the FCC Rules. These limits are designed to provide reasonable protection
residential environment. This equipment generates, uses, and can radiate
AM P1H5
POWER MONITORING
INSTALLATION GUIDE
Compact Power and Energy Meter
With BACnet MS/TP Support
SPECIFICATIONS
Measurement A ccuracy:
Real Power and Energy IEC 62053-22 Class 0.5S, ANSI C12.20 0.5%
Reactive Power and Energy IEC 62053-23 Class 2, 2%
Current 0.4% (+0.015% per °C deviation from 25°C) from 5% to 100% of range;
0.8% (+0.015% per °C deviation from 25°C) from 1% to 5% of range
Volt age 0.4% (+0.015% per °C deviation from 25°C) from 90 V
n
C
e
A
t
B
·
®
·
T
S
E
E
S
I
T
R
I
O
N
RoHS
T
G
A
L
R
A
O
B
Compliant
Sample Rate 2520 samples per second
Data Update Rate 1 sec
Type of Measurement True RMS up to the 21st harmonic 60 Hz
One to three phase AC system
Input Voltage Characteristics:
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Any covers that may be displaced during the installation must be reinstalled
before powering the unit.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
Failure to follow these instructions will result in death or serious injury.
A qualied person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved. NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
Measured AC Voltage Minimum 90 V
UL Maximums: 600 V
Metering Over-Range +20%
Impedance 2.5 MΩ
Frequency Range 45 to 65 Hz
Input Current Characteristics:
CT Scaling Primary: Adjustable from 5 A to 32,000 A
Measurement Input Range 0 to 0.333 VAC or 0 to 1.0 VAC (+20% over-range)
Impedance 10.6 kΩ (1/3 V mode) or 32.1 kΩ (1 V mode)
Control Power:
AC 5 VA max.; 90 V min.
UL Maximums: 600 V
DC* 3 W max.; UL and CE: 125 to 300 VDC
Ride Through Time 100 msec at 120 VAC
Input:
Pulse Solid-state or mechanical contacts (current less than 1 mA);
2 pulse inputs)
Minimum Pulse Width 20 msec
Output:
(347 V
L-L
(347 V
L-L
L-N
(156 V
L-N
L-N
) for stated accuracy;
L-L
); CE Maximum: 300 V
); CE Maximum: 300 V
RS-485 Port 2-wire, 9600 to 115.2 kbaud, BACnet MS/TP
NOTICE
Mechanical Characteristics:
Weight 0.62 lb (0.28 kg)
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found to
comply with the limits for a class B digital device, pursuant to part 15 of
against harmful interference when the equipment is operated in a
IP Degree of Protection (IEC 60529) IP40 front display; IP20 Meter
Display Charac teristics Back-lit blue LCD
Terminal Block Screw Torque 0.37 ft-lb (0.5 N·m) nominal/0.44 ft-lb (0.6 N·m) max.
Terminal Block Wire Size 24 to 14 AWG (0.2-2.1 mm2)
Rail T35 (35 mm) DIN Rail per EN50022
Environmental Conditions:
Operating Temperature -30° to 70°C (-22° to 158°F)
Storage Temperature -40° to 85°C (-4 0° to 185°F)
Humidity Range <95% RH (non-condensing)
Altitude of Operation 3 km max.
radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including
interference that may cause undesired operation.
Modifications to this product without the express authorization of the
manufacturer nullify this statement.
For use in a Pollu tion Degree 2 or bet ter environment only. A Pollut ion Degree 2 environme nt must
control conductive pollution and the possibility of condensation or high humidity. Consider the
enclosure, t he correct use of ven tilation, thermal pro perties of the equ ipment, and the relatio nship
with the env ironment. Installat ion category: CAT II or C AT III
Metering Category:
North America CAT III; for distribu tion systems up to 347 V
CE CAT III; for distribution systems up to 300 V
Dielectric Withs tand Per UL 508, EN61010
Conducted and Radiated Emissions FCC part 15 Class B, EN55011/EN61000 Class B
(residential and light indus trial)
Conducted and Radiated Immunity EN61000 Class A (heavy industrial)
Agency Approvals:
US and Canada (cULus) UL508 (open ty pe device)/CSA 22.2 No. 14-05
Europe (CE) EN61010-1:2001
* External DC current limiting is required, see fuse recommendations.
Provide a dis connect device to dis connect the meter f rom the supply source. P lace this device
in close pr oximity to the equipm ent and within easy reac h of the operator, and mark it as t he
disconnec ting device. The disc onnecting device sh all meet the relevant re quirements of IEC 609 471 and IEC 60947-3 and shall be su itable for the applic ation. In the US and Canada, dis connecting
fuse hold ers can be used. Prov ide overcurrent prote ction and discone cting device for sup ply
conduct ors with approved cu rrent limiting device s suitable for prote cting the wiring. I f the
equipment i s used in a manner not spec ied by the manufac turer, the protection p rovided by the
device may be im paired.
The AMP1H5 DIN rail power meter provides a solution for measuring energy data with
a single device. Inputs include control power, CT, and 3-phase voltage. The meter
supports BACnet MS/TP protocol and has data logging capability and two pulse
contact inputs. The LCD screen on the faceplate allows instant output viewing.
The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail
according to EN50022. It can be mounted with any orientation over the entire
ambient temperature range, either on a DIN rail or in a panel. The AMP1H5 meter is
not sensitive to CT orientation, reducing installation errors.
The red Alarm LED lights
when any of the 3 phase
voltages drop below the
selected threshold.
The green Energy LED lights
when the pulse 1 input
contacts are active or closed.
VOLTAGE INPUTS
CAT III 50/60 Hz
ABCN12
VA
VB
INSTALLATION
Disconnect power prior to installation.
IB
IC
+
Pulse Input 1
Pulse Input 2
BACnet
RS-485
12+ - S
Shield
+
–
UL: 90V
- 600V
CE: 90V
L-N
VC
Neutral
- 300V
L-L
L-N
L-N
CONTROL POWER
0.1A 50/60 Hz
Earth
Control
Power
Reinstall any covers that are displaced during the
installation before powering the unit.
Mount the meter in an appropriate electrical enclosure
near equipment to be monitored.
Do not install on the load side of a Variable Frequency Drive
(VFD), aka Variable Speed Drive (VSD) or Adjustable Frequency
Drive (AFD).
The meter can be mounted in two ways: on standard 35 mm DIN rail or screwmounted to the interior surface of the enclosure.
A. DIN Rail Mounting
1. Attach mounting clips to the underside of the housing by sliding them into the
slots from the inside. The stopping pegs must face the housing, and the outside
edge of the clip must be ush with the outside edge of the housing.
2. Snap the clips onto the DIN rail. See diagram of the underside of the housing
(below).
Clip flush with
outside edge
Snap onto
Insert clips from inside
DIN rail
3. To prevent horizontal shifting across the DIN rail, use two end stop clips.
B. Screw Mounting
1. Attach the mounting clips to the underside of the housing by sliding them into the
slots from the outside. The stopping pegs must face the housing, and the screw
hole must be exposed on the outside of the housing.
2. Use three #8 screws (not supplied) to mount the device to the inside of the
enclosure. See diagram of the underside of the housing (below).
The AMP1H5 power meter has a number of dierent possible system wiring congurations (see Wiring Diagrams, page 5). To congure the meter, set the System Type via the
User Interface or by writing the Present_Value of AV2 with the System Type value in the table below. The System Type tells the meter which of its current and voltage inputs
are valid, which are to be ignored, and if neutral is connected. Setting the correct System Type prevents unwanted energy accumulation on unused inputs, selects the formula
to calculate the Theoretical Maximum System Power, and determines which phase loss algorithm is to be used. The phase loss algorithm is congured as a percent of the Lineto-Line System Voltage (except when in System Type 10) and also calculates the expected Line to Neutral voltages for system types that have Neutral (12 & 40).
Values that are not valid in a particular System Type will display as “----” on the User Interface or as QNAN in the BACnet objec ts.
CTsVoltage ConnectionsSystem TypePhase Loss MeasurementsWiring
Diagram
Number
of wires
Single-Phase Wiring
21A2A, NL-N101L + 1nAN1
21A2A, BL- L112LAB2
32A, B3A, B, NL-L with N 122L + 1nABAN, BNAN-BN3
Three-Phase Wiring
33A, B, C 3A, B, CDelta313LAB, BC, CAA B- BC- CA4
43A, B, C 4A, B, C, N Grounded
QtyIDQtyIDTypeBACnet object
AV2
403L + 1nAB, BC, CAAN, BN, CN AN-BN-CN &
Wye
User Interf ace:
SE TU P>S SY S
VLLVLNBalanceDiagram
number
5, 6
AB -B C-C A
WIRING
To avoid distortion, use parallel wires for control power and voltage inputs.
The following symbols are used in the wiring diagrams on the following pages.
SymbolDescription
Voltage Disconnect Switch
Fuse (installer is responsible for ensuring compliance with
local requirements. No fuses are included with the meter.)
Earth ground
S1
S2
Current Transducer
Potential Transformer
Protection containing a voltage disconnect s witch with a
fuse or disconnect circuit breaker. The protection device
must be rated for the available short-circuit current at the
connection point.
CAUTION
RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with 1V or 0.33V current
transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT.
• Failure to follow these instructions can result in overheating and
permanent equipment damage.
DATA OUTPUTS
Full Data Set (FDS):
Power (kW)
Energy (kWh)
Congurable for CT & PT ratios, system type, and passwords
Diagnostic alerts
Current: 3-phase average
Volts: 3-phase average
Current: by phase
Volts: by phase Line-Line and Line-Neutral
Power: Real, Reactive, and Apparent 3-phase total and per phase
Power Factor: 3-phase average and per phase
Frequency
Power Demand: Most Recent and Peak
Demand Conguration: Fixed, Rolling Block, and External Sync
Real Time Clock: uses BACnet Time Synchronization services
Data Logging (includes all FDS outputs, plus):
3 BACnet Log_Events: each buer holds 5760 time-stamped 32-bit entries
(User congures which 3 data points are stored in these buers)
User congurable logging interval
(When congured for a 15 minute interval, each buer holds 60 days of
data)
Continuous and Single Shot logging modes: user selectable
Line to Line from 90 VAC to 600 VAC (UL) (520 VAC for CE). In UL installations the lines may be
oating (such as a delta). If any lines are tied to an earth (such as a corner grounded de lta), see the
Line to Neutral installation limi ts. In CE compliant installations, the lines must be neut ral (earth)
referenced at less than 300 VAC
L-N
Direct Connect Control Power (DC Control Power)
1 2G
Direct Connect Control Power (Line to Neutral)
1 2G
L1NL2 L3
Line to Neutral from 90 VAC to 347 VAC (UL) or 300 VAC (CE)
Control Power Transformer (CPT) Connection
1 2G
L1NL2 L3
Fuse Recommendations:
Keep the fuses close to the power source (obey local and national code requirements).
For selecting fuses and circuit breakers, use the following criteria:
• Select current interrupt capacity based on the installation category and
fault current capability.
• Select over-current protection with a time delay.
• Use a voltage rating sucient for the input voltage applied.
• Provide overcurrent protection and disconnecting means to protect
the wiring. For DC installations, provide external circuit protection.
Suggested: 0.5A, high-interrupt capability time delay fuses rated for DC
operation at or above the supply voltage.
• The earth connec tion is required for electromagnetic compatibility (EMC)
and is not a protective earth ground.
The Control Power Transformer may be wired L-N or L-L. Output to meet meter input requirementsDC Control Power from 125 VDC to 300 VDC (UL and CE max.)
RS-485 Equipped Units Only:
Transmit Data
Receive Data
Receive Data Error
INSTALLATION GUIDE
B. To Enter BACnet communication parameters
1. Navigate to the S BAC (set BACnet) Setup screen (see section A above).
+
2. Press to go to the MAC screen and through the address digits. Use
to select the BACnet MAC address (default is 0 01 ).
3. Press to accept the value and go to the KBAUD screen. Use
the baud rate (default is 76. 8K).
4. Press to go to the ID1 screen and through the upper four digits of the Device
Instance. Use
+
+
or – to select the ID digits. The setup screen splits the Device
ID into two parts, the most signicant four digits (ID1) and the least signicant
three digits (ID2). The AMP1H5 supports BACnet Device ID values from 1 to
4,193,999. Units are shipped with a factory default setting that is pseudorandomly generated in the range from 1,000,000 to 3,097,151.
5. Press to accept the value and go to the ID 2 screen and through the lower
three digits of the Device Instance. Use
+
+
or – to select the ID digits.
6. Press to accept the value and go back to the S BAC screen.
+
or –
+
+
or – to select
(Left)
Back
(Right)
Next
–
(Down)
Select
QUICK SETUP INSTRUCTIONS
Use this section to enter:
- BACnet communication parameters
- CT (Current Transducer) output voltage and input current ranges
- The service type to be monitored
These instruc tions assume the meter is set to factory defaults. If it has been
previously congured, check all optional values.
A. To Navigate to the Setup screens:
+
+
1. Press
2. Press to get to the PAS WD screen.
3. Press to move through the digits. Use the
or – repeatedly until SETU P screen appears.
password (the default is 00000).
+
+
or – buttons to enter your
C. To Enter the CT output voltage and input current ranges:
1. Navigate to the S CT (Set Current Transducer) Setup screen (see section A
above).
+
2. Press to go to the CT V screen. Use
+
or – to select the voltage mode
Current Transducer output voltage (default is 1. 00).
+
3. Press to go to the CT SZ screen and through the digits. Use
+
or – to
select the CT size in amps (default is 100). accept the value and
4. Press to accept the value and go back to the S CT screen.
D. To Enter the service type to be monitored:
1. Navigate to the S SYS (Set System) Setup screen (see section A above).
+
2. Press to go to the SY STM screen. Use
(see wiring diagrams - default is 3LN-1N).
Press to go back to the S SYS screen. For full setup instructions, see the
conguration instructions on the following pages.
+
or – to select the conguration
4. Press to move to the rst Setup screen (S BAC)
+
+
5. Use
or – to select the parameter screen you want to set.
+
6. After you set the parameters you want, use
+
or – to select the next Setup
screen or to exit the Setup screens (return to S ETU P).
The AMP1H5 has two inputs with pulse accumulators for solid state or mechanical
contacts in other sensors, such as water or gas ow meters. These inputs are isolated
from the measured circuits and referenced to the communication signal ground. Use
with contacts that do not require current to remove oxidation.
Pulse Input
Contacts
SComm
Output
Comm
Ground
Equivalent
Circuit
4-10 VDC
nominal
~10 kΩ
+
UI MENU ABBREVIATIONS DEFINED
The user can set the display mode to IEC or IEEE notation in the SETUP menu.