GE Digital IC200MDD840, IC200MDD842, IC200MDD843, IC200MDD844, IC200MDD845 Data sheet

...
4 (1)

Process Automation Control Systems

 

VersaMax Control

 

 

 

 

 

Discrete Mixed I/O Modules

 

 

 

Discrete mixed modules provide maximum flexibility by combining inputs and outputs in a single,

 

compact module.. Discrete input modules receive signals from input devices such as sensors,

 

pushbuttons, and switches that can have two states: on or off, open or closed.. Discrete output modules

 

send control signals to devices such as contactors, indicator lamps, and interposing relays that can also

 

have two states.. Discrete mixed modules provide maximum flexibility by combining inputs and outputs in

 

a single, compact module.. Modules require a carrier base (IC200CHSxxx)..

 

IC200MDD840

IC200MDD842

IC200MDD843

 

 

 

 

 

VersaMax Discrete Mixed Modules,

VersaMax Discrete Mixed Modules

VersaMax Discrete Mixed Modules

Product Name

24 VDC Pos Logic Input 20 points/

24 VDC Pos Logic Input 16/Output

24 VDC Positive Logic Input

 

Output Relay 2..0 A, 12 points

24 VDC 0..5 A with ESCP

10/Output Relay 6

 

 

 

 

Lifecycle Status

Active

Active

Active

 

 

 

 

Input Voltage

24 VDC

24 VDC

24 VDC

 

 

 

 

 

0-125 VDC, 5/24/125 VDC nominal;

24 VDC

0-125 VDC, 5/24/125 VDC nominal;

Output Voltage

0-265 VAC (47-63 Hz),

 

0-265 VAC (47-63 Hz),

 

120/240 VAC nominal

 

120/240 VAC nominal

 

 

 

 

Number of Points

20 in/12 out

16 in/16 out

10 in/6 out

 

 

 

 

Channel to Channel Isolation

No

No

No

 

 

 

 

Load Current per Point

2..0 A for 5-265 VAC, 2..0 A for 5-30 VDC

0..5 A for 30 VDC

2..0 A for 5-265 VAC, 2..0 A for 5-30 VDC, 0..2 A

 

 

for 31-125 VDC

 

 

 

 

 

 

 

Input and Output Response

0..5 and 10

0..5 and 0..5

0..5 and 10

TimeOn/Off(ms)

 

 

 

 

 

 

 

Protection

No internal fuses or snubbers

Short circuit protection, overcurrent

No internal fuses or snubbers

 

protection, free-wheeling diodes

 

 

 

 

 

 

 

 

On State Current

2..0-5..5 mA

2..0-5..5 mA

2..0-5..5 mA

 

 

 

 

Off State Current

0-0..5 mA

0-0..5 mA

0-0..5 mA

 

 

 

 

External Power Supply

0-125 VDC, 5/24/125 VDC nominal; 0-265

18-30 VDC, 24 VDC nominal

0-125 VDC, 5/24/125 VDC nominal, 0-265

VAC (47-63 Hz), 120/240 VAC nominal

 

VAC (47-63 Hz), 120/240 VAC nominal

 

 

 

 

 

 

Input Impedance

10 kOhms maximum

10 kOhms maximum

10 kOhms maximum

 

 

 

 

 

2..0 A for 5-265 VAC or

0..5 Amp at 30 VDC

10 mA per point minimum,

 

5-30 VDC, 0..2 A for 31-125 VDC

maximum (resistive);

8..0 A maximum per module;

 

 

2..0 Amps maximum for

2..0 Amps for 5 to 265 VAC

Load Current

 

100ms inrush

maximum (resistive);

 

 

2..0 Amps for 5 to 30 VDC

 

 

 

 

 

 

maximum (resistive);

 

 

 

0..2 Amp for 31 to 125 VDC

 

 

 

maximum (resistive)

 

 

 

 

5V Backplane Current

375 maximum

100 maximum

190 maximum

Consumption (mA)

 

 

 

 

 

 

 

 

One LED per point shows individual

One LED per point shows individual

One LED per point shows individual

LED Indicators

point on/off state (logic side); OK LED

point on/off state (logic side); OK LED

point on/off state (logic side); OK LED

 

indicates backplane power is present

indicates backplane power is present

indicates backplane power is present

 

 

 

 

 

110 mm (4..3 in) x 66..8 mm (2..63 in) x

110 mm (4..3 in) x 66..8 mm (2..63 in) x

110 mm (4..3 in) x 66..8 mm (2..63 in) x

Dimensions (W x H x D)

50 mm (1..956 in), not including the

50 mm (1..956 in), not including the

50 mm (1..956 in), not including the

height of the carrier or the

height of the carrier or the

height of the carrier or the

 

 

mating connectors

mating connectors

mating connectors

 

 

 

 

www.geautomation.com

Automation & Control Systems 1..123

VersaMax Control

Process Automation Control Systems

 

 

 

Discrete Mixed I/O Modules

 

Discrete mixed modules provide maximum flexibility by combining inputs and outputs in a single,

 

compact module.. Discrete input modules receive signals from input devices such as sensors,

 

pushbuttons, and switches that can have two states: on or off, open or closed.. Discrete output modules

 

send control signals to devices such as contactors, indicator lamps, and interposing relays that can also

 

have two states.. Discrete mixed modules provide maximum flexibility by combining inputs and outputs in

 

a single, compact module.. Modules require a carrier base (IC200CHSxxx)..

 

IC200MDD844

IC200MDD845

IC200MDD846

 

 

 

 

 

VersaMax Discrete Mixed

VersaMax Discrete Mixed

VersaMax Discrete Mixed Modules

Product Name

Modules 24 VDC Positive Logic

Modules 24 VDC Positive Logic Input

120 VAC Input 8 points/Outpoints

 

Input 16/Output 24 VDC 0..5 A 16 points

16/Output Relay 2..0A Isolated 8 points

Relay 2..0A Isolated 8 points

 

 

 

 

Lifecycle Status

Active

Active

Active

 

 

 

 

Input Voltage

24 VDC

24 VDC

120 VAC

 

 

 

 

 

24 VDC

0-125 VDC, 5/24/125 VDC nominal;

0-125 VDC, 5/24/125 VDC nominal;

Output Voltage

 

0-265 VAC (47-63 Hz),

0-265 VAC (47-63 Hz),

 

 

120/240 VAC nominal

120/240 VAC nominal

 

 

 

 

Number of Points

16 in/16 out

16 in/8 out

8 in/8 out

 

 

 

 

Channel to Channel Isolation

No

Yes, outputs

Yes, outputs

 

 

 

 

Load Current per Point

0..5 A for 30 VDC

2..0 A for 5-265 VAC, 2..0 A for 5-30 VDC,

2..0 A for 5-265 VAC, 2..0 A for 5-30 VDC,

 

0..2 A for 31-125 VDC

0..2 A for 31-125 VDC

 

 

 

 

 

 

Input and Output Response

0..5 and 0..2 ON / 1..0 OFF

0..5 and 10

1 AC cycle minimum and 2 AC cycle

TimeOn/Off(ms)

(Hz dependent) maximum and 10..0 OFF

 

 

 

 

 

 

Protection

No internal fuses

No internal fuses or snubbers

No internal fuses or snubbers

 

 

 

 

On State Current

2..0-5..5 mA

2..0-5..5 mA

5 mA minimum

 

 

 

 

Off State Current

0-0..5 mA

0-0..5 mA

2..5 mA maximum

 

 

 

 

External Power Supply

18-30 VDC, 24 VDC nominal

0-125 VDC, 5/24/125 VDC nominal;

0-125 VDC, 5/24/125 VDC nominal;

 

0-265 VAC (47-63 Hz), 120/240 VAC nominal

0-265 VAC (47-63 Hz), 120/240 VAC nominal

 

 

 

 

 

 

Input Impedance

10 kOhms maximum

10 kOhms maximum

8..6 kOhms (reactive) at 60 Hz, typical;

 

 

10..32 kOhms (reactive) at 50 Hz, typical

 

 

 

 

 

 

 

 

0..5 Amp at 30 VDC maximum (resistive) 2..0

10 mA per point minimum

10 mA per point minimum

Load Current

Amps maximum for 100ms inrush

2..0 A for 5 to 265 VAC maximum (resistive)

2..0 A for 5 to 265 VAC maximum (resistive)

 

2..0 A for 5 to 30 VDC maximum (resistive)

2..0 A for 5 to 30 VDC maximum (resistive)

 

 

 

 

0..2 A for 31 to 125 VDC maximum (resistive)

0..2 A for 31 to 125 VDC maximum (resistive)

 

 

 

 

5V Backplane Current

70 maximum

270 maximum

300 maximum

Consumption (mA)

 

 

 

 

 

 

 

 

One LED per point shows individual

One LED per point shows individual

One LED per point shows individual

LED Indicators

point on/off state (logic side); OK LED

point on/off state (logic side); OK LED

point on/off state (logic side); OK LED

 

indicates backplane power is present

indicates backplane power is present

indicates backplane power is present

 

 

 

 

 

110 mm (4..3 in) x 66..8 mm (2..63 in) x

110 mm (4..3 in) x 66..8 mm (2..63 in) x

110 mm (4..3 in) x 66..8 mm (2..63 in) x

Dimensions (W x H x D)

50 mm (1..956 in), not including the

50 mm (1..956 in), not including the

50 mm (1..956 in), not including the

height of the carrier or the

height of the carrier or the

height of the carrier or the

 

 

mating connectors

mating connectors

mating connectors

 

 

 

 

1..124 Automation & Control Systems

www.geautomation.com

Process Automation Control Systems

 

VersaMax Control

 

 

 

 

 

Discrete Mixed I/O Modules

 

 

 

Discrete mixed modules provide maximum flexibility by combining inputs and outputs in a single,

 

compact module.. Discrete input modules receive signals from input devices such as sensors,

 

pushbuttons, and switches that can have two states: on or off, open or closed.. Discrete output modules

 

send control signals to devices such as contactors, indicator lamps, and interposing relays that can also

 

have two states.. Discrete mixed modules provide maximum flexibility by combining inputs and outputs in

 

a single, compact module.. Modules require a carrier base (IC200CHSxxx)..

 

IC200MDD847

IC200MDD848

IC200MDD849

 

 

 

 

 

VersaMax Discrete Mixed Modules

VersaMax Discrete Mixed Modules

VersaMax Discrete Mixed Modules

Product Name

240 VAC Input 8 points/Output Relay

120 VAC Input 8 points/Output

120 VAC Input Isolated 8 points/Output

 

2..0A Isolated 8 points

120 VAC 0..5A Isolated 8 points

Relay 2..0 A Isolated 8 points

 

 

 

 

Lifecycle Status

Active

Active

Active

 

 

 

 

Input Voltage

240 VAC

120 VAC

0-132 VAC (47 to 63 Hz), 120 VAC nominal

 

 

 

 

 

0-125 VDC, 5/24/125 VDC nominal;

120 VAC

0-125 VDC, 5/24/125 VDC nominal;

Output Voltage

0-265 VAC (47-63 Hz),

 

0-265 VAC (47-63 Hz),

 

120/240 VAC nominal

 

120/240 VAC nominal

 

 

 

 

Number of Points

8 in/8 out

8 in/8 out

8 in/8 out

 

 

 

 

Channel to Channel Isolation

Yes, outputs

Yes

Yes

 

 

 

 

Load Current per Point

2..0 A for 5-265 VAC, 2..0 A for 5-30 VDC,

10 mA min, 0..5 A max.., 5 A for 1 cycle

2..0 A

0..2 A for 31-125 VDC

(20 ms) max.. inrush

 

 

 

 

 

 

 

Input and Output Response

1 AC cycle minimum and 2 AC cycle

1 cycle/2 cycle and

1 cycle/2 cycle and

TimeOn/Off(ms)

(Hz dependent) maximum and 10..0 OFF

<1/2 cycle/<1/2 cycle

10/10

 

 

 

 

Protection

No internal fuses or snubbers

Snubber and MOVs (each output)

No internal fuses or snubbers

 

 

 

 

On State Current

4 mA minimum

5 mA minimum

5 mA minimum

 

 

 

 

Off State Current

1..5 mA maximum

2..5 mA maximum

2..5 mA maximum

 

 

 

 

External Power Supply

0-125 VDC, 5/24/125 VDC nominal;

0-125 VDC, 5/24/125 VDC nominal;

N/A

0-265 VAC (47-63 Hz), 120/240 VAC nominal

0-265 VAC (47-63 Hz), 120/240 VAC nominal

 

 

 

 

 

 

 

Input Impedance

38..5 kOhms (reactive) at 60 Hz, typical;

8..6 kOhms (reactive) at 60 Hz, typical;

8..6 kOhms (reactive) at 60 Hz, typical;

46..3 kOhms (reactive) at 50 Hz, typical

10..32 kOhms (reactive) at 50 Hz, typical

10..32 kOhms (reactive) at 50 Hz, typical

 

 

 

 

 

 

10 mA per point minimum

10 mA minimum per point,

10 mA per point minimum;

Load Current

2..0 Amps for 5 to 265 VAC maximum (resistive)

0..5 A maximum per point, 5..0 A for

2..0 A for 5-265 VAC maximum (resistive);

2..0 Amps for 5 to 30 VDC maximum (resistive)

one cycle (20 ms) maximum inrush

2..0 A for 5-30 VDC maximum (resistive);

 

 

0..2 Amp for 31 to 125 VDC maximum (resistive)

 

0..2 A for 31-125 VDC maximum (resistive)

 

 

 

 

5V Backplane Current

300 maximum

125 maximum

300 maximum

Consumption (mA)

 

 

 

 

 

 

 

 

One LED per point shows individual point

One LED per point shows individual point

One LED per point shows individual point

LED Indicators

on/off state (logic side); OK LED indicates

on/off state (logic side); OK LED indicates

on/off state (logic side); OK LED indicates

 

backplane power is present

backplane power is present

backplane power is present

 

 

 

 

 

110 mm (4..3 in) x 66..8 mm (2..63 in) x

110 mm (4..3 in) x 66..8 mm (2..63 in) x

110 mm (4..3 in) x 66..8 mm (2..63 in) x

Dimensions (W x H x D)

50 mm (1..956 in), not including the

50 mm (1..956 in), not including the

50 mm 1..956 in), not including the

height of the carrier or the

height of the carrier or the

height of (the carrier or the

 

 

mating connectors

mating connectors

mating connectors

 

 

 

 

www.geautomation.com

Automation & Control Systems 1..125

GE Digital IC200MDD840, IC200MDD842, IC200MDD843, IC200MDD844, IC200MDD845 Data sheet

VersaMax Control

Process Automation Control Systems

 

 

 

Discrete Mixed I/O Modules

 

Discrete mixed modules provide maximum flexibility by combining inputs and outputs in a single,

 

compact module.. Discrete input modules receive signals from input devices such as sensors,

 

pushbuttons, and switches that can have two states: on or off, open or closed.. Discrete output modules

 

send control signals to devices such as contactors, indicator lamps, and interposing relays that can also

 

have two states.. Discrete mixed modules provide maximum flexibility by combining inputs and outputs in

 

a single, compact module.. Modules require a carrier base (IC200CHSxxx)..

 

IC200MDD850

IC200MDD851

 

 

 

 

VersaMax Discrete Mixed Modules

VersaMax Discrete Mixed Modules

Product Name

240 VAC Input Isolated 4 points/Output

5/12 VDC Input 16 points/Output

 

Relay 2..0 A Isolated 8 points

12/24 VDC 16 points

 

 

 

Lifecycle Status

Active

Active

 

 

 

Input Voltage

0-264 VAC (47-63 Hz), 240 VAC nominal

0 to 15 VDC, +5/12 VDC nominal

 

 

 

 

0-125 VDC, 5/24/125 VDC nominal;

+10..2 to +30 VDC, +12/24 VDC nominal

Output Voltage

0-265 VAC (47-63 Hz),

 

 

120/240 VAC nominal

 

 

 

 

Number of Points

8 out/4 in

16 out/16 in

 

 

 

Channel to Channel Isolation

Yes

No

 

 

 

Load Current per Point

2..0 A

0..5 Amps at 30 VDC maximum (resistive)

 

2..0 Amps maximum for 100ms inrush

 

 

 

 

 

Input and Output Response

1 cycle/2 cycle

0..25ms maximum/0..2ms ON

TimeOn/Off(ms)

and 10/10

and 1..0ms OFF maximum

 

 

 

Protection

No internal fuses or snubbers

No internal fuses or snubbers

 

 

 

On State Current

4 mA minimum

1..45 mA minimum

 

 

 

Off State Current

1..5 mA maximum

0 to 0..7 mA maximum

 

 

 

External Power Supply

N/A

+10..2 to +30 VDC, +12/24 VDC nominal

Input Impedance

Load Current

38..5 kOhms (reactive) at 60 Hz, typical;

2..4kOhms typical @ 12 VDC

46..3 kOhms (reactive) at 50 Hz, typical

 

10 mA per point minimum;

0..5 Amps at 30 VDC maximum (resistive);

2..0 A for 5-265 VAC maximum (resistive);

2..0 Amps maximum for 100ms inrush

2..0 A for 5-30 VDC maximum (resistive);

 

0..2 A for 31-125 VDC maximum (resistive)

 

5V Backplane Current

260 maximum

115 maximum

Consumption (mA)

 

 

 

 

 

 

One LED per point shows individual point

One LED per point shows individual point

LED Indicators

on/off state logic side); OK LED indicates

on/off state (logic side); OK LED indicates

 

backplane power is present

backplane power is present

 

 

 

 

110 mm (4..3 in) x 66..8 mm (2..63 in) x

110 mm (4..3 in) x 66..8 mm (2..63 in) x

Dimensions (W x H x D)

50 mm (1..956 in), not including the

50 mm (1..956 in), not including the

height of the carrier or the

height of the carrier or the

 

 

mating connectors

mating connectors

 

 

 

1..126 Automation & Control Systems

www.geautomation.com

Process Automation Control Systems

VersaMax Control

 

 

Discrete Input Modules

Discrete input modules receive signals from input devices such as sensors, pushbuttons, and switches that can have two states: on or off, open or closed.. Modules require a carrier base (IC200CHSxxx)..

 

IC200MDL140

IC200MDL141

IC200MDL143

 

 

 

 

 

VersaMax Discrete Input

VersaMax Discrete Input

VersaMax Discrete Input

Product Name

Module 120 VAC,

Module 240 VAC,

Module 120 VAC Isolated,

 

8 points

8 points

8 points

 

 

 

 

Lifecycle Status

Active

Active

Active

 

 

 

 

Input Voltage

0-132 VAC

0-264 VAC

0-132 VAC

 

 

 

 

Number of Points

8

8

8

 

 

 

 

Channel to Channel Isolation

No

No

Yes

 

 

 

 

Input and Output Response

1 cycle/2 cycles

1 cycle/2 cycles

1 cycle/2 cycles

TimeOn/Off (ms)

 

 

 

 

 

 

 

Points per Common

1 group of 8

1 group of 8

8 groups of 1

 

 

 

 

On State Current

5 mA minimum

7 mA minimum

5 mA minimum

 

 

 

 

Off State Current

2..5 mA maximum

1..5 mA maximum

2..5 mA maximum

 

 

 

 

Input Impedance

8..6 kOhms (reactive) at 60 Hz, typical;

38..5 kOhms (reactive) at 60 Hz, typical;

8..6 kOhms (reactive) at 60 Hz, typical;

10..32 kOhms (reactive) at 50 Hz, typical

46..3 kOhms (reactive) at 50 Hz, typical

10..32 kOhms (reactive) at 50 Hz, typical

 

 

 

 

 

5V Backplane Current

55 maximum

55 maximum

50 maximum

Consumption (mA)

 

 

 

 

 

 

 

 

One LED per point shows

One LED per point shows

One LED per point shows

LED Indicators

individual point ON/OFF status..

individual point ON/OFF status..

individual point ON/OFF status..

OK LED indicates backplane

OK LED indicates backplane

OK LED indicates backplane

 

 

power is present

power is present

power is present

 

 

 

 

 

110 mm (4..3 in) x 66..8 mm (2..63 in) x

110 mm (4..3 in) x 66..8 mm (2..63 in) x

110 mm (4..3 in) x 66..8 mm (2..63 in) x

Dimensions (W x H x D)

50 mm (1..956 in), not including the

50 mm (1..956 in), not including the

50 mm (1..956 in), not including the

height of the carrier or the

height of the carrier or the

height of the carrier or the

 

 

mating connectors

mating connectors

mating connectors

 

 

 

 

www.geautomation.com

Automation & Control Systems 1..127

VersaMax Control

Process Automation Control Systems

 

 

Discrete Input Modules

Discrete input modules receive signals from input devices such as sensors, pushbuttons, and switches that can have two states: on or off, open or closed.. Modules require a carrier base (IC200CHSxxx)..

 

IC200MDL144

IC200MDL240

IC200MDL241

 

 

 

 

 

VersaMax Discrete Input

VersaMax Discrete Input

VersaMax Discrete Input

Product Name

Module 240 VAC Isolated,

Module, 120 VAC Positive Logic,

Module, 240 VAC Positive Logic,

 

4 points

16 points

16 points

 

 

 

 

Lifecycle Status

Active

Active

Active

 

 

 

 

Input Voltage

0-264 VAC

0-132 VAC

0-264 VAC

 

 

 

 

Number of Points

4

16

16

 

 

 

 

Channel to Channel Isolation

Yes

No

No

 

 

 

 

Input and Output Response

1 cycle/2 cycles

1 cycle/2 cycles

1 cycle/2 cycles

TimeOn/Off (ms)

 

 

 

 

 

 

 

Points per Common

4 groups of 1

2 groups of 8

2 groups of 8

 

 

 

 

On State Current

7 mA minimum

5 mA minimum

4 mA minimum

 

 

 

 

Off State Current

3 mA maximum

2..5 mA maximum

1..5 mA maximum

 

 

 

 

Input Impedance

38..5 kOhms (reactive) at 60 Hz, typical;

8..6 kOhms (reactive) at 60 Hz, typical;

38..5 kOhms (reactive) at 60 Hz, typical;

46..3 kOhms (reactive) at 50 Hz, typical

10..32 kOhms (reactive) at 50 Hz, typical

46..3 kOhms (reactive) at 50 Hz, typical

 

 

 

 

 

5V Backplane Current

30 maximum

110 maximum

110 maximum

Consumption (mA)

 

 

 

 

 

 

 

 

One LED per point shows

One LED per point shows

One LED per point shows

LED Indicators

individual point ON/OFF status..

individual point ON/OFF status..

individual point ON/OFF status..

OK LED indicates backplane

OK LED indicates backplane

OK LED indicates backplane

 

 

power is present

power is present

power is present

 

 

 

 

 

110 mm (4..3 in) x 66..8 mm (2..63 in) x

110 mm (4..3 in) x 66..8 mm (2..63 in) x

110 mm (4..3 in) x 66..8 mm (2..63 in) x

Dimensions (W x H x D)

50 mm (1..956 in), not including the

50 mm (1..956 in), not including the

50 mm (1..956 in), not including the

height of the carrier or the

height of the carrier or the

height of the carrier or the

 

 

mating connectors

mating connectors

mating connectors

 

 

 

 

1..128 Automation & Control Systems

www.geautomation.com

Loading...