GE DPSB620ECCC, DPSB620ECWW Installation Instructions Manual

Page 1
Installation Instructions
Electric Dryer
37
BEFORE YOU BEGIN
TOOLS YOU
WILL NEED
MATERIALS YOU WILL NEED
WARNING
Read these instructions completely and carefully.
PHILLIPS SCREWDRIVER
SLIP JOINT PLIERS
LEVEL
GLOVES
SAFETY GLASSES
DRYER POWER
CORD KIT
(NOT PROVIDED
WITH DRYER)
UL RATED 120/240V, 30A WITH 3 OR 4 PRONGS. IDENTIFY THE PLUG TYPE AS PER THE HOUSE RECEPTACLE BEFORE PURCHASING LINE CORD.
4" DUCT CLAMPS (2) OR 4" SPRING CLAMPS (2)
EXHAUST HOOD
3/4" STRAIN RELIEF UL RECOGNIZED
• Use only rigid metal or flexible metal 4-in. diameter ductwork for exhausting to the outdoors. Never use plastic or other combustible, easy-to-puncture ductwork.
• This appliance must be properly grounded and installed as described in these instructions.
• Do not install or store appliance in an area where it will be exposed to water and/or weather
• Install the dryer where the temperature is above 50ºF for satisfactory operation of the dryer control system.
4" DIA. METAL
ELBOW
IMPORTANT - Save these
instructions for local inspector’s use.
IMPORTANT - Observe all
governing codes and ordinances.
• Note to Installer - Be sure to leave these instructions with the customer.
• Note to Customer - Keep these instructions with your Use and Care Book for future reference.
Exhausting the dryer to the outdoors is strongly recom­ mended to prevent large amounts of moisture from being blown into the room.
Before the old dryer is removed from service or discarded, remove the dryer door.
Service information and the wiring diagram are located in the control console.
Do not allow children on or in the appliance. Close supervision of children is necessary when the appliance is used near children.
NOTE: Installation and service of this dryer requires basic mechanical and electrical skills. It is your responsibility to contact a qualified installer to make the electrical connections.
Step 1 Prepare the Area and Exhaust for Installation of
New Dryer (see section 1).
Step 2 Check and Ensure the Existing External Exhaust is
Clean (see section 1) and Meets Attached Installation
Specifications (see section 3). Step 3 Remove the Foam Shipping Pads (see section 1). Step 4 Move the Dryer to the Desired Location. Step 5 Connect the Power Supply (see section 2). Step 6 Connect the External Exhaust (see section 4). Step 7 Level Your Dryer (see section 5).
Step 8 Check the Operation of the Power Supply
and Venting.
Step 9 Place the Owners Manual and the Installation
Instructions in a Location Where They Will Be Noticed By the Owner.
For Alcove or Closet Installation, see section 6. For Bathroom or Bedroom Installation, see section 7. For Mobile or Manufactured Home see, section 8. For side or bottom exhaust, see section 9.
Questions on Installation? Call: 1-800-GECARES (US)
or Visit our Web site at:
www.GEAppliances.com (US)
4" DIA. METAL DUCT
(RECOMMENDED)
4" DIA. FLEXIBLE METAL DUCT
(IF NEEDED)
FLAT BLADE SCREWDRIVER
DUCT TAPE
49
Page 2
Installation Instructions
Minimum Clearance Other Than Alcove or Closet Installation
Minimum clearance to combustible surfaces and for air opening are: 0 in. clearance both sides and 1 in. rear. Consideration must be given to provide adequate clearance for installation and service.
1 PREPARING FOR INSTALLATION OF NEW DRYER
EXTERNAL DUCT OPENING
DUCT TAPE OR DUCT CLAMP
4" METAL DUCT
DUCT TAPE OR DUCT CLAMP
TIP: Install your dryer before installing your washer. This will allow better access when installing dryer exhaust.
REMOVING LINT FROM WALL EXHAUST OPENING
2 ELECTRICAL CONNECTION INFORMATION
WARNING - TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK AND PERSONAL INJURY:
• DO NOT USE AN EXTENSION CORD OR AN ADAPTER PLUG WITH THIS APPLIANCE.
Dryer must be electrically grounded in accordance with local codes and ordinances, or in the absence of local codes, in accordance with the NATIONAL ELECTRI­CAL CODE, ANSI/NFPA NO. 70.
ELECTRICAL REQUIREMENTS
This dryer must be connected to an individual branch circuit, protected by the required time-delay fuses or circuit breakers. A four or three-wire, single phase, 120/240V or 120/208V, 60Hz, 30 amp circuit is required.
If the electric supply does not meet the above specifications, then call a licensed electrician.
GROUNDING INSTRUCTIONS
This dryer must be connected to a grounded metal, permanent wiring system, or an equipment-grounding conductor must be run with the circuit conductors and connected to the equipment­grounding terminal on the appliance.
WALL
INTERNAL DUCT OPENING
TILT THE DRYER SIDEWAYS AND REMOVE THE FOAM SHIPPING PADS BY PULLING AT THE SIDES AND BREAKING THEM AWAY FROM THE DRYER LEGS. BE SURE TO REMOVE ALL OF THE FOAM PIECES AROUND THE LEGS.
CHECK THAT EXHAUST HOOD DAMPER OPENS AND CLOSES FREELY.
CONNECTING DRYER USING 4-WIRE CONNECTION (MUST BE USED FOR MOBILE HOME INSTALLATION)
NOTE: Since January 1, 1996, the National Electric Code requires that new constructions utilize a 4 wire connection to an electric dryer.
REMOVE GROUND STRAP AND DISCARD. KEEP GREEN GROUND SCREW
SCREWS (3)
COVER
2
HOT
RELOCATE GREEN
WIRE
GROUND SCREW
L1
N
L2
NEUTRAL (White)
4 #10 AWG MINIMUM COPPER CONDUCTORS OR 120/240V 30A POWER SUPPLY CORD KIT MARKED FOR USE WITH DRYERS & PROVIDED WITH CLOSED LOOP OR SPADE TERMINALS WITH UPTURNED ENDS (NOT SUPPLIED).
HERE
HOT WIRE
3/4", UL RECOGNIZED STRAIN RELIEF
GREEN OR YELLOW WIRE
STRAIN RELIEF BRACKET
Page 3
3
Installation Instructions
1. Turn off the circuit breaker (s) (30 amp) or remove the dryer’s circuit fuse at the electrical box.
2. Be sure the dryer cord is unplugged from the wall.
3. Remove the power cord cover located at the lower back.
4. Install 3/4 in. UL recognized strain relief to power cord entry hole. Bring power cord through strain relief.
5. Connect power cord as follows: A. Connect the 2 hot lines to the outer screws of the
terminal block (marked L1 and L2).
B. Connect the neutral (white) line to the center of
the terminal block (marked N).
6. Be sure ground strap is connected to neutral (center)
terminal of block and to green ground screw on cabinet rear. Tighten all terminal block screws (3) completely.
7. Properly secure power cord to strain relief.
8. Reinstall the cover.
CONNECTING DRYER USING 3-WIRE CONNECTION
L1
L2
STRAIN RELIEF BRACKET
3/4", UL RECOGNIZED STRAIN RELIEF
HOT WIRE
HOT WIRE
GROUND STRAP
GREEN GROUND SCREW
NEUTRAL (White)
SCREWS (3)
IF REQUIRED, BY LOCAL CODE, INSTALL EXTERNAL GROUND (NOT PROVIDED) TO GROUNDED METAL, COLD WATER PIPE, OR OTHER ESTABLISHED GROUND DETERMINED BY A QUALIFIED ELECTRICIAN.
COVER
3 #10 AWG MINIMUM COPPER CONDUCTORS OR 120/240V 30A POWER SUPPLY CORD KIT MARKED FOR USE WITH DRYERS & PROVIDED WITH CLOSED LOOP OR SPADE TERMINALS WITH UPTURNED ENDS (NOT SUPPLIED).
1. Turn off the circuit breaker (s) (30 amp) or remove the dryer’s circuit fuse at the electrical box.
2. Be sure the dryer cord is unplugged from the wall receptacle.
3. Remove the power cord cover located at the lower back.
4. Remove and discard ground strap. Keep the green ground screw for step 7.
5. Install 3/4 in. UL recognized strain relief to power cord entry hole. Bring power cord through strain relief.
6. Connect power cord as follows: A. Connect the 2 hot lines to the outer screws of the terminal block (marked L1 and L2). B. Connect the neutral (white) line to the center of
the terminal block (marked N).
7. Attach ground wire of power cord with the green ground
screw (hole above strain relief bracket). Tighten all terminal block screws (3) completely.
8. Properly secure power cord to strain relief.
9. Reinstall the cover.
WARNING: NEVER LEAVE THE
COVER OFF OF THE TERMINAL BLOCK.
WARNING: NEVER LEAVE THE
COVER OFF OF THE TERMINAL BLOCK.
3 EXHAUST INFORMATION
WARNING - USE ONLY METAL 4-IN. DUCT. DO NOT USE DUCT LONGER THAN SPECIFIED IN THE EXHAUST LENGTH TABLE.
Using exhaust longer than specified length will:
• Increase the drying times and the energy cost.
• Reduce the dryer life.
• Accumulate lint, creating a potential fire hazard.
The MAXIMUM ALLOWABLE length of the exhaust system depends upon the type of duct, number of turns, the type of exhaust hood (wall cap), and all conditions noted below. Both rigid and flexible metal duct are shown in the table below.
The correct exhaust installation is YOUR RESPONSIBILITY. Problems due to incorrect installation are not covered by the warranty.
EXHAUST SYSTEM CHECK LIST
EXHAUST LENGTH
4" DIA.
4"
4" DIA.
4" DIA.
2-1/2"
RECOMMENDED MAXIMUM LENGTH
Exhaust Hood Types
Recommended
No. of 90º
Elbows
Flexible
Metal
Rigid
Metal
Rigid
Metal
90 Feet 60 Feet 45 Feet 35 Feet 25 Feet
0 1 2 3 4
55 Feet 40 Feet 30 Feet 20 Feet 15 Feet
60 Feet 45 Feet 35 Feet 25 Feet 15 Feet
45 Feet 30 Feet 20 Feet 15 Feet 10 Feet
Flexible
Metal
Use only for short
run installations
HOOD OR WALL CAP
• Terminate in a manner to prevent back drafts or entry of birds or other wildlife.
• Termination should present minimal resistance to the exhaust air flow and should require little or no maintenance to prevent clogging.
Never install a screen in or over the exhaust duct.
This could cause lint build up.
• Wall caps must be installed at least 12 in. above ground level or any other obstruction with the opening pointed down.
• If roof vents or louvered plenums are used, they must be equivalent to a 4-in. dampened wall cap in regard to resistance to air flow, prevention of back drafts, and maintenance required to prevent clogging.
SEPARATION OF TURNS
For best performance, separate all turns by at least 4 ft. of straight duct, including distance between last turn and exhaust hood.
TURNS OTHER THAN 90º
• One turn of 45º or less may be ignored.
• Two 45º turns should be treated as one 90º turn.
• Each turn over 45º should be treated as one 90º turn.
SEALING OF JOINTS
• All joints should be tight to avoid leaks. The male end of each section of duct must point away from the dryer.
• Do not assemble the ductwork with fasteners that extend into the duct. They will serve as a collection point for lint.
• Duct joints can be made air and moisture-tight by wrapping the overlapped joints with duct tape.
• Horizontal runs should slope down toward the outdoors 1/2 inch per foot
INSULATION
Duct work that runs through an unheated area or is near air conditioning should be insulated to reduce condensation and lint build-up.
If using flexible metal duct, please refer to page 5.
EXHAUST LENGTH
RECOMMENDED MAXIMUM LENGTH
Recommended
4" DIA.
4"
No. of 90º
Elbows
0 1 2 3
4 5
If using flexible metal duct, please refer to page 5.
Rigid
Metal 150 Feet 135 Feet 125 Feet 115 Feet 105 Feet
95 Feet
Exhaust Hood Types
Use only for short
run installations
4" DIA.
4" DIA.
Flexible
Metal 55 Feet 52 Feet 49 Feet 46 Feet 43 Feet 40 Feet
Rigid
Metal 125 Feet 115 Feet 105 Feet
95 Feet 85 Feet 75 Feet
2-1/2"
Flexible
Metal 45 Feet 42 Feet
39 Feet 36 Feet
33 Feet 30 Feet
Page 4
Installation Instructions
4 EXHAUST CONNECTION
WARNING - TO REDUCE THE RISK OF FIRE OR PERSONAL INJURY:
Exhausting the dryer to the outdoors is strongly recom-
mended to prevent large amounts of moisture from being blown into the room.
• Use only metal duct.
• Do not terminate exhaust in a chimney, any gas vent, under an enclosed floor (crawl space), or into an attic. The accumulated lint could create a fire hazard.
• Provide an access for inspection and cleaning of the exhaust system, especially at turns. Inspect and clean at least once a year.
• Never terminate the exhaust into a common duct with a kitchen exhaust. A combination of lint and grease could create a fire hazard.
• Do not obstruct incoming or exhausted air.
THIS DRYER COMES READY FOR REAR EXHAUSTING. IF SPACE IS LIMITED, USE THE INSTRUCTIONS IN SECTION 9 TO EXHAUST DIRECTLY FROM THE SIDES OR BOTTOM OF THE CABINET.
STANDARD REAR EXHAUST
(Vented above floor level)
ELBOW HIGHLY RECOMMENDED
RECOMMENDED CONFIGURATION TO MINIMIZE EXHAUST BLOCKAGE.
ELBOW HIGHLY RECOMMENDED
NOTE: ELBOWS WILL PREVENT DUCT KINKING AND COLLAPSING.
STANDARD REAR EXHAUST
(Vented at floor level)
FOR STRAIGHT LINE INSTALLATION, CONNECT THE DRYER EXHAUST TO THE EXTERNAL EXHAUST HOOD USING DUCT TAPE OR CLAMP.
5 LEVELING AND STABILIZING YOUR DRYER
STAND THE DRYER UPRIGHT NEAR THE FINAL LOCATION AND ADJUST THE 4 LEVELING LEGS, AT THE CORNERS, TO ENSURE THAT THE DRYER IS LEVEL FROM SIDE TO SIDE AND FRONT TO REAR.
LEVEL FRONT-TO-BACK.
LEVEL SIDE-TO-SIDE.
(CORD NOT SUPPLIED
CUT THE METAL EXHAUST DUCT (NOT SUPPLIED) TO THE PROPER LENGTH.
NOTE: WE STRONGLY RECOMMEND SOLID METAL EXHAUST DUCTING. HOWEVER, IF FLEXIBLE DUCTING IS USED IT MUST BE METAL NOT PLASTIC.
WITH DRYER)
4 LEVELING LEGS
4
Page 5
5
Installation Instructions, Indoor Exhausting
6
ALCOVE OR CLOSET INSTALLATION
7
BATHROOM OR BEDROOM
INSTALLATION
8
MOBILE OR MANUFACTURED
HOME INSTALLATION
If rigid all-metal duct cannot be used, then flexible all-metal ducting can be used, but it will reduce the maximum recommended duct length. In special installations when it is impossible to use only metal ducting, then UL-listed clothes dryer flexible metal transition duct may be used as transition venting between the dryer and wall connection only. The use of this ducting will affect dry time.
If flexible transition duct is necessary, the following directions must be followed.
• Use the Shortest Length Possible.
• Stretch the Duct to Its Maximum Length to avoid kinks.
• Do Not Crush or Collapse the Duct.
• Never Use Transition Duct Inside the Wall or Inside the Dryer.
• Avoid Resting the Duct on Sharp Objects.
Venting Must Conform to Local Building Codes.
USING FLEXIBLE METAL DUCTS
• If your dryer is approved for installation in an alcove or closet, it will be stated on a label on the dryer back.
• The dryer MUST be vented to the outdoors. See the EXHAUST INFORMATION sections 3 & 4.
• Minimum clearance between dryer cabinet and adjacent walls or other surfaces is:
0 in. either side 3 in. front and rear
• Minimum vertical space from floor to overhead cabinets, ceiling, etc. is 52 in.
• Closet doors must be louvered or otherwise ventilated and must contain a minimum of 60 sq. in. of open area equally distributed. If the closet contains both a washer and a dryer, doors must contain a minimum of 120 sq. in. of open area equally distributed.
OTHER INSTALLATIONS: If the installation makes it impossible to exhaust to the outdoors, a 4" exhaust deflector (WE25X278) must be installed. A clearance of 8" is required between the rear of the dryer and the wall, and the deflector should be pointing up.
• Installation must conform to the MANUFACTURED HOME CONSTRUCTION & SAFETY STANDARD, TITLE 24, PART 32-80 or, when such standard is not applicable, with AMERICAN NATIONAL STANDARD FOR MOBILE HOME, ANSI/NFPA NO. 501B.
• The dryer MUST be vented to the outdoors with the termination securely fastened to the mobile home structure. (See EXHAUST INFORMATION section 3 & 4.)
• The vent MUST NOT be terminated beneath a mobile or manufactured home.
• The vent duct material MUST BE METAL.
• Do not use sheet metal screws or other fastening devices which extend into the interior of the exhaust vent.
• See section 2 for electrical connection information.
INDOOR EXHAUSTING
NOTE: MOBILE HOME, BEDROOM, BATHROOM, ALCOVE OR CLOSET INSTALLATIONS MUST BE EXHAUSTED TO THE OUTDOORS
NOTE: EXHAUSTING TO THE OUTDOORS IS STRONGLY RECOMMENDED, EXHAUSTING INDOORS MAY CAUSE LINT ACCUMULATION, AND MOISTURE DAMAGE INCLUDING MOLD AND MILDEW.
ELBOWS HIGHLY RECOMMENDED
ELBOW HIGHLY RECOMMENDED
DO NOT SIT DRYER ON FLEXIBLE EXHAUST.
DO NOT USE EXCESSIVE EXHAUST LENGTH
DO NOT CRUSH FLEXIBLE EXHAUST AGAINST WALL.
DO
DON’T
• The dryer MUST be vented to the outdoors. See EXHAUST INFORMATION section 3 & 4.
• The installation must conform with local codes or, in the absence of local codes, with the NATIONAL ELECTRI- CAL CODE, ANSI/NFPA NO. 70.
DO
DO
ELBOW HIGHLY RECOMMENDED
ELBOWS HIGHLY RECOMMENDED
Page 6
Page 7
Installation Instructions
PLATE (KIT WE1M454)
500A187P049
(
)
ADDING ELBOW FOR EXHAUST THROUGH BOTTOM OF CABINET
• Insert the elbow through the rear opening and connect it to the dryer internal duct.
• Apply duct tape on the joint between the dryer internal duct and elbow, as shown on page 6.
CAUTION: Internal duct joints must be secured with tape, otherwise they may separate and cause a safety hazard.
ADDING COVER PLATE TO REAR OF CABINET (SIDES AND BOTTOM EXHAUST)
10 CHANGING DIRECTION OF DOOR OPENING
1. Open the door and remove the filler plugs opposite the hinges. With the door completely open, remove the bottom screws from each hinge on the dryer face. Insert these screws about half way into the TOP holes, for each hinge on the opposite side (where you removed the filler plugs). Apply firm pressure to get the screw started.
2. Loosen the top screws from each hinge on the dryer face half way. With one hand holding the top of the door and the other hand holding the bottom, remove the door from the dryer by lifting it UP and OUT.
3. Rotate the door 180º. Insert the door on the opposite side of the opening by moving the door IN and DOWN until the top hinge and the bottom hinge are resting on the top screws inserted in step 1.
4. Remove the remaining screws from the side of the opening from which the door was removed. With these screws secure each hinge at the bottom. Tighten the two top screws on each hinge. Reinsert the plastic plugs on the side from which the door was removed.
REMOVE THE BOTTOM SCREW FROM EACH HINGE ON THE DRYER FACE.
LOOSEN THE TOP SCREWS FROM EACH HINGE ON THE DRYER FACE HALF WAY.
PLATE (KIT WE1M454)
Connect standard metal elbows and ducts to complete the exhaust system. Cover back opening with a plate (Kit WE1M454) available from your local service provider. Place dryer in final location.
PLATE
KIT WE1M454
WARNING - NEVER LEAVE THE BACK OPENING WITHOUT THE PLATE. (Kit WE1M454)
TO REGISTER YOUR DRYER
CALL TOLL-FREE
1-888-269-1192
Prompt registration confirms your right to protection under the
terms of your warranty.
www.GEAppliances.com (US)
For Questions on Installation, Call: 1-800-626-2003 (US)
500A187P037 2-01 ON Pub # 31-15475
Pub. # 31-16109
MOVE THE DOOR IN AND DOWN UNTIL THE TOP HINGE
AND THE BOTTOM HINGE ARE RESTING ON THE TOP SCREWS INSERTED IN STEP 1.
SECURE EACH HINGE AT THE BOTTOM AND TIGHTEN THE TWO TOP SCREWS OF EACH HINGE.
11 SERVICING
WARNING - LABEL ALL WIRES PRIOR TO DISCONNECTING WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION AFTER SERVICING/INSTALLATION.
For servicing phone numbers for replacement parts, and other information, refer to Owner’s Manual or visit our Web site.
7
Page 8
Notes
Loading...