Find these numbers on a label on the side of
the air conditioner.
Air Conditioners
49-7717-1 10-15 GE
IMPORTANT SAFETY INFORMATION.
READ ALL INSTRUCTIONS BEFORE USING.
SAFETY INFORMATION
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety
messages will follow the safety alert symbol and the word “DANGER”, “WARNING”, or “CAUTION”. These words are defined as:
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
WARNING
For your safety, the information in this manual must be followed to minimize the risk of fire, electric shock or personal
injury.
SAFETY PRECAUTIONS
Use this appliance only for its intended purpose as
described in this Owner’s Manual.
This air conditioner must be properly installed in
accordance with the Installation Instructions before it
is used.
Never unplug your air conditioner by pulling on the
power cord. Always grip plug firmly and pull straight
out from the receptacle.
Replace immediately all electric service cords that
have become frayed or otherwise damaged. A
damaged power supply cord must be replaced
with a new power supply cord obtained from the
manufacturer and not repaired. Do not use a cord
that shows cracks or abrasion damage along its
length or at either the plug or connector end.
Turn the unit OFF and unplug your air conditioner
before cleaning.
GE does not support any servicing of the air
conditioner. We strongly recommend that you do not
attempt to service the air conditioner yourself.
For your safety…do not store or use combustible
materials, gasoline or other flammable vapors or
liquids in the vicinity of this or any other appliance.
All air conditioners contain refrigerants, which under
federal law must be removed prior to product
disposal. If you are getting rid of an old product
with refrigerants, check with the company handling
disposal about what to do.
If the receptacle does not match the plug, the
receptacle must be changed out by a qualified
electrician.
These R410A air conditioning systems require
contractors and technicians to use tools, equipment
and safety standards approved for use with this
refrigerant. DO NOT use equipment certified for
R22 refrigerant only.
2
GEAppliances.com
WARNING
HOW TO CONNECT ELECTRICITY
Do not, under any circumstances, cut or remove the third
(ground) prong from the power cord. For personal safety,
this appliance must be properly grounded.
DO NOT use an adapter plug with this appliance.
The power cord of this appliance is equipped with a
3-prong (grounding) plug which mates with a standard
3-prong (grounding) wall outlet to minimize the
possibility of electric shock hazard from this appliance.
Power cord includes a current interrupter device. A
test and reset button is provided on the plug case. The
device should be tested on a periodic basis by first
pressing the TEST button and then the RESET button
while plugged into the outlet. If the TEST button does
not trip or if the RESET button will not stay engaged,
discontinue use of the air conditioner and contact a
qualified service technician.
Have the wall outlet and circuit checked by a qualified
electrician to make sure the outlet is properly grounded.
USE OF EXTENSION CORDS
RISK OF FIRE. Could cause serious injury or death.
Where a 2-prong wall outlet is encountered, it is your
personal responsibility and obligation to have it replaced
with a properly grounded 3-prong wall outlet.
The air conditioner should always be plugged into its
own individual electrical outlet which has a voltage
rating that matches the rating plate.
This provides the best performance and also prevents
overloading house wiring circuits which could cause a
fire hazard from overheated wires.
See the Installation Instructions, Electrical Requirements
section for specific electrical connection requirements.
• DO NOT use an extension cord with this Window Air
Conditioner.
• DO NOT use surge protectors or multi-outlet adaptors
with this Window Air Conditioner.
READ AND FOLLOW THIS SAFETY INFORMATION
CAREFULLY
SAVE THESE INSTRUCTIONS
RECYCLING INFORMATION
For appliance recycling information please visit www.
geappliances.com/recycling.
.
3
About the controls on the air conditioner.
Features and appearance will vary.
Lights next to the touch pads on the air conditioner control panel indicate the selected settings.
Light indicates the unit is in the
temperature or delay time Set mode.
Light indicates the
delay timer is set.
Power
On/Off
Auto
High
Med
Low
FanMode
NOTE: The display always shows the room temperature
except when setting the Set temperature or the Delay timer.
Cool
Fan Only
Energy Saver
Set
Reset
Filter
Air Conditioner Controls
Controls (on some models)
Power Pad
Turns air conditioner on and off. When turned
on, the display will show the room temperature.
Display
Shows the room temperature or time remaining
on the Delay timer. Shows the Set temperature
while setting the temperature in Cool or Energy Saver modes. The Set light will turn on while
setting.
NOTE: The display will change to show the room
temperature after settings have been made.
Temp Increase Ÿ /Decrease ź Pads
Use to set temperature when in Cool or Energy
Saver mode. The Set light will turn on while
setting.
Delay Timer Increase Ÿ (+) /Decrease ź(–)
Pads
Each touch of the Increase Ÿ/ Decreaseź
pads on the unit or the Increase + / Decrease –
pads on the remote control will set the delay
time when using the Delay 1–24hr
Set light will turn on while setting.
Fan Speed Pads
Use to set the fan speed to Low, Med, High
or Auto on the unit. NOTE: On the remote
control, use the fan speed Increase + /
Decrease – pads to set the fan speeds to Low,
Med or High. Use the Auto pad to turn Auto
fan on.
+
-
Delay
1-24 Hrs
8
timer. The
Delay 1–24hr
Delay timer
Decrease
Mode select
Fan speed
Decrease
Temperature
set Increase
and Decrease
FanFan
Remote Control
Mode Pad
Use to set the air conditioner to Cool, Energy
Saver or Fan Only mode.
Delay Pads/Delay 1-24hr Pad
Delay ON³:KHQWKHDLUFRQGLWLRQHULVRIILWFDQ
be set to automatically come on in 1 to 24 hours
at its previous mode and fan settings.
Delay OFF³:KHQWKHDLUFRQGLWLRQHULVRQ
it can be set to automatically turn off in 1 to
24 hours.
How to set:
Press the Delay 1–24hr pad on the unit or the
Delay pad on the remote control. Each touch
of the Increase Ÿ / Decrease źpads on the
unit or the Increase + / Decrease – pads on
the remote control will set the timer in 1-hour
intervals. The Set light will turn on while setting.
To review the remaining time on the Delay 1–24hr timer, press the Delay 1–24hr pad on
the unit or the Delay pad on the remote control.
Use the Increase Ÿ/ Decreaseźpads on the
unit or the Increase
remote control to set a new time if desired.
To cancel the timer, press the Delay 1–24hr pad
until the light on the Delay 1–24hr pad goes off.
Reset Filter
LED will turn on when fan has accumulated 250
hours of run time as a reminder to clean filter.
Press Reset Filter to turn off the LED and reset
the accumulated run time.
+ / Decrease – pads on the
Delay timer
Increase
Auto Fan on
Fan speed
Increase
Unit power
on/off
Note: The default temperature reading on the display is degree Fahrenheit ( °F). To change the display to
degree Celcius (°C), press the Temp Increase Ÿ and Temp Decrease ź buttons together and hold for 3
4
seconds. Repeat the process to change back to degree Fahrenheit (°F)
GEAppliances.com
Do Not Operate in Freezing Outdoor Conditions
This cool-only air conditioner was not designed for freezing
outdoor conditions. It must not be used in freezing outdoor
conditions.
Remote Control
To ensure proper operation, aim the remote control at the
signal receiver on the air conditioner.
Make sure nothing is between the air conditioner and the
remote control that could block the signal.
The remote control signal has a range of up to 20 feet.
Make sure batteries are fresh and installed correctly as
indicated on the remote control.
Remote contains a magnet allowing it to attach to metal
surfaces.
Cool Mode
Use the Cool mode at Low, Med, High or Auto Fan Speed
for cooling. Use the Temperature IncreaseŸ / Decrease ź
pads to set the desired temperature between 64°F and 86°F
in 1°F increments.
An electronic thermostat is used to maintain the room
temperature. The compressor will cycle on and off to keep
the room at the set level of comfort. Set the thermostat at a
lower number and the indoor air will become cooler. Set the
thermostat at a higher number and the indoor air will become
warmer.
NOTE: If the air conditioner is off and is then turned on
while set to a Cool setting or if turned from a fan setting to
a Cool setting, it may take approximately 3 minutes for the
compressor to start and cooling to begin.
Cooling Descriptions
For Normal Cooling³6HOHFWWKHCool mode and High or Med
fan with a middle set temperature.
For Maximum Cooling³6HOHFWWKH Cool mode and High fan
with a lower set temperature.
For Quieter and Nighttime Cooling³6HOHFWWKHCool mode
and Low fan with a middle set temperature.
Energy Saver Mode
This mode optimizes the cooling power of your air
conditioner, thereby saving you energy. Once the set
point temperature has been reached, the fan will cycle
off to save energy. The fan will cycle back on periodically
to insure all cooling capacity in the system is used. This
mode is the default mode for the unit. Each time the unit is
powered off, it will restart in Energy Saver mode ON. This
includes Delay timer mode. The first time the unit is turned on,
the settings will be 70° and Low fan. You can adjust the fan
speed and temperature to your personal comfort.
Fan Only Mode
Use the Fan Only Mode at Low, Med or High fan speed to
provide air circulation and filtering without cooling. Since
fan-only settings do not provide cooling, a Set temperature
cannot be entered. The room temperature will appear in the
display.
Auto Fan Speed
Set to Auto fan speed for the fan speed to automatically set
to the speed needed to provide optimum comfort settings
with the set temperature.
If the room needs more cooling, the fan speed will
Energy Saver ON³Helps minimize electricity use. It is
normal for the fan to cycle off and then back on in this
mode. This on/off cycle can repeat multiple times. Because
the fan will cycle off, you may notice a variation in room
temperature and humidity.
Energy Saver OFF³When this mode is not engaged, the fan
will run continuously, and in Cool mode the compressor
will cycle on and off to maintain room temperature.
NOTE: Auto Fan Speed cannot be used when in the
Fan Only Mode.
automatically increase. If the room needs less cooling, the fan
speed will automatically decrease.
NOTE: Auto Fan Speed cannot be used when in the Fan Only
Mode.
Power Outage Recovery Feature
In the case of a power outage or interruption, the unit will
automatically restart in the settings last used after the power
is restored. If the Delay 1–24hr feature was set, it will resume
countdown. You may need to set a new time if desired.
5
About the controls on the air conditioner.GEAppliances.com
Additional important information.
Air Direction
Use the lever to adjust the air direction left and right
only.
Care and cleaning of the air conditioner.
Grille and Case
Turn the air conditioner off and remove the plug from
the wall outlet before cleaning.
Air Filter
The air filter behind the front grille should be checked
and cleaned at least every 30 days or more often if
necessary.
To clean, use water and a mild detergent. Do not use
bleach or abrasives.
To remove:
Pull the tab on the right side of the unit until the filter
is out.
To remove:
Open the inlet grille by pulling downward on the tabs
at the top upper corners of the inlet grille until the
grille is in a 45º position. Remove the filter.
Clean the filter with warm, soapy water. Rinse and let
the filter dry before replacing it. Do not clean the filter
in a dishwasher.
CAUTION: DO NOT operate the air
conditioner without a filter because dirt and lint will
clog it and reduce performance.
Outdoor Coils
The coils on the outdoor side of the air conditioner
should be checked regularly. If they are clogged with
dirt or soot, they may be professionally cleaned.
Tab
Tab
How to Insert the Batteries in the Remote Control
Remove the battery cover by sliding it according
1
to the arrow direction.
Insert new batteries, making sure that the (+)
2
and (–) of battery are installed correctly.
Reattach the cover by sliding it back
3
into position.
6
NOTES:
Use 2 “AAA” (1.5 volt) alkaline batteries. Do not
use rechargeable batteries.
Remove the batteries from the remote control if
the system is not going to be used for a long time.
Do not mix old and new batteries. Do not mix
alkaline, standard (carbon-zinc) or rechargeable
(ni-cad, ni-mh, etc) batteries.
Installation
Air Conditioner
Instructions
Questions? Call 800.GE.CARES (800.432.2737) or Visit our Website at: GEAppliances.com
BEFORE YOU BEGIN
Read these instructions completely
and carefully.
•
IMPORTANT ³ Save these instructions
for local inspector’s use.
•
IMPORTANT ³ Observe all governing
codes and ordinances.
•
Note to Installer – Be sure to leave these
instructions with the Consumer.
• Note to Consumer – Keep these instructions for
future reference.
• Skill level – Installation of this appliance requires
basic mechanical skills.
• Completion time –
• We recommend that two people install this
product.
• Proper installation is the responsibility of the
installer.
• Product failure due to improper installation is not
covered under the Warranty.
• You MUST use all supplied parts and use proper
installation procedures as described in these
instructions when installing this air conditioner.
Approximately 1 hour
CAUTION:
Do not, under any circumstances, cut or remove
the third (ground) prong from the power cord.
Do not change the plug on the power cord
of this air conditioner.
Aluminum house wiring may present special
SUREOHPV³FRQVXOWDTXDOLILHGHOHFWULFLDQ
TOOLS YOU WILL NEED
Phillips head screwdriver
Flat-blade screwdriver
ELECTRICAL REQUIREMENTS
Some models require a 115/120-volt AC,
60-Hz grounded outlet protected with a
15-amp time-delay fuse or circuit breaker.
The 3-prong grounding plug minimizes the
possibility of electric shock hazard. If the wall outlet
you plan to use is only a 2-prong outlet, it is your
responsibility to have it replaced with a properly
grounded 3-prong wall outlet.
Some models require 230/208-volt AC,
protected with a time-delay fuse or circuit
breaker. These models should be installed
on their own single branch circuit for best
performance and to prevent overloading
house or apartment wiring circuits, which
could cause a possible fire hazard from
overheating wires.
Ruler or tape measurePencil
Level
Power cord includes a current interrupter
device. A test and reset button is provided on the
plug case. The device should be tested on a periodic
basis by first pressing the TEST button and then the
RESET button while plugged into the outlet. If the
TEST button does not trip or
if the RESET button will not stay engaged, discontinue
use of the air conditioner and contact a qualified
service technician.
7
Scissors or knife
PARTS INCLUDED
(Appearance may vary)
Top mounting rail
Installation Instructions
Accordion panel
seal (2)
Window
sill and sash seal (2)
Foam top window
gasket
Air
conditioner
accordion
Top mounting rail
seal strip
Left
panel
Right
accordion
panel
Foam
Insulation (2)
Type A (4)Type B (6)
Window locking
bracket (1)
8
Installation Instructions
WINDOW REQUIREMENTS
1
• These instructions are for a standard double-hung
window. You will need to modify them for other types
of windows.
• The air conditioner can be installed without the
accordion panels if needed to fit in a narrow
window. See the window opening dimensions.
• All supporting parts must be secured
to firm wood, masonry or metal.
• The electrical outlet must be within reach of the
power cord.
• Follow the dimensions in the table and illustration
for your model.
Models A B
AEH06 13 1/2smin. 22 1/2s–38s
AEH08
A
B
(With accordion panels)
ATTACH THE TOP MOUNTING RAIL
3
SEAL STRIP
(Some models may have the seal strip already
attached to the top mounting rail. If applicable,
skip this step.)
Remove the backing from the top mounting rail
seal strip and attach the seal strip to the bottom
of the top mounting rail, along the front edge.
Top mounting rail
Remove
backing
from seal
strip
FRONT VIEW
Top mounting rail
STORM WINDOW REQUIREMENTS
2
A storm window frame will not allow the air
conditioner to tilt toward the outside, and will keep it
from draining properly.
To adjust for this, attach a piece of wood to the sill.
WOOD PIECES
WIDTH: 2s
LENGTH: Long enough to fit inside the window
frame.
THICKNESS: To determine the thickness, place a
piece of wood on the sill to make it 1/2s higher
than the top of the storm window frame or the vinyl
frame.
Attach securely with nails or screws provided by the
installer.
1/2shigher
than vinyl frame
(on some windows)
1/2shigher
than storm
window
frame
Storm window
frame
Sill
Vinyl frame
Wood
Seal strip
4
PREPARE THE AIR CONDITIONER
Install the top mounting rail with 4 Type A
A
screws from the outside of the case.
Top mounting rail
Bottom mounting rail
Hold the accordion panel in one hand and
B
gently pull back to free the open end.
9
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.