GE Industrial Solutions ASPMETER Install User Manual

TM
the user will be required to correct the interference at his own expense.
POWER MONITORING
INSTALLATION GUIDE
ASP METER
ASP METER
Panelboard Monitoring System
Installer’s Specifications
Performance:
Operation:
Input Voltage 90-277 VAC Frequency 50/60 H z Sampling Frequency 2560 Hz Update Rate 1.8 seconds (both panels) Overload Capability 22 kAIC
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case
Modifications to this product without the express authorization of Veris Industries nullify this statement.
PRODUCT IDENTIFICATION
Description
ASPMETER
A = Advanced B = Interme diate C = Basic
Z206024-0B PAGE 1 ©2011 For technical support please contact 10111 DET-756 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
# of CTs
42
42 = 2 strips*
*Each strip contains 21 current sensors.
AQ = THQB circu it breakers AE = TEY circ uit breakers
Ribbon Cable Suppor t up to 20 ft. (6 m) available (at or round) (sold separately) Operating Temperature Range 0° to 60°C (32° to 140°F) (<95% RH, non-condensing) Storage Temperature Range -40° to 70°C (-4 0° to 158°F)
Network Communications:
Type Modbus RTU Connection DIP switch-selectable 2-wire or 4-wire, RS-4 85 Address DIP switch-selectable address 1 to 247 (in pairs of 2)** Baud Rate DIP switch-selec table 9600, 19200, 38400 Parity DIP switch-selectable NONE, ODD, EVEN Communication Format 8-data-bits, 1-start-bit, 1-stop-bit Termination 5-position depluggable connector (TX+ TX- SHIELD TX+/RX+ TX-/RX-)
Note: Standard IEC62053-21 Table 8 temp erature coeci ents apply for temperatures above and below 25°C. * Add 1% for 0.8 PF to 0.5 PF. ** See Conguration section for d etails.
QUICK INSTALL
Observe handling precautions for static sensitive devices to avoid damage to the circuitry which would not be covered under the factory warranty.
1. Disconnect and lock out power. Use a properly rated voltage sensing device to conrm power is o.
2. Mount current sensor strips adjacent to breaker terminations.
3. Verify that the serial numbers on the CTs match that on the board.
4. Congure communication and addressing parameters using DIP switches.
5. Mount the main acquisition board in the electrical enclosure.
6. Connect current sensor strip cables to the main board, observing the 2-strip setup and their orientation (A or B) within the panel.
7. Wire RS-485 communications.
8. Connect CTs to the auxiliary inputs and connect them onto the main conductors in the enclosure (optional).
9. Wire control power and voltage taps (ASPMETERA and ASPMETERB only).
10. Download the free E3x Conguration Tool from www.veris.com to commission the device for operation.
ASPMETER
TM
INSTALLATION GUIDE
OPERATION
The ASPMETER Series Branch Current Monitor is a device designed to measure the current, voltage, and energy consumption of up to for 46 circuits (42 branch circuits, 1 3-phase main, and 1 neutral).
The ASPMETER consists of a data acquisition board and two 21-unit current sensor strips, with four auxiliary inputs. The strips are mounted on each side of the panel board along the termination points of each breaker. The conductor passes through the appropriate current sensor before terminating at the breaker. Each strip transmits the current data to the data acquisition board.
Data is transmitted using an RS-485 Modbus protocol. Each data acquisition board requires one Modbus address for the set of two current sensors and four auxiliary inputs. Data is updated roughly every two seconds. As a circuit approaches the user­dened threshold, the ASPMETER activates the alarm indicators.
The ASPMETERA measures both current and power for the mains and branch circuits. The ASPMETERB measures both current and power for the mains, and current only in each circuit. The ASPMETERC measures current only for the mains and branch circuits.
DIMENSIONS
Circuit Board and Mounting Bracket
8.3”
(211 mm)
7.9”
(200 mm)
PRODUCT DIAGRAM
A
1
B
8
2
3
4
5
6
1. 50-Pin Ribbon Cable Connectors (Data Acquisition Board): 18 inch (457 mm) ribbon cables are provided for easy connection of current sensor strips to this point of the data acquisition board.
Note: Connect CT strips to the correc t ribbon cable connectors for each panel. The top connector is for Strip A, and the bottom conector is for Strip B.
2. Auxiliary Inputs: These 0.333 VAC inputs are used for monitoring the main breaker or other high amperage source.
7
11
10
2
9
12
13
3.9”
(100 mm)
Ø = 0.2”
(5 mm)
1.2”
(30mm)
2.0”
(50mm)
7.3”
(184 mm)
8.9”
(288 mm)
Solid-Core CT Strips
25.0” (635mm)
slot: 0.25” x 0.5”
0.4” (10mm) opening
(7 x 13mm)
1.0” (26mm) on center
1.75”
(45 mm)
4.8”
(122 mm)
1.2”
(31mm)
5.8”
(146 mm)
3. Control (Mains) Power Connection: Easy 2-wire 90-277 VAC 50/60 Hz
connection.
4. Control Power Fuse: 600 VAC, 500 mA time lag, factory-replaceable.
5. Alive LED: Red/green/amber LEDs. Blink codes are on page 3.
6. Voltage Taps: 1, 2, or 3 phase plus neutral connections. For voltage sensing and
power calculations (no voltage taps on the ASPMETERC).
7. Communications Address DIP Switches: Each Modbus device must have a
unique address. Switches are binary weighted. Left-most switch has a value of 1; right-most switch has a value of 128.
8. Communications Settings DIP Switch: Congures baud rate, parity, 2/4 wire
communications.
9. RS-485 2 Connection: Used for Modbus serial communications. The Universal
plug accomodates 2 or 4 wire connec tions.
10. RS-485 LEDs: The RX LED (closest to DIP switches) indicates the RS-485
is receiving information; the TX LED (farthest from DIP switches) indicates transmission of information.
11. Power LED: Indicates power to main board
12. Current Sensors: Each current sensor is capable of monitoring conductors rated
up to a maximum of 100 amps.
13. 50 Pin Ribbon Cable Connectors (Current Sensor Strips): Connects current
signal from the sensor strip to the main board via the ribbon connectors.
Z206024-0B PAGE 2 ©2011 For technical support please contact 10111 DET-756 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
ASPMETER
TM
INSTALLATION GUIDE
DATA OUTPUT
Monitoring at Mains ASPMETERA ASPMETERB ASPMETERC
Current per phase
Max. current per phase
Current demand per phase
Max. current demand per phase
Energy (kWh) per phase
Real Power (kW) per phase
Apparent Power (kVA)
Power factor total *
Power factor per phase
Voltage - L-L and average
Voltage - L-N and average
Frequency (phase A)
Monitoring at Branch Circuit
Current
Max. current
Current demand
Max. current demand
Real power (kW)
Real power (kW) demand
Real power (kW) demand max.
Energy (kWh) per circuit
Power factor
Apparent Power (kVA)
Modbus Alarms
Voltage over/under
Current over/under
BLINK CODES FOR STATUS LED
Color and Pattern Status Description
Green, once per second Normal operation
Amber, once per second Volts or Amps clipping
Amber, twice per second Invalid rmware image
Amber, three per second Incorrect strips or strip order
Red, solid or blink Device Failure
COMMISSIONING
1. Install according to instructions in Appendix A.
1. Provide control power to main circuit board.
2. Congure installation mode using Modbus Register 6.
3. Congure CT scaling.
4. Congure alarms.
5. Congure demand.
Download the free E3x Conguration Tool from www.veris.com to commission the ASPMETER for operation. (Click path: www.veris.com >> “Design Resources” >> “Protocol Info” >> “Modbus” >> “E3x Conguration Tool”)
* Based on a 3-phase breaker rotation.
Z206024-0B PAGE 3 ©2011 For technical support please contact 10111 DET-756 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
ASPMETER
+
TM
WIRING
Power must be disconnected and locked out before making any wiring connections.
Connect 2-wire or 4-wire Modbus RS-485 daisy chain network (Figures 9 and 10).
INSTALLATION GUIDE
Figure 9
SHIELD RX- TX- RX+ TX+ TX­TX+
Fig ure 10
2-Wire 4-Wire
Master or Slave
TX+
TX-
RX+
TX+
SHIELD
RX-
TX–
SHLD
SHIELD
1. Mechanically secure the RS-485 cable where it enters the electrical panel.
2. Connect all RS-485 devices in a daisy-chain fashion, and properly terminate the chain (Figure 11).
3. Shield the RS-485 cable using twisted-pair wire, such as Belden 1120A. The cable must be voltage-rated for the installation.
Fi gu re 11
TX+
Master
TX+
TX-
TX–
RX+
SHLD
RX-
SHIELD
TX+
Slave
TX+
TX-
TX–
RX+
SHLD
RX-
SHIELD
2-Wire Example
Belden 1120A or
equivalent
120 Ω terminator
on last device of
daisy chain
4. When tightening terminals, ensure that the correct torque is applied: 0.5 to 0.6 N·m (0.37 to 0.44 ft·lb ) for connectors on main board, 0.22 to 0.26 N·m (0.16 to
0.19 ft·lb) for connectors on adapter boards (Figure 12).
WARNING: After wiring the RS-485 cable, remove all scraps of wire or foil shield from the electrical panel. Wire scraps coming into contact with high voltage conductors could be DANGEROUS!
Not Used
Fi gu re 12
– +
Z206024-0B PAGE 4 ©2011 For technical support please contact 10111 DET-756 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
ASPMETER
TM
CONFIGURATION
1. Communications Conguration: Communications parameters for the ASPMETER series are eld selectable for your convenience. Please see the Product Diagram section (page 2) for selector location. The following parameters are congurable:
INSTALLATION GUIDE
3. Address the ASPMETER as any whole number between and including 1-246. Each unit is equipped with a set of 8 DIP switches for addressing. See below.
• Baud Rate: 9600, 19200, 38400
• Parity On or O
• Parity: odd or even
• Wiring: two or four
Bø
B1
Off/
On
Parity
Odd/
Even
Parity
2/4
Wire
Reserved
Example: 2-wire 19200 Baud No Parity (Default Only)
1 2 3 4 5 6 7 8
o o X X X 9600
on o X X X 192 00
o on X X X 38400
on on X X X Reserved
o o X X X No Parity
on o X X X Odd Parity
o on X X X No Parity
on on X X X Even Parity
on X X X 4-wire RS-
485
o X X X 2-wire RS-
485
=
1
LSB MSB
1 2 4 8 16 32 64 128
4. To determine an address, simply add the values of any switch that is on.
For example:
LSB
Switch number 4 has an ON Value of 8 and switch number 6 has an ON Value of 32.
(8 + 32 = 40). Therefore, the address for the ASPMETER is 40.
See the Address Setup section (page 8) for a pictorial listing of the rst 63 switch positions.
DIP Switch Values
=
40
MSB
DEFAULT DIP SWITCH SETTINGS
The ASPMETER includes two DIP switches, as shown below. Switches are shown in their default positions.
2. Address Conguration: Each Modbus device on a single network must have a unique address. Set the switch block to assign a unique address before the device is connected to the Modbus RS-485 network. If an address is selected which conicts with another device, neither device will be able to communicate.
Comms Address Comms Settings
Z206024-0B PAGE 5 ©2011 For technical support please contact 10111 DET-756 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
ADDRESS SETUP
ASPMETER
TM
INSTALLATION GUIDE
DO NOT
USE ZERO
1 2 3 4 5 6 7 8 9 10
11 12 13 14 15 16 17 18 19 20 21
22 23 24 25 26 27 28 29 30 31 32
33 34 35 36 37 38 39 40 41 42 43
44 45 46 47 48 49 50 51 52 53 54
55 56 57 58 59 60 61 62 63 246
Z206024-0B PAGE 6 ©2011 For technical support please contact 10111 DET-756 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
......
APPENDIX A:
ASPMETER
TM
INSTALLATION GUIDE
MECHANICAL INSTALLATION
Observe handling precautions for static sensitive devices to avoid damage to the circuitry which would not be covered under the factory warranty.
Disconnect power to the electrical panel and lock it out.
1. Install the current sensor strips in the panel (Figure 1).
2. Arrange the sensor strips in one of the four congurations shown in Figure 2. Adjust orientation of the circuit numbers in the eld during commissioning by writing to Modbus Register 6 or use free conguration software at www.veris. com.
Figure 2
B
A
2
1
5
9
13
17
21
25
29
33
37
41
4
3
6
8
7
10
12
11
14
16
15
18
20
19
22
24
23
26
28
27
30
32
31
34
36
35
38
40
39
42
Top Feed Bottom Feed
A
B
Register 6 Value = 0
(Default)
Figure 1
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
CTs accept a maximum #2 AWG (0.384” O.D.)
wire with THHN insulation.
Use this gauge wire or smaller for 100 A circuits .
B
A
A
B
2
1
4
3
7
11
15
19
23
27
31
35
39
6
5
8
10
9
12
14
13
16
18
17
20
22
21
24
26
25
28
30
29
32
34
33
36
38
37
40
42
41
Register 6 Value = 1
20
2020202020202020
20
20202020202020202020
20
Single Row: Sequential Single Row: Odd/Even
A
A
1
2
4
6
8
10
12
14
16
18
20
22
B
24
26
28
30
32
34
36
38
40
42
B
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
Register 6 Value = 2
Z206024-0B PAGE 7 ©2011 For technical support please contact 10111 DET-756 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
A
A
A
1
B
3
7
11
15
19
23
27
31
35
39
2
B
6
10
14
18
22
26
30
34
38
42
B
5
9
13
17
21
25
29
33
37
41
4
8
12
16
20
24
28
32
36
40
Register 6 Value = 3
ASPMETER
TM
INSTALLATION GUIDE
3. Verify that the serial numbers printed on the current strip and on the data acquisition board match. The board and the strip are sold as a calibrated set.
4. Congure communication and addressing parameters using DIP switches. See the Conguration section for more information.
5. Install the ASPMETER acquisition board mounting bracket in the panel using screws and bolts provided (Figure 3). A grounding connection is located on the mounting bracket, near the lower right corner. Use this stud to ground the bracket when it is mounted on a plastic surface.
6. Connect current sensor ribbon cables to the 50-pin connectors on the main board (Figures 4 and 5). Orient cables so that the red stripe is on the left.
Figure 4
Red Stripe
Align ribbon cable key with
connector keyhole.
Orient ribbon cable so that th e
red stripe is on the lef t side of
the connector.
Figure 3
Figure 5
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
A B
Pane l 1
Z206024-0B PAGE 8 ©2011 For technical support please contact 10111 DET-756 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
ASPMETER
I1
I2
I3
IN
±
±
±
±
TM
7. Wire RS-485 communications (see diagrams in Wiring section, page 6).
8. Connect 0.333 VAC CTs to the main conductors by snapping CTs around lines, observing local codes regarding bending radius (optional; Figure 6).
Figure 6
E30 CURRENT SENSOR STRIP
E30 CURRENT SENSOR STRIP
Recommended CT:
Veris Industries H6810, H6811, H6812 Series with 0.333VAC output.
Available in 100A max. to 2400A max.
Call a Veris sales rep if higher amperages a re require d.
INSTALLATION GUIDE
SAFETY
If ASPMETER products are used in installations with circuits higher than the product ratings, the circuits must be kept segregated per UL508A Sec. 17.5.
Note: 277/480 VAC Wye connected (center grounded) power systems operate within the 300 VAC line to neutral safety rating of the ASPMETER series, and the operational voltage limit (single-phase connection) as the line to neutral voltage is 277 VAC in such power systems. Corner-grounded delta 480 VAC systems would not qualif y, as the actual line to earth voltage is 480 VAC on each leg, exceeding the ASPMETER ratings.
Note: ASPMETER internal circuitr y (cables and CTs) are not circuits as dened by UL508A, as they do not extend beyond the ASPMETER itself without further safety/re isolation.
UL listed under standard 508 as an “open type device.”
Maximum ambient air temperature for use is 60°C.
Installation categor y: CAT III
The ASPMETER Series must be installed in an appropriate electrical and re enclosure per local regulations.
9. Connect 2-wire 90-277 VAC power to main power terminals. Observe polarity. For the ASPMETERA and ASPMETERB, connec t voltage lines to the voltage taps (Figure
8). Equip voltage lines with fuses.
Figure 7
CT Input
(0 -0.333 VAC)
Set up Modbus registers 115-118 for CT scaling.
Figure 8
V2/N
90 -277 VAC
V1
For use in a Pollution Degree 2 or better environment only.
A Pollution Degree 2 environment must control conductive pollution and the possibility of condensation or high humidity. Consideration must be given to the enclosure, the correct use of ventilation, thermal properties of the equipment and the relationship with the environment.
If the equipment is used in a manner not specied by the manufacturer, the protection provided by the device may be impaired.
IEC/EN 61010-1
This symbol indicates an electrical shock hazard exists.
Documentation must be consulted where this symbol is used on the product.
V1 V2 V3 N
L - L L - N
Z206024-0B PAGE 9 ©2011 For technical support please contact 10111 DET-756 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
Line to Line (L-L) Voltage: 150 to 480 VAC
Line to Neutral (L-N) voltage: 90 to 277 VAC
TM
TROUBLESHOOTING
Problem Solution
Product is not communicating over Modbus daisy chain
RX LED is solid
The main board has a fast ashing amber light
The main board has a slow ashing amber light
The main board has a ashing green light
The main board is a ashing or solid red light
Power factor reading is not as expected
Current reading is not as expected, or reading is on dierent CT number
than expected
Current is reading zero, even when small currents are still owing through
circuit
E3x Cong Tool returns Modbus error on read/write
ASPMETER
Check the unit Modbus address to ensure that each device on the daisy chain has a unique address.
Check Parity.
Check the communications wiring.
Check that the daisy chain is properly terminated.
Check for reversed polarity on Modbus comms.
Check for sucient biasing on the Modbus bus. Modbus physical specication calls for 450-650Ohm biasing.
This is usually provided by the master.
Check that the 1A and 1B CT strips are connected to the left top and left bottom ribbon cable connections; 2A and 2B must be connected to the right top and right bottom ribbon cable connections (see illustrations in the product install).
Verify ribbon cable connectors are inserted in the correct orientation.
If cables are correct, reset main board to re-initialize product.
Verify serial number on strips matches serial number on main board.
One or more channels is clipping, this can be caused by a signal greater than 100 A or 277 V L-N, or by a signal
with high THD near the gain stage switching points (1.5 A and 10 A).
Everything is wired properly and the main board has power.
Light may be red briey while device powers up.
If light is red for more the 60 sec. device has encountered an error. Contact technical support.
Verify voltage taps are connected in appropriate phase rotation.
Verify strip conguration register matches actual strip installation.
Verify phase rotation of breakers (rmware rev. 1.012 or higher allows for custom rotation if needed).
Verify strip conguration register matches actual strip installation.
Verify ribbon cable is fully seated and in the correct orientation.
The product cuts o at 50 mA, and will set the reporting register to 0 mA for currents near or below this range.
Verify using the latest release of E3x Cong Tool as older versions may not support all features in current product
rmware. Latest version is available on our website http://www.veris.com/modbus.aspx
INSTALLATION GUIDE
Z206024-0B PAGE 10 ©2011 For technical support please contact 10111 DET-756 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
Loading...