GE Industrial Solutions Limitamp AR User Manual

GE
Limitamp® AR: Installation Guide
CR 194 One/Two-High Vacuum Limitamp® AR Control
imagination at work
Table of Contents
Introduction ..............................................................................................3
Opening High Voltage Door .................................................................3
High-Voltage Door Latches .................................................................4
Isolation Switch Handle to Contactor
Mechanical Interlock ..............................................................................5
High-Voltage Door Defeater Latch....................................................6
Low-Voltage Box Wiring Details .........................................................7
Plenum Installation Guide ....................................................................7
Turned Extension Plenum Installation Guide (Front/Rear) .....10
Turned Extension Plenum Installation Guide (Top/Bottom) ... 11
Limitamp AR Extension Plenum ...................................................... 13
Extension Plenum - General Guidelines ........................................ 14
Cable Entry From Top or Bottom ....................................................16
Dimensions ............................................................................................ 16
CR 194 One/Two-High Vacuum Limitamp® AR Control Page 2
Introduction
GE’s Limitamp® AR is the solution for applications where an extra margin of protection is essential. It meets the IEEE C37.20.7 Type 2B and IEC 62271-200, TYPE-A standards and is available in one- and two-high versions of FVNR motor starters, rated for 2.4-7.2kV-400A, 5kV-800A.
This instruction book is to be used in conjunction with GEH­6263 (Two high vacuum equipment), GEH-5306 (vacuum contactor) and GEH 5396B (800A) instructions.
Figure 1. 36” wide Two-High AR FVNR starter with low-voltage doors open.
WARNING: Before any adjustments, servicing, parts
replacement or any other act is performed requiring physical contact with the electrical working components or wiring of this equipment, all power must be removed and locked off from all sources and all attached rotating equipment must have come to a complete stop. User personnel must be completely familiar with the following operating and maintenance instructions before attempting to service this equipment.
WARNING: The vacuum interrupter integrity test should be performed before the high voltage vacuum contactors are energized for the first time and each time the contactors are returned to service after maintenance, adjustment or repair. Failure to perform this test may result in serious injury or death.
CAUTION: Product is not intended for nuclear use.
Opening High-Voltage Door
The high-voltage doors on the CR194 Two-High Vacuum Limitamp AR are mechanically interlocked to prevent the opening of the doors, when equipment is energized. For safe opening of high-voltage door, follow the step-by-step procedure as mentioned below.
Step 1: Push in the handle latch release and rotate the isolation switch handle to the full “OFF” position. The latch release must pop back out. See figure 3.
Step 2: Rotate the handle (Black color handle) down with a rapid positive motion, to bring it to “OFF” Position.
Step 3: Rotate the high-voltage door latch handle (silver color) 90° in the counter-clockwise direction to disengage the multi latches on the inside of the door.
Step 4: Turn all flange nuts simultaneously until disengaged from hat brackets.
Step 5: The high-voltage door may then be opened by pulling out on the latch handle.
Figure 2. 36” wide Two-High AR FVNR starter with high-voltage doors open.
Figure 3. Push in the handle latch
WARNING: Confirm that equipment is de-energized before
opening the high-voltage doors.
CR 194 One/Two-High Vacuum Limitamp® AR Control Page 3
Figure 4. Rotating the high-voltage door latch handle.
Locking Pins in Unlocked Position
Latch Handle
Locking Pins in Locked Position
Figure 6. View of locking pins on high-voltage door.
High-Voltage Door Latches
The Limitamp AR design uses special high strength door latch parts to keep the door closed during an arcing event. All of the latches must be properly engaged for the product to function properly. On the outside of the high-voltage door there is a door latch operating handle. Rotating this handle operates all of the latch locking pins at one time.
The door latch locking pins are all adjusted prior to shipping from the factory. If any of the door latch pins are moved or replaced make sure they are adjusted per the sketch below. Make sure to tighten the locking stud on the locking pin bridge.
When the door handle is in the locked position adjust locking pin bridge to provide a 0.150” gap between the bridge and the welded “U” fork on the door.
Locking Stud
.150
The mating part of the latch system is shown in the Figure 7 below. The enclosure side latch parts are mounted to the frame using a stud plate that passes through the flange of the case. The latch parts can be adjusted in all directions using the slots in the latch parts and special spacers that mount under the latch parts. The latch parts should be adjusted so the locking pins on the door engage the open slot on the case side latch part. The nominal position for the latch part is flush with the front edge of the enclosure flange.
Latch Plates Should Be Flush With Front Flange of Enclosure
Figure 5. View to show gap between locking pin bridge and “U” fork on the door.
CR 194 One/Two-High Vacuum Limitamp
Figure 7. View of enclosure mounted latch parts.
WARNING: Barriers or enclosure door latch parts removed
to service the equipment must be re-installed in the exact location for safe operation. Not complying with this instruction could lead to serious injury. Mark the location of these items with the ink for ease of re-assembly.
®
AR Control Page 4
Isolation Switch Handle to Contactor Mechanical Interlock
The Limitamp AR two-high vacuum starter is equipped with a quick-make, quick-break isolation switch in each starter. This isolation switch is not designed to make or break motor load current. To insure that the isolation switch handle cannot be operated when the contactor is energized, a mechanical interlock mechanism is provided between the contactor and the isolation switch handle. Operation of this mechanical interlock for each starter should be checked per the following procedure.
WARNING: Confirm the equipment is de-energized before performing this check.
Adjustment Nuts On the Interlock Assembly
Step 1: Adjust the nuts to shift the connecting rod position as
shown in Figure 10.
Step 2: With the contactor open the connecting rod should be adjusted up to a point where the pusher will pass through the round hole in the connecting rod.
Step 3: Once adjusted tighten the two nuts against the block.
Connecting Rod Pusher Rod
Figure 10. Showing how pusher is unblocked when the contactor is open.
Figure 8. View of the contactor to isolation switch mechanical interlock at the vacuum contactor.
Figure 9. Adjusting connecting rod
Pusher Rod Blocked
Figure 11. Showing how pusher is blocked when the contactor is closed.
To verify that the interlock is properly adjusted push down on the top of the contactor moving armature and hold it down. Now attempt to press the handle latch release (pusher). The mechanical interlock should prevent the handle release from going in and prevent the handle from being moved.
CR 194 One/Two-High Vacuum Limitamp
®
AR Control Page 5
High-Voltage Door Defeater Latch
WARNING: The following steps should be taken only as a last
resort to enter a malfunctioning controller. It is imperative that all power to main bus be removed before proceeding.
IN CASE OF EMERGENCY, remove all power to the controller, then the high-voltage door may be opened with the contactor in the closed position and with the isolation switch closed, by following the procedure listed below.
WARNING: Do not proceed unless all power to the controller is removed. In this situation, doors must not be opened with power connected to the bus.
Door Interlock Defeater Locking Nuts
Step 1: Remove the door interlock defeater locking nuts as
shown in Figure 12. Step 2: Rotate the door latch operating handle 90° counter-
clockwise to disengage the multiple door latches on the inside of the high-voltage door.
Step 3: Turn all flange nuts simultaneously until disengaged from hat brackets.
Step 4: The high-voltage door should be able to be opened by pulling out on the silver handle. As you pull on the door, the door interlock defeater will pull away from the door.
WARNING: Defeating high-voltage door interlock leaves the power fuses and contactor connected to the bus. The bus power must remain de-energized while the high-voltage door is open.
Door Interlock Defeater
Figure 12. View showing door interlock defeater locking nuts. Figure 13. View showing door interlock defeater.
CR 194 One/Two-High Vacuum Limitamp® AR Control Page 6
Low-Voltage Box Wiring Details
Plenum Installation Guide
Step 1: All low voltage wiring entering and exiting the low
voltage box must be routed through the bushings provided on the box.
Step 2: Once all wiring is complete fill the bushings with R.T.V or other equivalent sealant material.
Step 3: Wrap the outside of bushings and wiring with 3M, 130C tape. Tape must extend down the wire bundle for a minimum of 6 inches. Refer figure 14 for details.
WARNING: Ensure all wire way openings are properly sealed before energizing.
Bushing Provided for Customer Wiring Purpose
The Limitamp AR design requires the use of a ventilation plenum to route any arcing gases away from the equip­ment. Each section requires a plenum and extra extension plenum parts can be used to exhaust the arcing gases out of the building. The plenum parts are shipped with the equipment and it is the end user’s responsibility to install the plenum part on the equipment.
Store the plenum or extension plenums on a level surface to avoid distortion. Ensure pleum or extension plenums are kept in clean and dry condition with ample air circulation. NOTE: It is recommended NOT to store the plenum outdoors.
At the installation site, remove all separately packaged components shipped within the Limitamp AR unit. Find the plenums, cover plates, mounting hardware and place them in the work area. It is recommended that the plenum parts be installed in the sequence listed below.
WARNING: Allow at least 12 feet of unobstructed space for exhaust gases. Serious injury or death may occur.
Step 1: Before plenum installation begins remove all plastic snap-in clips in top vent flaps to ensure vent flaps operate properly.
Properly Sealed and Taped Bushing
Figure 14. Low-voltage box wiring.
Step 2: Apply a strip of sealer around the top perimeter of
the first shell. Sealer should be placed on the outside of the mounting holes on the shell top.
Step 3: Lift plenum box for the first section with appropriate means and place it on top of the unit taking care to not damaging flaps on roof.
Sealer
Figure 15. Apply sealer around the top perimeter of the shell.
CR 194 One/Two-High Vacuum Limitamp® AR Control Page 7
Step 4: Align holes on shell top and the plenum. Attach the plenum using the 3/8“ hardware provided with kit as shown in Figure 16.
Figure 16. View of hardware to mount plenum to the shell.
Step 5: Apply sealer around perimeter of plenum side that will
be closed.
Sealer
Figure 17. Apply sealer on closed end of plenum.
Step 6: Mount plenum end cover using 3/8” hardware. Refer to
Table 1 for torque details.
3/8” Hardware
Torque Recommendations.
Table 1
Bolt Size SAE Grade 5 Bolt Torque (Ft-lb)
1/4 - 20 4 5/16 - 18 9 3/18 - 16 16
1/2 - 13 39
3/8” Hardware
Figure 18. Mount end cover plate on plenum.
CR 194 One/Two-High Vacuum Limitamp
®
AR Control Page 8
Step 7: Apply sealer around perimeter of the other side of the plenum and on the top of the second shell.
Sealer
Figure 19. Application of sealer to plenum and shell.
Step 8: Lift second plenum and position to align holes. Bolt the
second plenum in place. Install 3/8” hardware in all holes between the plenums and to the top of the shell.
Bolts Installed to Seal Joint
Step 9: Apply a layer of sealer on the bottom plate of the first
extension plenum. Attach bottom plate to the plenum.
Sealer
Figure 21. Mount extension plenum bottom plate in place.
Figure 20. Bolting the plenums together
Step 10: Apply a layer of sealer to the open end of the plenum
that is mounted on the end of the lineup. Lift the extension plenum and hold it in place until bolts can be mounted to attach the two plenums together. Extension plenum should be supported by additional supports from the roof of the building.
Sealer
Figure 22. Assemble the extension plenum using 3/8” Hardware.
CR 194 One/Two-High Vacuum Limitamp
®
AR Control Page 9
Step 11: Continue the assembly of extension plenums following the same procedure. At the end of the extension plenum the end duct assembly must be installed.
Turned Extension Plenum Installation Guide (Front/Rear)
Sealer
3/8” Hardware
Figure 23. Assembly of end duct to the last segment of the plenum.
End Duct
3/8” Hardware
If customer chooses to install their own version of end duct segment then the duct must allow a minimum open exhaust area of 428 in2.
Step 12: Once all the plenums are in place and bolted together apply gasket around the perimeter of each plenum frame and mount the cover plates using 3/8” hardware.
At the installation site, remove all separately packaged components shipped within the Limitamp AR unit. Find the Turned Plenum, mounting hardware and place them in the work area.
Step 1: Remove top cover plate on existing extension plenum for assembly. Apply sealer around perimeter of existing extension plenum side flanges, where turned plenum (Front/ Rear) will be attached.
Sealer
Figure 25. How to apply sealer around perimeter of plenum.
Step 2: Install 3/8” diameter mounting bolts to attach turned
plenum (Front/Rear) to the extension plenum.
Figure 24. Mount top covers using 3/8” diameter bolts.
Figure 26. Use 3/8” hardware to mount turned plenum (Front/Rear).
CR 194 One/Two-High Vacuum Limitamp® AR Control Page 10
3/8” Hardware
Step 3: Apply sealer around perimeter of turned plenum (Front/Rear) flanges where extension plenum will be attached.
Sealer
Figure 27. Apply sealer around perimeter of turned plenum (Front/Rear).
Step 4: Install 3/8” diameter mounting bolts to attach
extension plenum to turned plenum.
Step 5: Once all the plenums are in place and bolted together apply sealer around the perimeter of each plenum frame and mount the cover plates using 3/8” hardware.
Sealer
Figure 29. Assemble top covers using 3/8” diameter bolts.
Turned Extension Plenum Installation Guide (Up/Down)
3/8” Hardware
Figure 28. Use 3/8” hardware to mount extension plenum.
At the installation site, remove all separately packaged components shipped within the Limitamp AR unit. Find the Turned Plenum, mounting hardware and place them in the work area.
Step 1: Remove top covers on existing extension plenum for assembly. Apply sealer around perimeter of existing extension plenum side flanges where turned plenum (up/down) will be attached.
Sealer
Figure 30. Apply sealer around perimeter of plenum.
CR 194 One/Two-High Vacuum Limitamp® AR Control Page 11
Step 2: Install 3/8” diameter mounting bolts to attach turned plenum (top/bottom) to the extension plenum.
3/8” Hardware
Figure 31. Use 3/8” hardware to mount turned plenum.
Step 3: Apply sealer around perimeter of turned plenum (top/
bottom) flanges where extension plenum will be attached.
Sealer
Step 4: Install 3/8” diameter mounting bolts to attach
extension plenum to turned plenum
3/8” Hardware
Figure 33. Mount extension plenum on turned plenum (up/down).
Step 5: Once all the plenums are in place and bolted together
apply sealer around the perimeter of each plenum frame and mount the cover plates using 3/8” hardware.
Figure 32. Apply sealer around perimeter of turned plenum.
Sealer
Figure 34. Use 3/8” hardware to mount cover plates.
CR 194 One/Two-High Vacuum Limitamp® AR Control Page 12
Limitamp AR Extension Plenum
Limitamp AR Extension Plenum - Straight
D”
H”
2”
L”
Extension Plenum Type
12” straight 55B528942ENG4 12 24 42 90
22” straight 55B528942ENG1 22 24 42 135
24” straight 55B528942ENG5 24 24 42 140
36” straight 55B528942ENG2 36 24 42 195
40” straight 55B528942ENG3 40 24 42 215
48” straight 55B528942ENG6 48 24 42 250
Note: 2 inch bottom cover plate has ø 0.635 holes to support the extension plenum
Part number L (in) H (in) D (in)
Approx.
Weight (lbs)
Limitamp AR Extension Plenum – Elbow – Up/ Down
24”
D”
H”
L”
Extension Plenum Type
Up/Down Elbow 55B528942GJG1 42.5 42.5 41.5 300
Note: Rotate the extension plenum suitably to create up/down elbow
Part number L (in) H (in) D (in)
Approx.
Weight (lbs)
Limitamp AR Extension Plenum – End Duct
24”
Limitamp AR Extension Plenum – Elbow – Front/Rear
H”
2”
D”
Extension Plenum Type
Front /Rear Elbow 55B528942FZG1 44 24 44 260
Note: Rotate the extension plenum suitably to create Front/Rear elbow
Part number L (in) H (in) D (in)
L”
Approx.
Weight (lbs)
L”
D”
H”
Extension Plenum Type
End Duck 55C682150ALG1 15 24 42 60
Note: End duct will be provided along with a Rodent screen
Part number L (in) H (in) D (in)
Approx.
Weight (lbs)
CR 194 One/Two-High Vacuum Limitamp
®
AR Control Page 13
Extension Plenum – General guidelines
1. Support the Extension plenum minimum 40 inches span
throughout the straight length.
2. Straight lengths can be used along with Front/Rear and/or Up/Down elbows to fit the customer layout.
3. Use the bottom cover plate with ø 0.635 holes for supporting the extension plenum.
4. Optionally, Contact GE factory to order collars which can be installed on the plenum for supporting the straight extension plenum from the top.
5. Extension plenums are constructed using 12 gauge sheet metal.
6. Allow minimum 76 inches straight length between turns when designing the layout of the extension plenum.
7. Customer can install his own version of End duct or if there is a local code requirement with a minimum exhaust area of 428 in
2
.
8. Refer installation section to assemble extension plenums.
CR 194 One/Two-High Vacuum Limitamp® AR Control Page 14
Plenum Flange details to connect the plenum extension or End Duct
Straight extension plenum with Collar installed (Side View)
Collar Collar
Bottom Cover plate
Collar
CR 194 One/Two-High Vacuum Limitamp® AR Control Page 15
Cable Entry From Top or Bottom
Removable cable entry plates are provided on the top and bottom of the equipment.
Step 1: Remove cable entry cover plates. Cut an appropriate size hole for required conduit bushing.
Step 2: Install a conduit bushing(s) capable of sealing against 20-psig minimum pressure on all cables entering or exiting the arc resistant unit.
WARNING: Conduit bushings capable of sealing against 20-psig minimum should be installed on all cables entering or exiting the enclosure. If these bushings are not installed, hot arc gases can escape thru open area around cables. Serious injury or death may result.
Plenum
Conduit Cutout Cover Plates
Figure 35. Conduit cover plate in plenum for top cable entry.
Conduit Bushing
Figure 37. Assembly of conduit bushing on the bottom conduit plates for bottom cable entry.
Dimensions
Vacuum Limitamp AR controllers are normally 42-inches deep and 90-inches high. The width of the CR 194 Two-High Vacuum Limitamp AR is 36 inches (40 inches optional).
Refer Figure 38 (Bottom cable entry) and Figure 39 (Top cable entry) for dimensional details.
The width of the 800A CR 194 One-High Vacuum Limitamp AR is 48 inches. Refer to Figure 40.
Conduit Bushing
Figure 36. Assembly of conduit bushing on to the plenum top cover for top cable entry.
CR 194 One/Two-High Vacuum Limitamp® AR Control Page 16
CR194 AR 400A, Stationary or Draw-out, Outline Dimensions, Two-High, Bottom Cable Entry.
GE Limitamp® AR Medium Voltage Motor Control Enclosures
Enclosure Outline dimensions 2400-7200 Volts CR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)-BTM CABLE ENTRY
PLENUM
13
12
16
E
L1
L2
L3
13
68
16
1
6
2
11
L2
L3
3
11
14
16
13
52
5
16
7
42
8
T1
*
T2
*
T3
*
B1
1
6
2
B2
T1
D
42
L.H.SIDE VIEW
Notes: B1 — AC Power Bus, 1200A B2 — AC Power Bus, 3000A C — Control Lead Terminal Board D — Motor Lead Terminal Connection E — Ground Bus Terminal Connection G — Space Required to Open Doors 135° H — Four-foot Aisle for Contactor Removal J — Mounting Holes for 1/2" Diameter Anchor Bolts M — Recommended Position for Incoming Motor Conduit N — Recommended Position for Incoming Control Conduit
* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
D
T3
*
*
T2
*
3
18
16
1
7
2
C
1
18
1
16
6
2
L1
1
16
2
FRONT
1
7
2
C
3
10
4
76
H
48
G
32
-2200 lbs 998 Kg
BTM CABLE ENTRY
9
4
16
7
6
15
61
16
13
6
16
69
3
11
4
1
19
4
11
D
1
16 11
16
13 16
D
3
16
T1
*
T2
*
T3
*
T1-T3
*
T2
*
FRONT VIEW
FLOOR PLAN
PLENUM
UPPER UNIT
LOWER UNIT
36
GE Limitamp® AR Medium Voltage Motor Control
Enclosures
Enclosure Outline dimensions 2400-7200 Volts CR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)-BTM CABLE ENTRY
13 16
E
1
6
2
PLENUM
3
14
16
B2
13
5
16
L.H.SIDE VIEW
3
18
16
1
7
2
D
T1
T2
T3
B1
6
D
42
C
* *
*
1 2
T1
1
18
1
16
6
2
L1
1
16
2
FRONT
1
7
2
C
H
T3
*
*
48
*
G
T2
36
3
10
4
-2450 lbs 1112 Kg
4
16
15
61
13
16
76
16
69
11
19
15
BTM CABLE ENTRY
2
1
6
24
C
90
1
43
4
C
15
20
16
2-HI
13
68
16
12
L1
11
L2
L2
L3
11
L3
52
7
42
8
Notes: B1 — AC Power Bus, 1200A B2 — AC Power Bus, 3000A C — Control Lead Terminal Board D — Motor Lead Terminal Connection E — Ground Bus Terminal Connection G — Space Required to Open Doors 135°
REV: 01
H — Four-foot Aisle for Contactor Removal J — Mounting Holes for 1/2" Diameter Anchor Bolts M — Recommended Position for Incoming Motor Conduit N — Recommended Position for Incoming Control Conduit
3
17
8
13
6
16
* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
9
D
7
16 11
6
16
13
6
16
3 4
1 4
16
5 8
1
2
6
N
1
D
3
T1
*
T2
*
T3
*
T1-T3
*
T2
*
FRONT VIEW
M
M
FLOOR PLAN
2
1 2
PLENUM
UPPER UNIT
LOWER UNIT
40
10
2
16
C
C
2-HI
UPPER UNIT
LOWER UNIT
5
24
90
1
43
4
15
20
16
1
1
2
2
TYP.
J
3
66
4
FRONT
TYP.
REV: 01
Figure 38. Bottom Cable Entry 400A
CR 194 One/Two-High Vacuum Limitamp® AR Control Page 17
CR194 AR 400A, Stationary or Draw-out,
13 16
Enclosure Outline dimensions 2400-7200 Volts CR194 AR 400A, 2 High, 36" Wide (Stationary or Draw-out)-TOP CABLE ENTRY
GE Limitamp Enclosures
E4A
Outline Dimensions, Two-High, Top Cable Entry.
®
AR Medium Voltage Motor Control
6
3
17
8
13
6
16
5
2
8
LOWER UNIT
M
UPPER UNIT
6
M
N
1
5
2
2
2
16
FRONT
6
TOP VIEW
GE Limitamp® AR Medium Voltage Motor Control
Enclosures
Enclosure Outline dimensions 2400-7200 Volts
CR194 AR 400A, 2 High, 40" Wide (Stationary or Draw-out)-TOP CABLE ENTRY
6
6
3
17
8
N
13
6
16
5
2
8
M
M
10
TOP VIEW
LOWER UNIT
UPPER UNIT
1
2
2
5
2
16
FRONT
PLENUM
13
12
16
E
L1
L2
L3
1
6
2
11
L2
L3
3
11
14
16
13
5
16
52
7
42
8
1
6
2
T1
*
D
T2
B1
B2
T1
*
T2
*
T3
*
42
L.H.SIDE VIEW
Notes: B1 — AC Power Bus, 1200A B2 — AC Power Bus, 3000A C — Control Lead Terminal Board D — Motor Lead Terminal Connection E — Ground Bus Terminal Connection G — Space Required to Open Doors 135° H — Four-foot Aisle for Contactor Removal J — Mounting Holes for 1/2" Diameter Anchor Bolts M — Recommended Position for Incoming Motor Conduit N — Recommended Position for Incoming Control Conduit
* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
7
T3
*
*
D
1 2
C
1
7
2
1
6
2
L1
3
10
4
FRONT
18
C
G 32
3
17
8
1
18
16
75
H
48
-2200 lbs 998 Kg
TOP CABLE ENTRY
PLENUM
13
6
16
D
5 8
1
4
2
7
63
D
8
6
3
34
8
9
26
16
11
18
16
3
11
16
1
1
2
3 4
7
T1-T3
*
T2
*
T1
*
T2
*
T3
*
FRONT VIEW
C
UPPER UNIT
C
LOWER UNIT
2-HI
36
FLOOR PLAN
24
12
L1
L2
90
1
43
4
15
20
16
1
1
2
2
TYP.
J
3
66
4
FRONT
TYP.
REV: 01
L3
13
68
16
Notes: B1 — AC Power Bus, 1200A B2 — AC Power Bus, 3000A C — Control Lead Terminal Board D — Motor Lead Terminal Connection E — Ground Bus Terminal Connection G — Space Required to Open Doors 135° H — Four-foot Aisle for Contactor Removal J — Mounting Holes for 1/2" Diameter Anchor Bolts M — Recommended Position for Incoming Motor Conduit N — Recommended Position for Incoming Control Conduit
1
6
2
11
L2
L3
11
14
52
7
42
8
E
5
13 16
3
16
13 16
PLENUM
1
6
2
T1
D
B1
B2
T1
*
T2
*
T3
*
42
L.H.SIDE VIEW
* *
T2
T3
*
D
1
7
2
C
1
7
1
2
6
2
L1
3
10
4
FRONT
18
C
H
48
G 36
3
17
8 1
18
16
-2450 lbs 1112 Kg
TOP CABLE ENTRY
6
4
5
75
8
7
63
8
3
34
8
9
26
16
11
18
16
15
13 16
9
16
6
1
D
D
3 4
7
3
16
1 2
T1-T3
*
T2
*
T1
*
T2
*
T3
*
FRONT VIEW
FLOOR PLAN
PLENUM
UPPER UNIT
LOWER UNIT
40
24
C
90
1
43
4
C
15
20
16
2-HI
1
1
2
2
TYP.
J
3
66
4
FRONT
TYP.
REV: 01
* — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
Figure 39. Top Cable Entry 400A
CR 194 One/Two-High Vacuum Limitamp® AR Control Page 18
CR194 AR 800A, Stationary or Draw-out, Outline Dimensions, One-High, Top/Bottom Cable Entry.
GE Limitamp® AR Medium Voltage Motor Control Enclosures
H
72
- 1800 LBS.
- 816 KG.
2-9/16
K
5-3/4
E
*
B
X
4-3/16
4-1/2
F
2
10-1/2
42
2-5/16
3/4
Enclosure Outline dimensions 2400-7200 Volts CR194 AR 800A, 1-High, 48" Wide
C
4
6-1/2
10
E
B1
X
5-1/2
11-1/2
6
D
T1T2T3
G
FRONT
17
48
68-4/5
17-5/8
14-3/16
L1
6-1/2
L2
6-1/2
L3
10-1/2
52
F
26
42
L.H.SIDE VIEW
Notes: B — Incoming Power Terminal Connection B1 —
AC Power Bus, 800A
— Control Lead Terminal Board
C
— Motor Lead Terminal Connection
D
Ground Bus Terminal Connection
E F — Ground Bus Terminal Connection
(If Ordered)
Space Required to Open Doors 90°
G
Four-Foot Aisle for contactor removal
H J
Mounting Holes for 1/2" Diameter Anchor Bolts
K — Space Available for Incoming Conduit
— —
M
Recommended Position for Incoming Motor Conduit
Recommended Position for Incoming Control Conduit
N
Recommended Position for Incoming Power Conduit
P
— —
X
LV Box * — Indicates Terminal Location - Approximate for Cable Length — Approximate Weight
10-1/2
14
6
P
8-7/16
M
6
3-1/2
N7-9/16
FRONT
2-1/2
9
TOP VIEW
PLENUM
C
10-5/8
2-3/4
L1
L2
12-1/2
L3
13-1/2
T2
D
T1,T3
6
27-3/4
9
16-3/4
48
24
7
12-3/4
90
FRONT VIEW
1-1/2
P
M
K
6
FLOOR PLAN
6
6
7-9/16
10-1/2
14
8-7/16
FRONT
1-1/2
26
2
N
K
3
1-5/16
J
6
REV: 01
Figure 40. Top/Bottom Cable Entry 800A
CR 194 One/Two-High Vacuum Limitamp® AR Control Page 19
GE Industrial Solutions
41 Woodford Avenue Plainville, CT 06062 www.geindustrial.com
© 2012 GE Company
imagination at work
DEH-6790A 10/12
Loading...