This addendum contains information that relates to the D30 Line Distance Protection System, version 6.0x. This addendum lists a number of information items that appear in the instruction manual GEK-113599 (revision X1) but are not
included in the current D30 operations.
The following functions and items are not yet available with the current version of the D30 relay:
• Signal sources SRC 3 to SRC 6.
Version 4.0x and higher releases of the D30 relay includes new hardware (CPU and CT/VT modules).
• The new CPU modules are specified with the following order codes: 9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R, and 9S.
• The new CT/VT modules are specified with the following order codes: 8F, 8G 8L, 8M.
The following table maps the relationship between the old CPU and CT/VT modules to the newer versions:
MODULEOLDNEWDESCRIPTION
CPU9A9ERS485 and RS485 (Modbus RTU, DNP)
9C9GRS485 and 10Base-F (Ethernet, Modbus TCP/IP, DNP)
9D9HRS485 and redundant 10Base-F (Ethernet, Modbus TCP/IP, DNP)
---9JRS485 and multi-mode ST 100Base-FX
---9KRS485 and multi-mode ST redundant 100Base-FX
---9LRS485 and single mode SC 100Base-FX
---9MRS485 and single mode SC redundant 100Base-FX
---9NRS485 and 10/100Base-T
---9PRS485 and single mode ST 100Base-FX
---9RRS485 and single mode ST redundant 100Base-FX
---9SRS485 and six-port managed Ethernet switch
CT/VT8A8FStandard 4CT/4VT
8B8GSensitive ground 4CT/4VT
--8LStandard 4CT/4VT with enhanced diagnostics
--8MSensitive ground 4CT/4VT with enhanced diagnostics
The new CT/VT modules can only be used with the new CPUs (9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R, and 9S), and
the old CT/VT modules can only be used with the old CPU modules (9A, 9C, 9D). To prevent any hardware mismatches, the new CPU and CT/VT modules have blue labels and a warning sticker stating “Attn.: Ensure CPU andDSP module label colors are the same!”. In the event that there is a mismatch between the CPU and CT/VT module,
the relay will not function and a
All other input/output modules are compatible with the new hardware.
With respect to the firmware, firmware versions 4.0x and higher are only compatible with the new CPU and CT/VT modules. Previous versions of the firmware (3.4x and earlier) are only compatible with the older CPU and CT/VT modules.
DSP ERROR or HARDWARE MISMATCH error will be displayed.
Page 4
Page 5
Table of Contents
TABLE OF CONTENTS
1. GETTING STARTED1.1 IMPORTANT PROCEDURES
1.1.1CAUTIONS AND WARNINGS ........................................................................... 1-1
D30E00HCHF8AH6AM6BP8BX7A
000
837772A3
GEK-113269
MAZB98000029
D
2005/01/05
Control Power:
Contact Inputs:
Contact Outputs:
88-300V DC @ 35W / 77-265V AC @ 35VA
300V DC Max 10mA
Standard Pilot Duty / 250V AC 7.5A
360V A Resistive / 125V DC Break
4A @ L/R = 40mS / 300W
RATINGS:
D30
GE Multilin
Made in
Canada
- M A A B 9 7 0 0 0 0 9 9 -
Line Distance Relay
837805A1.CDR
NOTE
1 GETTING STARTED 1.1IMPORTANT PROCEDURES
Please read this chapter to help guide you through the initial setup of your new GE Mutilin structured template.
1.1.1 CAUTIONS AND WARNINGS
Before attempting to install or use the relay, it is imperative that all NOTE, CAUTION and WARNING icons in this document
are reviewed to help prevent personal injury, equipment damage, or downtime.
1.1.2 INSPECTION CHECKLIST
1.Open the relay packaging and inspect the unit for physical damage.
2.View the rear nameplate and verify that the correct model has been ordered.
1
Figure 1–1: REAR NAMEPLATE (EXAMPLE)
3.Ensure that the following items are included:
• Instruction manual.
• GE EnerVista CD (includes the EnerVista UR Setup software and manuals in PDF format).
• Mounting screws.
For product information, instruction manual updates, and the latest software updates, please visit the GE Multilin website at
http://www.GEmultilin.com
.
If there is any noticeable physical damage, or any of the contents listed are missing, please contact GE
Multilin immediately.
GE MULTILIN CONTACT INFORMATION AND CALL CENTER FOR PRODUCT SUPPORT:
GE Multilin
215 Anderson Avenue
Markham, Ontario
Canada L6E 1B3
TELEPHONE:(905) 294-6222,1-800-547-8629 (North America only)
FAX:(905) 201-2098
E-MAIL:gemultilin@ge.com
HOME PAGE:http://www.GEmultilin.com
GE MultilinD30 Line Distance Protection System1-1
Page 14
1.2 UR OVERVIEW1 GETTING STARTED
1.2UR OVERVIEW1.2.1 INTRODUCTION TO THE UR
1
Historically, substation protection, control, and metering functions were performed with electromechanical equipment. This
first generation of equipment was gradually replaced by analog electronic equipment, most of which emulated the singlefunction approach of their electromechanical precursors. Both of these technologies required expensive cabling and auxiliary equipment to produce functioning systems.
Recently, digital electronic equipment has begun to provide protection, control, and metering functions. Initially, this equipment was either single function or had very limited multi-function capability, and did not significantly reduce the cabling and
auxiliary equipment required. However, recent digital relays have become quite multi-functional, reducing cabling and auxiliaries significantly. These devices also transfer data to central control facilities and Human Machine Interfaces using electronic communications. The functions performed by these products have become so broad that many users now prefer the
term IED (Intelligent Electronic Device).
It is obvious to station designers that the amount of cabling and auxiliary equipment installed in stations can be even further
reduced, to 20% to 70% of the levels common in 1990, to achieve large cost reductions. This requires placing even more
functions within the IEDs.
Users of power equipment are also interested in reducing cost by improving power quality and personnel productivity, and
as always, in increasing system reliability and efficiency. These objectives are realized through software which is used to
perform functions at both the station and supervisory levels. The use of these systems is growing rapidly.
High speed communications are required to meet the data transfer rates required by modern automatic control and monitoring systems. In the near future, very high speed communications will be required to perform protection signaling with a
performance target response time for a command signal between two IEDs, from transmission to reception, of less than 3
milliseconds. This has been established by the IEC 61850 standard.
IEDs with the capabilities outlined above will also provide significantly more power system data than is presently available,
enhance operations and maintenance, and permit the use of adaptive system configuration for protection and control systems. This new generation of equipment must also be easily incorporated into automation systems, at both the station and
enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals.
1-2D30 Line Distance Protection SystemGE Multilin
Page 15
1 GETTING STARTED1.2 UR OVERVIEW
827822A2.CDR
Input Elements
LAN
Programming
Device
Operator
Interface
Contact InputsContact Outputs
Virtual Inputs
Virtual Outputs
Analog Inputs
Analog Outputs
CT Inputs
VT Inputs
Input
Status
Table
Output
Status
Table
Pickup
Dropout
Operate
Protective Elements
Logic Gates
Remote Outputs
-DNA
-USER
CPU ModuleOutput Elements
Remote Inputs
Direct Inputs
Direct Outputs
1.2.2 HARDWARE ARCHITECTURE
a) UR BASIC DESIGN
The UR is a digital-based device containing a central processing unit (CPU) that handles multiple types of input and output
signals. The UR can communicate over a local area network (LAN) with an operator interface, a programming device, or
another UR device.
Figure 1–2: UR CONCEPT BLOCK DIAGRAM
The CPU module contains firmware that provides protection elements in the form of logic algorithms, as well as programmable logic gates, timers, and latches for control features.
Input elements accept a variety of analog or digital signals from the field. The UR isolates and converts these signals into
logic signals used by the relay.
Output elements convert and isolate the logic signals generated by the relay into digital or analog signals that can be used
to control field devices.
1
b) UR SIGNAL TYPES
The contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Both ‘wet’ and ‘dry’
contacts are supported.
The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include
signals generated by the local user interface. The virtual outputs are outputs of FlexLogic™ equations used to customize
the device. Virtual outputs can also serve as virtual inputs to FlexLogic™ equations.
The analog inputs and outputs are signals that are associated with transducers, such as Resistance Temperature Detec-
tors (RTDs).
The CT and VT inputs refer to analog current transformer and voltage transformer signals used to monitor AC power lines.
The UR-series relays support 1 A and 5 A CTs.
The remote inputs and outputs provide a means of sharing digital point state information between remote UR-series
devices. The remote outputs interface to the remote inputs of other UR-series devices. Remote outputs are FlexLogic™
operands inserted into IEC 61850 GSSE and GOOSE messages.
The direct inputs and outputs provide a means of sharing digital point states between a number of UR-series IEDs over a
dedicated fiber (single or multimode), RS422, or G.703 interface. No switching equipment is required as the IEDs are connected directly in a ring or redundant (dual) ring configuration. This feature is optimized for speed and intended for pilotaided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis.
GE MultilinD30 Line Distance Protection System1-3
Page 16
1.2 UR OVERVIEW1 GETTING STARTED
827823A1.CDR
PKP
DPO
OP
Protective Elements
Protection elements
serviced by sub-scan
Read Inputs
Solve Logic
Set Outputs
c) UR SCAN OPERATION
The UR-series devices operate in a cyclic scan fashion. The device reads the inputs into an input status table, solves the
1
logic program (FlexLogic™ equation), and then sets each output to the appropriate state in an output status table. Any
resulting task execution is priority interrupt-driven.
Figure 1–3: UR-SERIES SCAN OPERATION
1.2.3 SOFTWARE ARCHITECTURE
The firmware (software embedded in the relay) is designed in functional modules which can be installed in any relay as
required. This is achieved with object-oriented design and programming (OOD/OOP) techniques.
Object-oriented techniques involve the use of objects and classes. An object is defined as “a logical entity that contains
both data and code that manipulates that data”. A class is the generalized form of similar objects. By using this concept,
one can create a protection class with the protection elements as objects of the class, such as time overcurrent, instantaneous overcurrent, current differential, undervoltage, overvoltage, underfrequency, and distance. These objects represent
completely self-contained software modules. The same object-class concept can be used for metering, input/output control,
hmi, communications, or any functional entity in the system.
Employing OOD/OOP in the software architecture of the D30 achieves the same features as the hardware architecture:
modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection,
transformer protection, distance protection) is constructed by combining objects from the various functionality classes. This
results in a common look and feel across the entire family of UR-series platform-based applications.
1.2.4 IMPORTANT CONCEPTS
As described above, the architecture of the UR-series relays differ from previous devices. To achieve a general understanding of this device, some sections of Chapter 5 are quite helpful. The most important functions of the relay are contained in
“elements”. A description of the UR-series elements can be found in the Introduction to elements section in chapter 5.
Examples of simple elements, and some of the organization of this manual, can be found in the Control elements section of
chapter 5. An explanation of the use of inputs from CTs and VTs is in the Introduction to AC sources section in chapter 5. A
description of how digital signals are used and routed within the relay is contained in the Introduction to FlexLogic™ section
in chapter 5.
1-4D30 Line Distance Protection SystemGE Multilin
Page 17
1 GETTING STARTED1.3 ENERVISTA UR SETUP SOFTWARE
1.3ENERVISTA UR SETUP SOFTWARE1.3.1 PC REQUIREMENTS
The faceplate keypad and display or the EnerVista UR Setup software interface can be used to communicate with the relay.
The EnerVista UR Setup software interface is the preferred method to edit settings and view actual values because the PC
monitor can display more information in a simple comprehensible format.
The following minimum requirements must be met for the EnerVista UR Setup software to properly operate on a PC.
•Pentium class or higher processor (Pentium II 300 MHz or higher recommended)
•Windows 95, 98, 98SE, ME, NT 4.0 (Service Pack 4 or higher), 2000, XP
•Internet Explorer 4.0 or higher
•128 MB of RAM (256 MB recommended)
•200 MB of available space on system drive and 200 MB of available space on installation drive
•Video capable of displaying 800 x 600 or higher in high-color mode (16-bit color)
•RS232 and/or Ethernet port for communications to the relay
The following qualified modems have been tested to be compliant with the D30 and the EnerVista UR Setup software.
•US Robotics external 56K FaxModem 5686
•US Robotics external Sportster 56K X2
•PCTEL 2304WT V.92 MDC internal modem
1.3.2 INSTALLATION
After ensuring the minimum requirements for using EnerVista UR Setup are met (see previous section), use the following
procedure to install the EnerVista UR Setup from the enclosed GE EnerVista CD.
1.Insert the GE EnerVista CD into your CD-ROM drive.
2.Click the Install Now button and follow the installation instructions to install the no-charge EnerVista software.
3.When installation is complete, start the EnerVista Launchpad application.
4.Click the IED Setup section of the Launch Pad window.
1
5.In the EnerVista Launch Pad window, click the Add Product button and select the “D30 Line Distance Protection System” from the Install Software window as shown below. Select the “Web” option to ensure the most recent software
GE MultilinD30 Line Distance Protection System1-5
Page 18
1.3 ENERVISTA UR SETUP SOFTWARE1 GETTING STARTED
release, or select “CD” if you do not have a web connection, then click the Add Now button to list software items for
the D30.
1
6.EnerVista Launchpad will obtain the software from the Web or CD and automatically start the installation program.
7.Select the complete path, including the new directory name, where the EnerVista UR Setup will be installed.
8.Click on Next to begin the installation. The files will be installed in the directory indicated and the installation program
will automatically create icons and add EnerVista UR Setup to the Windows start menu.
9.Click Finish to end the installation. The UR-series device will be added to the list of installed IEDs in the EnerVista
Launchpad window, as shown below.
1.3.3 CONFIGURING THE D30 FOR SOFTWARE ACCESS
a) OVERVIEW
The user can connect remotely to the D30 through the rear RS485 port or the rear Ethernet port with a PC running the
EnerVista UR Setup software. The D30 can also be accessed locally with a laptop computer through the front panel RS232
port or the rear Ethernet port using the Quick Connect feature.
1-6D30 Line Distance Protection SystemGE Multilin
Page 19
1 GETTING STARTED1.3 ENERVISTA UR SETUP SOFTWARE
•To configure the D30 for remote access via the rear RS485 port(s), refer to the Configuring Serial Communications
section.
•To configure the D30 for remote access via the rear Ethernet port, refer to the Configuring Ethernet Communications
section. An Ethernet module must be specified at the time of ordering.
•To configure the D30 for local access with a laptop through either the front RS232 port or rear Ethernet port, refer to
the Using the Quick Connect Feature section. An Ethernet module must be specified at the time of ordering for Ethernet communications.
b) CONFIGURING SERIAL COMMUNICATIONS
Before starting, verify that the serial cable is properly connected to the RS485 terminals on the back of the device. The
faceplate RS232 port is intended for local use and is not described in this section; see the Using the Quick Connect Feature
section for details on configuring the RS232 port.
A GE Multilin F485 converter (or compatible RS232-to-RS485 converter) is will be required. Refer to the F485 instruction
manual for additional details.
1.Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or
online from http://www.GEmultilin.com
2.Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.
3.Click the Device Setup button to open the Device Setup window and click the Add Site button to define a new site.
4.Enter the desired site name in the “Site Name” field. If desired, a short description of site can also be entered along
with the display order of devices defined for the site. In this example, we will use “Location 1” as the site name. Click
the OK button when complete.
5.The new site will appear in the upper-left list in the EnerVista UR Setup window. Click the Device Setup button then
select the new site to re-open the Device Setup window.
6.Click the Add Device button to define the new device.
7.Enter the desired name in the “Device Name” field and a description (optional) of the site.
8.Select “Serial” from the Interface drop-down list. This will display a number of interface parameters that must be
entered for proper serial communications.
). See the Software Installation section for installation details.
1
Figure 1–4: CONFIGURING SERIAL COMMUNICATIONS
GE MultilinD30 Line Distance Protection System1-7
Page 20
1.3 ENERVISTA UR SETUP SOFTWARE1 GETTING STARTED
9.Enter the relay slave address, COM port, baud rate, and parity settings from the SETTINGS PRODUCT SETUP COM-
1
MUNICATIONS SERIAL PORTS menu in their respective fields.
10. Click the Read Order Code button to connect to the D30 device and upload the order code. If an communications
error occurs, ensure that the EnerVista UR Setup serial communications values entered in the previous step correspond to the relay setting values.
11. Click “OK” when the relay order code has been received. The new device will be added to the Site List window (or
Online window) located in the top left corner of the main EnerVista UR Setup window.
The Site Device has now been configured for RS232 communications. Proceed to the Connecting to the D30 section to
begin communications.
c) CONFIGURING ETHERNET COMMUNICATIONS
Before starting, verify that the Ethernet network cable is properly connected to the Ethernet port on the back of the relay. To
setup the relay for Ethernet communications, it will be necessary to define a Site, then add the relay as a Device at that site.
1.Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or
online from http://www.GEmultilin.com
2.Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.
3.Click the Device Setup button to open the Device Setup window, then click the Add Site button to define a new site.
4.Enter the desired site name in the “Site Name” field. If desired, a short description of site can also be entered along
with the display order of devices defined for the site. In this example, we will use “Location 2” as the site name. Click
the OK button when complete.
5.The new site will appear in the upper-left list in the EnerVista UR Setup window. Click the Device Setup button then
select the new site to re-open the Device Setup window.
6.Click the Add Device button to define the new device.
7.Enter the desired name in the “Device Name” field and a description (optional) of the site.
8.Select “Ethernet” from the Interface drop-down list. This will display a number of interface parameters that must be
entered for proper Ethernet functionality.
). See the Software Installation section for installation details.
Figure 1–5: CONFIGURING ETHERNET COMMUNICATIONS
1-8D30 Line Distance Protection SystemGE Multilin
Page 21
1 GETTING STARTED1.3 ENERVISTA UR SETUP SOFTWARE
9.Enter the relay IP address specified in the SETTINGS PRODUCT SETUP COMMUNICATIONS NETWORK IP
ADDRESS) in the “IP Address” field.
10. Enter the relay slave address and Modbus port address values from the respective settings in the SETTINGS PROD-
11. Click the Read Order Code button to connect to the D30 device and upload the order code. If an communications
error occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay
setting values.
12. Click OK when the relay order code has been received. The new device will be added to the Site List window (or
Online window) located in the top left corner of the main EnerVista UR Setup window.
The Site Device has now been configured for Ethernet communications. Proceed to the Connecting to the D30 section to
begin communications.
1.3.4 USING THE QUICK CONNECT FEATURE
a) USING QUICK CONNECT VIA THE FRONT PANEL RS232 PORT
Before starting, verify that the serial cable is properly connected from the laptop computer to the front panel RS232 port
with a straight-through 9-pin to 9-pin RS232 cable.
1.Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or
online from http://www.GEmultilin.com
2.Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.
3.Click the Quick Connect button to open the Quick Connect dialog box.
). See the Software Installation section for installation details.
1
4.Select the Serial interface and the correct COM Port, then click Connect.
5.The EnerVista UR Setup software will create a site named “Quick Connect” with a corresponding device also named
“Quick Connect” and display them on the upper-left corner of the screen. Expand the sections to view data directly
from the D30 device.
Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communications to the D30. This ensures that configuration of the EnerVista UR Setup software matches the D30 model number.
b) USING QUICK CONNECT VIA THE REAR ETHERNET PORTS
To use the Quick Connect feature to access the D30 from a laptop through Ethernet, first assign an IP address to the relay
from the front panel keyboard.
1.Press the MENU key until the SETTINGS menu is displayed.
2.Navigate to the
3.Enter an IP address of “1.1.1.1” and select the ENTER key to save the value.
4.In the same menu, select the
5.Enter a subnet IP address of “255.0.0.0” and press the ENTER key to save the value.
It may be necessary to restart the laptop for the change in IP address to take effect (Windows 98 or NT).
1-12D30 Line Distance Protection SystemGE Multilin
Page 25
1 GETTING STARTED1.3 ENERVISTA UR SETUP SOFTWARE
Before using the Quick Connect feature through the Ethernet port, it is necessary to disable any configured proxy settings
in Internet Explorer.
1.Start the Internet Explorer software.
2.Select the Tools > Internet Options menu item and click on Connections tab.
3.Click on the LAN Settings button to open the following window.
4.Ensure that the “Use a proxy server for your LAN” box is not checked.
If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been disconnected from the D30 relay.
1.Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE enerVista CD or
online from http://www.GEmultilin.com). See the Software Installation section for installation details.
2.Start the Internet Explorer software.
3.Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.
4.Click the Quick Connect button to open the Quick Connect dialog box.
1
5.Select the Ethernet interface and enter the IP address assigned to the D30, then click Connect.
6.The EnerVista UR Setup software will create a site named “Quick Connect” with a corresponding device also named
“Quick Connect” and display them on the upper-left corner of the screen. Expand the sections to view data directly
from the D30 device.
Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communications to the D30. This ensures that configuration of the EnerVista UR Setup software matches the D30 model number.
When direct communications with the D30 via Ethernet is complete, make the following changes:
1.From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con-
nections window.
2.Right-click the Local Area Connection icon and select the Properties item.
3.Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button.
GE MultilinD30 Line Distance Protection System1-13
Page 26
1.3 ENERVISTA UR SETUP SOFTWARE1 GETTING STARTED
4.Set the computer to “Obtain a relay address automatically” as shown below.
1
If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been disconnected from the D30 relay.
AUTOMATIC DISCOVERY OF ETHERNET DEVICES
The EnerVista UR Setup software can automatically discover and communicate to all UR-series IEDs located on an Ethernet network.
Using the Quick Connect feature, a single click of the mouse will trigger the software to automatically detect any UR-series
relays located on the network. The EnerVista UR Setup software will then proceed to configure all settings and order code
options in the Device Setup menu, for the purpose of communicating to multiple relays. This feature allows the user to
identify and interrogate, in seconds, all UR-series devices in a particular location.
1-14D30 Line Distance Protection SystemGE Multilin
Page 27
1 GETTING STARTED1.3 ENERVISTA UR SETUP SOFTWARE
842743A3.CDR
Communications status indicators:
Green = OK
Red = No communications
UR icon = report is open
Quick action hot links
Expand the site list by double-clicking
or selecting the +/– box.
NOTE
1.3.5 CONNECTING TO THE D30 RELAY
1.Open the Display Properties window through the Site List tree as shown below:
1
2.The Display Properties window will open with a status indicator on the lower left of the EnerVista UR Setup window.
3.If the status indicator is red, verify that the Ethernet network cable is properly connected to the Ethernet port on the
back of the relay and that the relay has been properly setup for communications (steps A and B earlier).
If a relay icon appears in place of the status indicator, than a report (such as an oscillography or event record) is open.
Close the report to re-display the green status indicator.
4.The Display Properties settings can now be edited, printed, or changed according to user specifications.
Refer to chapter 4 in this manual and the EnerVista UR Setup Help File for more information about the
using the EnerVista UR Setup software interface.
QUICK ACTION HOT LINKS
The EnerVista UR Setup software has several new quick action buttons that provide users with instant access to several
functions that are often performed when using D30 relays. From the online window, users can select which relay to interrogate from a pull-down window, then click on the button for the action they wish to perform. The following quick action functions are available:
•View the D30 event record.
•View the last recorded oscillography record.
•View the status of all D30 inputs and outputs.
•View all of the D30 metering values.
•View the D30 protection summary.
GE MultilinD30 Line Distance Protection System1-15
Page 28
1.4 UR HARDWARE1 GETTING STARTED
1.4UR HARDWARE1.4.1 MOUNTING AND WIRING
1
Please refer to Chapter 3: Hardware for detailed mounting and wiring instructions. Review all WARNINGS and CAUTIONS
carefully.
1.4.2 COMMUNICATIONS
The EnerVista UR Setup software communicates to the relay via the faceplate RS232 port or the rear panel RS485 / Ethernet ports. To communicate via the faceplate RS232 port, a standard straight-through serial cable is used. The DB-9 male
end is connected to the relay and the DB-9 or DB-25 female end is connected to the PC COM1 or COM2 port as described
in the CPU communications ports section of chapter 3.
Figure 1–7: RELAY COMMUNICATIONS OPTIONS
To communicate through the D30 rear RS485 port from a PC RS232 port, the GE Multilin RS232/RS485 converter box is
required. This device (catalog number F485) connects to the computer using a “straight-through” serial cable. A shielded
twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the D30 rear communications port. The converter terminals (+, –, GND) are connected to the D30 communication module (+, –, COM) terminals. Refer to the CPU communica-tions ports section in chapter 3 for option details. The line should be terminated with an R-C network (that is, 120 , 1 nF)
as described in the chapter 3.
1.4.3 FACEPLATE DISPLAY
All messages are displayed on a 2 20 backlit liquid crystal display (LCD) to make them visible under poor lighting conditions. Messages are descriptive and should not require the aid of an instruction manual for deciphering. While the keypad
and display are not actively being used, the display will default to user-defined messages. Any high priority event driven
message will automatically override the default message and appear on the display.
1-16D30 Line Distance Protection SystemGE Multilin
Page 29
1 GETTING STARTED1.5 USING THE RELAY
1.5USING THE RELAY1.5.1 FACEPLATE KEYPAD
Display messages are organized into pages under the following headings: actual values, settings, commands, and targets.
The MENU key navigates through these pages. Each heading page is broken down further into logical subgroups.
The MESSAGE keys navigate through the subgroups. The VALUE keys scroll increment or decrement numerical setting
values when in programming mode. These keys also scroll through alphanumeric values in the text edit mode. Alternatively, values may also be entered with the numeric keypad.
The decimal key initiates and advance to the next character in text edit mode or enters a decimal point. The HELP key may
be pressed at any time for context sensitive help messages. The ENTER key stores altered setting values.
1.5.2 MENU NAVIGATION
Press the MENU key to select the desired header display page (top-level menu). The header title appears momentarily followed by a header display page menu item. Each press of the MENU key advances through the following main heading
pages:
•Actual values.
•Settings.
•Commands.
•Targets.
•User displays (when enabled).
1.5.3 MENU HIERARCHY
The setting and actual value messages are arranged hierarchically. The header display pages are indicated by double
scroll bar characters (), while sub-header pages are indicated by single scroll bar characters (). The header display
pages represent the highest level of the hierarchy and the sub-header display pages fall below this level. The MESSAGE
UP and DOWN keys move within a group of headers, sub-headers, setting values, or actual values. Continually pressing
the MESSAGE RIGHT key from a header display displays specific information for the header category. Conversely, continually pressing the MESSAGE LEFT key from a setting value or actual value display returns to the header display.
1
HIGHEST LEVELLOWEST LEVEL (SETTING VALUE)
SETTINGS
PRODUCT SETUP
SETTINGS
SYSTEM SETUP
The relay is defaulted to the “Not Programmed” state when it leaves the factory. This safeguards against the installation of
a relay whose settings have not been entered. When powered up successfully, the Trouble LED will be on and the In Service LED off. The relay in the “Not Programmed” state will block signaling of any output relay. These conditions will remain
until the relay is explicitly put in the “Programmed” state.
GE MultilinD30 Line Distance Protection System1-17
Page 30
1.5 USING THE RELAY1 GETTING STARTED
NOTE
To put the relay in the “Programmed” state, press either of the VALUE keys once and then press ENTER. The faceplate
Trouble LED will turn off and the In Service LED will turn on. The settings for the relay can be programmed manually (refer
1
to Chapter 5) via the faceplate keypad or remotely (refer to the EnerVista UR Setup help file) via the EnerVista UR Setup
software interface.
1.5.5 RELAY PASSWORDS
It is recommended that passwords be set up for each security level and assigned to specific personnel. There are two user
password security access levels, COMMAND and SETTING:
1. COMMAND
The COMMAND access level restricts the user from making any settings changes, but allows the user to perform the following operations:
•operate breakers via faceplate keypad
•change state of virtual inputs
•clear event records
•clear oscillography records
•operate user-programmable pushbuttons
2. SETTING
The SETTING access level allows the user to make any changes to any of the setting values.
Refer to the Changing Settings section in Chapter 4 for complete instructions on setting up security level
passwords.
1.5.6 FLEXLOGIC™ CUSTOMIZATION
FlexLogic™ equation editing is required for setting up user-defined logic for customizing the relay operations. See the FlexLogic™ section in Chapter 5 for additional details.
1-18D30 Line Distance Protection SystemGE Multilin
Page 31
1 GETTING STARTED1.5 USING THE RELAY
1.5.7 COMMISSIONING
The D30 requires a minimum amount of maintenance when it is commissioned into service. Since the D30 is a microprocessor-based relay, its characteristics do not change over time. As such, no further functional tests are required.
Furthermore, the D30 performs a number of continual self-tests and takes the necessary action in case of any major errors
(see the Relay Self-tests section in chapter 7 for details). However, it is recommended that D30 maintenance be scheduled
with other system maintenance. This maintenance may involve the in-service, out-of-service, or unscheduled maintenance.
In-service maintenance:
1.Visual verification of the analog values integrity such as voltage and current (in comparison to other devices on the cor-
responding system).
2.Visual verification of active alarms, relay display messages, and LED indications.
3.LED test.
4.Visual inspection for any damage, corrosion, dust, or loose wires.
5.Event recorder file download with further events analysis.
Out-of-service maintenance:
1.Check wiring connections for firmness.
2.Analog values (currents, voltages, RTDs, analog inputs) injection test and metering accuracy verification. Calibrated
test equipment is required.
3.Protection elements setting verification (analog values injection or visual verification of setting file entries against relay
settings schedule).
4.Contact inputs and outputs verification. This test can be conducted by direct change of state forcing or as part of the
system functional testing.
5.Visual inspection for any damage, corrosion, or dust.
6.Event recorder file download with further events analysis.
7.LED Test and pushbutton continuity check.
Unscheduled maintenance such as during a disturbance causing system interruption:
1.View the event recorder and oscillography or fault report for correct operation of inputs, outputs, and elements.
If it is concluded that the relay or one of its modules is of concern, contact GE Multilin for prompt service.
1
GE MultilinD30 Line Distance Protection System1-19
Page 32
1
1.5 USING THE RELAY1 GETTING STARTED
1-20D30 Line Distance Protection SystemGE Multilin
The D30 Line Distance Protection System is a microprocessor-based relay intended for use on transmission lines of any
voltage level, without, with, and in the vicinity of series compensation, in three-pole tripping applications. The primary function of the relay consists of three phase and ground distance zones of protection, either mho or quadrilateral as per user
selection. The distance elements are optimized to provide good measurement accuracy with a fast operating time, even
when used with capacitive voltage transformers, and can be supervised by detection of power swings. The relay also provides directional ground overcurrent elements, which are commonly used as part of an overall line protection system.
D30 phase distance zones can be configured to work with voltages and currents fed from VTs and CTs located independently from one another on either side of a three-phase power transformer. The relay compensates accordingly to preserve
reach and correct target information regardless of the location and type of fault. This feature allows backup protection applications for generators and power transformers.
A close-into-fault (or switch-on-to-fault) function is performed by the line pickup element. Out-of-step tripping, three-pole
autoreclosing, synchrocheck, fault location, and many other functions are also available. In addition, overcurrent and
undervoltage protection, fault diagnostics, power metering, and RTU functions are provided. The D30 provides phase, neutral, and ground time overcurrent protection. The time overcurrent functions can be programmed with multiple curve shapes
or FlexCurve™ for optimum coordination.
Voltage, current, and power metering is built into the relay as a standard feature. Current parameters are available as total
waveform RMS magnitude, or as fundamental frequency only RMS magnitude and angle (phasor).
Diagnostic features include an event recorder capable of storing 1024 time-tagged events, oscillography capable of storing
up to 64 records with programmable trigger, content and sampling rate, and data logger acquisition of up to 16 channels,
with programmable content and sampling rate. The internal clock used for time-tagging can be synchronized via IRIG-B or
via the SNTP protocol over the Ethernet port. This precise time stamping allows the sequence of events to be determined
throughout the system. Events can also be programmed (via FlexLogic™ equations) to trigger oscillography data capture
which may be set to record the measured parameters before and after the event for viewing on a personal computer (PC).
These tools significantly reduce troubleshooting time and simplify report generation in the event of a system fault.
A faceplate RS232 port may be used to connect to a PC for the programming of settings and the monitoring of actual values. A variety of communications modules are available. Two rear RS485 ports allow independent access by operating and
engineering staff. All serial ports use the Modbus
®
RTU protocol. The RS485 ports may be connected to system computers
with baud rates up to 115.2 kbps. The RS232 port has a fixed baud rate of 19.2 kbps. Optional communications modules
include a 10Base-F Ethernet interface which can be used to provide fast, reliable communications in noisy environments.
Another option provides two 10Base-F fiber optic ports for redundancy. The Ethernet port supports IEC 61850, Modbus/
TCP, and TFTP protocols, and allows access to the relay via any standard web browser (D30 web pages). The IEC 608705-104 protocol is supported on the Ethernet port. DNP 3.0 and IEC 60870-5-104 cannot be enabled at the same time.
The D30 IEDs use flash memory technology which allows field upgrading as new features are added. The following single
line diagram illustrates the relay functionality using ANSI (American National Standards Institute) device numbers.
2
Table 2–1: DEVICE NUMBERS AND FUNCTIONS
DEVICE
NUMBER
21GGround Distance51_2Negative Sequence Time Overcurrent
DNP 3.0 or IEC 60870-5-104 protocolNon-volatile selector switchVT fuse failure
Event recorderOscillography
2
t)Fault detector and fault reportSetting groups (6)
Figure 2–1: SINGLE LINE DIAGRAM
factor, frequency
User-programmable pushbuttons
2.1.2 ORDERING
a) OVERVIEW
The D30 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following modules: power supply, CPU, CT/VT, digital input and output, transducer input and output, and inter-relay communications.
Each of these modules can be supplied in a number of configurations specified at the time of ordering. The information
required to completely specify the relay is provided in the following tables (see chapter 3 for full details of relay modules).
Order codes are subject to change without notice. Refer to the GE Multilin ordering page at
http://www.GEindustrial.com/multilin/order.htm
The order code structure is dependent on the mounting option (horizontal or vertical) and the type of CT/VT modules (regu-
for the latest details concerning D30 ordering options.
lar CT/VT modules or the HardFiber modules). The order code options are described in the following sub-sections.
2-2D30 Line Distance Protection SystemGE Multilin
Page 35
2 PRODUCT DESCRIPTION2.1 INTRODUCTION
b) ORDER CODES WITH TRADITIONAL CTS AND VTS
The order codes for the horizontal mount units with traditional CTs and VTs are shown below.
Table 2–3: D30 ORDER CODES (HORIZONTAL UNITS WITH TRADITIONAL CTS AND VTS)
BASE UNITD30| || | ||||||| Base Unit
CPUE || | ||||||| RS485 and RS485
SOFTWARE00| | ||||||| No Software Options
MOUNT/COATINGH | ||||||| Horizontal (19” rack)
FACEPLATE/ DISPLAYC ||||||| English display
POWER SUPPLY
(redundant supply must
be same type as main supply)
CT/VT MODULES8F||||| Standard 4CT/4VT
DIGITAL INPUTS/OUTPUTSXXXXXXXXXX No Module
TRANSDUCER
INPUTS/OUTPUTS
(select a maximum of 3 per unit)
INTER-RELAY
COMMUNICATIONS
(select a maximum of 1 per unit)
D30 - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/ X ** Full Size Horizontal Mount
G || | ||||||| RS485 and multi-mode S T 10Base-F
H || | ||||||| RS485 and multi-mode ST redundant 10Base-F
J || | ||||||| RS485 and multi-mode ST 100Base-FX
K || | ||||||| RS485 and multi-mode ST r edundant 100Base-FX
N || | ||||||| RS485 and 10/100Base-T
S || | ||||||| RS485 and managed six-port E thernet switch
03| | ||||||| IEC 61850; not available for Type E CPUs
A | ||||||| Horizontal (19” rack) with harsh environmental coating
D ||||||| French display
R ||||||| Russian display
A ||||||| Chinese display
P ||||||| English display with 4 small and 12 large programmable pushbut tons
G ||||||| French display wi th 4 small and 12 large programmable pushbuttons
S ||||||| Russian display with 4 small and 12 large programmable pushbuttons
B ||||||| Chinese display with 4 small and 12 large programmable pushbuttons
K ||||||| Enhanced front panel with English display
M ||||||| Enhanced front panel with French display
Q ||||||| Enhanced front panel with Russian display
U ||||||| Enhanced front panel with Chinese display
L ||||||| Enhanced front panel with English display and user-programmable pushbuttons
N ||||||| Enhanced front panel with French display and user-programmable pushbuttons
T ||||||| Enhanced front panel with Russian display and user-programmable pushbuttons
V ||||||| Enhanced front panel with Chinese display and user-programmable pushbut tons
W ||||||| Enhanced front panel with Turkish display
Y ||||||| Enhanced front panel with Turkish display and user-programmable pushbuttons
H|||||| 125 / 250 V AC/DC power supply
H|||||RH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
L|||||| 24 to 48 V (DC only) power supply
L|||||RL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
8G||||| Sensitive Ground 4CT/4VT
4A4A4A4A4A 4 Solid-State (no monitoring) MOSFET out puts
4B4B4B4B4B 4 Solid-State (voltage with optional current) MOSFE T outputs
4C4C4C4C4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D4D4D4D4D 16 digital inputs with Auto-Burnishing
4L4L4L4L4L 14 Form-A (no monitoring) Latching outputs
6767676767 8 Form-A (no monitoring) outputs
6A6A6A6A6A 2 Form-A ( voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B6B6B6B6B 2 Form-A ( voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C6C6C6C6C 8 Form-C outputs
6D6D6D6D6D 16 digital inputs
6E6E6E6E6E 4 Form-C outputs, 8 digital inputs
6F6F6F6F6F 8 Fast Form-C outputs
6G6G6G6G6G 4 Form-A (voltage with optional curr ent) outputs, 8 digital inputs
6H6H6H6H6H 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K6K6K6K6K 4 Form-C and 4 Fast Form-C outputs
6L6L6L6L6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M6M6M6M6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N6N6N6N6N 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P6P6P6P6P 6 Form-A ( current with optional voltage) outputs, 4 digital inputs
6R6R6R6R6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S6S6S6S6S 2 Form-A ( no monitoring) and 4 Form-C outputs, 4 digital inputs
6T6T6T6T6T 4 Form-A (no monitoring) outputs, 8 digital inputs
6U6U6U6U6U 6 Form-A (no monitoring) outputs, 4 digital inputs
6V6V6V6V6V 2 Form-A ou tputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
5A5A5A5A5A 4 dcmA inputs, 4 dcmA out puts (only one 5A module is allowed)
5C5C5C5C5C 8 RTD inputs
5D5D5D5D5D 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed)
5E5E5E5E5E 4 RTD inputs, 4 dcmA inputs
5F5F5F5F5F 8 dcmA inputs
The order codes for the reduced size vertical mount units with traditional CTs and VTs are shown below.
Table 2–4: D30 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH TRADITIONAL CTS AND VTS)
BASE UNITD30| || | ||||| Base Unit
CPUE || | ||||| RS485 and RS485
SOFTWARE00| | ||||| No Software Options
MOUNT/COATINGV | ||||| Vertical (3/4 rack)
2
FACEPLATE/ DISPLAYF ||||| English display
POWER SUPPLYH|||| 125 / 250 V AC/DC power supply
CT/VT MODULES8F||| Standard 4CT/4VT
DIGITAL INPUTS/OUTPUTSXXXXXX No Module
TRANSDUCER
INPUTS/OUTPUTS
(select a maximum of 3 per unit)
INTER-RELAY
COMMUNICATIONS
(select a maximum of 1 per unit)
For the last module, slot P is used for digital and transducer
input/output modules; slot R is used for inter-relay
communications modules.
D30 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
G || | ||||| RS 485 and multi-mode ST 10Base-F
H || | ||||| RS485 and multi-mode ST redundant 10Base-F
J || | ||||| RS485 and multi-mode ST 100Base-FX
K || | ||||| RS485 and multi-mode ST redundant 100Base-FX
N || | ||||| RS485 and 10/100Base-T
03| | ||||| IEC 61850; not available for Type E CPUs
B | ||||| Vertical (3/4 rack) with harsh environmental coating
D ||||| French display
R ||||| Russian display
A ||||| Chinese display
K ||||| Enhanced front panel with English display
M ||||| Enhanced front panel with French display
Q ||||| Enhanced front panel with Russian display
U ||||| Enhanced front panel with Chi nese display
L ||||| Enhanced front panel with English display and user-programmable pushbuttons
N ||||| Enhanced front panel with Fr ench display and user-programmable pushbuttons
T ||||| Enhanced front panel with Russian display and user-programmable pushbuttons
V ||||| Enhanced front panel with Chinese display and user-programmable pushbuttons
W ||||| Enhanced front panel wit h Turkish display
Y ||||| Enhanced front panel with Turkish display and user-programmable pushbuttons
L|||| 24 to 48 V (DC only) power supply
8G||| Sensitive Ground 4CT/4VT
4A4A4A 4 Solid-State (no monitoring) MOSFET outputs
4B4B4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C4C4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D4D4D 16 digital inputs with Auto-Burnishing
4L4L4L 14 Form-A (no monitoring) Latching outputs
676767 8 Form-A (no monitoring) out puts
6A6A6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B6B6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C6C6C 8 Form-C outputs
6D6D6D 16 digital inputs
6E6E6E 4 Form-C outputs, 8 digital inputs
6F6F6F 8 Fast Form-C outputs
6G6G6G 4 Form-A (voltage with optional current) outp uts, 8 digital inputs
6H6H6H 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K6K6K 4 Form-C and 4 Fast Form-C outputs
6L6L6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M6M6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N6N6N 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P6P6P 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R6R6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S6S6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T6T6T 4 For m-A (no monitoring) outputs, 8 digital inputs
6U6U6U 6 Form-A (no monitoring) outputs, 4 digital inputs
6V6V6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
5A5A5A 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed)
5C5C5C 8 RTD inputs
5D5D5D 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed)
5E5E5E 4 RTD inputs, 4 dcmA inputs
5F5F5F 8 dcmA i nputs
2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
2E Bi-phase, single channel
The order codes for the horizontal mount units with the process bus module are shown below.
Table 2–5: D30 ORDER CODES (HORIZONTAL UNITS WITH PROCESS BUS)
BASE UNITD30| || | ||||||| Base Unit
CPUE || | ||||||| RS485 and RS485
SOFTWARE00| | ||||||| No Software Options
MOUNT/COATINGH | ||||||| Horizontal (19” rack)
FACEPLATE/ DISPLAYC ||||||| English display
POWER SUPPLY
(redundant supply must
be same type as main supply)
PROCESS BUS MODULE|81|||| Standard 4CT/4VT
DIGITAL INPUTS/OUTPUTSXXXXXXXXXX No Module
INTER-RELAY
COMMUNICATIONS
(select a maximum of 1 per unit)
D30 - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/ X ** Full Size Horizontal Mount
G || | ||||||| RS485 and multi-mode ST 10Base-F
H || | ||||||| RS485 and multi-mode ST redundant 10Base- F
J || | ||||||| RS485 and mult i-mode ST 100Base-FX
K || | ||||||| RS485 and multi-mode ST redundant 100Base-FX
L || | ||||||| RS485 and single mode SC 100Base-F X
M || | ||||||| RS485 and sing le mode SC redundant 100Base-FX
N || | ||||||| RS485 and 10/100Base-T
03| | ||||||| IEC 61850; not available for Type E CPUs
A | ||||||| Horizontal (19” rack) with harsh environmental coating
D ||||||| French display
R ||||||| Russian disp lay
A ||||||| Chinese display
P ||||||| English display with 4 small and 12 large programmable pushbuttons
G ||||||| French display wi th 4 small and 12 large programmable pushbuttons
S ||||||| Russian display with 4 small and 12 large programmable pushbuttons
B ||||||| Chinese display with 4 small and 12 large programmable pushbuttons
K ||||||| Enhanced front panel with English display
M ||||||| Enhanced front panel with French display
Q ||||||| Enhanced front panel with Russian display
U ||||||| Enhanced front panel with Chinese display
L ||||||| Enhanced front panel with English display and user-programmable pushbuttons
N ||||||| Enhanced front panel with French display and user-programmable pushbuttons
T ||||||| Enhanced front panel with Russian display and user-programmable pushbuttons
V ||||||| Enhanced front panel with Chinese display and user-programmable pushbuttons
H|||||| 125 / 250 V AC/DC power supply
H|||||RH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
L|||||| 24 to 48 V (DC only) power supply
L|||||RL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
4A4A| 4 Solid-State (no monitoring) MOSFET outputs
4B4B| 4 Solid-State (voltage with optional current) MOSFET outputs
4C4C| 4 Solid-State (current with optional voltage) MOSFET out puts
4D4D| 16 digital inputs with Auto-B urnishing
4L4L| 14 Form-A (no monitoring) Latching outputs
6767| 8 Form-A (no monitoring) outputs
6A6A| 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B6B| 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C6C| 8 Form-C outputs
6D6D| 16 digital inputs
6E6E| 4 Form-C outputs, 8 digital inputs
6F6F| 8 Fast Form-C outputs
6G6G| 4 Form-A (voltage with optional current) outputs, 8 digital inputs
6H6H| 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K6K| 4 Form-C and 4 Fast Form-C outputs
6L6L| 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M6M| 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N6N| 4 Form-A (curr ent with optional voltage) outputs, 8 digital inputs
6P6P| 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R6R| 2 Form-A (no monit oring) and 2 Form-C outputs, 8 digital inputs
6S6S| 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T6T| 4 Form-A (no monitoring) outputs, 8 digital inputs
6U6U| 6 Form-A (no monit oring) outputs, 4 digital inputs
6V6V| 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
The order codes for the reduced size vertical mount units with the process bus module are shown below.
Table 2–6: D30 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS)
BASE UNITD30| || | ||||| Base Unit
CPUE || | ||||| RS485 and RS485
SOFTWARE00| | ||||| No Software Options
2
MOUNT/COATINGV | ||||| Vertical (3/4 rack)
FACEPLATE/ DISPLAYF ||||| English display
POWER SUPPLYH|||| 125 / 250 V AC/DC power supply
PROCESS BUS MODULE|81|| Standard 4CT/4VT
DIGITAL INPUTS/OUTPUTSXXXXXX No Module
INTER-RELAY
COMMUNICATIONS
(select a maximum of 1 per unit)
For the last module, slot P is used for digital
input/output modules; slot R is used for inter-relay
communications modules.
D30 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
G || | ||||| RS485 and multi-mode ST 10Base-F
H || | ||||| RS485 and multi-mode ST r edundant 10Base-F
J || | ||||| RS485 and multi-mode ST 100Base-FX
K || | ||||| RS485 and multi-mode ST redundant 100Base-FX
L || | ||||| RS485 and single mode S C 100Base-FX
M || | ||||| RS485 and single mode SC redundant 100Base-FX
N || | ||||| RS485 and 10/100Base-T
03| | ||||| IEC 61850; not available for Type E CPUs
B | ||||| Vertical (3/4 rack) with harsh envir onmental coating
D ||||| French display
R ||||| Russian display
A ||||| Chinese display
K ||||| Enhanced front panel with English display
M ||||| Enhanced front panel with French display
Q ||||| Enhanced front panel with Russian display
U ||||| Enhanced front panel with Chi nese display
L ||||| Enhanced front panel with English display and user-programmable pushbuttons
N ||||| Enhanced front panel with Fr ench display and user-programmable pushbuttons
T ||||| Enhanced front panel with Russian display and user-programmable pushbuttons
V ||||| Enhanced front panel with Chinese display and user-programmable pushbuttons
L|||| 24 to 48 V (DC only) power supply
4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 16 digital inputs with Auto-Burnishing
4L 14 Form-A (no monitoring) Latching out puts
67 8 Form-A (no monitoring) outputs
6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C 8 Form-C outputs
6D 16 digital inputs
6E 4 Form-C outputs, 8 digital inputs
6F 8 Fast Form-C outputs
6G 4 Form-A (voltage with optional current) outputs, 8 digital inputs
6H 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K 4 Form-C and 4 Fast Form-C outputs
6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T 4 Form-A (no monitoring) outputs, 8 digital inputs
6U 6 Form-A (no monitoring) outputs, 4 digital inputs
6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 dig ital inputs
2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
2E Bi-phase, single channel
2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
72 1550 nm, single-mode, LASER, 1 Channel
73 1550 nm, single-mode, LASER, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 n m, single-mode, LASER
75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, LASER, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multi-mode, LED, 2 Channels
Replacement modules can be ordered separately as shown below. When ordering a replacement CPU module or faceplate, please provide the serial number of your existing unit.
Not all replacement modules may be applicable to the D30 relay. Only the modules specified in the order codes are
available as replacement modules.
Replacement module codes are subject to change without notice. Refer to the GE Multilin ordering page at http://
www.GEindustrial.com/multilin/order.htm for the latest details concerning D30 ordering options.
2-6D30 Line Distance Protection SystemGE Multilin
Page 39
2 PRODUCT DESCRIPTION2.1 INTRODUCTION
The replacement module order codes for the horizontal mount units are shown below.
Table 2–7: ORDER CODES FOR REPLACEMENT MODULES, HORIZONTAL UNITS
POWER SUPPLY
(redundant supply only available in horizontal units;
must be same type as main supply)
CPU|9E| RS485 and RS485 (Modbus RTU, DNP 3.0)
FACEPLATE/DISPLAY|3C| Horizontal faceplate with keypad and Engli sh display
DIGITAL INPUTS AND OUTPUTS|4A| 4 Solid-State (no monitoring) MOSFET o utputs
CT/VT
MODULES
(NOT AVAILABLE FOR THE C30)
INTER-RELAY COMMUNICATIONS|2A| C37.94SM, 1300nm single-mode, ELED, 1 channel single -mode
TRANSDUCER
INPUTS/OUTPUTS
UR - ** - *
|1H| 125 / 250 V AC /DC
|1L| 24 to 48 V (DC only)
|RH| redundant 125 / 250 V AC/DC
|RH| redundant 24 to 48 V (DC only)
|9G| RS485 and 10Base-F (E thernet, Modbus TCP/IP, DNP 3.0)
|9H| RS485 and Redundant 10Base-F (Ethernet, Modbus TCP /IP, DNP 3.0)
|9J| RS485 and mu lti-mode ST 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
|9K| RS485 and multi-mode ST redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
|9L| RS485 and single mode SC 100Base-FX (Ethernet , Modbus TCP/IP, DNP 3.0)
|9M| RS485 and single mode SC redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
|9N| RS485 and 10/100Base-T
|9S| RS485 and six-port managed Ethernet switch
|3D| Horizontal faceplate with keypad and Fre nch display
|3R| Horizontal faceplate with keypad and Russian display
|3A| Horizontal faceplate with keypad and Chinese display
|3P| Horizontal faceplate with keypad, user-programmable pushbuttons, and English display
|3G| Horizontal faceplate with keypad, user-programmable pushbuttons, and French display
|3S| Horizontal faceplate with keypad, user-programmable pushbuttons, and Russian display
|3B| Horizontal faceplate with keypad, user-programmable pushbuttons, and Chinese display
|3K| Enhanced front panel with English display
|3M| Enhanced front panel with French display
|3Q| Enhanced front panel with Russian display
|3U| Enhanced front panel wit h Chinese display
|3L| Enhanced fro nt panel with English display and user-programmable pushbuttons
|3N| Enhanced front panel wit h French display and user-programmable pushbuttons
|3T| Enhanced fro nt panel with Russian display and user-programmable pushbuttons
|3V| Enhanced front panel with Chinese display and user-programmable pushbut tons
|4B| 4 Solid-State (voltage with optional current) MOSF ET outputs
|4C| 4 Solid-State (current with optional voltage) MOSFET outputs
|4D| 16 digital inputs with Auto-Burnishing
|4L| 14 Form-A (no monitoring) Latching out puts
|67| 8 Form-A (no monitoring) outputs
|6A| 2 Form-A (voltage with opt ional current) and 2 Form-C outputs, 8 digital inputs
|6B| 2 Form-A (voltage with opt ional current) and 4 Form-C outputs, 4 digital inputs
|6C| 8 Form-C outputs
|6D| 16 digital inputs
|6E| 4 Form-C outputs, 8 di gital inputs
|6F| 8 Fast Form-C o utputs
|6G| 4 Form-A (voltage with opt ional current) outputs, 8 digital inputs
|6H| 6 Form-A (voltage with optional current) outputs, 4 digital inputs
|6K| 4 Form-C and 4 Fast Form-C outputs
|6L| 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
|6M| 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
|6N| 4 Form-A (current with optional voltage) outputs, 8 digital inputs
|6P| 6 Form-A (curr ent with optional voltage) outputs, 4 digital inputs
|6R| 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
|6S| 2 Form-A (no moni toring) and 4 Form-C outputs, 4 digital inputs
|6T| 4 Form-A (no monitoring) outputs, 8 digital inputs
|6U| 6 Form-A (no monitoring) outputs, 4 digital inputs
|6V| 2 Form-A outputs, 1 Fo rm-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
|8F| Standard 4CT/4VT
|8G| Sensitive Ground 4CT/4VT
|8H| Standard 8CT
|8J| Sensitive Ground 8CT
|8L| Standard 4CT/4VT with enhanced diagnostics
|8M| Sensitive Ground 4CT/4VT with enhanced diagnostics
|8N| Standard 8CT with enhanced diagnostics
|8R| Sensitive Ground 8CT with enhanced diagnostics
|9G| RS485 and 10Base-F (E thernet, Modbus TCP/IP, DNP 3.0)
|9H| RS485 and Redundant 10Base-F (Ethernet, Modbus TCP /IP, DNP 3.0)
|9J| RS485 and mu lti-mode ST 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
|9K| RS485 and multi-mode ST redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
|9L| RS485 and single mode SC 100Base-FX (Ethernet , Modbus TCP/IP, DNP 3.0)
|9M| RS485 and single mode SC redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
|9N| RS485 and 10/100Base-T
|3D| Vertical faceplate with keypad and French display
|3R| Vertical faceplate with keypad and Russian display
|3K| Vertical faceplate with keypad and Chinese display
|3K| Enhanced front panel with English display
|3M| Enhanced front panel with French display
|3Q| Enhanced front panel with Russian display
|3U| Enhanced front panel wit h Chinese display
|3L| Enhanced fro nt panel with English display and user-programmable pushbuttons
|3N| Enhanced front panel wit h French display and user-programmable pushbuttons
|3T| Enhanced fro nt panel with Russian display and user-programmable pushbuttons
|3V| Enhanced front panel with Chinese display and user-programmable pushbut tons
|4A| 4 Solid-State (no monitoring) MOSFET o utputs
|4B| 4 Solid-State (voltage with optional current) MOSFET out puts
|4C| 4 Solid-State (current with optional voltage) MOSFET outputs
|4D| 16 digital inputs with Auto-Burnishing
|4L| 14 Form-A (no monitoring) Latching out puts
|67| 8 Form-A (no monitoring) outputs
|6A| 2 Form-A (voltage with opt ional current) and 2 Form-C outputs, 8 digital inputs
|6B| 2 Form-A (voltage with opt ional current) and 4 Form-C outputs, 4 digital inputs
|6C| 8 Form-C outputs
|6D| 16 digital inputs
|6E| 4 Form-C outputs, 8 di gital inputs
|6F| 8 Fast Form-C o utputs
|6G| 4 Form-A (voltage with opt ional current) outputs, 8 digital inputs
|6H| 6 Form-A (voltage with optional current) outputs, 4 digital inputs
|6K| 4 Form-C and 4 Fast Form-C outputs
|6L| 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
|6M| 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
|6N| 4 Form-A (current with optional voltage) outputs, 8 digital inputs
|6P| 6 Form-A (curr ent with optional voltage) outputs, 4 digital inputs
|6R| 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
|6S| 2 Form-A (no moni toring) and 4 Form-C outputs, 4 digital inputs
|6T| 4 Form-A (no monitoring) outputs, 8 digital inputs
|6U| 6 Form-A (no monitoring) outputs, 4 digital inputs
|6V| 2 Form-A outputs, 1 Fo rm-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
|8F| Standard 4CT/4VT
|8G| Sensitive Ground 4CT/4VT
|8H| Standard 8CT
|8J| Sensitive Ground 8CT
|8L| Standard 4CT/4VT with enhanced diagnostics
|8M| Sensitive Ground 4CT/4VT with enhanced diagnostics
|8N| Standard 8CT with enhanced diagnostics
|8R| Sensitive Ground 8CT with enhanced diagnostics
2.2SPECIFICATIONSSPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
2.2.1 PROTECTION ELEMENTS
The operating times below include the activation time of a trip rated form-A output contact unless otherwise indicated. FlexLogic™ operands of a given element are 4 ms faster. This should be taken into account when using
FlexLogic™ to interconnect with other protection or control elements of the relay, building FlexLogic™ equations, or
interfacing with other IEDs or power system devices via communications or different output contacts.
PHASE DISTANCE
Characteristic:mho (memory polarized or offset) or
quad (memory polarized or non-directional), selectable individually per zone
Number of zones:3
Directionality:forward, reverse, or non-directional per
zone
Reach (secondary ):0.02 to 500.00 in steps of 0.01
Reach accuracy:±5% including the effect of CVT tran-
sients up to an SIR of 30
Distance:
Characteristic angle:30 to 90° in steps of 1
Comparator limit angle: 30 to 90° in steps of 1
Directional supervision:
Characteristic angle:30 to 90° in steps of 1
Limit angle:30 to 90° in steps of 1
Right blinder (Quad only):
Reach:0.02 to 500 in steps of 0.01
Characteristic angle:60 to 90° in steps of 1
Left Blinder (Quad only):
Reach:0.02 to 500 in steps of 0.01
Characteristic angle:60 to 90° in steps of 1
Time delay:0.000 to 65.535 s in steps of 0.001
Timing accuracy:±3% or 4 ms, whichever is greater
Current supervision:
Level:line-to-line current
Pickup:0.050 to 30.000 pu in steps of 0.001
Dropout: 97 to 98%
Memory duration:5 to 25 cycles in steps of 1
VT location:all delta-wye and wye-delta transformers
CT location:all delta-wye and wye-delta transformers
Voltage supervision pickup (series compensation applications):
0 to 5.000 pu in steps of 0.001
PHASE DISTANCE OPERATING TIME CURVES
The operating times are response times of a microprocessor part
of the relay. See output contacts specifications for estimation of
the total response time for a particular application. The operating
times are average times including variables such as fault inception
angle or type of a voltage source (magnetic VTs and CVTs).
2
GE MultilinD30 Line Distance Protection System2-9
Page 42
2.2 SPECIFICATIONS2 PRODUCT DESCRIPTION
Ground Element (21G)
0
5
10
15
20
25
30
35
0%10%20%30%40%50% 60%70%80%
Fault Location [%]
Operating Time [ms]
SIR = 0.1
SIR = 1
SIR = 10
SIR = 20
SIR = 30
GROUND DISTANCE
Characteristic:Mho (memory polarized or offset) or
Quad (memory polarized or non-directional), selectable individually per zone
Reactance polarization: negative-sequence or zero-sequence
current
Non-homogeneity angle: –40 to 40° in steps of 1
Number of zones:3
2
Directionality:forward, reverse, or non-directional per
zone
Reach (secondary ):0.02 to 500.00 in steps of 0.01
Distance characteristic angle: 30 to 90° in steps of 1
Distance comparator limit angle: 30 to 90° in steps of 1
Directional supervision:
Characteristic angle:30 to 90° in steps of 1
Limit angle:30 to 90° in steps of 1
Zero-sequence compensation
Z0/Z1 magnitude:0.00 to 10.00 in steps of 0.01
Z0/Z1 angle:–90 to 90° in steps of 1
Zero-sequence mutual compensation
Z0M/Z1 magnitude:0.00 to 7.00 in steps of 0.01
Z0M/Z1 angle:–90 to 90° in steps of 1
Right blinder (Quad only):
Reach:0.02 to 500 in steps of 0.01
Characteristic angle:60 to 90° in steps of 1
Left blinder (Quad only):
Reach:0.02 to 500 in steps of 0.01
Characteristic angle:60 to 90° in steps of 1
Time delay:0.000 to 65.535 s in steps of 0.001
Timing accuracy:±3% or 4 ms, whichever is greater
Current supervision:
Level:neutral current (3I_0)
Pickup:0.050 to 30.000 pu in steps of 0.001
Dropout: 97 to 98%
Memory duration:5 to 25 cycles in steps of 1
Voltage supervision pickup (series compensation applications):
0 to 5.000 pu in steps of 0.001
GROUND DISTANCE OPERATING TIME CURVES
The operating times are response times of a microprocessor part
of the relay. See output contacts specifications for estimation of
the total response time for a particular application. The operating
times are average times including variables such as fault inception
angle or type of a voltage source (magnetic VTs and CVTs).
LINE PICKUP
Phase instantaneous overcurrent: 0.000 to 30.000 pu
Undervoltage pickup:0.000 to 3.000 pu
Overvoltage delay:0.000 to 65.535 s
PHASE/NEUTRAL/GROUND TOC
Current:Phasor or RMS
Pickup level:0.000 to 30.000 pu in steps of 0.001
Dropout level:97% to 98% of pickup
Level accuracy:
for 0.1 to 2.0 CT:±0.5% of reading or ±0.4% of rated
for > 2.0 CT:±1.5% of reading > 2.0 CT rating
Curve shapes:IEEE Moderately/Very/Extremely
Curve multiplier:Time Dial = 0.00 to 600.00 in steps of
Reset type:Instantaneous/Timed (per IEEE)
Timing accuracy:Operate at > 1.03 actual pickup
(whichever is greater)
Inverse; IEC (and BS) A/B/C and Short
Inverse; GE IAC Inverse, Short/Very/
Extremely Inverse; I
2
t; FlexCurves™
(programmable); Definite Time (0.01 s
base curve)
0.01
±3.5% of operate time or ±½ cycle
(whichever is greater)
2-10D30 Line Distance Protection SystemGE Multilin
Page 43
2 PRODUCT DESCRIPTION2.2 SPECIFICATIONS
PHASE/NEUTRAL/GROUND IOC
Pickup level:0.000 to 30.000 pu in steps of 0.001
Dropout level:97 to 98% of pickup
Level accuracy:
0.1 to 2.0 CT rating: ±0.5% of reading or ±0.4% of rated
(whichever is greater)
> 2.0 CT rating±1.5% of reading
Overreach:<2%
Pickup delay:0.00 to 600.00 s in steps of 0.01
Reset delay:0.00 to 600.00 s in steps of 0.01
Operate time:<16 ms at 3 pickup at 60 Hz
Timing accuracy:Operate at 1.5 pickup
(Phase/Ground IOC)
<20 ms at 3 pickup at 60 Hz
(Neutral IOC)
±3% or ±4 ms (whichever is greater)
NEGATIVE SEQUENCE TOC
Pickup level:0.000 to 30.000 pu in steps of 0.001
Dropout level:97% to 98% of pickup
Level accuracy:±0.5% of reading or ±0.4% of rated
Curve shapes:IEEE Moderately/Very/Extremely
Curve multiplier (Time dial): 0.00 to 600.00 in steps of 0.01
Reset type:Instantaneous/Timed (per IEEE) and Lin-
Timing accuracy:Operate at > 1.03 actual pickup
(whichever is greater)
from 0.1 to 2.0 x CT rating
±1.5% of reading > 2.0 x CT rating
Inverse; IEC (and BS) A/B/C and Short
Inverse; GE IAC Inverse, Short/Very/
Extremely Inverse; I
(programmable); Definite Time (0.01 s
base curve)
ear
±3.5% of operate time or ±½ cycle
(whichever is greater)
2
t; FlexCurves™
NEGATIVE SEQUENCE IOC
Pickup level:0.000 to 30.000 pu in steps of 0.001
Dropout level:97 to 98% of pickup
Level accuracy:0.1 to 2.0 CT rating: ±0.5% of reading
Overreach: 2%
Pickup delay:0.00 to 600.00 s in steps of 0.01
Reset delay:0.00 to 600.00 s in steps of 0.01
Operate time:< 20 ms at 3 pickup at 60 Hz
Timing accuracy:Operate at 1.5 pickup
or ±0.4% of rated (whichever is greater);
2.0 CT rating: ±1.5% of reading
±3% or ±4 ms (whichever is greater)
PHASE DIRECTIONAL OVERCURRENT
Relay connection:90° (quadrature)
Quadrature voltage:ABC phase seq.: phase A (V
B (V
), phase C (VAB); ACB phase
CA
seq.: phase A (V
phase C (V
Polarizing voltage threshold: 0.000 to 3.000 pu in steps of 0.001
Nominal AC voltage:100 to 240 V AC, 0.26 to 0.16 A/26 to 39
VA at 50/60 Hz
Minimum AC voltage:85 V AC, 0.31 A/22 VA at 50/60 Hz
Maximum AC voltage:265 V AC, 0.16 A/42 VA at 50/60 Hz
Internal fuse:3 A / 350 V AC, Ceramic, Axial SLO
BLO;
Manufacturer: Conquer; Part number:
SCD-A 003
RS232
Front port:19.2 kbps, Modbus® RTU
RS485
1 or 2 rear ports:Up to 115 kbps, Modbus® RTU, isolated
Typical distance:1200 m
Isolation:2 kV
together at 36 Vpk
ETHERNET (FIBER)
PARAMETERFIBER TYPE
10MB MULTI-
MODE
Wavelength820 nm1310 nm1310 nm
ConnectorSTSTSC
Transmit power–20 dBm–20 dBm–15 dBm
Receiver sensitivity–30 dBm–30 dBm–30 dBm
Power budget10 dB10 dB15 dB
Maximum input
power
Typical distance1.65 km2 km15 km
Duplexfull/halffull/halffull/half
Redundancyyesyesyes
–7.6 dBm–14 dBm–7 dBm
100MB MULTI-
MODE
100MB SINGLE-
MODE
ETHERNET SWITCH (LOW VOLTAGE, TYPE 2T)
Nominal voltage:48 V DC, 0.31 A/15 W
Minimum voltage:30 V DC, 0.43 A/16 W
Maximum voltage:60 V DC
Internal fuse:5 A / 350 V AC, Ceramic, Axial SLO
BLO;
Manufacturer: Conquer; Part number:
SCD-A 005
2.2.8 COMMUNICATIONS
ETHERNET SWITCH FIBER OPTIC PORTS
Maximum fiber segment length calculation:
The maximum fiber segment length between two adjacent
switches or between a switch and a device is calculated as follows. First, calculate the optical power budget (OPB) of each
device using the manufacturer’s data sheets.
where OPB = optical power budget, P
and P
= receiver sensitivity.
R
The worst case optical power budget (OPB
lated by taking the lower of the two calculated power budgets, subtracting 1 dB for LED aging, and then subtracting the total insertion
loss. The total insertion loss is calculated by multiplying the number of connectors in each single fiber path by 0.5 dB. For example,
with a single fiber cable between the two devices, there will be a
minimum of two connections in either transmit or receive fiber
paths for a total insertion loss of 1db for either direction:
The worst-case optical power budget between two type 2T or 2S
modules using a single fiber cable is:
= transmitter output power,
T
) is then calcu-
WORST
2
The UR-2S and UR-2T only support 100 Mb multimode
ETHERNET (10/100 MB TWISTED PAIR)
Modes:10 MB, 10/100 MB (auto-detect)
Connector:RJ45
SNTP clock synchronization error: <10 ms (typical)
To calculate the maximum fiber length, divide the worst-case optical power budget by the cable attenuation per unit distance specified in the manufacturer data sheets. For example, typical
attenuation for 62.5/125 m glass fiber optic cable is approxi-
mately 2.8 dB per km. In our example, this would result in the following maximum fiber length:
The customer must use the attenuation specified within the manufacturer data sheets for accurate calculation of the maximum fiber
length.
ETHERNET SWITCH 10/100BASE-T PORTS
Connector type:RJ45
MAXIMUM 10 MBPS ETHERNET SEGMENT LENGTHS
Unshielded twisted pair: 100 m (328 ft.)
MAXIMUM STANDARD FAST ETHERNET SEGMENT LENGTHS
10Base-T (CAT 3, 4, 5 UTP): 100 m (328 ft.)
100Base-TX (CAT 5 UTP):100 m (328 ft.)
Shielded twisted pair: 150 m (492 ft.)
Shielded twisted pair: 150 m (492 ft.)
GE MultilinD30 Line Distance Protection System2-17
Page 50
2.2 SPECIFICATIONS2 PRODUCT DESCRIPTION
NOTE
NOTE
NOTE
NOTE
2.2.9 INTER-RELAY COMMUNICATIONS
SHIELDED TWISTED-PAIR INTERFACE OPTIONS
INTERFACE TYPETYPICAL DISTANCE
RS4221200 m
G.703100 m
2
RS422 distance is based on transmitter power
and does not take into consideration the clock
source provided by the user.
LINK POWER BUDGET
EMITTER,
FIBER TYPE
820 nm LED,
Multimode
1300 nm LED,
Multimode
1300 nm ELED,
Singlemode
1300 nm Laser,
Singlemode
1550 nm Laser,
Singlemode
TRANSMIT
POWER
–20 dBm–30 dBm10 dB
–21 dBm–30 dBm9 dB
–23 dBm–32 dBm9 dB
–1 dBm–30 dBm29 dB
+5 dBm–30 dBm35 dB
RECEIVED
SENSITIVITY
These power budgets are calculated from the
manufacturer’s worst-case transmitter power
and worst case receiver sensitivity.
The power budgets for the 1300nm ELED are calculated from the manufacturer's transmitter
power and receiver sensitivity at ambient temperature. At extreme temperatures these values will
deviate based on component tolerance. On average, the output power will decrease as the temperature is increased by a factor 1dB / 5°C.
MAXIMUM OPTICAL INPUT POWER
EMITTER, FIBER TYPEMAX. OPTICAL
820 nm LED, Multimode–7.6 dBm
1300 nm LED, Multimode–11 dBm
1300 nm ELED, Singlemode–14 dBm
1300 nm Laser, Singlemode–14 dBm
1550 nm Laser, Singlemode–14 dBm
INPUT POWER
POWER
BUDGET
TYPICAL LINK DISTANCE
EMITTER TYPECABLE
820 nm LED,
multimode
1300 nm LED,
multimode
1300 nm ELED,
single mode
1300 nm Laser,
single mode
1550 nm Laser,
single-mode
TYPE
62.5/125 μmST1.65 km
62.5/125 μmST3.8 km
9/125 μmST11.4 km
9/125 μmST64 km
9/125 μmST105 km
CONNECTOR
TYPE
TYPICAL
DISTANCE
Typical distances listed are based on the following assumptions for system loss. As
actual losses will vary from one installation to
another, the distance covered by your system
may vary.
CONNECTOR LOSSES (TOTAL OF BOTH ENDS)
ST connector2 dB
FIBER LOSSES
820 nm multimode3 dB/km
1300 nm multimode1 dB/km
1300 nm singlemode0.35 dB/km
1550 nm singlemode0.25 dB/km
Splice losses:One splice every 2 km,
at 0.05 dB loss per splice.
SYSTEM MARGIN
3 dB additional loss added to calculations to compensate for
all other losses.
Compensated difference in transmitting and receiving (channel
asymmetry) channel delays using GPS satellite clock: 10 ms
2.2.10 ENVIRONMENTAL
AMBIENT TEMPERATURES
Storage temperature:–40 to 85°C
Operating temperature: –40 to 60°C; the LCD contrast may be
impaired at temperatures less than –
20°C
OTHER
Altitude:2000 m (maximum)
Pollution degree:II
Overvoltage category:II
Ingress protection:IP20 front, IP10 back
HUMIDITY
Humidity:operating up to 95% (non-condensing) at
55°C (as per IEC60068-2-30 variant 1,
6days).
2-18D30 Line Distance Protection SystemGE Multilin
Page 51
2 PRODUCT DESCRIPTION2.2 SPECIFICATIONS
2.2.11 TYPE TESTS
D30 TYPE TESTS
TESTREFERENCE STANDARDTEST LEVEL
Dielectric voltage withstandEN60255-52.2 kV
Impulse voltage withstandEN60255-55 kV
Damped oscillatoryIEC61000-4-18 / IEC60255-22-12.5 kV CM, 1 kV DM
Power frequency immunityEN61000-4-7 / IEC60255-22-7Class A and B
Voltage interruption and ripple DCIEC60255-1112% ripple, 200 ms interrupts
Radiated and conducted emissionsCISPR11 / CISPR22 / IEC60255-25Class A
Sinusoidal vibrationIEC60255-21-1Class 1
Shock and bumpIEC60255-21-2Class 1
SeismicIEC60255-21-3Class 1
Power magnetic immunityIEC61000-4-8Level 5
Pulse magnetic immunityIEC61000-4-9Level 4
Damped magnetic immunityIEC61000-4-10Level 4
Voltage dip and interruptionIEC61000-4-110, 40, 70, 80% dips; 250 / 300 cycle interrupts
Damped oscillatoryIEC61000-4-122.5 kV CM, 1 kV DM
Conducted RF immunity, 0 to 150 kHz IEC61000-4-16Level 4
Voltage rippleIEC61000-4-1715% ripple
Ingress protectionIEC60529IP40 front, IP10 back
ColdIEC60068-2-1–40°C for 16 hours
HotIEC60068-2-285°C for 16 hours
HumidityIEC60068-2-306 days, variant 1
Damped oscillatoryIEEE/ANSI C37.90.12.5 kV, 1 MHz
RF immunityIEEE/ANSI C37.90.220 V/m, 80 MHz to 1 GHz
SafetyUL508e83849 NKCR
SafetyUL C22.2-14 e83849 NKCR7
SafetyUL1053e83849 NKCR
2
2.2.12 PRODUCTION TESTS
THERMAL
Products go through an environmental test based upon an
Accepted Quality Level (AQL) sampling process.
GE MultilinD30 Line Distance Protection System2-19
Page 52
2
NOTE
2.2 SPECIFICATIONS2 PRODUCT DESCRIPTION
2.2.13 APPROVALS
APPROVALS
COMPLIANCEAPPLICABLE
CE complianceLow voltage directiveEN60255-5
North America---UL508
COUNCIL DIRECTIVE
EMC directiveEN60255-26 / EN50263
---UL1053
---C22.2 No. 14
ACCORDING TO
EN61000-6-5
2.2.14 MAINTENANCE
MOUNTING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds)
of torque.
CLEANING
Normally, cleaning is not required; but for situations where dust
has accumulated on the faceplate display, a dry cloth can be used.
Units that are stored in a de-energized state should be
powered up once per year, for one hour continuously, to
avoid deterioration of electrolytic capacitors.
2-20D30 Line Distance Protection SystemGE Multilin
Page 53
3 HARDWARE3.1 DESCRIPTION
17.56”
[446,02 mm]
9.687”
[246,05 mm]
11.016”
[279,81 mm]
7.460”
[189,48 mm]
6.960”
[176,78 mm]
19.040”
[483,62 mm]
6.995”
[177,67 mm]
842807A1.CDR
3 HARDWARE 3.1DESCRIPTION3.1.1 PANEL CUTOUT
a) HORIZONTAL UNITS
The D30 Line Distance Protection System is available as a 19-inch rack horizontal mount unit with a removable faceplate.
The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains
additional user-programmable pushbuttons and LED indicators.
The modular design allows the relay to be easily upgraded or repaired by a qualified service person. The faceplate is
hinged to allow easy access to the removable modules, and is itself removable to allow mounting on doors with limited rear
depth. There is also a removable dust cover that fits over the faceplate, which must be removed when attempting to access
the keypad or RS232 communications port.
The case dimensions are shown below, along with panel cutout details for panel mounting. When planning the location of
your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or from adjacent
equipment.
The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator
access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws
supplied with the relay.
Figure 3–3: D30 HORIZONTAL MOUNTING AND DIMENSIONS (STANDARD PANEL)
b) VERTICAL UNITS
The D30 Line Distance Protection System is available as a reduced size (¾) vertical mount unit, with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
The modular design allows the relay to be easily upgraded or repaired by a qualified service person. The faceplate is
hinged to allow easy access to the removable modules, and is itself removable to allow mounting on doors with limited rear
depth. There is also a removable dust cover that fits over the faceplate, which must be removed when attempting to access
the keypad or RS232 communications port.
The case dimensions are shown below, along with panel cutout details for panel mounting. When planning the location of
your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or from adjacent
equipment.
3-2D30 Line Distance Protection SystemGE Multilin
Page 55
3 HARDWARE3.1 DESCRIPTION
14.025”
7.482”
15.000”
4.000”
9.780”
11.015”
1.329”
13.560”
843809A1.CDR
The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator
access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws
supplied with the relay.
Figure 3–5: D30 VERTICAL MOUNTING AND DIMENSIONS (STANDARD PANEL)
For details on side mounting D30 devices with the enhanced front panel, refer to the following documents available online
from the GE Multilin website.
•GEK-113180: UR-series UR-V side-mounting front panel assembly instructions.
•GEK-113181: Connecting the side-mounted UR-V enhanced front panel to a vertical UR-series device.
•GEK-113182: Connecting the side-mounted UR-V enhanced front panel to a vertically-mounted horizontal UR-series
device.
For details on side mounting D30 devices with the standard front panel, refer to the figures below.
3-4D30 Line Distance Protection SystemGE Multilin
Page 57
3 HARDWARE3.1 DESCRIPTION
3
Figure 3–6: D30 VERTICAL SIDE MOUNTING INSTALLATION (STANDARD PANEL)
GE MultilinD30 Line Distance Protection System3-5
Page 58
3
WARNING
WARNING
3.1 DESCRIPTION3 HARDWARE
Figure 3–7: D30 VERTICAL SIDE MOUNTING REAR DIMENSIONS (STANDARD PANEL)
3.1.2 MODULE WITHDRAWAL AND INSERTION
Module withdrawal and insertion may only be performed when control power has been removed from the
unit. Inserting an incorrect module type into a slot may result in personal injury, damage to the unit or connected equipment, or undesired operation!
Proper electrostatic discharge protection (for example, a static strap) must be used when coming in contact with modules while the relay is energized!
The relay, being modular in design, allows for the withdrawal and insertion of modules. Modules must only be replaced with
like modules in their original factory configured slots.
The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows
for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens
completely and allows easy access to all modules in the D30.
3-6D30 Line Distance Protection SystemGE Multilin
Page 59
3 HARDWARE3.1 DESCRIPTION
842812A1.CDR
Figure 3–8: UR MODULE WITHDRAWAL AND INSERTION (ENHANCED FACEPLATE)
The standard faceplate can be opened to the left, once the sliding latch on the right side has been pushed up, as shown
below. This allows for easy accessibility of the modules for withdrawal.
Figure 3–9: UR MODULE WITHDRAWAL AND INSERTION (STANDARD FACEPLATE)
To properly remove a module, the ejector/inserter clips, located at the top and bottom of each module, must be pulled
simultaneously. Before performing this action, control power must be removed from the relay. Record the original location of the module to ensure that the same or replacement module is inserted into the correct slot. Modules with current
input provide automatic shorting of external CT circuits.
To properly insert a module, ensure that the correct module type is inserted into the correct slot position. The ejector/
inserter clips located at the top and at the bottom of each module must be in the disengaged position as the module is
smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously.
When the clips have locked into position, the module will be fully inserted.
All CPU modules except the 9E are equipped with 10/100Base-T or 100Base-F Ethernet connectors. These connectors must be individually disconnected from the module before it can be removed from the chassis.
D30D00HCHF8AH6AM6BP8BX7A
000
ZZZZZZ
D
MAZB98000029
D
1998/01/05
Control Power:
Contact Inputs:
Contact Outputs:
88-300V DC @ 35W / 77-265V AC @ 35VA
300V DC Max 10mA
Standard Pilot Duty / 250V AC 7.5A
360V A Resistive / 125V DC Break
4A @ L/R = 40mS / 300W
RATINGS:
D30
Made in
Canada
- M A A B 9 7 0 0 0 0 9 9 -
Line Distance Relay
http://www.GEIndustrial.com/Multilin
GE Multilin
Optional
Ethernet
switch
Optional
direct
input/output
module
CPU module
(Ethernet not
available when
ordered with
Ethernet switch)
Optional
contact
input/output
module
CT/VT
module
Power
supply
module
Tx1
Tx2
Rx1
Rx2
Tx1
Tx2
837771A3.CDR
WARNING
3.1 DESCRIPTION3 HARDWARE
The 4.0x release of the D30 relay includes new hardware modules.The new CPU modules are specified with codes
9E and higher. The new CT/VT modules are specified with the codes 8F and higher.
The new CT/VT modules can only be used with new CPUs; similarly, old CT/VT modules can only be used with old
CPUs. To prevent hardware mismatches, the new modules have blue labels and a warning sticker stating “Attn.:Ensure CPU and DSP module label colors are the same!”. In the event that there is a mismatch between the
CPU and CT/VT module, the relay will not function and a
DSP ERROR or HARDWARE MISMATCH error will be dis-
played.
All other input and output modules are compatible with the new hardware. Firmware versions 4.0x and higher are
only compatible with the new hardware modules. Previous versions of the firmware (3.4x and earlier) are only compatible with the older hardware modules.
3.1.3 REAR TERMINAL LAYOUT
Do not touch any rear terminals while the relay is energized!
The relay follows a convention with respect to terminal number assignments which are three characters long assigned in
order by module slot position, row number, and column letter. Two-slot wide modules take their slot designation from the
first slot position (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following
figure for an example of rear terminal assignments.
This diagram is based on the following order code:
This diagram provides an example of how the
device is wired, not specifically how to wire the
device. Please refer to the Instruction Manual for
additional details on wiring based on various
configurations.
D30-E00-HCL-F8F-H6H-M6K-P6C-U6D-W6A
GE Consumer & Industrial
Multilin
3.2WIRING3.2.1 TYPICAL WIRING
3
3-10D30 Line Distance Protection SystemGE Multilin
Figure 3–12: TYPICAL WIRING DIAGRAM
Page 63
3 HARDWARE3.2 WIRING
CAUTION
NOTE
3.2.2 DIELECTRIC STRENGTH
The dielectric strength of the UR-series module hardware is shown in the following table:
Table 3–1: DIELECTRIC STRENGTH OF UR-SERIES MODULE HARDWARE
MODULE
TYPE
1Power supplyHigh (+); Low (+); (–)Chassis2000 V AC for 1 minute
1Power supply48 V DC (+) and (–)Chassis2000 V AC for 1 minute
1Power supplyRelay terminalsChassis2000 V AC for 1 minute
2ReservedN/AN/AN/A
3ReservedN/AN/AN/A
4ReservedN/AN/AN/A
5Analog inputs/outputsAll except 8bChassis< 50 V DC
6Digital inputs/outputsAllChassis2000 V AC for 1 minute
7
8CT/VTAllChassis2000 V AC for 1 minute
9CPUAllChassis2000 V AC for 1 minute
MODULE FUNCTIONTERMINALSDIELECTRIC STRENGTH
FROMTO
G.703All except 2b, 3a, 7b, 8aChassis2000 V AC for 1 minute
RS422All except 6a, 7b, 8aChassis< 50 V DC
(AC)
Filter networks and transient protection clamps are used in the hardware to prevent damage caused by high peak voltage
transients, radio frequency interference (RFI), and electromagnetic interference (EMI). These protective components canbe damaged by application of the ANSI/IEEE C37.90 specified test voltage for a period longer than the specified one minute.
3
3.2.3 CONTROL POWER
CONTROL POWER SUPPLIED TO THE RELAY MUST BE CONNECTED TO THE MATCHING POWER SUPPLY
RANGE OF THE RELAY. IF THE VOLTAGE IS APPLIED TO THE WRONG TERMINALS, DAMAGE MAY
OCCUR!
The D30 relay, like almost all electronic relays, contains electrolytic capacitors. These capacitors are well
known to be subject to deterioration over time if voltage is not applied periodically. Deterioration can be
avoided by powering the relays up once a year.
The power supply module can be ordered for two possible voltage ranges, with or without a redundant power option. Each
range has a dedicated input connection for proper operation. The ranges are as shown below (see the Technical specifica-tions section of chapter 2 for additional details):
•Low (LO) range: 24 to 48 V (DC only) nominal.
•High (HI) range: 125 to 250 V nominal.
The power supply module provides power to the relay and supplies power for dry contact input connections.
The power supply module provides 48 V DC power for dry contact input connections and a critical failure relay (see the
Typical wiring diagram earlier). The critical failure relay is a form-C device that will be energized once control power is
applied and the relay has successfully booted up with no critical self-test failures. If on-going self-test diagnostic checks
detect a critical failure (see the Self-test errors section in chapter 7) or control power is lost, the relay will de-energize.
For high reliability systems, the D30 has a redundant option in which two D30 power supplies are placed in parallel on the
bus. If one of the power supplies become faulted, the second power supply will assume the full load of the relay without any
interruptions. Each power supply has a green LED on the front of the module to indicate it is functional. The critical fail relay
of the module will also indicate a faulted power supply.
GE MultilinD30 Line Distance Protection System3-11
Page 64
3.2 WIRING3 HARDWARE
AC or DC
NOTE:
14 gauge stranded
wire with suitable
disconnect devices
is recommended.
Heavy copper conductor
or braided wire
Switchgear
ground bus
UR-series
protection system
FILTER
SURGE
–
+
LOW
+
HIGH
B8b B8a B6a B6b B5b
CONTROL
POWER
827759AA.CDR
—
+
OPTIONAL
ETHERNET SWITCH
AC or DC
GND
CAUTION
An LED on the front of the control power module shows the status of the power supply:
LED INDICATIONPOWER SUPPLY
CONTINUOUS ONOK
ON / OFF CYCLINGFailure
OFFFailure
3
Figure 3–13: CONTROL POWER CONNECTION
3.2.4 CT/VT MODULES
A CT/VT module may have voltage inputs on channels 1 through 4 inclusive, or channels 5 through 8 inclusive. Channels 1
and 5 are intended for connection to phase A, and are labeled as such in the relay. Likewise, channels 2 and 6 are intended
for connection to phase B, and channels 3 and 7 are intended for connection to phase C.
Channels 4 and 8 are intended for connection to a single-phase source. For voltage inputs, these channel are labelled as
auxiliary voltage (VX). For current inputs, these channels are intended for connection to a CT between system neutral and
ground, and are labelled as ground current (IG).
Verify that the connection made to the relay nominal current of 1 A or 5 A matches the secondary rating of
the connected CTs. Unmatched CTs may result in equipment damage or inadequate protection.
CT/VT modules may be ordered with a standard ground current input that is the same as the phase current input. Each AC
current input has an isolating transformer and an automatic shorting mechanism that shorts the input when the module is
withdrawn from the chassis. There are no internal ground connections on the current inputs. Current transformers with 1 to
50000 A primaries and 1 A or 5 A secondaries may be used.
CT/VT modules with a sensitive ground input are also available. The ground CT input of the sensitive ground modules is
ten times more sensitive than the ground CT input of standard CT/VT modules. However, the phase CT inputs and phase
VT inputs are the same as those of regular CT/VT modules.
The above modules are available with enhanced diagnostics. These modules can automatically detect CT/VT hardware
failure and take the relay out of service.
CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram.
The exact placement of a zero-sequence core balance CT to detect ground fault current is shown below. Twisted-pair
cabling on the zero-sequence CT is recommended.
3-12D30 Line Distance Protection SystemGE Multilin
Page 65
3 HARDWARE3.2 WIRING
Ground connection to neutral
must be on the source side
The phase voltage channels are used for most metering and protection purposes. The auxiliary voltage channel is used as
input for the synchrocheck and volts-per-hertz features.
Substitute the tilde “~” symbol with the slot position of the module in the following figure.
3
Figure 3–15: CT/VT MODULE WIRING
3.2.5 PROCESS BUS MODULES
The D30 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin
HardFiber system, allowing bi-directional IEC 61850 fiber optic communications with up to eight HardFiber merging units,
known as Bricks. The HardFiber system has been designed to integrate seamlessly with the existing UR-series applications, including protection functions, FlexLogic™, metering, and communications.
The IEC 61850 process bus system offers the following benefits.
•Drastically reduces labor associated with design, installation, and testing of protection and control applications using
the D30 by reducing the number of individual copper terminations.
•Integrates seamlessly with existing D30 applications, since the IEC 61850 process bus interface module replaces the
traditional CT/VT modules.
•Communicates using open standard IEC 61850 messaging.
For additional details on the HardFiber system, refer to GE publication GEK-113500: HardFiber System Instruction Manual.
GE MultilinD30 Line Distance Protection System3-13
Every contact input/output module has 24 terminal connections. They are arranged as three terminals per row, with eight
rows in total. A given row of three terminals may be used for the outputs of one relay. For example, for form-C relay outputs,
the terminals connect to the normally open (NO), normally closed (NC), and common contacts of the relay. For a form-A
output, there are options of using current or voltage detection for feature supervision, depending on the module ordered.
The terminal configuration for contact inputs is different for the two applications.
The contact inputs are grouped with a common return. The D30 has two versions of grouping: four inputs per common
return and two inputs per common return. When a contact input/output module is ordered, four inputs per common is used.
The four inputs per common allows for high-density inputs in combination with outputs, with a compromise of four inputs
sharing one common. If the inputs must be isolated per row, then two inputs per common return should be selected (4D
module).
The tables and diagrams on the following pages illustrate the module types (6A, etc.) and contact arrangements that may
3
be ordered for the relay. Since an entire row is used for a single contact output, the name is assigned using the module slot
position and row number. However, since there are two contact inputs per row, these names are assigned by module slot
position, row number, and column position.
Some form-A / solid-state relay outputs include circuits to monitor the DC voltage across the output contact when it is open,
and the DC current through the output contact when it is closed. Each of the monitors contains a level detector whose output is set to logic “On = 1” when the current in the circuit is above the threshold setting. The voltage monitor is set to “On =
1” when the current is above about 1 to 2.5 mA, and the current monitor is set to “On = 1” when the current exceeds about
80 to 100 mA. The voltage monitor is intended to check the health of the overall trip circuit, and the current monitor can be
used to seal-in the output contact until an external contact has interrupted current flow.
Block diagrams are shown below for form-A and solid-state relay outputs with optional voltage monitor, optional current
monitor, and with no monitoring. The actual values shown for contact output 1 are the same for all contact outputs.
Figure 3–16: FORM-A AND SOLID-STATE CONTACT OUTPUTS WITH VOLTAGE AND CURRENT MONITORING
The operation of voltage and current monitors is reflected with the corresponding FlexLogic™ operands (
CONT OP # VOFF, and CONT OP # ION) which can be used in protection, control, and alarm logic. The typical application of
the voltage monitor is breaker trip circuit integrity monitoring; a typical application of the current monitor is seal-in of the
control command.
3-14D30 Line Distance Protection SystemGE Multilin
CONT OP # VON,
Page 67
3 HARDWARE3.2 WIRING
WARNING
NOTE
NOTE
NOTE
Refer to the Digital elements section of chapter 5 for an example of how form-A and solid-state relay contacts can be
applied for breaker trip circuit integrity monitoring.
Relay contacts must be considered unsafe to touch when the unit is energized! If the relay contacts need to
be used for low voltage accessible applications, it is the customer’s responsibility to ensure proper insulation levels!
USE OF FORM-A AND SOLID-STATE RELAY OUTPUTS IN HIGH IMPEDANCE CIRCUITS
For form-A and solid-state relay output contacts internally equipped with a voltage measuring cIrcuit across the
contact, the circuit has an impedance that can cause a problem when used in conjunction with external high input
impedance monitoring equipment such as modern relay test set trigger circuits. These monitoring circuits may continue to read the form-A contact as being closed after it has closed and subsequently opened, when measured as
an impedance.
The solution to this problem is to use the voltage measuring trigger input of the relay test set, and connect the formA contact through a voltage-dropping resistor to a DC voltage source. If the 48 V DC output of the power supply is
used as a source, a 500 , 10 W resistor is appropriate. In this configuration, the voltage across either the form-A
contact or the resistor can be used to monitor the state of the output.
Wherever a tilde “~” symbol appears, substitute with the slot position of the module; wherever a number
sign “#” appears, substitute the contact number
When current monitoring is used to seal-in the form-A and solid-state relay contact outputs, the FlexLogic™ operand driving the contact output should be given a reset delay of 10 ms to prevent damage of
the output contact (in situations when the element initiating the contact output is bouncing, at values in the
region of the pickup value).
3
Table 3–2: CONTACT INPUT AND OUTPUT MODULE ASSIGNMENTS
~8Solid-State~8Solid-State~8a, ~8c2 Inputs~8Not Used
OUTPUT OR
INPUT
~4B MODULE~4C MODULE~4D MODULE~4L MODULE
OUTPUTTERMINAL
TER MINA L
ASSIGNMENT
ASSIGNMENT
7Not Used~7a, ~7c2 Inputs~72 Outputs
OUTPUT OR
INPUT
OUTPUTTERMINAL
TERMINAL
ASSIGNMENT
ASSIGNMENT
OUTPUTTERMINAL
OUTPUTTERMINAL
ASSIGNMENT
ASSIGNMENT
OUTPUT
OUTPUT
3-16D30 Line Distance Protection SystemGE Multilin
Page 69
3 HARDWARE3.2 WIRING
842762A2.CDR
3
Figure 3–17: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2)
GE MultilinD30 Line Distance Protection System3-17
Page 70
3
DIGITAL I/O
6K
1b
2b
3b
4b
5b
7b
6b
8b
1a
2a
3a
4a
5a
7a
6a
8a
1c
2c
3c
4c
5c
7c
6c
8c
1
5
7
2
6
8
3
4
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
I
V
I
V
I
V
I
V
I
V
I
V
DIGITAL I/O
6P
1b
2b
3b
4b
5b
6b
1a
2a
3a
4a
5a
6a
1c
2c
3c
4c
5c
6c
1
5
2
6
3
4
8a
7b
7a
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
CONTACT IN 7a
CONTACT IN 7c
CONTACT IN 8a
CONTACT IN 8c
COMMON 7b
SURGE
8c
7c
8b
DIGITAL I/O
6U
1b
2b
3b
4b
5b
6b
1a
2a
3a
4a
5a
6a
1c
2c
3c
4c
5c
6c
1
5
2
6
3
4
8a
7b
7a
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
CONTACT IN 7a
CONTACT IN 7c
CONTACT IN 8a
CONTACT IN 8c
COMMON 7b
SURGE
8c
7c
8b
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
I
V
I
V
DIGITAL I/O
6M
1b
2b
3b
4b
5b
6b
1a
2a
3a
4a
5a
6a
1c
2c
3c
4c
5c
6c
1
5
2
6
3
4
8a
7b
7a
CONTACT IN 7a
CONTACT IN 7c
CONTACT IN 8a
CONTACT IN 8c
COMMON 7b
SURGE
8c
7c
8b
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
DIGITAL I/O
6S
1b
2b
3b
4b
5b
6b
1a
2a
3a
4a
5a
6a
1c
2c
3c
4c
5c
6c
1
5
2
6
3
4
8a
7b
7a
CONTACT IN 7a
CONTACT IN 7c
CONTACT IN 8a
CONTACT IN 8c
COMMON 7b
SURGE
8c
7c
8b
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
I
V
I
V
I
V
I
V
DIGITAL I/O
6N
1b
2b
3b
4b
6c
1a
2a
3a
4a
5a
6a
1c
2c
3c
4c
5c
5b
1
2
3
4
8a
7b
7a
CONTACT IN 7a
CONTACT IN 5a
CONTACT IN 7c
CONTACT IN 5c
CONTACT IN 8a
CONTACT IN 6a
CONTACT IN 8c
CONTACT IN 6c
COMMON 7b
COMMON 5b
SURGE
8c
7c
8b
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
DIGITAL I/O
6T
1b
2b
3b
4b
6c
1a
2a
3a
4a
5a
6a
1c
2c
3c
4c
5c
5b
1
2
3
4
8a
7b
7a
CONTACT IN 7a
CONTACT IN 5a
CONTACT IN 7c
CONTACT IN 5c
CONTACT IN 8a
CONTACT IN 6a
CONTACT IN 8c
CONTACT IN 6c
COMMON 7b
COMMON 5b
SURGE
8c
7c
8b
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
I
V
I
V
DIGITAL I/O
6L
1b
2b
3b
4b
6c
1a
2a
3a
4a
5a
6a
1c
2c
3c
4c
5c
5b
1
2
3
4
8a
7b
7a
CONTACT IN 7a
CONTACT IN 5a
CONTACT IN 7c
CONTACT IN 5c
CONTACT IN 8a
CONTACT IN 6a
CONTACT IN 8c
CONTACT IN 6c
COMMON 7b
COMMON 5b
SURGE
8c
7c
8b
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
DIGITAL I/O
6R
1b
2b
3b
4b
6c
1a
2a
3a
4a
5a
6a
1c
2c
3c
4c
5c
5b
1
2
3
4
8a
7b
7a
CONTACT IN 7a
CONTACT IN 5a
CONTACT IN 7c
CONTACT IN 5c
CONTACT IN 8a
CONTACT IN 6a
CONTACT IN 8c
CONTACT IN 6c
COMMON 7b
COMMON 5b
SURGE
8c
7c
8b
842763A2.CDR
CAUTION
3.2 WIRING3 HARDWARE
CORRECT POLARITY MUST BE OBSERVED FOR ALL CONTACT INPUT AND SOLID STATE OUTPUT CONNECTIONS FOR PROPER FUNCTIONALITY.
Figure 3–18: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2)
3-18D30 Line Distance Protection SystemGE Multilin
Page 71
3 HARDWARE3.2 WIRING
827741A4.CDR
CRITICAL
FAILURE
1bB
B
B
B
B
B
B
B
B
B
1a
2b
3a -
3b +
-
5b HI+
6b LO+
6a
8a
8b
48 VDC
OUTPUT
CONTROL
POWER
SURGE
FILTER
POWER SUPPLY 1
24-250V
(Wet)(Dry)
7a
DIGITAL I/O 6B
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~7c
8a
8c
7b
+
-
8b
+
+
+
CONTACT IN 7a
CONTACT IN 7c
CONTACT IN 8a
CONTACT IN 8c
COMMON 7b
SURGE
7a
DIGITAL I/O 6B
7c
8a
8c
7b
+
-
8b
+
+
+
CONTACT IN 7a
CONTACT IN 7c
CONTACT IN 8a
CONTACT IN 8c
COMMON 7b
SURGE
NOTE
CONTACT INPUTS:
A dry contact has one side connected to terminal B3b. This is the positive 48 V DC voltage rail supplied by the power supply module. The other side of the dry contact is connected to the required contact input terminal. Each contact input group
has its own common (negative) terminal which must be connected to the DC negative terminal (B3a) of the power supply
module. When a dry contact closes, a current of 1 to 3 mA will flow through the associated circuit.
A wet contact has one side connected to the positive terminal of an external DC power supply. The other side of this contact
is connected to the required contact input terminal. If a wet contact is used, then the negative side of the external source
must be connected to the relay common (negative) terminal of each contact group. The maximum external source voltage
for this arrangement is 300 V DC.
The voltage threshold at which each group of four contact inputs will detect a closed contact input is programmable as
17 V DC for 24 V sources, 33 V DC for 48 V sources, 84 V DC for 110 to 125 V sources, and 166 V DC for 250 V sources.
3
Figure 3–19: DRY AND WET CONTACT INPUT CONNECTIONS
Wherever a tilde “~” symbol appears, substitute with the slot position of the module.
Contact outputs may be ordered as form-a or form-C. The form-A contacts may be connected for external circuit supervision. These contacts are provided with voltage and current monitoring circuits used to detect the loss of DC voltage in the
circuit, and the presence of DC current flowing through the contacts when the form-A contact closes. If enabled, the current
monitoring can be used as a seal-in signal to ensure that the form-A contact does not attempt to break the energized inductive coil circuit and weld the output contacts.
There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We
recommend using an external DC supply.
GE MultilinD30 Line Distance Protection System3-19
The contact inputs sense a change of the state of the external device contact based on the measured current. When external devices are located in a harsh industrial environment (either outdoor or indoor), their contacts can be exposed to various types of contamination. Normally, there is a thin film of insulating sulfidation, oxidation, or contaminates on the surface
of the contacts, sometimes making it difficult or impossible to detect a change of the state. This film must be removed to
establish circuit continuity – an impulse of higher than normal current can accomplish this.
The contact inputs with auto-burnish create a high current impulse when the threshold is reached to burn off this oxidation
layer as a maintenance to the contacts. Afterwards the contact input current is reduced to a steady-state current. The
impulse will have a 5 second delay after a contact input changes state.
3
Figure 3–20: CURRENT THROUGH CONTACT INPUTS WITH AUTO-BURNISHING
Regular contact inputs limit current to less than 3 mA to reduce station battery burden. In contrast, contact inputs with autoburnishing allow currents up to 50 to 70 mA at the first instance when the change of state was sensed. Then, within 25 to
50 ms, this current is slowly reduced to 3 mA as indicated above. The 50 to 70 mA peak current burns any film on the contacts, allowing for proper sensing of state changes. If the external device contact is bouncing, the auto-burnishing starts
when external device contact bouncing is over.
Another important difference between the auto-burnishing input module and the regular input modules is that only two contact inputs have common ground, as opposed to four contact inputs sharing one common ground (refer to the Contact Inputand Output Module Wiring diagrams). This is beneficial when connecting contact inputs to separate voltage sources. Consequently, the threshold voltage setting is also defined per group of two contact inputs.
The auto-burnish feature can be disabled or enabled using the DIP switches found on each daughter card. There is a DIP
switch for each contact, for a total of 16 inputs.
Figure 3–21: AUTO-BURNISH DIP SWITCHES
The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, the auto-burnish
functionality can be checked using an oscilloscope.
3-20D30 Line Distance Protection SystemGE Multilin
Page 73
3 HARDWARE3.2 WIRING
NOTE
3.2.7 TRANSDUCER INPUTS/OUTPUTS
Transducer input modules can receive input signals from external dcmA output transducers (dcmA In) or resistance temperature detectors (RTD). Hardware and software is provided to receive signals from these external transducers and convert these signals into a digital format for use as required.
Transducer output modules provide DC current outputs in several standard dcmA ranges. Software is provided to configure
virtually any analog quantity used in the relay to drive the analog outputs.
Every transducer input/output module has a total of 24 terminal connections. These connections are arranged as three terminals per row with a total of eight rows. A given row may be used for either inputs or outputs, with terminals in column "a"
having positive polarity and terminals in column "c" having negative polarity. Since an entire row is used for a single input/
output channel, the name of the channel is assigned using the module slot position and row number.
Each module also requires that a connection from an external ground bus be made to terminal 8b. The current outputs
require a twisted-pair shielded cable, where the shield is grounded at one end only. The figure below illustrates the transducer module types (5A, 5C, 5D, 5E, and 5F) and channel arrangements that may be ordered for the relay.
Wherever a tilde “~” symbol appears, substitute with the slot position of the module.
GE MultilinD30 Line Distance Protection System3-21
Page 74
3.2 WIRING3 HARDWARE
NOTE
NOTE
3.2.8 RS232 FACEPLATE PORT
A 9-pin RS232C serial port is located on the D30 faceplate for programming with a personal computer. All that is required to
use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for the
RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
The baud rate for this port is fixed at 19200 bps.
3
Figure 3–23: RS232 FACEPLATE PORT CONNECTION
3.2.9 CPU COMMUNICATION PORTS
a) OPTIONS
In addition to the faceplate RS232 port, the D30 provides two additional communication ports or a managed six-port Ethernet switch, depending on the installed CPU module.
The CPU modules do not require a surge ground connection.
Table 3–3: CPU MODULE COMMUNICATIONS
CPU TYPECOM1COM2
9ERS485RS485
9G10Base-F and 10Base-TRS485
9HRedundant 10Base-FRS485
9J100Base-FXRS485
9KRedundant 100Base-FXRS485
9L100Base-FXRS485
9MRedundant 100Base-FXRS485
3-22D30 Line Distance Protection SystemGE Multilin
Page 75
3 HARDWARE3.2 WIRING
1250$/
$/7(51$7(
&20
%DVH)/
%DVH)
%DVH7
7[
5[
7[
5[
&20021
³
³
'D
'D
'D
'E
'D
%1&
%1&
,5,*%RXWSXW
,5,*%
LQSXW
&38+
&RD[LDOFDEOH
&RD[LDOFDEOH
6KLHOGHG
WZLVWHGSDLUV
00ILEHU
RSWLFFDEOH
*URXQGDW
UHPRWH
GHYLFH
56
&20
%DVH)/
7[
5[
&20021
³
³
'D
'D
'D
'E
'D
%1&
%1&
,5,*%RXWSXW
,5,*%
LQSXW
&38
56
&20
-
&201250$/
&RD[LDOFDEOH
&RD[LDOFDEOH
00ILEHU
RSWLFFDEOH
*URXQGDW
UHPRWH
GHYLFH
1250$/
$/7(51$7(
&20
%DVH)/
%DVH)
7[
5[
7[
5[
&20021
³
³
'D
'D
'D
'E
'D
%1&
%1&
,5,*%RXWSXW
,5,*%
LQSXW
&38.
&RD[LDOFDEOH
&RD[LDOFDEOH
6KLHOGHGWZLVWHGSDLUV
00ILEHURSWLFFDEOH
*URXQGDW
UHPRWH
GHYLFH
56
&20
%DVH)/
&20021
³
³
'D
'D
'D
'E
'D
%1&
%1&
,5,*%RXWSXW
,5,*%
LQSXW
&38
56
&20
/
&201250$/
&RD[LDOFDEOH
&RD[LDOFDEOH
60ILEHU
RSWLFFDEOH
*URXQGDW
UHPRWH
GHYLFH
1250$/
$/7(51$7(
&20
%DVH)/
%DVH)
&20021
³
³
'D
'D
'D
'E
'D
%1&
%1&
,5,*%RXWSXW
,5,*%
LQSXW
&380
&RD[LDOFDEOH
&RD[LDOFDEOH
6KLHOGHGWZLVWHGSDLUV
60ILEHURSWLFFDEOH
*URXQGDW
UHPRWH
GHYLFH
56
&20
&20021
³
³
'D
'D
'D
'E
'D
%1&
%1&
,5,*%RXWSXW
,5,*%
LQSXW
&38(
56
&20
&20021
³
'E
'E
'E
56
&20
*URXQGDW
UHPRWH
GHYLFH
&RD[LDOFDEOH
&RD[LDOFDEOH
6KLHOGHGWZLVWHGSDLUV
1250$/
&20
%DVH)/
%DVH7
7[
5[
&20021
³
³
'D
'D
'D
'E
'D
%1&
%1&
,5,*%RXWSXW
,5,*%
LQSXW
&38*
56
&20
6KLHOGHGWZLVWHGSDLUV
&RD[LDOFDEOH
&RD[LDOFDEOH
00ILEHU
RSWLFFDEOH
*URXQGDW
UHPRWH
GHYLFH
$&'5
&386
&20021
³
³
'D
'D
'D
'E
'D
%1&
%1&
,5,*%RXWSXW
,5,*%
LQSXW
&RD[LDOFDEOH
&RD[LDOFDEOH
6KLHOGHGWZLVWHGSDLUV
*URXQGDW
UHPRWH
GHYLFH
56
&20
3
b) RS485 PORTS
RS485 data transmission and reception are accomplished over a single twisted pair with transmit and receive data alternating over the same two wires. Through the use of these ports, continuous monitoring and control from a remote computer,
Figure 3–24: CPU MODULE COMMUNICATIONS WIRING
SCADA system or PLC is possible.
To minimize errors from noise, the use of shielded twisted pair wire is recommended. Correct polarity must also be
observed. For instance, the relays must be connected with all RS485 “+” terminals connected together, and all RS485 “–”
terminals connected together. Though data is transmitted over a two-wire twisted pair, all RS485 devices require a shared
reference, or common voltage. This common voltage is implied to be a power supply common. Some systems allow the
shield (drain wire) to be used as common wire and to connect directly to the D30 COM terminal (#3); others function correctly only if the common wire is connected to the D30 COM terminal, but insulated from the shield.
To avoid loop currents, the shield should be grounded at only one point. If other system considerations require the shield to
be grounded at more than one point, install resistors (typically 100 ohms) between the shield and ground at each grounding
point. Each relay should also be daisy-chained to the next one in the link. A maximum of 32 relays can be connected in this
GE MultilinD30 Line Distance Protection System3-23
Page 76
3.2 WIRING3 HARDWARE
CAUTION
CAUTION
manner without exceeding driver capability. For larger systems, additional serial channels must be added. It is also possible
to use commercially available repeaters to have more than 32 relays on a single channel. Star or stub connections should
be avoided entirely.
Lightning strikes and ground surge currents can cause large momentary voltage differences between remote ends of the
communication link. For this reason, surge protection devices are internally provided at both communication ports. An isolated power supply with an optocoupled data interface also acts to reduce noise coupling. To ensure maximum reliability, all
equipment should have similar transient protection devices installed.
Both ends of the RS485 circuit should also be terminated with an impedance as shown below.
3
Figure 3–25: RS485 SERIAL CONNECTION
c) 10BASE-FL AND 100BASE-FX FIBER OPTIC PORTS
ENSURE THE DUST COVERS ARE INSTALLED WHEN THE FIBER IS NOT IN USE. DIRTY OR SCRATCHED
CONNECTORS CAN LEAD TO HIGH LOSSES ON A FIBER LINK.
OBSERVING ANY FIBER TRANSMITTER OUTPUT MAY CAUSE INJURY TO THE EYE.
The fiber optic communication ports allow for fast and efficient communications between relays at 10 Mbps or 100 Mbps.
Optical fiber may be connected to the relay supporting a wavelength of 820 nm in multi-mode or 1310 nm in multi-mode
and single-mode. The 10 Mbps rate is available for CPU modules 9G and 9H; 100Mbps is available for modules 9H, 9J, 9K,
9L, 9M, 9N, 9P, and 9R. The 9H, 9K, 9M, and 9R modules have a second pair of identical optical fiber transmitter and
receiver for redundancy.
The optical fiber sizes supported include 50/125 µm, 62.5/125 µm and 100/140 µm for 10 Mbps. The fiber optic port is
designed such that the response times will not vary for any core that is 100 µm or less in diameter, 62.5 µm for 100 Mbps.
For optical power budgeting, splices are required every 1 km for the transmitter/receiver pair. When splicing optical fibers,
the diameter and numerical aperture of each fiber must be the same. In order to engage or disengage the ST type connector, only a quarter turn of the coupling is required.
3-24D30 Line Distance Protection SystemGE Multilin
Page 77
3 HARDWARE3.2 WIRING
RELAY
BNC (IN)
RECEIVER
RG58/59 COAXIAL CABLE
GPS SATELLITE SYSTEM
GPS CONNECTION
OPTIONAL
IRIG-B(-)
4A
+
-
827756A5.CDR
IRIG-B
TIME CODE
GENERATOR
(DC SHIFT OR
AMPLITUDE MODULATED
SIGNAL CAN BE USED)
4B
IRIG-B(+)
BNC (OUT)
REPEATER
TO OTHER DEVICES
(DC-SHIFT ONLY)
NOTE
3.2.10 IRIG-B
IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices within
1 millisecond. The IRIG time code formats are serial, width-modulated codes which can be either DC level shifted or amplitude modulated (AM). Third party equipment is available for generating the IRIG-B signal; this equipment may use a GPS
satellite system to obtain the time reference so that devices at different geographic locations can also be synchronized.
3
Figure 3–26: IRIG-B CONNECTION
The IRIG-B repeater provides an amplified DC-shift IRIG-B signal to other equipment. By using one IRIG-B serial connection, several UR-series relays can be synchronized. The IRIG-B repeater has a bypass function to maintain the time signal
even when a relay in the series is powered down.
Figure 3–27: IRIG-B REPEATER
Using an amplitude modulated receiver will cause errors up to 1 ms in event time-stamping.
GE MultilinD30 Line Distance Protection System3-25
The D30 direct inputs and outputs feature makes use of the type 7 series of communications modules. These modules are
also used by the L90 Line Differential Relay for inter-relay communications. The direct input and output feature uses the
communications channels provided by these modules to exchange digital state information between relays. This feature is
available on all UR-series relay models except for the L90 Line Differential relay.
The communications channels are normally connected in a ring configuration as shown below. The transmitter of one module is connected to the receiver of the next module. The transmitter of this second module is then connected to the receiver
of the next module in the ring. This is continued to form a communications ring. The figure below illustrates a ring of four
UR-series relays with the following connections: UR1-Tx to UR2-Rx, UR2-Tx to UR3-Rx, UR3-Tx to UR4-Rx, and UR4-Tx
to UR1-Rx. A maximum of sixteen (16) UR-series relays can be connected in a single ring
3
Figure 3–28: DIRECT INPUT AND OUTPUT SINGLE CHANNEL CONNECTION
The interconnection for dual-channel Type 7 communications modules is shown below. Two channel modules allow for a
redundant ring configuration. That is, two rings can be created to provide an additional independent data path. The required
connections are: UR1-Tx1 to UR2-Rx1, UR2-Tx1 to UR3-Rx1, UR3-Tx1 to UR4-Rx1, and UR4-Tx1 to UR1-Rx1 for the first
ring; and UR1-Tx2 to UR4-Rx2, UR4-Tx2 to UR3-Rx2, UR3-Tx2 to UR2-Rx2, and UR2-Tx2 to UR1-Rx2 for the second
ring.
The following diagram shows the connection for three UR-series relays using two independent communication channels.
UR1 and UR3 have single type 7 communication modules; UR2 has a dual-channel module. The two communication channels can be of different types, depending on the Type 7 modules used. To allow the direct input and output data to cross-over from channel 1 to channel 2 on UR2, the
forces UR2 to forward messages received on Rx1 out Tx2, and messages received on Rx2 out Tx1.
3-26D30 Line Distance Protection SystemGE Multilin
Figure 3–29: DIRECT INPUT AND OUTPUT DUAL CHANNEL CONNECTION
DIRECT I/O CHANNEL CROSSOVER setting should be “Enabled” on UR2. This
Page 79
842013A1.CDR
Tx
Tx
UR #1
Channel #1
Channel #2
UR #2
UR #3
Rx
Rx
Tx1
Tx2
Rx1
Rx2
NOTE
3 HARDWARE3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS
3
Figure 3–30: DIRECT INPUT AND OUTPUT SINGLE/DUAL CHANNEL COMBINATION CONNECTION
The interconnection requirements are described in further detail in this section for each specific variation of type 7 communications module. These modules are listed in the following table. All fiber modules use ST type connectors.
Not all the direct input and output communications modules may be applicable to the D30 relay. Only the modules
specified in the order codes are available as direct input and output communications modules.
Table 3–4: CHANNEL COMMUNICATION OPTIONS (Sheet 1 of 2)
OBSERVING ANY FIBER TRANSMITTER OUTPUT MAY CAUSE INJURY TO THE EYE.
3
3.3.2 FIBER: LED AND ELED TRANSMITTERS
The following figure shows the configuration for the 7A, 7B, 7C, 7H, 7I, and 7J fiber-only modules.
The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser module.
When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maximum optical input power to the receiver.
Figure 3–31: LED AND ELED FIBER MODULES
3.3.3 FIBER-LASER TRANSMITTERS
Figure 3–32: LASER FIBER MODULES
3-28D30 Line Distance Protection SystemGE Multilin
Page 81
3 HARDWARE3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS
842773A2.CDR
X
X
X
X
X
X
X
X
X
X
X
X
8a
8b
7S
Rx +
Tx +
Shield
Tx –
Shield
Rx –
Tx –
Rx +
Tx +
Rx –
Inter-relay communications
2b
6a
7a
1b
1a
3a
6b
7b
2a
3b
G.703
channel 2
G.703
channel 1
Surge
Surge
831727A3.CDR
X
X
X
X
X
X
X
X
X
X
X
X
8a
8b
7S
Rx +
Tx +
Shld.
Tx -
Shld.
Rx -
Tx -
Rx +
Tx +
Rx -
COMM.
2b
6a
7a
1b
1a
3a
6b
7b
2a
3b
G.703
CHANNEL 2
G.703
CHANNEL 1
SURGE
SURGE
X
X
X
X
X
X
X
X
X
X
X
X
8a
8b
7S
Rx +
Tx +
Shld.
Tx -
Shld.
Rx -
Tx -
Rx +
Tx +
Rx -
COMM.
2b
6a
7a
1b
1a
3a
6b
7b
2a
3b
G.703
CHANNEL 2
G.703
CHANNEL 1
SURGE
SURGE
NOTE
3.3.4 G.703 INTERFACE
a) DESCRIPTION
The following figure shows the 64K ITU G.703 co-directional interface configuration.
The G.703 module is fixed at 64 kbps. The
SETTINGS PRODUCT SETUP DIRECT I/O DIRECT I/O DATA RATE
setting is not applicable to this module.
AWG 24 twisted shielded pair is recommended for external connections, with the shield grounded only at one end. Connecting the shield to pin X1a or X6a grounds the shield since these pins are internally connected to ground. Thus, if pin X1a
or X6a is used, do not ground at the other end. This interface module is protected by surge suppression devices.
3
Figure 3–33: G.703 INTERFACE CONFIGURATION
The following figure shows the typical pin interconnection between two G.703 interfaces. For the actual physical arrangement of these pins, see the Rear terminal assignments section earlier in this chapter. All pin interconnections are to be
maintained for a connection to a multiplexer.
Figure 3–34: TYPICAL PIN INTERCONNECTION BETWEEN TWO G.703 INTERFACES
Pin nomenclature may differ from one manufacturer to another. Therefore, it is not uncommon to see pinouts numbered TxA, TxB, RxA and RxB. In such cases, it can be assumed that “A” is equivalent to “+” and
“B” is equivalent to “–”.
b) G.703 SELECTION SWITCH PROCEDURES
1.Remove the G.703 module (7R or 7S). The ejector/inserter clips located at the top and at the bottom of each module,
must be pulled simultaneously in order to release the module for removal. Before performing this action, controlpower must be removed from the relay. The original location of the module should be recorded to help ensure that
the same or replacement module is inserted into the correct slot.
2.Remove the module cover screw.
3.Remove the top cover by sliding it towards the rear and then lift it upwards.
4.Set the timing selection switches (channel 1, channel 2) to the desired timing modes.
5.Replace the top cover and the cover screw.
GE MultilinD30 Line Distance Protection System3-29
Page 82
3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS3 HARDWARE
6.Re-insert the G.703 module. Take care to ensure that the correct module type is inserted into the correct slot position.
The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged position as
the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the
clips simultaneously. When the clips have locked into position, the module will be fully inserted.
If octet timing is enabled (on), this 8 kHz signal will be asserted during the violation of bit 8 (LSB) necessary for connecting
to higher order systems. When D30s are connected back to back, octet timing should be disabled (off).
d) G.703 TIMING MODES
There are two timing modes for the G.703 module: internal timing mode and loop timing mode (default).
•Internal Timing Mode: The system clock is generated internally. Therefore, the G.703 timing selection should be in
the internal timing mode for back-to-back (UR-to-UR) connections. For back-to-back connections, set for octet timing
(S1 = OFF) and timing mode to internal timing (S5 = ON and S6 = OFF).
•Loop Timing Mode: The system clock is derived from the received line signal. Therefore, the G.703 timing selection
should be in loop timing mode for connections to higher order systems. For connection to a higher order system (URto-multiplexer, factory defaults), set to octet timing (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 =
OFF).
ON octet timing 8 kHz
S5 = ON and S6 = OFF internal timing mode
S5 = OFF and S6 = ON minimum remote loopback mode
S5 = ON and S6 = ON dual loopback mode
3-30D30 Line Distance Protection SystemGE Multilin
Page 83
3 HARDWARE3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS
842752A1.CDR
DMR
DMX
G7X
G7R
DMR = Differential Manchester Receiver
DMX = Differential Manchester Transmitter
G7X = G.703 Transmitter
G7R = G.703 Receiver
842774A1.CDR
DMR
DMX
G7X
G7R
DMR = Differential Manchester Receiver
DMX = Differential Manchester Transmitter
G7X = G.703 Transmitter
G7R = G.703 Receiver
842775A1.CDR
The switch settings for the internal and loop timing modes are shown below:
e) G.703 TEST MODES
In minimum remote loopback mode, the multiplexer is enabled to return the data from the external interface without any
processing to assist in diagnosing G.703 line-side problems irrespective of clock rate. Data enters from the G.703 inputs,
passes through the data stabilization latch which also restores the proper signal polarity, passes through the multiplexer
and then returns to the transmitter. The differential received data is processed and passed to the G.703 transmitter module
after which point the data is discarded. The G.703 receiver module is fully functional and continues to process data and
passes it to the differential Manchester transmitter module. Since timing is returned as it is received, the timing source is
expected to be from the G.703 line side of the interface.
3
Figure 3–36: G.703 MINIMUM REMOTE LOOPBACK MODE
In dual loopback mode, the multiplexers are active and the functions of the circuit are divided into two with each receiver/
transmitter pair linked together to deconstruct and then reconstruct their respective signals. Differential Manchester data
enters the Differential Manchester receiver module and then is returned to the differential Manchester transmitter module.
Likewise, G.703 data enters the G.703 receiver module and is passed through to the G.703 transmitter module to be
returned as G.703 data. Because of the complete split in the communications path and because, in each case, the clocks
are extracted and reconstructed with the outgoing data, in this mode there must be two independent sources of timing. One
source lies on the G.703 line side of the interface while the other lies on the differential Manchester side of the interface.
Figure 3–37: G.703 DUAL LOOPBACK MODE
GE MultilinD30 Line Distance Protection System3-31
Page 84
3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS3 HARDWARE
~
~
~
~
~
~
~
~
~
~
~
~
~
~
Shield
Shield
COM
Tx +
Tx +
Tx –
Tx –
Rx –
Rx –
Rx +
Rx +
3b
5b
2a
4a
6a
7b
8b
Clock
RS422
channel 1
RS422
channel 2
Surge
3a
5a
4b
6b
7a
2b
8a
Inter-relay communications7W
842776A3.CDR
Dual-channel RS422 module
~
~
~
~
~
Shield
Tx +
Tx –
Rx –
Rx +
3b
2a
6a
RS422
3a
4b
~
~
~
~
COM
8b
Clock
Surge
7a
2b
8a
Inter-relay comms.7T
Single-channel RS422 module
~ indicates the slot position
3.3.5 RS422 INTERFACE
a) DESCRIPTION
There are two RS422 inter-relay communications modules available: single-channel RS422 (module 7T) and dual-channel
RS422 (module 7W). The modules can be configured to run at 64 kbps or 128 kbps. AWG 24 twisted shielded pair cable is
recommended for external connections. These modules are protected by optically-isolated surge suppression devices.
The shield pins (6a and 7b) are internally connected to the ground pin (8a). Proper shield termination is as follows:
•Site 1: Terminate shield to pins 6a or 7b or both.
•Site 2: Terminate shield to COM pin 2b.
The clock terminating impedance should match the impedance of the line.
3
The following figure shows the typical pin interconnection between two single-channel RS422 interfaces installed in slot W.
All pin interconnections are to be maintained for a connection to a multiplexer.
b) TWO-CHANNEL APPLICATION VIA MULTIPLEXERS
The RS422 interface may be used for single channel or two channel applications over SONET/SDH or multiplexed systems. When used in single-channel applications, the RS422 interface links to higher order systems in a typical fashion
observing transmit (Tx), receive (Rx), and send timing (ST) connections. However, when used in two-channel applications,
certain criteria must be followed since there is one clock input for the two RS422 channels. The system will function correctly if the following connections are observed and your data module has a terminal timing feature. Terminal timing is a
common feature to most synchronous data units that allows the module to accept timing from an external source. Using the
terminal timing feature, two channel applications can be achieved if these connections are followed: The send timing outputs from the multiplexer (data module 1), will connect to the clock inputs of the UR–RS422 interface in the usual fashion.
In addition, the send timing outputs of data module 1 will also be paralleled to the terminal timing inputs of data module 2.
By using this configuration, the timing for both data modules and both UR–RS422 channels will be derived from a single
clock source. As a result, data sampling for both of the UR–RS422 channels will be synchronized via the send timing leads
on data module 1 as shown below. If the terminal timing feature is not available or this type of connection is not desired, the
G.703 interface is a viable option that does not impose timing restrictions.
3-32D30 Line Distance Protection SystemGE Multilin
Figure 3–38: RS422 INTERFACE CONNECTIONS
Figure 3–39: TYPICAL PIN INTERCONNECTION BETWEEN TWO RS422 INTERFACES
Page 85
3 HARDWARE3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS
Data module 1
Data module 2
Signal name
Signal name
SD(A) - Send data
TT(A) - Terminal timing
TT(B) - Terminal timing
SD(B) - Send data
RD(A) - Received data
RD(A) - Received data
SD(A) - Send data
SD(B) - Send data
RD(B) - Received data
RD(B) - Received data
RS(A) - Request to send (RTS)
RS(A) - Request to send (RTS)
RT(A) - Receive timing
CS(A) - Clear To send
CS(A) - Clear To send
RT(B) - Receive timing
CS(B) - Clear To send
CS(B) - Clear To send
Local loopback
Local loopback
Remote loopback
Remote loopback
Signal ground
Signal ground
ST(A) - Send timing
ST(A) - Send timing
ST(B) - Send timing
ST(B) - Send timing
RS(B) - Request to send (RTS)
RS(B) - Request to send (RTS)
831022A3.CDR
W
7a
W
2b
W
8a
7W
Shld.
Shld.
Tx1(+)
Tx2(+)
Tx1(-)
Tx2(-)
Rx1(+)
Rx2(+)
+
com
Rx1(-)
Rx2(-)
–
INTER-RELAY COMMUNICATIONS
W
3a
W
5b
W
5a
W
3b
W
2a
W
6a
W
6b
W
7b
W
8b
W
4b
W
4a
RS422
CHANNEL 1
RS422
CHANNEL 2
CLOCK
SURGE
Tx Clock
Tx Data
3
Figure 3–40: TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, 3-TERMINAL APPLICATION
Data module 1 provides timing to the D30 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides
timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been
omitted in the figure above since they may vary depending on the manufacturer.
c) TRANSMIT TIMING
The RS422 interface accepts one clock input for transmit timing. It is important that the rising edge of the 64 kHz transmit
timing clock of the multiplexer interface is sampling the data in the center of the transmit data window. Therefore, it is important to confirm clock and data transitions to ensure proper system operation. For example, the following figure shows the
positive edge of the Tx clock in the center of the Tx data bit.
d) RECEIVE TIMING
The RS422 interface utilizes NRZI-MARK modulation code and; therefore, does not rely on an Rx clock to recapture data.
NRZI-MARK is an edge-type, invertible, self-clocking code.
GE MultilinD30 Line Distance Protection System3-33
Figure 3–41: CLOCK AND DATA TRANSITIONS
Page 86
3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS3 HARDWARE
WARNING
~
~
~
~
~
~
~
~
~
Shield
COM
Tx1 +
Tx1 –
Rx1 –
Rx1 +
1a
2b
3a
4b
Fiber
channel 2
Clock
(channel 1)
RS422
channel 1
Surge
1b
2a
3b
6a
8a
Tx2
Rx2
Inter-relay comms.7L, 7M, 7N, 7P, 74
842777A1.CDR
WARNING
~
~
~
~
~
~
Shield
Tx –
Tx +
Rx –
Rx +
1a
2a
3a
Fiber
channel 2
G.703
channel 1
Surge
1b
2b
3b
Tx2
Rx2
Inter-relay
communications
7E, 7F, 7G,
7Q,75
842778A1.CDR
To recover the Rx clock from the data-stream, an integrated DPLL (digital phase lock loop) circuit is utilized. The DPLL is
driven by an internal clock, which is 16-times over-sampled, and uses this clock along with the data-stream to generate a
data clock that can be used as the SCC (serial communication controller) receive clock.
3.3.6 RS422 AND FIBER INTERFACE
The following figure shows the combined RS422 plus Fiber interface configuration at 64K baud. The 7L, 7M, 7N, 7P, and 74
modules are used in two-terminal with a redundant channel or three-terminal configurations where channel 1 is employed
via the RS422 interface (possibly with a multiplexer) and channel 2 via direct fiber.
AWG 24 twisted shielded pair is recommended for external RS422 connections and the shield should be grounded only at
one end. For the direct fiber channel, power budget issues should be addressed properly.
When using a LASER Interface, attenuators may be necessary to ensure that you do not exceed maximum
3
optical input power to the receiver.
Figure 3–42: RS422 AND FIBER INTERFACE CONNECTION
Connections shown above are for multiplexers configured as DCE (data communications equipment) units.
3.3.7 G.703 AND FIBER INTERFACE
The figure below shows the combined G.703 plus fiber interface configuration at 64 kbps. The 7E, 7F, 7G, 7Q, and 75 modules are used in configurations where channel 1 is employed via the G.703 interface (possibly with a multiplexer) and channel 2 via direct fiber. AWG 24 twisted shielded pair is recommended for external G.703 connections connecting the shield to
pin 1a at one end only. For the direct fiber channel, power budget issues should be addressed properly. See previous sections for additional details on the G.703 and fiber interfaces.
When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maximum optical input power to the receiver.
3-34D30 Line Distance Protection SystemGE Multilin
Figure 3–43: G.703 AND FIBER INTERFACE CONNECTION
Page 87
3 HARDWARE3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS
842753A1.CDR
3.3.8 IEEE C37.94 INTERFACE
The UR-series IEEE C37.94 communication modules (modules types 76, and 77) are designed to interface with IEEE
C37.94 compliant digital multiplexers or an IEEE C37.94 compliant interface converter for use with direct input and output
applications for firmware revisions 3.30 and higher. The IEEE C37.94 standard defines a point-to-point optical link for synchronous data between a multiplexer and a teleprotection device. This data is typically 64 kbps, but the standard provides
for speeds up to 64n kbps, where n = 1, 2,…, 12. The UR-series C37.94 communication modules are either 64 kbps (with n
fixed at 1) for 128 kbps (with n fixed at 2). The frame is a valid International Telecommunications Union (ITU-T) recommended G.704 pattern from the standpoint of framing and data rate. The frame is 256 bits and is repeated at a frame rate of
8000 Hz, with a resultant bit rate of 2048 kbps.
The specifications for the module are as follows:.
•IEEE standard: C37.94 for 2 64 kbps optical fiber interface (for 76 and 77 modules).
•Fiber optic cable type: 50 mm or 62.5 mm core diameter optical fiber.
•Fiber optic mode: multi-mode.
•Fiber optic cable length: up to 2 km.
•Fiber optic connector: type ST.
•Wavelength: 830 ±40 nm.
•Connection: as per all fiber optic connections, a Tx to Rx connection is required.
The UR-series C37.94 communication module can be connected directly to any compliant digital multiplexer that supports
the IEEE C37.94 standard as shown below.
3
The UR-series C37.94 communication module can be connected to the electrical interface (G.703, RS422, or X.21) of a
non-compliant digital multiplexer via an optical-to-electrical interface converter that supports the IEEE C37.94 standard, as
shown below.
The UR-series C37.94 communication module has six (6) switches that are used to set the clock configuration. The functions of these control switches is shown below.
For the internal timing mode, the system clock is generated internally. therefore, the timing switch selection should be internal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
GE MultilinD30 Line Distance Protection System3-35
Page 88
3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS3 HARDWARE
For the looped timing mode, the system clock is derived from the received line signal. Therefore, the timing selection
should be in loop timing mode for connections to higher order systems.
The IEEE C37.94 communications module cover removal procedure is as follows:
1.Remove the IEEE C37.94 module (type 76 or 77 module):
The ejector/inserter clips located at the top and at the bottom of each module, must be pulled simultaneously in order
to release the module for removal. Before performing this action, control power must be removed from the relay.
The original location of the module should be recorded to help ensure that the same or replacement module is inserted
into the correct slot.
2.Remove the module cover screw.
3.Remove the top cover by sliding it towards the rear and then lift it upwards.
4.Set the timing selection switches (channel 1, channel 2) to the desired timing modes (see description above).
3
5.Replace the top cover and the cover screw.
6.Re-insert the IEEE C37.94 module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged position as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted.
3-36D30 Line Distance Protection SystemGE Multilin
Page 89
3 HARDWARE3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS
842753A1.CDR
3.3.9 C37.94SM INTERFACE
The UR-series C37.94SM communication modules (2A and 2B) are designed to interface with modified IEEE C37.94 compliant digital multiplexers or IEEE C37.94 compliant interface converters that have been converted from 820 nm multi-mode
fiber optics to 1300 nm ELED single-mode fiber optics. The IEEE C37.94 standard defines a point-to-point optical link for
synchronous data between a multiplexer and a teleprotection device. This data is typically 64 kbps, but the standard provides for speeds up to 64n kbps, where n = 1, 2,…, 12. The UR-series C37.94SM communication module is 64 kbps only
with n fixed at 1. The frame is a valid International Telecommunications Union (ITU-T) recommended G.704 pattern from
the standpoint of framing and data rate. The frame is 256 bits and is repeated at a frame rate of 8000 Hz, with a resultant bit
rate of 2048 kbps.
The specifications for the module are as follows:
•Emulated IEEE standard: emulates C37.94 for 1 64 kbps optical fiber interface (modules set to n = 1 or 64 kbps).
•Fiber optic mode: single-mode, ELED compatible with HP HFBR-1315T transmitter and HP HFBR-2316T receiver.
•Fiber optic cable length: up to 10 km.
•Fiber optic connector: type ST.
•Wavelength: 1300 ±40 nm.
•Connection: as per all fiber optic connections, a Tx to Rx connection is required.
The UR-series C37.94SM communication module can be connected directly to any compliant digital multiplexer that supports C37.94SM as shown below.
3
It can also can be connected directly to any other UR-series relay with a C37.94SM module as shown below.
The UR-series C37.94SM communication module has six (6) switches that are used to set the clock configuration. The
functions of these control switches is shown below.
For the internal timing mode, the system clock is generated internally. Therefore, the timing switch selection should be
internal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
GE MultilinD30 Line Distance Protection System3-37
Page 90
3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS3 HARDWARE
For the looped timing mode, the system clock is derived from the received line signal. Therefore, the timing selection
should be in loop timing mode for connections to higher order systems.
The C37.94SM communications module cover removal procedure is as follows:
1.Remove the C37.94SM module (modules 2A or 2B):
The ejector/inserter clips located at the top and at the bottom of each module, must be pulled simultaneously in order
to release the module for removal. Before performing this action, control power must be removed from the relay.
The original location of the module should be recorded to help ensure that the same or replacement module is inserted
into the correct slot.
2.Remove the module cover screw.
3.Remove the top cover by sliding it towards the rear and then lift it upwards.
4.Set the timing selection switches (channel 1, channel 2) to the desired timing modes (see description above).
3
5.Replace the top cover and the cover screw.
6.Re-insert the C37.94SM module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged position as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted.
3-38D30 Line Distance Protection SystemGE Multilin
Page 91
3 HARDWARE3.4 MANAGED ETHERNET SWITCH MODULES
NOTE
842867A2.CDR
Two 10/100Base-T
ports
Four 100Base-FX
multimode ports
with ST connectors
Independent power
supply. Options:
2S: high-voltage
2T: low-voltage
RS232
console port
REAR VIEW
FRONT VIEW
3.4MANAGED ETHERNET SWITCH MODULES3.4.1 OVERVIEW
The type 2S and 2T embedded managed switch modules are supported by UR-series relays containing type 9S CPU modules with revisions 5.5x and higher. The modules communicate to the D30 through an internal Ethernet port (referred to as
the UR port or port 7) and provide an additional six external Ethernet ports: two 10/100Base-T ports and four multimode ST
100Base-FX ports.
The Ethernet switch module should be powered up before or at the same time as the D30. Otherwise, the switch
module will not be detected on power up and the
EQUIPMENT MISMATCH: ORDERCODE XXX self-test warning will be
issued.
3.4.2 MANAGED ETHERNET SWITCH MODULE HARDWARE
The type 2S and 2T managed Ethernet switch modules provide two 10/100Base-T and four multimode ST 100Base-FX
external Ethernet ports accessible through the rear of the module. In addition, a serial console port is accessible from the
front of the module (requires the front panel faceplate to be open).
The pin assignment for the console port signals is shown in the following table.
Table 3–6: CONSOLE PORT PIN ASSIGNMENT
PINSIGNALDESCRIPTION
1CDCarrier detect (not used)
2RXDReceive data (input)
3TXDTransmit data (output)
4N/ANot used
5GNDSignal ground
6 to 9N/ANot used
3
Figure 3–46: MANAGED ETHERNET SWITCHES HARDWARE
GE MultilinD30 Line Distance Protection System3-39
Page 92
3.4 MANAGED ETHERNET SWITCH MODULES3 HARDWARE
$&'5
%DVH);
%DVH);
7[
5[
7[
5[
*5281'
³
:D
:E
:D
3RZHUVXSSO\
&RSSHU
SRUWV
&3867
00ILEHURSWLFFDEOH
00ILEHURSWLFFDEOH
%DVH7
%DVH7
%DVH);
7[
5[
%DVH);
7[
5[
)LEHU
SRUWV
00ILEHURSWLFFDEOH
00ILEHURSWLFFDEOH
²
%DVH7FDEOH
%DVH7FDEOH
WR9'&
WR9$&
842868A2.CDR
Connection speed indicator (OFF = 10 Mbps; ON = 100 Mbps)
Link indicator (ON = link active; FLASHING = activity)
Duplex mode indicator (OFF = half-duplex; ON = full-duplex)
Link indicator (ON = link active; FLASHING = activity)
The wiring for the managed Ethernet switch module is shown below.
The 10/100Base-T and 100Base-FX ports have LED indicators to indicate the port status.
The 10/100Base-T ports have three LEDs to indicate connection speed, duplex mode, and link activity. The 100Base-FX
ports have one LED to indicate linkup and activity.
Figure 3–48: ETHERNET SWITCH LED INDICATORS
3.4.4 INITIAL SETUP OF THE ETHERNET SWITCH MODULE
a) DESCRIPTION
Upon initial power up of a D30 device with an installed Ethernet switch, the front panel trouble LED will be illuminated and
the
ENET MODULE OFFLINE error message will be displayed. It will be necessary to configure the Ethernet switch and then
place it online. This involves two steps:
1.Configuring the network settings on the local PC.
2.Configuring the D30 switch module through EnerVista UR Setup.
These procedures are described in the following sections. When the D30 is properly configured, the LED will be off and the
error message will be cleared.
3-40D30 Line Distance Protection SystemGE Multilin
Page 93
3 HARDWARE3.4 MANAGED ETHERNET SWITCH MODULES
&OLFNWKH3URSHUWLHVEXWWRQ
$&'5
b) CONFIGURING LAN COMMUNICATIONS
The following procedure describes how to initially configure the Ethernet switch to work on your LAN.
1.Initiate communications from a PC to the D30 through a front panel serial connection (refer to the Configuring serial
communications section in chapter 1 for details), or if you are familiar with the UR keypad you can use it to set up the
network IP address and check the Modbus slave address and Modbus TCP port.
2.Ensure that the PC and the D30 are on the same IP network.
If your computer is on another network or has a dynamic IP address assigned upon a network login, then setup your
own IP address as follows
2.1.From the Windows Start Menu, select the Settings > Network Connections menu item.
2.2.Right-click on the Local Area Connection icon and select the Properties item. This will open the LAN properties window.
2.3.Click the Properties button as shown below.
3
GE MultilinD30 Line Distance Protection System3-41
Page 94
3.4 MANAGED ETHERNET SWITCH MODULES3 HARDWARE
&OLFNKHUHWRVHWXS,3
DGGUHVV
$&'5
2.4.The following window is displayed. Select the Use the Following IP Address option and enter appropriate IP
address, Subnet mask, and Default gateway values. It may be necessary to contact your network administra-
tor for assistance.
3
2.5.Save the settings by clicking the OK button.
2.6.Click the Close button to exit the LAN properties window.
3.Connect your PC to port 1 or port 2 of the Ethernet switch module (with an RJ-45 – CAT5 cable).
4.Verify that the two LEDs beside the connected port turn green.
5.After few seconds you should see your local area connection attempting to connect to the switch. Once connected,
check your IP address by going to bottom of your screen and right-clicking the Local Area Connection icon as shown
below.
3-42D30 Line Distance Protection SystemGE Multilin
Page 95
3 HARDWARE3.4 MANAGED ETHERNET SWITCH MODULES
1HZVLWH
2OGVLWH
,QWHUIDFHLV(WKHUQHWQRZ
0DNHVXUHWKHVHVHWWLQJV
DUHFRUUHFW
$&'5
Alternately, you can open a command window (type “cmd” from the Run item in the Start menu) and enter the ipconfig
command.
6.Now that the PC should be able to communicate to the UR relay through the UR Setup software.
c) INITIAL ETHERNET SWITCH MODULE SETUP
This procedure describes how to configure the D30 switch module through EnerVista UR Setup. Before starting this procedure, ensure that the local PC is properly configured on the same network as the D30 device as shown in the previous section.
1.Launch the EnerVista UR Setup software.
2.Click the Device Setup button.
3.Click the Add Site button. This will launch the Device Setup window.
4.Set the Interface option to “Ethernet” and enter the IP Address, Slave Address, and Modbus Port values as shown
below.
3
5.Click the Read Order Code button. You should be able to communicate with the D30 device regardless of the value of
the Ethernet switch IP address and even though the front panel display states that the Ethernet module is offline.
GE MultilinD30 Line Distance Protection System3-43
Page 96
3.4 MANAGED ETHERNET SWITCH MODULES3 HARDWARE
CAUTION
6.Select the Settings > Product Setup > Communications > Ethernet Switch > Configure IP menu item as shown
below.
3
7.Enter (or verify) the MAC Address, IP Address, Subnet Mask, and Gateway IP Address settings.
8.Click the Save button. It will take few seconds to save the settings to the Ethernet switch module and the following
message displayed.
9.Verify that the target message is cleared and that the D30 displays the MAC address of the Ethernet switch in the
Actual Values > Status > Ethernet Switch window.
The D30 device and the Ethernet switch module communications setup is now complete.
3.4.5 CONFIGURING THE MANAGED ETHERNET SWITCH MODULE
A suitable IP/gateway and subnet mask must be assigned to both the switch and the UR relay for correct operation. The
Switch has been shipped with a default IP address of 192.168.1.2 and a subnet mask of 255.255.255.0. Consult your network administrator to determine if the default IP address, subnet mask or default gateway needs to be modified.
Do not connect to network while configuring the switch module.
3-44D30 Line Distance Protection SystemGE Multilin
Page 97
3 HARDWARE3.4 MANAGED ETHERNET SWITCH MODULES
a) CONFIGURING THE SWITCH MODULE IP SETTINGS
In our example configuration of both the Switch’s IP address and subnet mask must be changed to 3.94.247.229 and
255.255.252.0 respectively. The IP address, subnet mask and default gateway can be configured using either EnerVista
UR Setup software, the Switch’s Secure Web Management (SWM), or through the console port using CLI.
1.Select the Settings > Product Setup > Communications > Ethernet Switch > Configure IP menu item to open the
Ethernet switch configuration window.
2.Enter “3.94.247.229” in the IP Address field and “255.255.252.0” in the Subnet Mask field, then click OK.
The software will send the new settings to the D30 and prompt as follows when complete.
3
3.Cycle power to the D30 and switch module to activate the new settings.
b) SAVING THE ETHERNET SWITCH SETTINGS TO A SETTINGS FILE
The D30 allows the settings information for the Ethernet switch module to be saved locally as a settings file. This file contains the advanced configuration details for the switch not contained within the standard D30 settings file.
This feature allows the switch module settings to be saved locally before performing firmware upgrades. Saving settings
files is also highly recommended before making any change to the module configuration or creating new setting files.
The following procedure describes how to save local settings files for the Ethernet switch module.
1.Select the desired device from site tree in the online window.
Retreive Settings File item from the device settings tree.
GE MultilinD30 Line Distance Protection System3-45
Page 98
3.4 MANAGED ETHERNET SWITCH MODULES3 HARDWARE
NOTE
The system will request the name and destination path for the settings file.
3
3.Enter an appropriate folder and file name and click Save.
All settings files will be saved as text files and the corresponding file extension automatically assigned.
c) UPLOADING ETHERNET SWITCH SETTINGS FILES TO THE MODULE
The following procedure describes how to upload local settings files to the Ethernet switch module. It is highly recommended that the current settings are saved to a settings file before uploading a new settings file.
It is highly recommended to place the switch offline while transferring setting files to the switch. When transferring
settings files from one switch to another, the user must reconfigure the IP address.
1.Select the desired device from site tree in the online window.
2.Select the Settings > Product Setup > Communications > Ethernet Switch > Ethernet Switch Settings File >Transfer Settings File item from the device settings tree.
The system will request the name and destination path for the settings file.
3.Navigate to the folder containing the Ethernet switch settings file, select the file, then click Open.
The settings file will be transferred to the Ethernet switch and the settings uploaded to the device.
3-46D30 Line Distance Protection SystemGE Multilin
Page 99
3 HARDWARE3.4 MANAGED ETHERNET SWITCH MODULES
NOTE
NOTE
Version: 2.1 beta
842869A1.CDR
3.4.6 UPLOADING D30 SWITCH MODULE FIRMWARE
a) DESCRIPTION
This section describes the process for upgrading firmware on a UR-2S or UR-2T switch module.
There are several ways of updating firmware on a switch module:
•Using the EnerVista UR Setup software.
•Serially using the D30 switch module console port.
•Using FTP or TFTP through the D30 switch module console port.
It is highly recommended to use the EnerVista UR Setup software to upgrade firmware on a D30 switch module.
Firmware upgrades using the serial port, TFTP, and FTP are described in detail in the switch module manual.
b) SELECTING THE PROPER SWITCH FIRMWARE VERSION
The latest switch module firmware is available as a download from the GE Multilin web site. Use the following procedure to
determine the version of firmware currently installed on your switch
1.Log into the switch using the EnerVista web interface.
The default switch login ID is “manager” and the default password is “manager”.
3
The firmware version installed on the switch will appear on the lower left corner of the screen.
2.Using the EnerVista UR Setup program, select the Settings > Product Setup > Communications > Ethernet Switch
> Firmware Upload menu item.
GE MultilinD30 Line Distance Protection System3-47
Page 100
3.4 MANAGED ETHERNET SWITCH MODULES3 HARDWARE
NOTE
The following popup screen will appear warning that the settings will be lost when the firmware is upgraded.
It is highly recommended that you save the switch settings before upgrading the firmware.
3.After saving the settings file, proceed with the firmware upload by selecting Yes to the above warning.
3
Another window will open, asking you to point to the location of the firmware file to be uploaded.
4.Select the firmware file to be loaded on to the Switch, and select the Open option.
The following window will pop up, indicating that the firmware file transfer is in progress.
If the firmware load was successful, the following window will appear: