1. Read this manual thoroughly before using the ASTAT-IBP Plus and store in a safe
place for reference.
2. Make sure that this manual is delivered to the end user.
3. The policy of GE Industrial Systems is one of continuous improvement.
The right is reserved to alter the design on any structural details of the products at any
time without giving notice.
ASTAT®-IBP Plus Soft Starters
WARNINGS
1.Disconnect power before installing or servicing.
2.Hazardous voltages are present in the motor circuit even when the starter is OFF.
An isolation contactor, configured to provide automatic isolation when the motor
is turned OFF is recommended.
3.Unit may contain more than one live circuit. Disconnect both control and main
circuits before installing or servicing.
4.Soft stop should not be used as an Emergency stop.
5.Stopping mode must be set to meet applicable standards for operator safety.
6.Separate motor overcurrent protection is required to be provided in accordance
with the Canadian Electrical Code, Part 1. ASTAT-IBP Plus provides separate
motor protection.
CAUTIONS
1.Semi-conductor fuses specified may not provide branch circuit protection. Refer
to local applicable electrical codes.
2.Overload relay setting should be properly coordinated with motor.
3.Abnormal starting times in excess of 30 seconds or closely repeated operations
of acceleration ramp/deceleration ramp may cause motor damage. Contact motor
manufacturer to ensure proper motor selection has been made for these conditions.
4.If control power is lost between starts, the overload relay protection is reset to cold
start conditions.
ASTAT®-IBP Plus Soft Starters
PRECAUTIONS
1.Debranchez l'alimentation en courant électrique avant de raccorder ou d'intervenir.
2.Des tensions dangereuses sort présente dans le circuit moteur même si le soft
starter indique la position "arrêt". Un contacteur d'isolement assurant un isolement
automatique quand le moteur est arrête, est recommendé.
3.L'appareil peut renfermer plus d'un circuit sous tension de'brancher les circuits
principaux et les circuits de controle avant de raccorder ou d'intervenir.
4.Délestage "soft stop" ne devrait jamais être utilisé en lieu de délestage d'urgence.
5.Procédés de délestage doivent être conforme aux normes de sécurité des
utilisateurs.
AVERTISSEMENTS
1.Les fusibles semi-conducteurs specifies ne protégent pas obligatoirement les
circuits se conformer aux codes locaux d'installations électriques.
2.Le relais de courant de surcharge doit être proprement coordonné avec la marche
du moteur.
3.Les délais anormaux de mise en service d'une durée supérieure à 30 secondes,
ainsi que les montées/descentes en regime, sont suseptibles d'edommager le
moteur. Mettez-vous en rapport avec votre fabricant en ce qui concerne le choix
du moteur adéquat.
4.En cas d'interruption de l'alimentation entre deux dèmarrages, la protection
assurée par démarrage à froid.
5.Le moteur doit être muni d'une protection distincte contre les surintensites, et la
surchauffe conformement au code de l'electricite, premiere partie. ASTAT Plus le
relais de courant de surcharge doit être proprement coordonne avec la marche du
moteur.
There are numerous applications where soft starting and limited
current peaks are needed for the starting of squirrel cage induction
motors. Traditionally, reduced voltage starting was accomplished
using electromechanical starters, such as star delta starters,
autotransformer starters, stator resistance starters or by using
part-winding motors. These methods would provide a two-, threeor four-step torque change by switching the motor voltage from
reduced value to full voltage (in steps) after a preset time interval.
ASTAT-IBP Plus Solid State Reduced-Voltage Starters (also known
as soft starters) use solid state devices to gradually increase the
voltage from an initial preset level (initial torque) to full voltage over
a selected time period. The same solid state devices may also be
used to reduce the voltage for the deceleration of the motor should
this be required in the application. This starting and stopping
method provides smooth, stepless acceleration and deceleration
of AC squirrel-cage induction motors. The ASTAT-IBP Plus control
circuitry offers many additional functions, such as the monitoring,
protection and secondary functions listed.
Integral Bypass
The ASTAT-IBP Plus provides acceleration and deceleration control
using back-to-back SCRs. When the motor reaches the end of the
ramp, a bypass contactor is energized and the SCRs are switched
off. This allows the ASTAT-IBP Plus to run cooler than conventional
soft starters.
Advanced Features
The ASTAT-IBP Plus incorporates many additional advanced
features to ensure suitability for most applications.
Monitoring
• Motor Current
• Line Voltage (1)
• Line Power Factor
• Elapsed Time
• Fault History
Protection
• Password
• Lockout
• Undervoltage (1)
• Overvoltage (1)
• Undercurrent
• Overcurrent
• Long Start Time
• Stalled Rotor
Secondary Functions
• Secondary Ramp Up
• Secondary Ramp Down
• Tachometer Feedback
• Dual Motor Switch
Versatile Use
ASTAT-IBP Plus Solid State Reduced-Voltage Starters offer
customer-configurable functions, including pedestal voltage, kick
start (selectable), acceleration ramp, starting current limit, and soft
stop (selectable). Typical applications include the following:
• Belted Equipment• Centrifugal Fans
• Centrifuges• Compressors
• Conveyors• Crushers
• Extruders• Fans and Blowers
• Mixers• Packaging Equipment
• Pumps• Textile Machinery
The ASTAT-IBP Plus also features two programmable inputs, two
programmable output relays and serial communications control.
Note:(1) Monitors L1
1-1
1-2. Features and benefits
1. Overview
An increase in productivity and reliability with the use of
static soft starters.
Starting and stopping the motor without steps or transitions
lengthens the life of power-driven machines’ mechanical parts and
reduces stress on transmission belts and coupling parts.
Consequently, maintenance time is reduced and machine/facility
lifespans are lengthened.
Improvement in acceleration / deceleration characteristics
Starting with the voltage ramp or, alternatively, by starting current
limitation, the acceleration and deceleration ramp more closely fits
load characteristics. A kick start may also be selected in instances
of high static friction load.
Protected motor
The ASTAT-IBP Plus protects the motor from overloads as well as
from incorrect operating conditions, such as loss of an input or
output phase, stalled rotor, thyristor short circuit, etc.
Digital technology
The control system is based on the use of a highly specialized
microcontroller that treats the signals digitally, thereby avoiding
deratings and adjustments common to analog circuits. This type of
control ensures excellent precision and speed of execution. The
control board is designed using surface mounted devices (SMD)
to increases equipment reliability.
Easy to run and adjust
The ASTAT-IBP Plus can be used for a wide range of applications.
A keypad and a digital display make it easy to select options
that allow the equipment capabilities to be customized to
application needs.
Easy maintenance due to full monitoring
Advanced microprocessor technology allows starters to identify
20 different types of fault conditions. The last four errors are
retained in memory to facilitate trouble-shooting and to minimize
downtime.
Pump control
The ASTAT-IBP Plus includes a Pump Control function that is more
effective in fluid systems than standard soft starting and stopping.
The control reduces fluid surges and hammering in a pipe line
system. This method controls the motor speed by monitoring the
motor parameters with voltage control in a closed-loop system.
Advanced functions
ASTAT-IBP Plus includes advanced functions, such as linear
acceleration ramp, programmable I/O and connection to a computer
by serial communication (RS 232).
High level of immunity
The control signals are optoelectronically isolated. Various levels
of protection have been set up in the circuits to immunize the
equipment against external disturbance and their harmful effects.
1-2
2. Types and Ratings
2-1. Ratings (1)
Ratings for Standard Duty Applications (300% Current for 30 sec) for low inertia loads such as centrifugal pumps.
Notes:(1) = Ratings in Amps given for ambient temperature of up to 40°C and 1000m altitude. Temperatures inside the
enclosure must be kept within a 0°-45°C range. Derate output current by 1.5% per degree C above 40°C. Derate
output current by 1% per 100m above 1000m.
2-1
2. Types and Ratings
2-2. ASTAT®-IBP Plus, Thermal characteristics
The ASTAT-IBP Plus allows the user to select motor protection according IEC Class 10, 20 and NEMA 10, 20 or 30, selectable by "o" -overload- parameter
IEC Class 10IEC Class 20
Sec.Sec.
COLD
COLD
HOT
Multiples of motor FLA Rating In
NEMA 10NEMA 20
Sec.
COLD
HOT
Multiples of motor FLA Rating In
Sec.
HOT
Multiples of motor FLA Rating In
COLD
HOT
Multiples of motor FLA Rating In
NEMA 30
Sec.
Thermal memory:
If the control voltage is not removed, the unit has a cool down
characteristic. The time for cool down is 300 sec. after the
overload trip.
If the control voltage is removed after tripping, you must wait at
least 5 minutes before the unit can be restarted. See Section 4-10
for restart limitations.
COLD
HOT
Multiples of motor FLA Rating In
2-2
3. Technical Specifications
3-1. ASTAT®-IBP Plus, General specifications
Voltage Ratings 3ph AC SystemsUp to 600V, +10%, -15% for QI3xDP ASTAT-IBP
Plus series
Freq. Range50/60HzControl range of 45-65 Hz
ControlControl systemDigital system with microcontroller
SpecificationsStarting ramp with progressive increase in voltage and
current limitation
Initial voltage (pedestal)%30 - 95 U
Starting torque%10 - 90 M
Kick start%95 Un (90% M
Motor unit ratio (N)0.4 - 1.2
Current limit (starting)1 to 4.5 (Ir/In) Max 4.5 I
Acceleration ramp times1 to 45 (standard or linear ramp up)
BypassDirect control of a bypass contactor
Brake time by ramps1 to 60 (1 to 60 in secondary ramp) adjustable independently of starting
ramp time (types: standard, pump control or linear ramp down)
MonitoringMotor current, line voltage (1), power, power factor and elapsed time
RunningExternal controlStart - Stop
Acceleration phaseAdjustable time
Stop phasePower cut-off / Ramp / Pump control
Inputs / Outputs Inputs4 digital optocoupled. Two fixed (Start , Stop), and 2 programmable (I3, I4)
1 Analog 0-5VDC for Tachogenerator input feedback
Outputs2 Programmable relays (1r, 3r); 1 fixed relay (2r)
1 Analog 0-10VDC output for current metering
ProtectionsCurrent limitAdjustable 1 to 4.5 (I
OverloadIEC class 10 and 20 ; NEMA class 10, 20 and 30 all selectable
Cool-down time after
overload tripSee Restart Times on page 4-10
Loss on input phasesTrip at 3
Thyristor short circuitmsTrip at 200
Heatsink overheatingmsTrip at 200
Motor thermistormsTrip at 200 if thermistor impedance > response value
Loss on output phasesTrip at 3
Stalled rotormsTrip at 200
Supply frequency errorHzIf f < 45 or f > 65, will not start
Overcurrent100 to 150% In; trip time adjustable from 0 to 99 sec.
Undercurrent0 to 99% In; trip time adjustable from 0 to 99 sec.
Overvoltage (1)100 to 130% Un; trip time adjustable from 0 to 99 sec.
Undervoltage (1)0 to 50% Un; trip time adjustable from 0 to 99 sec.
Error (CPU)ms60
Memory4 former errors
Long start times2 x ta (ta = acceleration ramp time)
n
direct start
direct start
), adjustable 0 to 999 ms
n
/I
) Max 4.5 I
r
n
n
IActual measured motor current
I
m
I
n
I
r
LCurrent limit for starting Im/I
L
max
M
direct start
NI
SFService factor
U
n
Abbreviations
Maximum starting current desired
Nominal motor nameplate FLA
ASTAT rated nameplate FLA
450/N
Full voltage starting torque
n/Ir
Full line voltage
r
EnvironmentalTemperature°C0 to +55 (derate output current by 1.5% / °C above 40°C)
conditionsRelative humidity%95% without condensation
Maximum altitudem3000 (derate output current by 1% / 100m above 1000m)
Mounting positionVertical
Protection DegreeIP00, UL Open
StandardscUL, ULUL, cUL conforming to UL508
Conducted & radiated emissionsConforming IEC 947 -4-2, Class A
Electrostatic dischargesConforming to IEC 1000-4-2, level 3
Radioelectric interferenceConforming to IEC 1000-4-6, level 3 and to IEC 1000-4-3, level 3
Immunity to fast trasientsConforming to IEC 1000-4-4, level 3
Immunity to Surge VoltageConforming to IEC 1000-4-5, level 3
2T1, 4T2, 6T3Motor outputOutput terminals to 3ph AC motor
TBA1, TBA2Input Control Voltage110/120V AC, +10%, -15%
Digital Inputs
TerminalFunctionDescription
57Common for digital inputs This is a common terminal for the digital input terminals specified below.
1RunRun order. Command signal may be provided by one NO dry momentary contact to terminals 1 and 57.
2StopStop order. Command signal may be provided by one NC dry momentary contact to terminals 2 and 57.
NOTE: Run/Stop permanent command is allowed linking 1-57 and using one dry NO contact to 2-57
terminals.
3Programmable input I3These two inputs are programmable. Can be assigned to the following internal functions:
4Programmable input I4
-soft stop-linear ramp
-pump control-dual ramp selection
-kick start-local / remote control
Command signal should be provided by one NC dry contact to terminals 57-3 or terminals 57-4.
By switching this contact ON / OFF it is possible to enable or disable the assigned function.
23, 24Fixed relay 2r23-24 = N.O. dry contact. This relay is assigned to function EOR for bypass contactor control
33, 34Programmable relay 3r33-34 = N.O. dry contact. This relay can be assigned to several internal output functions (page 3-5).
Analog I/O
TerminalFunctionDescription
8Analog input common (-)This is a common terminal for the analog input terminal number 7 and analog output terminal number 9.
7TG feedback input (+)0-5V analog input for speed feedback. It should be provided by a DC tacho-generator coupled to the motor.
9Current output (+)0-10V DC analog Output for current measurement purpose. (1 x I
Motor thermistor terminals
TerminalFunctionDescription
5 , 6Motor thermistor inputThis input allows a motor thermistor with a response value from 2.8 to 3.2KΩ , and a reset value from 0.75 to
11-12 = NC, 11-14 = N.O. dry contacts. This relay can be assigned to several internal output functions (p. 3-5).
As default assigned to function RUN
Common for all relay output contactsMaximum usage voltage:380VAC (B300-UL)
5 main frequency cycles
30 to 95% Un (adjustable via initial torque setting T)
95% Un. Enabled by parameter "Pxxx" to ON, 0-999 ms (adjustable)
1-45 sec (adjustable). Dual ramp option.
Fast ramp (if motor is up to speed before end of normal ramp time)
Nominal voltage (bypass mode)
Deceleration ramp 1-60 sec (adjustable). Secondary ramp 1-60 sec.
Ramp down modes available are:
- Soft Stop -Voltage ramp down-. Enabled by "Sxxx" to ON
- Pump control. Selectable by "Sxxx" to ON and "Cxxx" to ON
- Linear ramp down (Tacho feedback needed)
Current limiting set point (100 to 450% x (Ir/In) Max 450% In)
Accelerating ramp (continuation of acceleration after motor amps drop below current limit)
Standard stopping (coast to rest)
100%
2
Starter
Output
Voltage (%)
1a
1
Starting by current limitation
Current to Motor
Out
100%
Starter
Output
Voltage (%)
1a
3
3
ut Voltage
7
5
6
4
8
Time
Motor Current
Max
450%
5
4
Current
Limit
8
9
Set Point
FLA
RampCurrent Limit
RampAt SpeedCoast StopTime
(Voltage Hold)
3-4
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.