assumes no responsibility or liability for any
losses or damages resulting from the use of the information contained in
this document.
GE Refuses any responsibility in case of nonobservance, unauthorised alterations or improper
use of the delivered UPS.
Modifications reserved Page 6/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
SAVE THESE INSTRUCTIONS
This manual contains important instructions for models LP 33 Series / 50 & 60 kVA that should be
followed during installation and maintenance of the UPS and battery.
- Move the UPS in an upright position in its original package to the final destination room.
- Check for sufficient floor and elevator loading capacity.
- Check the integrity of the UPS equipment carefully. If you notice visible damage, do not install or
start the UPS. Contact the nearest Service Center immediately.
- WARNING! RISK OF ELECTRICAL SHOCK: Do not remove covers; there are no user serviceable parts
inside.
- After switching off takes 10 minutes for the DC capacitors to discharge because a lethally high
voltage remains at the terminals of the electrolytic capacitors.
- All maintenance and service work should be performed by qualified service personnel.
The UPS contains its own energy source (battery).
- The field-wiring terminals may be electrically live, even when the UPS is disconnected from the
utility.
- Dangerous voltages may be present during battery operation.
The battery must be disconnected during maintenance or service work.
- This UPS contains potentially hazardous voltages.
- Be aware that the inverter can restart automatically after the utility voltage is restored.
INSTALLATION
- This UPS must be installed and connected only by trained personnel.
- Verify accurately during Commissioning and Maintenance of the UPS, for the following: Damaged
components, squeezed wires and cables, or not correctly inserted plugs.
- After removing the sidewalls of the UPS, make sure that all earth connections when reassembling,
are correctly reattached.
- This UPS is intended for use in a controlled indoor environment free of conductive contaminants and
protected against animals intrusion.
- HIGH GROUND LEAKAGE CURRENT: Ground connection is essential before connecting to AC input!
- Switching OFF the unit does not isolate the UPS from the utility.
- Do not install the UPS in an excessively humid environment or near water.
- Avoid spilling liquids on or dropping any foreign object into the UPS.
- The unit must be placed in a sufficiently ventilated area; the ambient temperature should not
exceed 104°F (40°C).
- Optimal battery life is obtained if the ambient temperature does not exceed 77°F (25°C).
- It is important that air can move freely around and through the unit. Do not block the air vents.
- Avoid locations in direct sunlight or near heat sources.
- Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (55°C).
- If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically
(time depending on storage temperature).
- The battery-voltage is dangerous for person’s safety.
-When replacing the battery, use the same cells number, voltage (V), capacity (Ah).
All the battery used, shall be of the same manufacturer and date of production.
- Proper disposal or recycling of the battery is required.
Refer to your local codes for disposal requirements.
- Never dispose of battery in a fire: They may explode.
- Do not open or mutilate battery: Their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
- Avoid charging in a sealed container.
- Never short circuit battery. When working with battery, remove watches, rings or other metal
objects, and only use insulated tools.
- In case of air shipment, the cables +/- going to the battery fuses/terminals shall be disconnected
and isolated.
GENERAL
STORAGE
BATTERY
Modifications reserved Page 7/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
Safety instructions when working with battery
THE BATTERY MUST BE INSTALLED AND CONNECTED TO THE UPS BY QUALIFIED
SERVICE PERSONNEL.
INSTALLATION PERSONNEL MUST READ THIS ENTIRE SECTION AND REFER TO THE
BATTERY MANUFACTURERS INSTALLATION MANUAL BEFORE HANDLING THE UPS
AND BATTERY.
Full voltage and current are always present at the Battery Terminals.
The Battery used in this system can provide dangerous voltages, extremely high currents and a risk of
electric shock.
They may cause severe injury if the terminals are shorted together or to ground.
You must be extremely careful to avoid electric shock and burns caused by contacting Battery Terminals or
shorting terminals during battery installation.
Do not touch un-insulated Battery Terminals.
A qualified service person that is familiar with Battery systems and required precautions must install and
service the Battery.
The installation must conform to national and local codes.
Keep unauthorized personnel away from Battery.
The qualified service person must take these precautions:
1 Wear protective clothing, such as rubber gloves and boots and protective eye wear.
Batteries contain caustic acids and toxic materials and can rupture or leak if mistreated.
Remove rings and metal wristwatches or other metal objects and jewelry.
Do not carry metal objects in your pockets where the objects can fall into the Battery Cabinet.
2 Tools must have insulated handles and must be insulated so that they will not short Battery Terminals.
Do not allow a tool to short between individual or separate Battery Terminals or to the cabinet or rack.
Do not lay tools or metal parts on top of the Battery, and do not lay them where they could fall onto the
Battery or into the cabinet.
3 Install the Battery as shown on the drawing provided with the Battery.
When connecting cables, never allow a cable to short across a Battery’s Terminals, the string of batteries,
or to the cabinet or rack.
4 Align the cables on the Battery Terminals so that the cable lug will not contact any part of the cabinet or
rack, even if the Battery is moved.
Keep the cable away from any sharp metal edges.
5 Install the Battery Cables so the UPS or Battery Cabinet Doors cannot pinch them.
6 Do not connect the Battery Terminal to Ground.
If any Battery Terminal is inadvertently grounded, remove the source of the ground.
Contacting any part of a grounded Battery can cause a risk of electric shock.
y
7 To reduce the risk of fire or electric shock, install the Battery in a temperature and humidity controlled
indoor area, free of contaminants.
8 Battery System Chassis Ground (earth) must be connected to the UPS chassis ground (earth).
If you use conduit, this ground conductor must be routed in the same conduit as the Battery Conductors.
9 Where conductors may be exposed to physical damage, protect the conductors in accordance with all
applicable codes.
10 If you are replacing Battery or repairing Battery Connections, shut OFF the UPS and remove the Battery
Fuses or open the Battery System disconnect.
DANGER!
Modifications reserved Page 8/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
Safety symbols and warnings
Safety warnings
The text of this manual contains some warnings to avoid risk to the persons and to avoid damages to
the UPS system and the supplied critical loads.
The non-observance of the warnings reminding hazardous situations could result in human injury and
equipment damages.
Please pay attention to the meaning of the following warnings and symbols.
Throughout this manual the following symbols are defined:
WARNING, if instruction is not followed injury or serious equipment damage
may occur!
CAUTION, internal parts have dangerous voltage present.
Risk of electric shock!
PE (Earth) – GND (Ground)
PROTECTIVE GROUNDING TERMINAL:
A terminal which must be connected to earth ground prior to making any other
connection to the equipment.
A terminal to which or from which an alternating (sine wave) current or voltage
may be applied or supplied.
A terminal to which or from which a direct current or voltage may be applied or
supplied.
This symbol indicated the word “phase”.
This symbol indicates the principal on/off switch in the on position.
This symbol indicates the principal on/off switch in the off position.
Modifications reserved Page 9/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
r
2 LAYOUT
2.1 LAYOUT LP 33 Series / 50 & 60 kVA
Fig. 2.1-1 General view stand-alone Fig. 2.1-2 General view stand-alone with open doo
Fig. 2.1-3 General view Fig. 2.1-4 General view with open door
Modifications reserved Page 10/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
t
t
Fig. 2.1-5 Control panel
Opening for input and output of cables
1
Fig. 2.1-6 General view without protection panels
FTM3
SNMP
Battery shelves
2
Customer Interface Board (optional)
CI
UPS output switch
Q1
Manual bypass switch
Q2
Battery breaker
Relay card
RC
RPA parallel board (optional)
RPA
Advanced SNMP Card (optional)
Terminals for common mains inpu
X1
connection (rectifier + bypass)
Terminals in case of dual mains inpu
X2
(optional)
Terminals for load output connection
X3
Terminals for external battery
X4
connection
Modifications reserved Page 11/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
3 INSTALLATION
3.1 TRANSPORT
The UPS is fixed on transport socket suitable for forklift, which include a special layer of Ethafoam to
protect the equipment against the transport shock.
Normally the UPS is packaged with carton box.
On request the equipment can be packaged in wooden case.
Move the UPS in its original package to the final destination room.
Do not stack other package on top: they could damage the upper side of the cabinet.
NOTE !
When moving the UPS, pay attention to:
FRAGILE
SENSITIVE
TO DAMPNESS
SENSITIVE
TO HEAT
SENSITIVE
TO FROST
Forklift
Forklift
The UPS may be lifted with a forklift in upright
position from right and left side.
Take note of the center of gravity marked on
the package.
Crane
NOTE !
Check for sufficient floor and elevator
loading capacity.
Transport UPS only in upright position.
Do not stack other package on top of the
UPS.
Crane
If the UPS has to be lifted by crane, use
suitable carrying belts taking note of the
center of gravity marked on the package.
Fig. 3.1-1 LP 33 Series lifting
damage to the cabinet while hoisting the
UPS
WARNING !
When loading / downloading and when
Take all necessary precautions to avoid
moving the UPS, it is forbidden:
When loading / downloading and when
moving the UPS, pay attention to:
Modifications reserved Page 12/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
3.1.1 Dimensions and weight
Fig. 3.1-1 LP 33 Series / 50 & 60 kVA
LP 33 Series / 50 & 60 kVA
Dimensions (W x D x H)
UPS weight without battery 1015 lbs / 460 Kg
UPS weight with battery 33 Ah (48 blocks) 2139 lbs / 970 Kg
UPS floor loading without battery
UPS floor loading with battery 33 Ah (48 blocks)
UPS with standard shipping 1081 lbs / 490 Kg
45.28” x 29.61” x 71.85”
1150 x 752 x 1825 mm
109 lbs/sq.ft / 532 Kg/m
230 lbs/sq.ft / 1122 Kg/m
2
2
NOTE !
The weight of each single piece is marked outside the package!
Modifications reserved Page 13/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
3.2 DELIVERY
When delivered, check carefully the package integrity and the physical conditions of the UPS
equipment.
In case of any damage to UPS during transport, immediately inform the carrier and contact your local
Service Center.
A detailed report on damage is necessary for any insurance claim.
NOTE !
A damaged UPS must never be installed or connected to utility or battery!
3.3 STORAGE
The equipment is carefully packed for transport
and storage so that it is in a perfect condition
when eventually installed.
Never leave an UPS outside the building and do
not store the UPS one on top of the other.
It is recommended to store the UPS in its
original package in a dry, dust free room and
far away from chemical substances, with
3.3.1 Storage of the UPS
Some important functions of UPS, such as the customized functions, are defined by parameters stored
in a RAM memory.
The RAM is supplied by a small backup battery located on the Control Unit board.
If the storage time of the UPS exceeds 1 year, these functions should be verified by an authorized
Service Center before putting the UPS into operation.
temperature not exceeding -13°F to 131°F (25°C to 55°C).
NOTE !
In case of storage of the UPS pay attention to:
FRAGILE
SENSITIVE
TO DAMPNESS
SENSITIVE
TO HEAT
SENSITIVE
TO FROST
Modifications reserved Page 14/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
3.3.2 Storage of the battery
In case of extended storage, when the delivery includes maintenance free batteries, keep in mind that
they are subject to auto-discharging process
To avoid permanent damages to the battery, you must observe the following instructions:
xThe storage time without charging the battery depends on the temperature of the storage ambient.
xThe optimal ambient temperature for the batteries is 68°F (20°C).
For storage temperature higher than 68°F (20°C), the storage time will decrease.
xEach additional 18°F (10°C) over the nominal temperature of 68°F (20°C) will decrease the storage
time, without freshening charge, by half.
In case of a maintenance free battery, the storage time without charging the battery is
approximately:
6 months with storage temperature 68°F (20°C)
3 months with storage temperature 86°F (30°C)
2 months with storage temperature 95°F (35°C)
NOTE !
In case of battery storage pay
attention to:
FRAGILE
SENSITIVE
TO DAMPNESS
SENSITIVE
TO HEAT
SENSITIVE
TO FROST
Modifications reserved Page 15/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
3.4 PLACE OF INSTALLATION
The UPS should be installed in a restricted area where only qualified personnel should be admitted.
The place of installation should be clean, dust-free, and provided with proper ventilation or air-
conditioning.
Verify for sufficient floor load capacity (see Section 3.1.1).
We strongly advice that the ambient temperature should not exceed 68° ÷ 77°F/ 20° ÷ 25°C (max. 95°F
/ 35°C). See Section 3.5.
Positioning of the UPS LP 33 Series / 50 and 60 kVA
The rear panel of the UPS may be
mounted flush to a wall or other
structure.
Clearance around the front of the unit
should be sufficient to enable free
passage of personnel with the doors fully
open, and to allow sufficient airflow to the
door vents.
To guarantee proper cooling air exhaust,
the recommended minimum clearance
between ceiling and top of the UPS is 16”
(400mm).
In case of additional cabinets (external
batteries), this must be placed beside the
left side of the UPS cabinet.
A single-phase power outlet (208 VAC)
should be provided near the UPS for
connection of power tools, test
equipment or connectivity devices.
Fig. 3.4-1 Positioning LP 33 Series / 50 & 60 kVA
This outlet must be grounded.
The LP 33 Series UPS can radiate radio frequency energy.
Although some RFI (Radio Frequency Interference) filtering is inherent to the UPS there is no guarantee
that the UPS will not influence sensitive devices such as cameras and monitors that are positioned close
by.
If interference is expected, the UPS should be moved away from the sensitive equipment.
NOTE !
Operating temperature is very important for valve regulated battery (maintenance
free).
Operation at temperatures higher than 68°F (20°C) will reduce life expectancy.
Respect the prescription of the battery supplier and other local standards.
The installation and cabling of the battery must be done by qualified people.
Modifications reserved Page 16/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
Opening for input and output cable connections LP 33 Series
Fig. 3.4-2 Opening on the bottom of the cabinet for input and output cables
Fixing of the UPS cabinet LP 33 Series on the floor
LP 33 Series opening is provided
on the bottom of the UPS for the
connection of input and output
cables.
Pay attention to the position of
this opening, when choosing the
placement of the UPS.
The UPS cabinet is free standing
Fig. 3.4-3 Fixing of the UPS cabinet on the floor
and normally does not require to
be bolted to the floor.
The UPS cabinet can be fixed
however to the floor by bolting it
with the supporting blocks to the
floor.
Fig. 3.4-4 UPS cabinet floor fixing points
Modifications reserved Page 17/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
Positioning of the UPS cabinet
Fig. 3.4-5 Bolts for the regulation of the cabinet
LP 33 Series is equipped with wheels for
easy placement of the UPS.
To make the UPS movable on wheels, the
bolts on each leg of the cabinet have to be
turned counter-clockwise, until they are
free from the floor and thus the cabinet
supported on wheels.
After having positioned the UPS at its final
location, the cabinet has to be secured by
rotating the bolts on each leg clockwise,
but the wheels must still touch the floor.
In case of parallel system, try to place
the UPS modules in sequence of their
numbers (marked on the packing).
If the units are positioned “side by side”,
the side panels must be mounted on all
units.
Fig. 3.4-6 RPA system disposition
Modifications reserved Page 18/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
3.5 VENTILATION AND COOLING
The heat produced by the UPS is transferred to the environment by its internal blowers.
Airflow through the UPS
It is important that the cooling air can freely flow
through the air inlets and outlets of the UPS.
NOTE !
Do not put any object on the top of the
Fig. 4.5-1 Airflow through the LP 33 Series
cabinet: it might obstruct the air flow.
Heat evacuation from UPS room
The heat must be evacuated from the
environment with a proper cooling /
ventilation system provided by the
user.
Fig. 4.5-2 Heat evacuation from UPS room
Air volume and losses of the UPS
The approximate minimum air volume needed to evacuate the heat generated by the UPS, for inlet
temperature max. 35°C (95°F), for the standard version at inverter nominal load with PF = 0.9 lag. and
battery charged, are the following:
UPS model
VFI Mode ECO Mode VFI Mode ECO Mode
Losses Cooling air flow
LP 33 Series / 50 kVA
16690 BTU/hr
4.89 kW
20478 BTU/hr
LP 33 Series / 60 kVA
6.0 kW
Modifications reserved Page 19/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
3482 BTU/hr
1.02 kW
4164 BTU/hr
1.22 kW
847 CFM
1440 m
3
1040 CFM
1767 m
3
/h
/h
173 CFM
294 m3 /h
211 CFM
359 m3 /h
3.6 UNPACKING
Move the equipment in it’s original packing, carton box or wooden case, until the place of installation
and remove the packing and the transport sockets only just before installing the UPS.
Procedure for the unpacking of the UPS:
x Make sure to have sufficient space
1
around the UPS before you start
unpacking.
x Cut the two straps “A” fixing the carton
box.
2
0
_
g
n
i
k
c
a
p
n
U
_
0
4
0
-
0
3
0
_
U
3
3
S
P
L
B
TM
y
g
e
r
E
n
g
i
a
l
t
ri
e
s
i
D
S
e
L
P
x Remove package “B and C”.
2
C
C
E
N
T
E
R
o
f
G
R
A
V
I
T
Y
D
L
U
R
E
T
N
E
C
f
o
Y
T
I
V
A
R
G
x Remove the protection “D” outside the
cabinet and the accessories bag.
x Remove the screws on the four small
bracket “E”.
x Use a forklift to raise the UPS from the
floor.
x Remove the three wooden plates “F”.
3
NOTE !
Be aware of the heavy
weight of the UPS, in
particular if already
equipped with Batteries.
Fig. 3.6-1 LP 33 Series unpacking sequence
Included in the delivery you can find the following parts:
x CD-ROM connectivity
x Control Bus cables (only for RPA parallel system) x An accessories bag
NOTE !
The wheels are designed only for limited movements on the installation site.
Modifications reserved Page 20/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
NOTE !
A damaged UPS must never be installed or connected to utility or battery!
In case of any damage sustained during the transport, immediately inform the
shipping agent!
A detailed report of the damage is necessary for any indemnity claim.
Packing material recycling
GE, in compliance with environment protection, use only environmentally
friendly material.
UPS packing materials must be recycled in compliance with all applicable
regulations.
Modifications reserved Page 21/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
3.7 ELECTRICAL WIRING
WARNING !
UPS installation and connection must be performed by QUALIFIED SERVICE
PERSONNEL only.
It is the responsibility of the installation technician to ensure that all local and
national electric codes are adhered to.
3.7.1 Utility input connection
WARNING !
Ensure that the AC and DC external isolators are OFF and locked out to prevent their
inadvertent operation.
Do not apply power to the equipment prior to the commissioning by a qualified service
engineer.
Before any other input connection, connect and check the grounding wire.
The UPS has equipped with input terminations for the Rectifier and Bypass.
The standard unit comes with common input terminals for rectifier and Bypass. Separate input terminals
The same power source is used for both
Bypass Supply and Rectifier Input (input F1).
Keep note that when the Utility Fuses are
opened there is a supply failure to the Rectifier
as well as to the Bypass and Manual Bypass.
Dual input Rectifier & Bypass (option)
The Bypass and Rectifier inputs are to be
powered from different Utility supplies (F2 and F3 inputs).
In this case, when the Rectifier Input Fuses are
opened, the Bypass and the Manual Bypass
are supplied by the other source.
Modifications reserved Page 22/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
3.7.2 Input/output over current protection and wire sizing
The cabling of the UPS system has to be sized according to the UPS power rating.
Ratings of circuit breakers, fuses and cables for Input Utility, Output Load and Battery must meet the
requirements of local and national electrical codes.
Before connecting the UPS, verify that the Utility Voltage and Frequency, the Output Load Voltage and Frequency and Battery Data (cells number, floating voltage, autonomy) are according to the required
specifications.
Output load configuration may be such that one phase may carry a load current at 100% of that
phases maximum current rating while the other two phases run at 0% or any combination in between.
Ensure that the load does not consist of any equipment that may require high starting currents such as
electric motors, laser printers, etc.
This may cause the UPS to occasionally go into Bypass due to overload conditions
To choose the correct input fuses or circuit breaker, consider the available short-circuit current of the
system up-stream. Choose the correct fuse or breaker using current data shown in the chart and the
appropriate NEC code.
The ratings indicated in the following chart do not consider any line voltage drop.
In case of optional input transformer the input protective devices should be sized to allow the
transformer magnetization inrush current.
Caution when using four-pole circuit breakers as protection.
A potential problem exists for situations with non-linear loads:
The neutral current could be greater than the phase currents.
The three-phase Utility power supply must be symmetrical with respect to ground, due to the existence
of voltage surge protection devices inside the UPS.
NOTE !
If you use ELCB breaker (Earth Limiting Circuit Breaker) to protect the input
connections, consider the high leakage current generated by the noise suppression
capacitors.
If these ELCB breakers are strictly necessary, we suggest using the largest type
suitable for non-linear current and for delayed operations.
To ensure coordination when the UPS is configured for Separate Bypass and Rectifier Inputs, special
care must be taken in choosing the fuse or circuit breaker ratings installed in the output distribution
circuits.
Protective devices on the output of the UPS should be coordinated with the Bypass Input circuit
protection.
Due to the relatively low short circuit capability of the UPS inverter, a short circuit in the load will cause
an immediate transfer to Bypass.
The largest fuse or circuit breaker in the output distribution should be rated at no more than 60% of the
rating of the protective device supplying the Bypass line.
If circuit selectivity is required while the load is fed from the inverter (Bypass Utility not available), the
largest fuse or circuit breaker should be rated at no more than 20% of the UPS output current rating.
Modifications reserved Page 23/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
Fig. 3.7.2-1 RPA Parallel System
In order to ensure a correct load sharing between the parallel units, when the load is
supplied by utility, it is recommended to keep the cable size and length from the
input distribution board to the output bus-bar the same for each parallel unit.
Utility Bypass input voltage must be the same for all units, thus avoiding phase shift
or phase rotation problems.
To avoid mutual induction effect, the input cables must be run in separate conduit
from the output cables.
NOTE !
No transformers, fuses or automatic circuit breakers should be inserted
between the unit’s output and the load common bus-bars.
The delivery and installation of fuses and input / output connections of the UPS are at the
customer’s expense, unless agreed otherwise.
NOTE !
It is recommended to provide an additional length of the input/output cables so that
the UPS can be moved for maintenance purpose.
It is recommended to use flexible input/output conductors with suitable length to
admit a sufficient displacement.
3.7.3 Battery over current protection and wire sizing
xPlease read the safety precautions at the front of this guide carefully, and thoroughly review the
battery manufacturers installation and maintenance manual before connecting the batteries to the
UPS.
xChoose an appropriate DC fuse or circuit breaker using the current data in the chart below.
xMinimum battery cable requirement is based on the current data below.
Modifications reserved Page 24/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
3.7.4 General dates table for current protection and wire sizing
The AC values below are current ratings per phase.
These maximum and nominal ratings should be considered when choosing the
appropriate AC over current protection device.
NEC (National Electric Code) Section 210-20 a rules must be applied.
DC current rating is the maximum battery discharge current which the UPS allows.
AC InputAC Input RectifierAC Input BypassDC Input
UPS Model
LP 33 Series / 50 kVA 145A
LP 33 Series / 60 kVA 178 A
F1
Nom. Max.
145 A
178 A
F2
F3 F4
174 A139 A175 A214 A167 A210 A
Size of Branch Circuit Over current Protection - All Models:
"CAUTION - To reduce the risk of fire, only connect UPS to a circuit provided with (see below)
maximum amperes branch circuit over current protection in accordance
with the NEC (National Electric Code), NSI / NFPA 70
UPS Model
LP 33 Series / 50 kVA
LP 33 Series / 60 kVA
AC Input AC Input Rectifier AC Input Bypass DC Input
F1 F2 F3 F4
200 A
200 A200 A213 A
225 A
225 A225 A250 A
Wire sizing according to NEC Section 210-20 (a) Table 310-16
For recommended wiring, see below table.
AC INPUT: 3-Phase, 4 wires plus GND
AC OUTPUT: 3-Phase, 4 wires plus GND
DC INPUT: 3 wires (positive, negative and neutral) plus GND
Use following single copper wire, AWG size (temperature rating of conductor)
UPS Model Rectifier Input Bypass Input AC Output DC Input
LP 33 Series / 50 kVA
LP 33 Series / 60 kVA
Modifications reserved Page 25/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
4 x 3/0 (75°C) 4 x 3/0 (75°C) 4 x 3/0 (75°C) 3 x 3/0 (90°C)
4 x 3/0 (90°C) 4 x 3/0 (90°C) 4 x 3/0 (90°C) 3 x 4/0 (90°C)
NEC SECTION 210-20 (a)
Table 310-16. Allowable Ampacities of Insulated Conductors Rated O Through 2000 Volts, 60°C
Trough 90°C (140°F Trough 194°F) Not More than Three Current-Carrying Conductors in Raceway,
Cable, or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F).
Size Temperature Rating of Conductor (See table 310-13)
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
3.8 WIRING CONNECTION
WARNING!
UPS installation and connection must be performed by QUALIFIED SERVICE
PERSONNEL only.
3.8.1 Power connections
Input/output and DC connections are provided with terminal blocks.
Please refer to chart for torque specifications.
Carefully read the following recommendations before proceeding:
xEnsure that the AC and DC external isolators are OFF and locked to prevent their inadvertent
operation.
xDo not close any external isolators prior the commissioning of the equipment.
xThe preferred power cable entry location for installation purposes is from the bottom right side of
the UPS (see Fig 3.8.1-1).
For cable entry from the bottom remove the cover plate and provide for a suitable isolated
protection cover.
xThe input/output cables must be connected in clockwise phase rotation for both Bypass and
Rectifier Input Terminals if separate, taking care to avoid risk of short circuit between different
poles.
xThe grounding and neutral connection of the electrical system must be in accordance with local
regulations.
xIn case of additional cabinets containing batteries, input/ output transformers, etc, their ground
terminals must be connected to the UPS main ground terminal.
xOnce the power cables have been connected, re-install the internal safety shields and close the
cabinets by re-installing all external panels.
Torque Specifications
Mechanical Terminals
Input / Output / Battery
UPS Model WIRE SIZE RANGE Lb - in Nm
LP 33 Series / 50 kVA & 60 kVA Max 350 MCM 88 - 130 10 - 15
Torque Specifications
Mechanical Terminals
GND
UPS Model WIRE SIZE RANGE Lb - in Nm
LP 33 Series / 50 kVA & 60 kVA Max 350 MCM 375 42
Modifications reserved Page 27/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
How to access the terminals for the cable connections
Fig. 3.8.1-1 Access to the input / output connections
NOTE !
Drill in the plate “C” appropriate holes for cable conduits (max. 4 x 2 1/2”).
Please remove the plate “C” before drilling any wholes.
See Fig 3.8.1-1 - details “C & D”.
3.8.2 Internal fuse ratings
To access input, output and battery
connections proceed as follows:
x Open the front door “A” of the cabinet.
x Remove the protection panel “B”.
x Remove the plate “C” for bottom cable
entry.
LP 33 Series internal fuses
The Battery cabinet is equipped
with Breaker FTM3.
In case of replacement the same
type and the same rating must be
used.
WARNING !
Wrong polarity
connection can cause
hazard to UPS and
personal. The
replacement of
battery breaker
must be performed
Fig. 3.8.2-1 Battery Breaker – FTM3
by QUALIFIED
SERVICE PERSONNEL
only.
Modifications reserved Page 28/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
3.9 ELECTRICAL CONNECTIONS
WARNING !
The connections to and from the UPS must be executed by QUALIFIED PERSONNEL
ONLY.
Refer to the “Safety prescriptions - Installation” described on page 6.
3.9.1 Common input utility
Fig. 3.9.1-1 Common input utility
Common input utility
The UPS delivered in standard version has
common input utility.
Only one input line (F1) supplies both rectifier
and bypass input terminals.
Bear in mind that when the utility fuses are
opened there is a supply failure to the rectifier
as well as to the automatic bypass and manual
LP 33 Series / 50 kVA 350 MCM Max. rating X1, X3 and X4 terminals:
LP 33 Series / 60 kVA 350 MCM
Connect wire to the Terminals using appropriate tools and appropriate torque.
Torque specification for Input / Output and DC power connections on Terminals: Section 3.8.1.
NOTE !
For UPS correct operation, the input utility phase rotation must be clock-wise.
Inside the UPS, all neutrals N1 and N2 are connected together.
NOTE !
This UPS is designed to operate in a wye-configured electrical system with a solidly
grounded neutral.
Modifications reserved Page 29/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
3.9.2 Dual input utility (option)
Fig. 3.9.2-1 Dual input utility (option)
Dual input utility
On request, the UPS can be delivered for dual input
utility.
Two independent lines (F2 and F3) supply separately
the rectifier and the bypass inputs
With this configuration, when the rectifier-input fuses
are opened, the automatic bypass and the
maintenance bypass are supplied by the other line.
Fig. 3.9.2-2 Terminals for dual input utility
X1 Mains 1 - Rectifier input utility connection
L1-1 = Rectifier Phase A
L2-1 = Rectifier Phase B
L3-1 = Rectifier Phase C
N1 = Mains Neutral
PE = Main Ground
X3 Load - Output load connection
L1 = Load Phase A
L2 = Load Phase B
L3 = Load Phase C
N2 = Load Neutral GND = Load Ground
Max. rating X1, X2 , X3 and X4 terminals:
NOTE !
For UPS correct operation, the input utility phase rotation must be clock-wise.
Inside the UPS, all neutrals N1 and N2 are connected together.
NOTE !
This UPS is designed to operate in a wye-configured electrical system with a solidly
grounded neutral.
X2 Mains 2 - Bypass input utility connection
L1-2 = Bypass Phase A
L2-2 = Bypass Phase B
L3-2 = Bypass Phase C
N = Mains Neutral
Connect wire to the terminals by using
appropriate tools and appropriate torque.
Torque specification for Input / Output and DC
power connections on Terminals: Section 3.8.1.
LP 33 Series / 50 kVA
LP 33 Series / 60 kVA
350 MCM
350 MCM
Modifications reserved Page 30/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
3.9.3 Battery connection
Before proceeding to an external battery connection, follow the Safety rules concerning the battery.
Make sure that the UPS is not powered and remove the external battery protections.
NOTE !
To meet standards concerning electromagnetic compliance, the connection between
the UPS and external Battery must be done by using a shielded cable or suitable
shielded (metal) conduit!
List of possible battery configurations on LP 33 Series
Battery cabinet Battery type
Block number
1 Battery cabinet 33 Ah – 12 V 48 9 8 See Fig. 3.9.3-1
2 Battery cabinets 50 Ah – 12 V
2 Battery cabinets 33 Ah – 12 V
3 Battery cabinets
4 Battery cabinets
50 Ah – 12 V
50 Ah – 12 V
48
(24+24)
96
(48+48)
72
(24+24+24)
96
(24+24+24+24)
UPS with battery cabinet
X4 Battery - Battery connection
- = Negative pole of the battery
0 = Central point of battery blocks
+ = Positive pole of the battery
Autonomy (min.)
50 kVA 60 kVA
Note
16 13 See Fig. 3.9.3-1
24 18 See Fig. 3.9.3-1
29 23 See Fig. 3.9.3-2
39 33 See Fig. 3.9.3-2
GND= Battery cabinet ground
(refer Fig. 3.9.2-2)
Fig. 3.9.3-1 Diagram battery connection
Note !
The UPS unit is supplied with the battery connected as above showed on Fig. 3.9.3-1.
Modifications reserved Page 31/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
UPS with four battery cabinets (max. possible configuration)
X4 Battery - Battery connection
- = Negative pole of the battery
0 = Central point of battery blocks
+ = Positive pole of the battery
GND = Battery cabinet ground
Fig. 3.9.3-2 Diagram battery connection
WARNING !
Modifications reserved Page 32/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
Before closing the “Battery breaker”, verify for correct polarity of the battery
connection.
s
s
3.9.4 RPA system - Control bus connection
WARNING !
This operation must be performed by trained personnel before the initial start-up
(ensure that the UPS installation is completely powered down).
Access to the RPA board
1 - Open the front door “A” of the UPS
cabinet.
2 - Remove the front panel “B”.
3 - Remove with appropriate tool the
metallic window “C” from the metal
screen “D”.
NOTE !
Put in place the front screen
“A” paying attention to not
Fig. 3.9.4-1 Access to the RPA board
damaging the control bus
cables.
LPS33U_030-040_RPA connection_GE_02
LP 33 Serie
1
P1
P13
P34
J4
J3
LP 33 Serie
2
P13
P1
Fig. 3.9.4-2 Bus connection RPA parallel system
P34
J4
J3
LP 33 Series
3
P13
P1
P34
LP 33 Series
4
J4
J3
P1
P13
Bus connection RPA parallel system
Connect the control bus cable between the parallel units as indicated in the diagram Fig. 3.9.5-2.
Provide that the connectors J3 and J4 are properly fixed with the included screws.
P13
JP1 JP2
P1
LPS33U_030-040_RPA connec tion_03
Fig. 3.9.4-3 Connection to Board P16
JP3
P34
J4
J3
NOTE !
The jumper JP1 - JP2 - JP3 must be
removed only on the intermediate units,
where the connectors J3 and J4 are both
inserted.
Do not insert or remove J3 and J4 from
the board “P16 - Connector adapter RPA”
when the parallel system is operating.
P34
J4
J3
Modifications reserved Page 33/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
Fig. 3.9.4-4 Control bus location RPA parallel system
Control bus location RPA parallel system
Place the cables and connect them as indicated in the diagram Fig. 3.9.5-4 following these
procedures:
xFix the control bus cables with the appropriate tie-wrap “E”.
xPlace the cables between the parallel units in separated protected conduit to avoid they could
be accidentally interrupted.
xPut in place the front screen “B”(Fig. 3.9.4-1) paying attention to not damaging the control bus
cables.
It is important to place the units in sequence of their assigned number.
A unit number from P1 to P4, is defined by the setting of parameters and displayed on the control panel.
This number is also marked inside and outside the packaging.
The standard length of the control bus cable between two parallel unit is 26 ft / 8 m.
Modifications reserved Page 34/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
4 CUSTOMER INTERFACE
Fig. 4-1 Slot connectivity
LP 33 Series is supplied by a standard Serial Port J27 - RS232 (see Section 4.1) and a Relay Card(see Section 4.2).
List of possible connectivity configurations on LP 33 Series
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
- -
Advanced SNMP Card
(optional)
Customer Interface (optional)
4.1 SERIAL PORT J27 - RS232
Serial Port J27 - RS232
(sub - D, female 9 pin)
Total remote management of the
system using software GE Power
Diagnostics, GE Data Protection or GE
Service Software for system protection
and management of the UPS systems.
Fig. 4.1-1 Serial Port J27 – RS232
The serial port J27 - RS232 is enabled on all the units of the parallel system.
Serial port J27 – RS232 connection to PC with RS232 1:1 cable DB9m – DB9f
Fig. 4.1-2 Serial port J27 - RS232 connection to PC
Modifications reserved Page 36/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
4.2 RELAY CARD
WARNING !
Connections described in this chapter shall be done only by a trained person or
SERVICE ENGINEERS.
The Relay Card, allows the programming of 4 output channels on dry contacts, which can be read on
either terminal J3 or plug J4 (sub - D - male 9 pin).
Default configuration:
1
2
3 General alarm (NO)
4 Utility failure (NC)
5 C (common)
6 Load on utility (NO)
7 Stop operation
8 C (common)
9 Utility failure (NO)
NO = Normally Open C = Common NC = Normally Closed
Voltage free contacts: Max.: 60VDC or 30VAC / 0.5A
Min. signal level: 5VDC / 5mA
Fig. 4.2-1 Relay Card
Output signals on voltage-free contacts
On terminals J3 or J4 connector 4 of the following 28 signals can be selected from the display
(access only with password): MENU / PARAMETER MENU / LEVEL 2: SERVICE.
0 - No signal 15 - Battery discharge
1 - Buzzer 16 - Manual bypass ON
2 - General alarm (NO) 17 - Rectifier ON
3 - Load on utility 18 - Inverter ON
4 - Stop operation 19 - Battery boostcharge
5 - Load on inverter 20 - Battery earth fault
6 - Utility failure 21 - Battery fault
7 - DC overvoltage 22 - Relay input 1
8 - Low battery 23 - Relay input 2
9 - Overload 24 - Relay output ON
10 - Overtemperature 25 - Relay output OFF
11 - Inverter utility not syncrony 26 - EPO (Emergency Power Off)
12 - Bypass locked 27 - ECO Mode ON
13 - Bypass utility failure 28 - General alarm (NC)
14 - Rectifier utility failure
NOTE !
The function GEN-ON is not available on the Relay Card.
In case this function is needed, the optional Customer Interface card must be installed
(see Section 4.4.1).
Modifications reserved Page 37/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
4.3 EPO (EMERGENCY POWER OFF)
WARNING !
Connections described in this chapter shall be done only by a trained person or
SERVICE ENGINEERS.
An external Emergency switch (NC Normally Closed voltage-free contact) can
be connected on terminals X7 / 1, 2 of the
P1 – Control board.
NOTE !
Check that the Jumper JP5 is
not installed on the P1 –
Control board.
In a parallel system a
separate NC (Normally Closed) contact must be
Fig. 4.3-1 Terminals X7 - EPO
connected individually to
each unit.
When activated, this switch causes the immediate shutdown of booster, battery-charger, inverter; and
the contactors K4, K6 and K7.
NOTE !
This procedure could imply a load shutdown.
When the EPO has been activated, the system must be restored as following:
xPress the push-button EPO (contact on X7 / 1, 2 is closed again).
xPerform the command INVERTER OFF entering the screen:
MENU/COMMAND MENU/INVERTER OFF.
INVERTER ON
INVERTER OFF *
xStart the inverter entering the screen:
MENU/COMMAND MENU/INVERTER ON.
INVERTER ON *
INVERTER OFF
COMMAND MENU
COMMAND MENU
Modifications reserved Page 38/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
4.4 CUSTOMER INTERFACE BOARD (OPTION)
WARNING !
The installation and cabling of the options must be performed by
QUALIFIED SERVICE PERSON.
Serial port J3 - RS232 (sub - D - female 9 pin)
Total remote management of the system using software GE
Power Diagnostics, GE Data Protection or GE Service
J3
Software for system protection and management of the UPS
systems.
J2 (sub – D female 25p) – Output signals on voltage-free contacts
J2 / 1, 2, 3
J2 / 4, 5, 6
J2 / 7, 8, 9
J2
J2 / 14, 15, 16
J2 / 17, 18, 19
J2 / 20, 21, 22
Pin 2: TX (out)
Pin 3: RX (in)
Pin 5: GND
NO, C, NC Utility failure
NO, C, NC Load on inverter
NO, C, NC Stop operation
NO, C, NC Load on utility
NO, C, NC General alarm (NO)
NO, C, NC Buzzer
JP3
21
X2
2221
201918
17
567891011
4
3
2
1
r
e
t
n
i
r
e
m
o
t
s
u
C
_
U
3
3
S
P
L
Fig. 4.4-1 Customer Interface
C=Common
NO
=Normally Open
NC
=Normally Closed
1615
14
13
12
1
0
_
e
c
fa
Signals on terminals X1 and on connector J2 are in parallel and
therefore not separated galvanically from each other.
The programmable signals on X1 and J2 will be disabled with Q1
open, with the exception of the signals for:
To enable this function, remove jumper JP3 on the Customer Interface and the cable on the terminal X2 / 1, 2.
(See Fig. 4.4-1).
Verify if the cable on the terminal X7 / 1, 2 and jumper JP8 on the
P2 – Mainboard are OFF (see Fig. 4.4-3).
25 – Relay output OFF
26 – EPO
X1 – Output signals on voltage-free contacts
NO, C, NC Utility failure
NO, C, NC Load on inverter
NO, C, NC Stop operation
NO, C, NC Load on utility
NO, C, NC General alarm (NO)
NO, C, NC Buzzer
X2 – Terminals EPO connection (Emergency Power Off)
NC EPO (Emergency Power Off)
Programmable
Programmable / Generator ON (NO)
Modifications reserved Page 39/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
Output signals on voltage-free contacts
On terminals X1 or J2connector 6 of the following 28 signals can be selected from the display
(access only with password): MENU / PARAMETER MENU / LEVEL 2: SERVICE.
0 - No signal 15 - Battery discharge
1 - Buzzer 16 - Manual bypass ON
2 - General alarm (NO) 17 - Rectifier ON
3 - Load on utility 18 - Inverter ON
4 - Stop operation 19 - Battery boostcharge
5 - Load on inverter 20 - Battery earth fault
6 - Utility failure 21 - Battery fault
7 - DC overvoltage 22 - Relay input 1
8 - Low battery 23 - Relay input 2
9 - Overload 24 - Relay output ON
10 - Overtemperature 25 - Relay output OFF
11 - Inverter utility not syncrony 26 - EPO (Emergency Power Off)
12 - Bypass locked 27 - ECO Mode ON
13 - Bypass utility failure 28 - General alarm (NC)
14 - Rectifier utility failure
Programmable functions on input contacts (X1 - J2)
Some UPS functions can be activated by parameters (access with password only) when an external
NO contact is closed on:
No function Inverter On
Inverter OFF Generator ON
Print all Status relay
External bypass ON External battery fuses
Voltage free contacts:
Gen Set signaling
If an Emergency generator set supplies the UPS in case of utility failure and the generator is particularly
unstable in frequency, it should be suitable to install the signal “generator on” on terminals X1 / 11, 22
(Normally Open voltage-free contact) or on connector J2 / 11, 24 (see Fig. 4.4-1 / X1 and J2).
Since the Parameter for of the reading of the Generator function is password protected, call the nearest
Service Center for it's activation.
When this contact closes, it causes the change of certain settable functions such as:
x Enabling or disabling of synchronization and consequently the load transfer to generator.
x The battery recharge inhibition during the generator operation, or after what delay from generator
start the battery will start to be recharged.
Consult your nearest Service Center for more information.
Max. DC / AC: 24V / 1.25A
IEC 60950 (SELV circuit)
Min. signal level: 5VDC / 5mA
Modifications reserved Page 40/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
EPO (Emergency Power Off)
An external Emergency switch (NC - Normally Closed voltage-free contact) can be connected on
terminals X2 / 1, 2 or connector J2 / 12, 25 of the Customer Interface (see Fig. 4.4-1 / X2 & J2).
J2
JP3
21
X2
2221201918
11
8910
Fig. 4.4-2 PCB Customer Interface
X1
Fig. 4.4-3 PCB P1 – Control board
NOTE !
To enable this function, remove jumper JP3 on the Customer Interface and the
cable on the terminal X2 / 1, 2 (see Fig. 4.4-2).
Verify if the cable on the terminal X7 / 1, 2 and jumper JP5 on the P1 – Control board are OFF (see Fig. 4.4-3).
In a parallel system a separate NC (Normally Closed) contact must be connected
individually to each unit.
When activated, this switch causes the immediate shutdown of booster, battery-charger, inverter; and
the contactors K4, K6 and K7.
NOTE !
This procedure could imply a load shutdown.
When the EPO has been activated, the system must be restored as following:
xPress the push-button EPO (contact on X2 / 1, 2 is closed again).
xPerform the command INVERTER OFF entering the screen:
MENU/COMMAND MENU/INVERTER OFF.
INVERTER ON
COMMAND MENU
INVERTER OFF *
xStart the inverter entering the screen:
MENU/COMMAND MENU/INVERTER ON.
COMMAND MENU
INVERTER ON *
INVERTER OFF
Modifications reserved Page 41/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
5 NOTES
5.1 NOTES FORM
It is recommended to note in this section Notes, with date and short description all the operations
performed on the UPS, as: maintenance, components replacement, abnormal situations, etc. .
Date Description Done by
Modifications reserved Page 42/42
OPM_LPS_3UI_50K_60K_0US_V010.doc Installation Guide LP 33 Series 50-60 kVA
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.