g
GEH5589 Installation Instructions R07
Spectra Series™ Power Panelboards
Type APN and APNB Panelboard Interiors into
Type APB Panelboard Enclosures
Installation
WARNING: Danger of electrical shock or injury.
Turn OFF power ahead of the panelboard or
switchboard before working inside the equipment or
removing any component. Equipment is to be
installed and maintained by properly trained and
qualified personnel only.
These instructions describe the installation of Type APN and
APNB panelboard interiors into Type APB panelboard
enclosures. Figure 1 shows a typical panel with four-piece trim.
Figure 2 shows a typical panel with a dead front and the door
removed.
Side Rail
End Filler
Mounting
Reference
Figure 6
Post
Figure 3. Deadfront assembly removed.
Load-End
Filler with
Labels
Enclosure
Back
Reference
Figure 5 or 7
Figure 1. Typical panel with four-
piece trim.
1. For ease of installation, it is necessary to remove the filler
plates and, if provided, the deadfront assembly. When
removing the deadfront, remove only the side rails and lineend filler plate, leaving the mounting posts and load-end
filler attached, as shown in Figure 3. Follow the
instructions for removal provided with each device, and set
aside.
NOTE: For panels not assembled at the factory, but that
require a deadfront, attach the mounting posts provided with
the deadfront kit at this time, following the instructions
provided with the kit.
2. Remove the four wing nuts and washers from the 3/8"
interior mounting studs on the back wall of the enclosure.
3. Locate the panel mounting studs that align with the
panelboard interior mounting holes, as shown in Figure 4.
The line end of the panel must be installed toward the line
end of the box.
Figure 2. Typical panel with a
deadfront.
Figure 4. Panelboard mounting studs.
4. Place the interior on the studs, and replace the washer and
wing nuts. Tighten the wing nuts.
5. Reinstall any filler plates removed earlier, starting at the
lower end of the interior. For device installation, refer to
the instructions furnished with the device. Once installation
is complete, wiring may be brought to the main and branch
devices. See the aluminum termination caution below.
Panels with Full-Height Door Fronts
6. If a full-height door front is to be used on the panel, it is
necessary to reinstall the deadfront once the wiring has
been brought into the panel. (These instructions are also
provided wit h the door front.)
27- and 31-inch-wide panels. To replace or install the
deadfront, first install the top and bottom ends to the
mounting post, as shown in Figure 5. Tighten the 1/4-20
hex-head screws to 50–60 in-lb.
Mounting
Post
End
Filler
Welded
Bracket
1
/4-20
Screw
Figure 5. Installing the ends to the mounting post.
27–44-inch-wide panels . Fasten the end filler plates to the
side plates with the 1/4-turn fasteners shown in Figure 6.
The end filler plate with labeling attached must be placed
at the load end of the panel, opposite to the incoming
power.
36–44-inch-wide panels. Refasten the end fillers to the
mounting posts, tightening the 1/4-20 screws to 50–60 in-lb,
as shown in Figure 7. The end filler plate with labeling
attached must be placed at the load end of the panel,
opposite to the incoming power.
Mounting
Post
1
/4-20
Screw
End
Filler
Figure 7. Fastening the end fillers to the mounting posts.
After Installing the Interior
Do not discard the remaining contents of the bag that contained
these instructions. The circuit identification tabs should be
used, as applicable, at the time the circuit protective devices are
installed. The NEMA instruction sheet provided should be
retained for use by maintenance personnel.
If plug-in devices are used, the area above the device-mo unting
latches should be kept clear of any wires running through the
side gutters. This facilitates the future removal of a device, if
necessary.
Attention – Procedure for Aluminum
Side
Plate
1
/4-Turn
Fastener
End
Filler
Figure 6. Fastening the end filler to the side plate.
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that
may be met in connection with installation, operation, or maintenance. Should further information be desired or should
articular problems arise that are not covered sufficiently for the purchaser’s purposes, th e matter should be referred to the
GE Company.
Terminations
1. Strip the insulation, being careful to not nick the wire.
2. Clean the wire strands with a wire brush.
3. Thoroughly coat the stripped conductor with a suitable
antioxidant compound, such as ALNOX or PENETROX
A13.
4. Insert the conductor and tighten the connector screw to the
required torque, as indicated on the rating label.
GE Industrial Systems
General Electric Company
41 Woodford Ave., Plainville, CT 06062
GEH5589 R07 0501 © 2001 General Electric Company