DPSB620ECC/WW
Side View
Rear View
36
42
Side View
Rear View
*24-1/2" from the edge of the side panel to the front.
25-1/2" from front to edge of endcaps.
51
42
36
27
28-1/4
25-1/2*
23-1/2*
8-1/2
2-1/2
2
11-1/2
27
3-1/2
GE Profile™ Super 7.0 Cu. Ft. Capacity Electric Dryer
Dimensions and Installation Information (in inches)
Exhaust Options:
4-way via rear, right, left and bottom.
NEMA Receptable codes:
3-prong dryer cord/30A/4' long (cat #WX9X2)
is for NEMA 10-30R receptable
4-prong dryer cord/30A/4' long (cat #WX9X18)
is for NEMA 14-30R receptacle
Circuit Requirements:
An individual, properly-grounded branch
circuit, protected by a 30-ammp circuit
breaker or a time-delay fuse, is required.
Electric Dryer Rating:
240V, 5600W, 24A, 60Hz
208V, 4400W, 22A, 60Hz
Note:
Dryer wall outlet must be located within 36"
of service cord entry and accessible when
dryer is mounted in position.
Installation Information:
For complete information, see installation
instructions packed with your dryer.
For answers to your Monogram,® GE Profile™ or
GE® appliance questions, visit our website at
ge.com or call GE Answer Center® service,
800.626.2000.
Specification Revised 10/07
Listed by
Underwriters
Laboratories
270181
DPSB620ECC/WW
GE Profile™ Super 7.0 Cu. Ft. Capacity Electric Dryer
For complete information, see installation instructions packed with your dryer.
Ducting Materials:
For best performance, this dryer should be vented with 4" diameter all rigid metal
exhaust duct. If “all rigid metal” duct cannot be used, then “flexible all metal” venting
can be used, but it will reduce the maximum recommended duct length.
Exhaust Length Calculation:
1. Determine the number of 90° turns needed for your installation. If you exhaust to the
side or bottom of dryer, add one turn.
2. The maximum length of 4" rigid (aluminum or galvanized) duct which can be tolerated
is shown in the table. The maximum length for flexible ducts are less than for rigid
duct. A turn of 45° or less may be ignored. Two 45° turns within the duct length should
be treated as a 90° elbow. A turn over 45° should be treated as a 90° elbow.
Exhausting the dryer to the outside is strongly recommended to prevent large
amounts of moisture and lint from being blown into the room. Gas dryers or any dryer
located in a closet must be exhausted to the outside.
Caution: For personal safety do not terminate exhaust into a chimney, under any
enclosed house floor (crawl space), or into an attic, since the accumulated lint could
create a fire hazard or moisture could cause damage. Never terminate the exhaust
into a common duct or plenum with a kitchen exhaust, since the combination of lint
and grease could create a fire hazard.
Exhaust ducts should be terminated in a dampered wall cap to prevent back drafts,
bird nesting, etc. The wall cap must also be located at least 12" above the ground or
any other obstruction with the opening pointed down.
Other terminations, such as louvered wall boxes, are acceptable provided they are
equivalent to a 4" opening dampered wall cap.
Dryer Elbow Kit, Pub. No. 14-A003 is available at additional cost. For use with side or
bottom exhaust options.
For more information on venting kits and accessories, please call 1-800-GE-CARES.
Special Installation Requirements
Alcove or Closet Installation:
• If your dryer is approved for installation in an alcove or closet, it will be stated on a label
on the dryer back.
• The dryer MUST be exhausted to the outside.
• Minimum clearances between dryer cabinet and adjacent walls or other surfaces are:
0" either side; 3" front and rear
• Minimum vertical space from floor to overhead cabinets, ceilings, etc. is 52”.
• Closet doors must be louvered or otherwise ventilated and must contain a minimum
of 60 sq. in. of open area equally distributed. If this closet contains both a washer and
a dryer, doors must contain a minimum of 120 sq. in. of open area equally distributed.
• No other fuel-burning appliance shall be installed in the same closet with a gas dryer.
Bathroom or Bedroom Installation:
• The dryer MUST be exhausted to the outdoors.
• The installation must conform with the local codes, or in the absence of local codes,
with the National Fuel Gas Code, ANSI Z223.
Minimum Clearances other than Alcove or Closet Installation:
• Minimum clearances to combustible surfaces are: 0" both sides; 3" rear
Dryer Exhausting Information: Use metal duct only, vertical and horizontal ducting.
Specification Revised 10/07
270181