DEH40394 Installation Instructions R02
Spectra Series™ Power Panelboards
Neutral and Ground Wire Kit for PQM Panel Metering
Catalog Number
APMNEUGNDWK
Application
For use with meter modules type APM6004PQM,
APM6003PQM, APM4804PQM, APM4803PQM,
APM2404PQM, APM2403PQM, and APM2084PQM.
Installation
WARNING: Danger of electrical shock or injury.
OFF
Turn
switchboard before workin
e
Equipment is to be installed and maintained b
properly trained and qualified personnel only.
In the following instructions and figures, numbers in
brackets refer to the items in Table 1.
1. Confirm the contents of the kit. This kit is for
installing the ground wire and neutral wire (if neutral
is required).
The kit contains parts for making the neutral
connection (if the meter module is provided with
one) and ground connection on PQM Panel
Metering. The 12-gauge wire is used for the ground
connection and thus is always used. If a neutral is not
required, then discard the 14-gauge wire. Figure 1
shows all the parts included in this kit, which are
listed in Table 1.
2. Locate the terminal board in the meter module. After
installation of the panel, ground, and neutral (if
required) into the enclosure, locate the module in the
panel interior. Open the door of the module and
locate the 12-point terminal board, as shown in Figure
2.
3. Installing the ground and neutral wire. Locate the
terminals marked GND 6 and VN (if required), as
shown in Figure 3. Loosen the slotted screws on the
right side of the terminal board. Insert one end of the
12-gauge wire [1] into the GND 6 slot. Insert one end
of the 14-gauge wire [2] into the VN slot. Tighten the
screws to 12 in-lb.
ower ahead of the panelboard or
inside the
ment or removing any component.
[3]
[1]
Figure 1. Parts Included In the neutral and/or ground wire kit, catalog
Item Description Part # Qty.
1 12-gauge black wire 273A7900P12BK19 8 ft.
2 14-gauge black wire 273A7900P14BK19 8 ft.
3 Tie wraps PEL#PLT1.5I-M 16
4 Saddles 331A2242P1 8
Table 1. Parts list for kit APMNEUGNDWK.
Figure 2. Location of the 12-point terminal board in the meter
[2]
[4]
number APMNEUGNDWK.
Terminal Board
module.
Terminal
VN
14-Gauge
Wire
Slotted
Screws
Equipment
Ground
Terminal
GND 6
12-Gauge
Wire
Figure 3. Terminal board in the meter module.
4. Run wires down the side of the interior. Determine
the shortest route to the equipment neutral (if
applicable) and ground using the side rails of the
panels. Be sure that the breaker cables will not
interfere with the wires. Attach saddles [4], spaced
approximately 1 foot apart, with tie wraps [3]. Wipe
off the metal with a paper towel or equivalent at the
point of saddle attachment. Use tie wraps [3] to secure
the wires to the saddles.
5. Attach the wire to neutral and ground. Cut and strip
the free end of the ground wire and attach to the
equipment ground, as shown in Figure 4. Select the
lug hole closest to the metering module. Do the same
for the neutral (if applicable), as shown in Figure 5.
Tighten the screws to the torque levels specified on
the component labels.
Ground
Wire
Figure 4. Attach the 12-gauge wire to the equipment ground.
Equipment
Neutral
Neutral
Wire
These instructions do not cover all details or variations in e
ma
be met in connection with installation, operation, or maintenance. Should further information be desired or should
articular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the
GE Company.
ment nor do they provide for every possible contingency that
GE Industrial Systems
General Electric Company
41 Woodford Ave., Plainville, CT 06062
DEH40394 R02 0901 © 2001 General Electric Company
Figure 5. Attach the 14-gauge wire to the equipment neutral.