GE Industrial Solutions AMP1H5 User Manual

TM
the FCC Rules. These limits are designed to provide reasonable protection
residential environment. This equipment generates, uses, and can radiate
AM P1H5
POWER MONITORING
INSTALLATION GUIDE
Compact Power and Energy Meter
With BACnet MS/TP Support
SPECIFICATIONS
Measurement A ccuracy:
Real Power and Energy IEC 62053-22 Class 0.5S, ANSI C12.20 0.5% Reactive Power and Energy IEC 62053-23 Class 2, 2% Current 0.4% (+0.015% per °C deviation from 25°C) from 5% to 100% of range;
0.8% (+0.015% per °C deviation from 25°C) from 1% to 5% of range Volt age 0.4% (+0.015% per °C deviation from 25°C) from 90 V
n
C
e
A
t
B
·
®
·
T
S
E
E
S
I
T
R
I
O
N
RoHS
T
G
A
L
R
A
O
B
Compliant
Sample Rate 2520 samples per second Data Update Rate 1 sec Type of Measurement True RMS up to the 21st harmonic 60 Hz One to three phase AC system
Input Voltage Characteristics:
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Turn off all power supplying equipment before working on or inside the equipment.
• Any covers that may be displaced during the installation must be reinstalled before powering the unit.
• Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
Measured AC Voltage Minimum 90 V UL Maximums: 600 V Metering Over-Range +20% Impedance 2.5 MΩ Frequency Range 45 to 65 Hz
Input Current Characteristics:
CT Scaling Primary: Adjustable from 5 A to 32,000 A Measurement Input Range 0 to 0.333 VAC or 0 to 1.0 VAC (+20% over-range) Impedance 10.6 kΩ (1/3 V mode) or 32.1 kΩ (1 V mode)
Control Power:
AC 5 VA max.; 90 V min. UL Maximums: 600 V DC* 3 W max.; UL and CE: 125 to 300 VDC Ride Through Time 100 msec at 120 VAC
Input:
Pulse Solid-state or mechanical contacts (current less than 1 mA); 2 pulse inputs) Minimum Pulse Width 20 msec
Output:
(347 V
L-L
(347 V
L-L
L-N
(156 V
L-N
L-N
) for stated accuracy;
L-L
); CE Maximum: 300 V
); CE Maximum: 300 V
RS-485 Port 2-wire, 9600 to 115.2 kbaud, BACnet MS/TP
NOTICE
Mechanical Characteristics:
Weight 0.62 lb (0.28 kg)
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION NOTE: This equipment has been tested by the manufacturer and found to
comply with the limits for a class B digital device, pursuant to part 15 of
against harmful interference when the equipment is operated in a
IP Degree of Protection (IEC 60529) IP40 front display; IP20 Meter Display Charac teristics Back-lit blue LCD Terminal Block Screw Torque 0.37 ft-lb (0.5 N·m) nominal/0.44 ft-lb (0.6 N·m) max. Terminal Block Wire Size 24 to 14 AWG (0.2-2.1 mm2) Rail T35 (35 mm) DIN Rail per EN50022
Environmental Conditions:
Operating Temperature -30° to 70°C (-22° to 158°F) Storage Temperature -40° to 85°C (-4 0° to 185°F) Humidity Range <95% RH (non-condensing) Altitude of Operation 3 km max.
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Modifications to this product without the express authorization of the
manufacturer nullify this statement.
For use in a Pollu tion Degree 2 or bet ter environment only. A Pollut ion Degree 2 environme nt must control conductive pollution and the possibility of condensation or high humidity. Consider the enclosure, t he correct use of ven tilation, thermal pro perties of the equ ipment, and the relatio nship with the env ironment. Installat ion category: CAT II or C AT III
Metering Category:
North America CAT III; for distribu tion systems up to 347 V CE CAT III; for distribution systems up to 300 V Dielectric Withs tand Per UL 508, EN61010 Conducted and Radiated Emissions FCC part 15 Class B, EN55011/EN61000 Class B (residential and light indus trial) Conducted and Radiated Immunity EN61000 Class A (heavy industrial)
Agency Approvals:
US and Canada (cULus) UL508 (open ty pe device)/CSA 22.2 No. 14-05 Europe (CE) EN61010-1:2001
* External DC current limiting is required, see fuse recommendations.
Provide a dis connect device to dis connect the meter f rom the supply source. P lace this device in close pr oximity to the equipm ent and within easy reac h of the operator, and mark it as t he disconnec ting device. The disc onnecting device sh all meet the relevant re quirements of IEC 609 47­1 and IEC 60947-3 and shall be su itable for the applic ation. In the US and Canada, dis connecting fuse hold ers can be used. Prov ide overcurrent prote ction and discone cting device for sup ply conduct ors with approved cu rrent limiting device s suitable for prote cting the wiring. I f the equipment i s used in a manner not spec ied by the manufac turer, the protection p rovided by the device may be im paired.
ZL 0115- 0A PAGE 1 ©2013 For technical support please contact 01132 DE T-785 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
to 600 VAC
L-N
L-N
/600 VAC
L-N
/5 MΩ
L-L
L-N
L-L
L-N
L-L
L-N
AMP1H5
TM
INSTALLATION GUIDE
TABLE OF CONTENTS
Operation 2
Product Identication 2
Dimensions 2
Product Diagram 3
Installation 3
Supported System Types 4
Wiring Symbols 4
Data Outputs 2
Wiring Diagrams 5
Control Power Diagrams 6
Display Screen Diagram 7
Quick Setup Instructions 7
Pulse Contac ts 8
User Interface Menu Abbreviations Dened 8
User Interf ace for Data Conguration 9
Alert/Reset Information 10
User Interf ace for Setup 11
RS-485 Communications 13
Data Logging 13
BACnet Default Settings 13
BACnet Programming Information 14
Data Logging 22
Troubleshooting 24
China RoHS Compliance Information 24
PRODUCT IDENTIFICATION
Model
AMP 1H5
BACnet MS/TP
Protocol Output
n n n
Alarm
Output
Full Data
Set
DIMENSIONS
2.3”
(59mm)
4.2”
(107mm)
Bottom View (DIN Mount Option)
4.2 “
(107 mm)
3.6 “
(91 mm)
Logging
1.8”
(45mm)
(39mm)
3.6”
(91mm)
1.5”
Data
Pulse Input
n
(2 pulses)
1.9”
(48mm)
PRODUCT OVERVIEW
4.3 “
(109 mm)
0.2 “
(4 mm)
Bottom View (Screw Mount Option)
2.4 “
(61 mm)
3.9“
(99 mm)
1.2 “
(31 mm)
+
++
0.3 “
(8 mm)
0.4 “
(10 mm)
The AMP1H5 DIN rail power meter provides a solution for measuring energy data with a single device. Inputs include control power, CT, and 3-phase voltage. The meter supports BACnet MS/TP protocol and has data logging capability and two pulse contact inputs. The LCD screen on the faceplate allows instant output viewing.
The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail according to EN50022. It can be mounted with any orientation over the entire ambient temperature range, either on a DIN rail or in a panel. The AMP1H5 meter is not sensitive to CT orientation, reducing installation errors.
ZL 0115- 0A PAGE 2 ©2013 For technical support please contact 01132 DE T-785 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
AMP1H5


TM
INSTALLATION GUIDE
PRODUCT DIAGRAM
IA
-+-+-
A B C Pulse Inputs
Common - 1 or 1/3 VAC Input
Two 5-character rows
of display text.
Top row alphanumeric;
Bottom row numeric only
Alarm Energy
The red Alarm LED lights when any of the 3 phase voltages drop below the selected threshold. The green Energy LED lights when the pulse 1 input contacts are active or closed.
VOLTAGE INPUTS CAT III 50/60 Hz
A B C N 1 2
VA
VB
INSTALLATION
Disconnect power prior to installation.
IB
IC
+
Pulse Input 1
Pulse Input 2
BACnet
RS-485
1 2 + - S
Shield
+
UL: 90V
- 600V
CE: 90V
L-N
VC
Neutral
- 300V
L-L
L-N
L-N
CONTROL POWER
0.1A 50/60 Hz
Earth
Control
Power
Reinstall any covers that are displaced during the installation before powering the unit.
Mount the meter in an appropriate electrical enclosure near equipment to be monitored.
Do not install on the load side of a Variable Frequency Drive (VFD), aka Variable Speed Drive (VSD) or Adjustable Frequency Drive (AFD).
The meter can be mounted in two ways: on standard 35 mm DIN rail or screw­mounted to the interior surface of the enclosure.
A. DIN Rail Mounting
1. Attach mounting clips to the underside of the housing by sliding them into the slots from the inside. The stopping pegs must face the housing, and the outside edge of the clip must be ush with the outside edge of the housing.
2. Snap the clips onto the DIN rail. See diagram of the underside of the housing (below).
Clip flush with outside edge
Snap onto
Insert clips from inside
DIN rail
3. To prevent horizontal shifting across the DIN rail, use two end stop clips.
B. Screw Mounting
1. Attach the mounting clips to the underside of the housing by sliding them into the slots from the outside. The stopping pegs must face the housing, and the screw hole must be exposed on the outside of the housing.
2. Use three #8 screws (not supplied) to mount the device to the inside of the enclosure. See diagram of the underside of the housing (below).
Insert clips from outside
Screw holes exposed for mounting
ZL 0115- 0A PAGE 3 ©2013 For technical support please contact 01132 DE T-785 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
AMP1H5
TM
INSTALLATION GUIDE
SUPPORTED SYSTEM TYPES
The AMP1H5 power meter has a number of dierent possible system wiring congurations (see Wiring Diagrams, page 5). To congure the meter, set the System Type via the User Interface or by writing the Present_Value of AV2 with the System Type value in the table below. The System Type tells the meter which of its current and voltage inputs are valid, which are to be ignored, and if neutral is connected. Setting the correct System Type prevents unwanted energy accumulation on unused inputs, selects the formula to calculate the Theoretical Maximum System Power, and determines which phase loss algorithm is to be used. The phase loss algorithm is congured as a percent of the Line­to-Line System Voltage (except when in System Type 10) and also calculates the expected Line to Neutral voltages for system types that have Neutral (12 & 40).
Values that are not valid in a particular System Type will display as “----” on the User Interface or as QNAN in the BACnet objec ts.
CTs Voltage Connections System Type Phase Loss Measurements Wiring
Diagram
Number
of wires
Single-Phase Wiring
2 1 A 2 A, N L-N 10 1L + 1n AN 1
2 1 A 2 A, B L- L 11 2L AB 2
3 2 A, B 3 A, B, N L-L with N 12 2L + 1n AB AN, BN AN-BN 3
Three-Phase Wiring
3 3 A, B, C 3 A, B, C Delta 31 3L AB, BC, CA A B- BC- CA 4
4 3 A, B, C 4 A, B, C, N Grounded
Qty ID Qty ID Type BACnet object
AV2
40 3L + 1n AB, BC, CA AN, BN, CN AN-BN-CN &
Wye
User Interf ace:
SE TU P>S SY S
VLL VLN Balance Diagram
number
5, 6
AB -B C-C A
WIRING
To avoid distortion, use parallel wires for control power and voltage inputs.
The following symbols are used in the wiring diagrams on the following pages.
Symbol Description
Voltage Disconnect Switch
Fuse (installer is responsible for ensuring compliance with
local requirements. No fuses are included with the meter.)
Earth ground
S1
S2
Current Transducer
Potential Transformer
Protection containing a voltage disconnect s witch with a
fuse or disconnect circuit breaker. The protection device must be rated for the available short-circuit current at the connection point.
CAUTION
RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT.
• Failure to follow these instructions can result in overheating and permanent equipment damage.
DATA OUTPUTS
Full Data Set (FDS):
Power (kW) Energy (kWh) Congurable for CT & PT ratios, system type, and passwords Diagnostic alerts Current: 3-phase average Volts: 3-phase average Current: by phase Volts: by phase Line-Line and Line-Neutral Power: Real, Reactive, and Apparent 3-phase total and per phase Power Factor: 3-phase average and per phase Frequency Power Demand: Most Recent and Peak Demand Conguration: Fixed, Rolling Block, and External Sync Real Time Clock: uses BACnet Time Synchronization services
Data Logging (includes all FDS outputs, plus):
3 BACnet Log_Events: each buer holds 5760 time-stamped 32-bit entries (User congures which 3 data points are stored in these buers) User congurable logging interval (When congured for a 15 minute interval, each buer holds 60 days of data) Continuous and Single Shot logging modes: user selectable
ZL 0115- 0A PAGE 4 ©2013 For technical support please contact 01132 DE T-785 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
TM
WIRING DIAGRAMS
RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE
CT negative terminals are referenced to the meter’s neutral and may be at elevated voltages
· Do not contact meter terminals while the unit is connected
· Do not connect or short other circuits to the CT terminals
Failure to follow these instructions may cause injury, death or equipment damage.
Diagram 1: 1-Phase Line-to-Neutral 2- Wire System 1 CT Diagram 2: 1-Phase Line-to-Line 2-Wire System 1 CT
USE SYSTEM TYPE 10 (1L + 1n)
N L1
AMP1H5
WARNING
INSTALLATION GUIDE
USE SYSTEM TYPE 11 (2L)
L1 L2
A B C N
X1
X2
White
Black
+
A
-
+
B
-
+
C
-
Diagram 3: 1-Phase Direct Voltage Connection 2 CT
N
L1 L2
USE SYSTEM TYPE 12 (2L + 1n) USE SYSTEM TYPE 31 (3L)
A B C N
X1
X2
X1
X2
White
Black
White
Black
+
A
-
+
B
-
+
C
-
X1
X2
Diagram 4: 3-Phase 3-Wire 3 CT no PT
L1 L2 L3
X1
X1
X2
X1
X2
X2
White
Black
White
Black
White
Black
White
Black
A B C N
+
A
-
+
B
-
+
C
-
A B C N
+
A
-
+
B
-
+
C
-
Diagram 5: 3-Phase 4-Wire Wye Direct Voltage Input Connection 3 CT
L1N L2 L3
X1
X2
USE SYSTEM TYPE 40 (3L + 1n)
X1
X2
X1
X2
White Black
White Black
White
Black
A B C N
+
A
-
+
B
-
+
C
-
Diagram 6: 3-Phase 4-Wire Wye Connection 3 CT 3 PT
L1N L2 L3
X1
X2
USE SYSTEM TYPE 40 (3L + 1n)
White
X1
X2
X1
X2
Black
White Black
White
Black
A B C N
+
A
-
+
B
-
+
C
-
ZL 0115- 0A PAGE 5 ©2013 For technical support please contact 01132 DE T-785 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
TM
CONTROL POWER
AMP1H5
INSTALLATION GUIDE
Direct Connect Control Power (Line to Line)
1 2G
L1
L2 L3
Line to Line from 90 VAC to 600 VAC (UL) (520 VAC for CE). In UL installations the lines may be
oating (such as a delta). If any lines are tied to an earth (such as a corner grounded de lta), see the
Line to Neutral installation limi ts. In CE compliant installations, the lines must be neut ral (earth)
referenced at less than 300 VAC
L-N
Direct Connect Control Power (DC Control Power)
1 2G
Direct Connect Control Power (Line to Neutral)
1 2G
L1N L2 L3
Line to Neutral from 90 VAC to 347 VAC (UL) or 300 VAC (CE)
Control Power Transformer (CPT) Connection
1 2G
L1N L2 L3
Fuse Recommendations:
Keep the fuses close to the power source (obey local and national code requirements).
For selecting fuses and circuit breakers, use the following criteria:
• Select current interrupt capacity based on the installation category and fault current capability.
• Select over-current protection with a time delay.
• Use a voltage rating sucient for the input voltage applied.
• Provide overcurrent protection and disconnecting means to protect
the wiring. For DC installations, provide external circuit protection. Suggested: 0.5A, high-interrupt capability time delay fuses rated for DC operation at or above the supply voltage.
• The earth connec tion is required for electromagnetic compatibility (EMC) and is not a protective earth ground.
The Control Power Transformer may be wired L-N or L-L. Output to meet meter input requirementsDC Control Power from 125 VDC to 300 VDC (UL and CE max.)
ZL 0115- 0A PAGE 6 ©2013 For technical support please contact 01132 DE T-785 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
TM
DISPLAY SCREEN DIAGRAM
LCD Screen:
Screen Name or Units
Diagnostic Alert:
indicates that one or
more of the alarm
bits (Binary_Objects
1-15) are active.
Logo
Numeric Data
Buttons:
 
(Up)
Select
Tx Rx ERR
+
AMP1H5
Alive Indicator
RS-485 Equipped Units Only: Transmit Data Receive Data Receive Data Error
INSTALLATION GUIDE
B. To Enter BACnet communication parameters
1. Navigate to the S BAC (set BACnet) Setup screen (see section A above).
+
2. Press to go to the MAC screen and through the address digits. Use to select the BACnet MAC address (default is 0 01 ).
3. Press to accept the value and go to the KBAUD screen. Use the baud rate (default is 76. 8K).
4. Press to go to the ID1 screen and through the upper four digits of the Device Instance. Use
+
+
or – to select the ID digits. The setup screen splits the Device ID into two parts, the most signicant four digits (ID1) and the least signicant three digits (ID2). The AMP1H5 supports BACnet Device ID values from 1 to 4,193,999. Units are shipped with a factory default setting that is pseudo­randomly generated in the range from 1,000,000 to 3,097,151.
5. Press to accept the value and go to the ID 2 screen and through the lower
three digits of the Device Instance. Use
+
+
or – to select the ID digits.
6. Press to accept the value and go back to the S BAC screen.
+
or –
+
+
or – to select
(Left)
Back
(Right)
Next
(Down)
Select
QUICK SETUP INSTRUCTIONS
Use this section to enter:
- BACnet communication parameters
- CT (Current Transducer) output voltage and input current ranges
- The service type to be monitored
These instruc tions assume the meter is set to factory defaults. If it has been previously congured, check all optional values.
A. To Navigate to the Setup screens:
+
+
1. Press
2. Press to get to the PAS WD screen.
3. Press to move through the digits. Use the
or – repeatedly until SETU P screen appears.
password (the default is 00000).
+
+
or – buttons to enter your
C. To Enter the CT output voltage and input current ranges:
1. Navigate to the S CT (Set Current Transducer) Setup screen (see section A
above).
+
2. Press to go to the CT V screen. Use
+
or – to select the voltage mode
Current Transducer output voltage (default is 1. 00).
+
3. Press to go to the CT SZ screen and through the digits. Use
+
or – to
select the CT size in amps (default is 100). accept the value and
4. Press to accept the value and go back to the S CT screen.
D. To Enter the service type to be monitored:
1. Navigate to the S SYS (Set System) Setup screen (see section A above).
+
2. Press to go to the SY STM screen. Use (see wiring diagrams - default is 3LN-1N).
Press to go back to the S SYS screen. For full setup instructions, see the conguration instructions on the following pages.
+
or – to select the conguration
4. Press to move to the rst Setup screen (S BAC)
+
+
5. Use
or – to select the parameter screen you want to set.
+
6. After you set the parameters you want, use
+
or – to select the next Setup
screen or to exit the Setup screens (return to S ETU P).
ZL 0115- 0A PAGE 7 ©2013 For technical support please contact 01132 DE T-785 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
AMP1H5
TM
INSTALLATION GUIDE
PULSE CONTACT INPUTS
The AMP1H5 has two inputs with pulse accumulators for solid state or mechanical contacts in other sensors, such as water or gas ow meters. These inputs are isolated from the measured circuits and referenced to the communication signal ground. Use with contacts that do not require current to remove oxidation.
Pulse Input
Contacts
SComm
Output
Comm
Ground
Equivalent
Circuit
4-10 VDC
nominal
~10 kΩ
+
UI MENU ABBREVIATIONS DEFINED
The user can set the display mode to IEC or IEEE notation in the SETUP menu.
Main Menu
IEC IEEE Description
D D Demand
MAX M Maximum Demand
P W Present Real Power
Q VAR Present Reactive Power
S VA Present Apparent Power
A A Amps
UAB, UBC, UAC VAB, VBC , VAC Voltage Line to Line
V VLN Voltage Line to Neut ral
PF PF Pow er Factor
U VLL Voltage Line to Line
HZ HZ Frequenc y
KSh K VAh Accumulated Apparent Energy
KQh KVA Rh Accumulated Reactive Energy
KPh KWh Accumulated Real Energy
PLOSS PLOSS Phase Loss
LOWPF LOWPF Low Power Factor Error
F ERR F ERR Frequency Error
I OVR I OVR Over Current
V OVR V OVR Over Voltage
PULSE PULSE kWh Pulse Output Overrun (conguration error)
_PHASE _PHASE Summar y Data for 1, 2, or 3 active phases
ALERT ALERT Diagnostic Alert Status
INFO INFO Unit Information
MODEL MODEL Model Number
OS OS Operating System
RS RS Reset System
SN SN Serial Number
RESET RESET Reset Data
PASWD PAS WD Enter Reset or Setup Pass word
ENERG ENERG Reset Energy Accumulators
DEMND DEMND Reset Demand Maximums
ZL 0115- 0A PAGE 8 ©2013 For technical support please contact 01132 DE T-785 our GE tech suppor t team at 1-800-GE-1-STOP (1-800-431-7867)
Loading...
+ 16 hidden pages