Find these numbers on a label
behind the room cabinet on the
base pan.
TINSEA576JBRZ49-761204-09 JR
IMPORTANT SAFETY INFORMATION.
READ ALL INSTRUCTIONS BEFORE USING.
WARNING!
For your safety, the information in this manual must be followed to minimize the risk of fire
or explosion, electric shock, or to prevent property damage, personal injury, or loss of life.
SAFETY PRECAUTIONS
■ This Zoneline must be properly installed
in accordance with the Installation
Instructions before it is used. See the
Installation Instructions in the back
of this manual.
■ Replace immediately all electric service
cords that have become frayed or
otherwise damaged. A damaged power
supply cord must be replaced with a
new power supply cord obtained from
the manufacturer and not repaired.
Do not use a cord that shows cracks
or abrasion damage along its length
or at either the plug or connector end.
■ Unplug or disconnect the Zoneline
at the fuse box or circuit breaker
before making any repairs.
NOTE: We strongly recommend that any
servicing be performed by a qualified
individual.
■ These R410A air conditioning systems
require contractors and technicians to
use tools, equipment and safety
standards approved for use with this
refrigerant. DO NOT use equipment
certified for R22 refrigerant only.
Replacing an existing unit?
For details, see the Installation Instructions
in this manual.
READ AND FOLLOW THISSAFETY INFORMATION CAREFULLY.
SAVE THESE INSTRUCTIONS
Consumer SupportTroubleshooting TipsCare and CleaningOperating InstructionsSafety Instructions
2
About the controls on your Zoneline.GEAppliances.com
Safety InstructionsOperating InstructionsCare and CleaningTroubleshooting TipsConsumer Support
TEMP CONTROL
Controls
Temp Control
The temp control is used to maintain the room
temperature. The compressor will cycle on
and off to keep the room at the same level
of comfort.
Press thepad to raise the temperature.
Press thepad to lower the temperature.
NOTE: The display shows the set temperature,
not the room temperature.
Sleep
Press to set the air conditioner to run for 8 hours
before it automatically returns to the previous
setting.
When in the cooling mode and the sleep timer
is set, the set temperature will automatically
increase 2°F after the second hour then 1°F
each hour over the next two hours. Also, the
fan speed will change to low. When in the
heating mode, the set temperature will
decrease in the same manner.
To cancel the sleep mode, press the MODE pad
or the SLEEP pad a second time.
▲
▼
+
–
FAN, MODE & SLEEP OPERATION
Fan, Mode and Operation Control
FAN—Sets the fan operation for HIGH,
LOW or AUTO speed. When set at AUTO,
it automatically switches between LOW
and HIGH as room temperature changes.
MODE—COOL—For cooling
FAN—For fan-only operation
HEAT—For heating
OPERATION—ON/STOP—Turns the unit
on or off. Power remains connected to
the Zoneline. The Freeze/Heat Sentinel
features still function if active.See the
Freezer/Heat Sentinel section on page 6.
NOTE: The temperature display will flash
to indicate a possible unit malfunction. Set
operation control to STOP and then restart
the unit. If the flashing light reappears within
30 minutes, call for service.
Quick Heat Recovery
Activates each time the thermostat is switched from
STOP or COOL mode to HEAT mode. Electric heaters
are energized until the thermostat set point
is reached. On heat pump models, the heat pump
operation will resume at the next call for heat.
About Your Heat Pump (6100 Series only)
Heat pumps can save money by removing heat
from the outside air—even when the outside
temperature is below freezing—and releasing
that heat indoors.
To get the best performance from your heat pump,
don’t change the room thermostat very often.
Raising the heat setting 2–3 degrees will cause
the Zoneline to use its electric heating elements in
order to reach the new temperature setting quickly.
There is a 3-minute minimum compressor
run time at any setting to prevent short cycling.
The indoor fan motor starts before the compressor
and stops after the compressor cycles off.
When the outdoor temperature is lower than 25°F,
heat is provided by the electric heater in the air
conditioner instead of by the heat pump.
The electric heating elements use much
more electricity than heat pumps and cost
more to operate.
3
Other features of your Zoneline.
Ventilation Control
NOTE: Two shipping screws must be removed
from the vent door before use. See the Installation
Instructions in the back of this manual. If you do not
plan to use the ventilation feature, leave these two
screws in place.
The ventilation control lever is located at
the middle left side of the Zoneline unit,
behind the room cabinet.
When set at the closed position, only the air
inside the room is circulated and filtered.
When set at the open position, some outdoor
air will be drawn into the room. This will reduce
the heating or cooling efficiency.
Energy Tip: Keep the vent control in the closed
position. The room air will be filtered and circulated.
To Remove the Room Cabinet
Additional controls are located behind the
room cabinet.
Open
osition
p
Vent control
(shown in
middle position)
Closed
position
Remove two
shipping screws
(if operation is
desired)
To remove: Pull out at the bottom to release it from
the tabs (1). Then lift up (2).
Air Direction
To change the air direction, remove the room
cabinet. Remove the 7 louver screws that hold
the louver insert in place. Flip the louver insert 180°,
replace the screws and the room cabinet.
Louver screws
To replace: Place the tabs over the top rail (1). Push
inward at the bottom until it snaps into place (2).
Remove the room cabinet and flip the louver
insert to change the air direction.
Default
Consumer SupportTroubleshooting TipsCare and CleaningOperating InstructionsSafety Instructions
4
Louver screws
position
Auxiliary controls on your Zoneline.GEAppliances.com
uxiliary Set Button
Auxiliary Controls—Aux Set Button
The auxiliary set controls are located behind
the room cabinet, below the control panel.
Remove the room cabinet. See the To Removethe Room Cabinet section.
The owner is responsible for ensuring the auxiliary
controls are set to the desired function. There are 9
different modes that can be set using the auxiliary
set button. To change modes, press AUX SET (“AU”
appears on the display). Press the mode button on
the control pad until the first digit in the display
shows the number corresponding to the mode you
are choosing and the correct HEAT/COOL LED is lit.
Press the up or down arrow (shown in the second
digit of the display) to make the mode setting
selection where applicable. Press the AUX SET
button to confirm the selection.
A
Access Cover
Safety InstructionsOperating InstructionsCare and CleaningTroubleshooting TipsConsumer Support
MODE 1
MODE 2
Smart Fan—Cooling/Heating
The default setting for Mode 1 is as follows:
Cooling: Continuous (ON)
Heating: Cycle (OFF)
Press MODE until a 1 appears in the first digit of the
display for Smart Fan cool mode. The COOL LED
light on the main control will be on. To change to
heat mode, press MODE again. The HEAT LED light
on the main control will be lit. Press the down arrow
to set the indoor fan to cycle on/off when the unit is
heating or cooling "." Press the up arrow to set
the indoor fanto run continuously "." This is
shown in the second digit of the display. Press AUXSET to confirm your selection and exit AUX SET
mode, or press MODE to continue setting other
functions.
Load Shedding (Central Desk Control)
The default setting for Mode 2 is OFF.
This feature is active only if the unit is connected to
a CDC and the CDC has control. Press MODE until a
2 appears in the first digit of the display for LoadShedding mode. Press the down arrow for OFF ""
or the up arrow for ON "." This is shown in the
second digit of the display. When this mode is on,
only the indoor fan can be turned ON or OFF with
the unit controls. When this mode is off, all
operation is disabled exceptHeat/Freeze Sentinel
(Mode 3). Press AUX SET to confirm your selection
and exit AUX SET mode, or press MODE to continue
setting other functions.
HIGHCOOL
LOWFAN
AUTOHEAT
Cooling – Cycle
HIGHCOOL
LOWFAN
AUTOHEAT
Cooling – Continuous
HIGHCOOL
LOWFAN
AUTOHEAT
Heating – Cycle
HIGHCOOL
LOWFAN
AUTOHEAT
Heating – Continuous
Load
Shedding
OFF
Load
Shedding
ON
5
Auxiliary controls on your Zoneline.
MODE 3
MODE 4
Freeze Sentinel/Heat Sentinel
In the default setting for Mode 3, Heat Sentinel is off, Freeze
entinel is on.
S
Press MODE until a 3 appears in the first digit of the display for
Freeze Sentinel mode. The COOL LEDlight on the main controlwill be on. Press MODE again to change to the Heat Sentinel. The
HEAT LED light on the main control will be on. Press the down
arrow for OFF "" or the up arrow for ON "." This is shown
in the second digit of the display. Press AUX SET to confirm your
selection and exit AUX SET mode, or press MODE to continue
setting other functions.
When Freeze Sentinel is activated, it automatically provides
heat without user interface. This helps to prevent plumbing
damage by turning the heater and indoor fan ON at 41ºF and
OFF at 46ºF.
When Heat Sentinel is activated, it automatically provides
cooling without user interface. This helps to prevent an
excessively hot room by turning the air conditioner ON at 85ºF
and OFF at 80ºF.
NOTE: These functions are active whenever the unit is
plugged in, even if the unit is in the STOP position.
Constant ON Fan
The default setting for Mode 4 is OFF.
Press MODE until a 4 appears in the first digit of the display to set
the fan to run continuously at high speed, even if the unit is in
the STOP position. Press the down arrow for OFF "" or the up
arrow for ON "." This is shown in the second digit of the
display. Press AUX SET to confirm your selection and exit AUXSET mode, or press MODE to continue setting other functions.
reeze Sentinel OFF
F
Freeze Sentinel ON
Heat Sentinel OFF
Heat Sentinel ON
Constant
Fan OFF
HIGHCOOL
LOWFAN
AUTOHEAT
HIGHCOOL
LOWFAN
UTOHEAT
A
IGHCOOL
H
LOWFAN
AUTOHEAT
HIGHCOOL
LOWFAN
AUTOHEAT
Constant
Fan ON
MODE 5
Temperature Limiting
The default setting for Mode 5 is as follows:
Cool: 0 (60ºF to 85ºF)
Heat: 7 (60ºF to 85ºF)
HIGHCOOL
LOWFAN
AUTOHEAT
HIGHCOOL
LOWFAN
AUTOHEAT
MODE 6
Press MODE until a 5 appears in the first digit of the display for
Temperature Limiting cool mode. The COOL LEDlight on the
main control will be lit. To change to heat mode, press MODE
again and the HEAT LED light on the main control will be lit. To
set the temperature limits, press the up or down arrow keys. The
second digit of the display will be between 0 and 7 depending on
the limit you want to set. The chart shows the limits available.
Press AUX SET to confirm your selection and exit AUX SET mode,
or press MODE to continue setting other functions.
Temperature limits—CoolTemperature limits—Heat
0 = 60°F to 85°F0 = 60°F to 65°F
1 = 64°F to 85°F1 = 60°F to 70°F
2 = 66°F to 85°F2 = 60°F to 72°F
3 = 68°F to 85°F3 = 60°F to 74°F
4 = 70°F to 85°F4 = 60°F to 76°F
5 = 72°F to 85°F5 = 60°F to 78°F
6 = 74°F to 85°F6 = 60°F to 80°F
7 = 76°F to 85°F7 = 60°F to 85°F
Remote Thermostat – Class 2
Temperature Limiting Cool – Limit 2
Temperature Limiting Heat – Limit 3
The default setting for Mode 6 is OFF.
Setting this mode to ON will allow the unit to operate with a Class
2 Remote Control Wall Thermostat. Press MODE until a 6 appears
in the first digit of the display for Class 2 mode. Press the down
Consumer SupportTroubleshooting TipsCare and CleaningOperating InstructionsSafety Instructions
6
arrow to turn the option OFF "." Press the up arrow to turn this
option ON "." This is shown in the second digit of the display.
Press AUX SET to confirm your selection and exit AUX SET mode,
or press MODE to continue setting other functions.
Class 2 OFF
Class 2 ON
GEAppliances.com
External Fan
Central Desk Control
Common
White - Heater
Yellow - Compressor
Black - Solenoid (AZ61 only)
Green - High Speed Fan
Green - Low Speed Fan
Red - 24 V AC only
EXT
FAN
CDC
24 VAC R
FAN LO G
FAN HI G
REV VAL B
COMP Y
AUX HEAT W
COMMON C
Safety InstructionsOperating InstructionsCare and CleaningTroubleshooting TipsConsumer Support
MODE 7
MODE 8
MODE 9
Duct Mode
The default setting for Mode 7 is OFF.
This setting is used when the unit is installed using a
duct adapter kit. If the unit is ducted, the Duct Mode
needs to be set to ON. This increases the fan speed to
ensure proper circulation.
Press MODE until a 7 appears in the first digit of the
display. Press the up or down arrow keys to set this
switch to OFF "" or ON "." This is shown in the
second digit of the display. Press AUX SET to confirm
your selection and exit AUX SET mode.
All-Electric Heat (AZ6100 only)
The default setting for Mode 8 is OFF.
This electric heat option functions only on the 6100
model. When this option is ON "," heat pump
operation is locked out, causing the unit to provide
only electric resistance heat.
To set All-Electric Heat option,
appears in the first digit of the display
press MODE until an 8
. Press the up or
down arrow keys to set this switch to OFF "" or
ON "." This is shown in the second digit of the display.
Heat Boost (AZ6100 only)
The default setting for Mode 9 is OFF.
When Heat Boost is ON and outer temperatures are
between 25ºF and 46ºF, heat pump only operation is
locked out. This setting is used to provide supplementary
heat to the heat pump operation by electric resistance
heat in conditions where the heat pump-only operation
is not sufficient to maintain a consistent, comfortable
room temperature. NOTE: Temperature Boost option
should not be used with remote thermostat operation.
This will cause the unit to switch to resistance heat when
the outdoor temperature is 46ºF.
For Model AZ6100, press MODE to continue setting
other functions. Pressing MODE on Model AZ4100 will
return you to AUX SET mode and an “AU” will appear in
the display.
Duct Mode OFF
Duct Mode ON
Press AUX SET to confirm your selection and exit AUX SET
mode, or press MODE to continue setting other functions.
All-Electric
Heat OFF
All-Electric
Heat ON
To set Heat Boost, press MODE until a 9 appears in the
first digit of the display. Press the up or down arrow keys
to set this switch to OFF "" or ON "." This is shown
in the second digit of the display. Press AUX SET to
confirm your selection and exit AUX SET mode.
Heat Boost OFF
Heat Boost ON
Auxiliary Controls—Terminal Connections
The auxiliary controls are located behind the room
cabinet beneath the access cover.
Turn off and unplug the unit.
1
Remove the room cabinet. See the To Remove the
2
Room Cabinet section.
Remove the screw from the access cover.
3
To make wiring connections, insert the wires into the
4
bottom of the terminals and tighten screws securely.
After all desired connections have been made,
5
replace the access cover and room cabinet.
Access Cover
The owner is responsible for making all connections and
setting the appropriate AUX SET mode.
CAUTION:
Improper wiring may damage the Zoneline electronics.
No common busing is permitted. Damage or erratic
operation may result. A separate wire pair must be run
from each separate controlling switch to each individual
Zoneline.
7
Auxiliary controls on your Zoneline.
External Fan (Obtained locally)
When connected, an auxiliary or external fan can be
controlled with the indoor fan motor on the Zoneline.
onnections provide 24 V AC to energize a remote relay,
C
turning on the external fan.
Central Desk Control
When connected, the unit can be turned ON or OFF with
a switch located at the Central Control Panel. A separate
wire pair must be run from each separate controlling
switch to each individual Zoneline.
Refer to MODE2 on page 5 for fan setting options.
Remote Thermostat
When connected to a remote thermostat, the indoor air
temperature sensing is shifted from the unit to the
remote thermostat. For this reason, the units will operate
slightly differently when connected to a remote
thermostat. The following chart shows the unit operation
when connected to a remote thermostat.
NOTE: The Class 2 Mode setting (Mode 6) must be set to
ON "" for the unit to operate with a Class 2 Remote
Wall Thermostat. (See the installation instructions
supplied with the remote thermostat and Mode
instructions on page 7.)
Class 2 Shown ON
IMPORTANT: The Zoneline thermostat
connections provide 24 V AConly.
If using a digital/electronic wall thermostat, you must set
it to the 24 V ACsetting. See the Installation Instructions
for the wall thermostat.
FeatureHeat PumpElectric Heat
Indoor Frost ControlYesYes
Freeze SentinelYesYes
Auto Fan SpeedNoNo
Electronic Temperature LimitingNoNo
Switch to Resistance Heat BasedDetermined byN/A
On Indoor TemperatureRemote Thermostat
Switch to Resistance Heat BasedYesN/A
On Outdoor Temperature
Consumer SupportTroubleshooting TipsCare and CleaningOperating InstructionsSafety Instructions
8
“Smart Fan” Fan CycleFan ON/AUTO Set OnFan ON/AUTO Set On
Remote ThermostatRemote Thermostat
Central Desk ControlYesYes
CAUTION:
Damage to a wall thermostat or to the Zoneline
electronics can result from improper connections. Special
care must be used in connecting the wires. No line
voltage connections should be made to any circuit.
Isolate all wires in building from line voltage.
Care and cleaning.
Room Cabinet and Case
Safety InstructionsOperating InstructionsCare and CleaningTroubleshooting TipsConsumer Support
urn the Zoneline off and disconnect the
T
power supply.
Outdoor Coils
The coils on the outdoor side of the Zoneline should
be checked regularly. If they are clogged with dirt
or soot, they may be professionally steam cleaned.
You will need to remove the unit from the wall
sleeve to inspect the coils. The dirt buildup occurs
on the fan side of the outdoor coil.
Base Pan
In some installations, dirt or other debris may be
blown into the unit from the outside and settle in
the base pan (the bottom of the unit).
o clean, use water and a mild detergent.
T
Do not use bleach or abrasives. Some commercial
cleaners may damage the plastic parts.
Coils
Grille
Clean the outside coils regularly.
In some areas of the United States, a naturally
occurring “gel-like” or “slime-like” substance may
be seen in the base pan.
Ventilation Filter
If the vent door is open, access requires the removal
of the unit from the wall sleeve. Clean the vent filter
twice a year or as required.
Turn the Zoneline off and unplug before cleaning.
Remove two
shipping screws
(if operation is
desired)
Check it periodically and clean, if necessary.
To clean the vent filter:
IMPORTANT:
This filter is not removable. Trying to remove this
filter will damage the unit.
■ Use a vacuum to remove debris from the filter.
■ Use a damp rag to wipe down the filter and
surrounding area after vacuuming.
9
FRONT
FRONT
Care and cleaning.
To maintain optimum performance, clean the filters at least every 30 days.
Air Filters
To remove the air filters:
Pull up
2 Air filters
Dirty filter—Needs cleaningClogged filter—Greatly
reduces cooling, heating
and airflow.
Turn the Zoneline off before cleaning.
The most important thing you can do to maintain
the Zoneline is to clean the filter at least every
30 days. Clogged filters reduce cooling, heating
and air flow.
Keeping these filters clean will:
■ Decrease cost of operation.
■ Save energy.
■ Prevent clogged heat exchanger coils.
■ Reduce the risk of premature component failure.
To clean the air filters:
■ Vacuum off the heavy soil.
■ Run water through the filters from the
back side.
■ Dry thoroughly before replacing.
NOTE: The air filters are interchangeable
and will fit in either the right or left side.
To replace the air filters:
Push down
CAUTION:Do not operate the
Zoneline without the filters in place. If a filter
becomes torn or damaged, it should be replaced
immediately.
Operating without the filters in place or with
damaged filters will allow dirt and dust to reach
the indoor coil and reduce the cooling, heating,
airflow and efficiency of the unit.
Replacement filters are available from your
salesperson, GE dealer, GE Service and Parts
Center or authorized Customer Care®servicers.
Consumer SupportTroubleshooting TipsCare and CleaningOperating InstructionsSafety Instructions
10
InstallationZoneline Air
InstructionsConditioners
Questions? Call 800.GE.CARES (800.432.2737) or Visit our Website at: GEAppliances.com
BEFORE YOU BEGIN
Read these instructions completely and carefully.
•
IMPORTANT – Save these instructions for
local inspector’s use.
•
IMPORTANT – Observe all governing
codes and ordinances.
• Note to Installer – Be sure to leave these
instructions with the owner.
• Note to Owner – Keep these instructions for
future reference.
• Proper installation is the responsibility of the installer.
• Product failure due to improper installation is not
covered under the Warranty.
TOOLS YOU WILL NEED
Phillips screwdriver
IMPORTANT ELECTRICAL
SAFETY—READ CAREFULLY
CAUTION:
• Follow the National Electrical Code (NEC) or local
codes and ordinances.
• For personal safety, this Zoneline must be properly
grounded.
• Protective devices (fuses or circuit breakers)
acceptable for Zoneline installations are specified
on the nameplate of each unit.
• Do not use an extension cord with this unit.
• Aluminum building wiring may present special
problems—consult a qualified electrician.
• When the unit is in the OFF position, there is
still voltage to the electrical controls.
• Disconnect the power to the unit before
servicing by:
1 Removing the power cord (if it has one) from
the wall receptacle.
OR
2 Removing the branch circuit fuses or turning
the circuit breakers off at the panel.
ZONELINE COMPONENTS
Appearance may vary.
Exterior grille/louver**
Wall case**
** Shipped with the Zoneline unit
** Check the “Essential Elements” list on the unit located on front of the base pan
11
Zoneline unit
Room cabinet*
Power supply kit**
Installation Instructions
REPLACING AN EXISTING UNIT?
Check the “Essential
Elements” label for
important information.
Use the correct wall case
This unit is designed to be installed in a GE plastic or
insulated metal wall case. This minimizes condensation
from forming on the room side of the case.
If the current wall case is not insulated, you can reduce
the possibility of condensation forming by installing
insulation kit RAK901L, available where you purchased
the unit.
NOTE: There are several extra holes in the unit side flanges
for installation in wall cases other than GE. To avoid
damaging the flange insulation, the installer should use
an awl or other sharp tool to puncture the insulation in
the appropriate holes before installing the attachment
screws.
Use the correct outdoor grille
You should use the outdoor grilles shown on the
“Essential Elements” label on the base pan.
• If an existing grille is not replaced, capacity and
efficiency will be reduced and the unit may fail to
operate properly or fail prematurely. A deflector kit,
RAK40, may be used with grilles that were not designed
for your new GE Zonelines. The RAK40 contains air
deflectors and gaskets that mount to the unit to direct
the hot exhaust air away from the air intake to allow
the unit to function properly. The grille must have a
65% minimum free area.
• Any vertical deflectors in the existing rear grille should
be removed to decrease condenser air recirculation
that can cause the unit to “short-cycle” and lead to
premature component failure.
Replacing a ducted unit
New ducted installation:
If this unit is to be installed in a new ducted application
using a duct adapter kit, the kit must be installed before
the unit is placed in the wall case. The installation
instructions are packed with the kit.
Duct kits available:
RAK6052
RAK601/602
Mounting
plate
Existing ducted installation:
Replacement of an existing ducted unit may require
different components. Request this information from your
sales representative.
• Replacing 230/208 volt units:
See page 13.
• Replacing 265 volt units:
See page 14.
When using a duct kit, you must always turn Mode 7 to
ON "." See Mode instructions on page 7.
Duct Mode
Shown ON
Duct
Case
Use the correct power cord
Local codes may require the use of arc fault or leakage
current detection devices on 230/208-volt installations.
12
Installation Instructions
230/208 VOLT ELECTRICAL CONNECTION OPTIONS
HOW TO CONNECT
1. Remove the room cabinet.
2. Connect to electrical power.
3. Review the following steps for applicable supply
voltages.
4. Reinstall the room cabinet.
Power cords may include an arc fault interruption
r a leakage current detection interruption device.
o
A test and reset button is provided on the plug case
or the inline case. The device should be tested on
a periodic basis by first pressing the TEST button
and then the RESET button. If the TEST button does
not trip or if the RESET button will not stay engaged,
discontinue use of the Zoneline and contact a
qualified service technician.
POWER CORD
CONNECTION
A power supply kit withLCDI must be used to supply power
to the Zoneline unit. The appropriatekit isdetermined by
the voltage, the means of electrical connection and
the amperage of the branch circuit.
Appearance may vary.
Power supply kit
Connections of 208 or 230-volt circuits may be with a
power supply kit or a junction box kit.
All wiring, including installation of the receptacle, must
be in accordance with the NEC and local codes,
ordinances and regulations. Codes require the use of
an arc fault or leakage current detection device on the
power cord except direct connect. Be sure to select the
correct cord for your installation.
ELECTRICAL SUBBASE
CONNECTION
230/208-volt models may be installed using one
of the following electrical subbases:
Branch Circuit andProper GE
Unit Amperage RatingSubbase Kit
15RAK204D15P
20RAK204D20P
30RAK204D30P*
*Not approved for use on 7000 BTUmodels.
Electrical subbases provide an enclosure for direct
connection or enclosed receptacles. The subbase kit
includes the power cord.
The instructions provided with the selected subbase kit
must be carefully followed. It is the responsibility of the
installer to ensure the connection of components is done
in accordance with these instructions and all electrical
codes.
Tandem
15 Amp.
230/208-volt receptacle configuration.
Branch Circuit andProper GE Power Cord
Unit Amperage Ratingwith LCDI Device
*Not approved for use on 7000 BTU models.
Perpendicular
20 Amp.
15RAK3153
20RAK3203
30RAK3303*
Large Tandem
30 Amp.
DIRECT CONNECTION
Order the following Kit for 230/208-volt direct
connection as required:
Branch Circuit andPower SupplyPower
Unit Amperage RatingAccessorySupply Kit
15RAK4002ARAK4157
20RAK4002ARAK4207
30RAK4002ARAK4307*
*Not approved for use on 7000 BTU models.
Skip to the “MAKE ELECTRICAL CONNECTION TO THE UNIT”
section.
13
Installation Instructions
265 VOLT ELECTRICAL CONNECTION OPTIONS
WARNING:
onnection of this 265V AC product to a branch circuit
C
MUST be done by direct connection in accordance with
the National Electrical Code. Plugging this unit into a
building-mounted exposed receptacle is not permitted
by code.
These models must be installed using the appropriate
GE power supply kit for the branch circuit amperage and
the electrical resistance heater wattage desired. Use the
POWER CONNECTION CHART on page 16 to determine
the correct kit required. One of the following installation
methods (A or B) must be used.
A. FOR SUBBASE INSTALLATION
Electrical subbase kits are available to provide a flexible
enclosure for direct connection.
Branch Circuit andProper GEPower
Unit Amperage RatingSubbase KitSupply Kit
15RAK204E15RAK5172
20RAK204E20RAK5202
B. FOR DIRECT CONNECT
INSTALLATION
If an electrical subbase is not used, direct connection to
branch circuit wiring inside the provided junction box must
be done in accordance with the following steps.
Order the following Kit for 265-volt direct connection
as required:
Branch Circuit andPower
Unit Amperage RatingSupply Kit
15RAK5157
20RAK5207
30RAK5307*
*Not approved for use on 7000 BTUmodels.
Proceed to the “MAKE ELECTRICAL CONNECTION TO THE
UNIT” section.
NOTE: Order Kit RAK4002CW to enable a quick
disconnect inside the junction box.
30RAK204E30RAK5302*
*Not approved for use on 7000 BTUmodels.
The instructions provided with the selected subbase kit
must be carefully followed. It is the responsibility of the
installer to ensure the connection of components is done
in accordance with these instructions and all electrical
codes.
14
Installation Instructions
MAKE ELECTRICAL CONNECTION TO THE UNIT
1
REMOVE JUNCTION BOX
1. Remove the junction box cover by removing the front
two screws.
2. Remove the junction box by removing the top and
bottom rear screws. Note how the tabs on the lower
left side of the junction box serve to hold the side in
place. This will help when the box is being reinstalled.
Unit connector
Junction
box cover
2
CONNECT THE CORDSET
Plug the connector, provided in the Direct Connect Kit,
fully into place in the unit mating connector. Be sure
the locking tabs at the sides are engaged.
Connector
NOTE: Order Kit RAK4002CW to enable a quick
disconnect inside the junction box.
Junction
box
3
ATTACH CONDUIT
1. Use the round knockout at the bottom of the junction
box to attach conduit coming from the branch circuit.
Remove the knockout, attach the conduit and bring
wires into the junction box. Leave 6″ of wire free at the
end of the conduit to allow connections to be made.
Conduit
2. If a fuse and fuseholder are to be used, the
knockout at the top of the box is for mounting
a Buss fuseholder. Be sure the fuse and fuseholder are
of the same rating as the branch circuit. Leadwires at
the fuse can be either soldered in place or attached
using UL-listed 1/4″ female (receptacle) crimp
connectors. Follow local codes.
4
REINSTALL JUNCTION BOX
• Reinstall the junction box by engaging the left tabs
on the lower right face of the unit, aligning the screw
holes at the top and bottom and driving the two
screws until secure. Be sure that all wire leads are
inside the box and not pinched between the box and
the unit. The green insulated ground wire from the unit
MUST be connected to the branch circuit ground wire.
Make all wire connections by using appropriate
UL-listed electrical connectors and techniques
(black to black, white to white and green to green).
15
5
REINSTALL JUNCTION BOX COVER
1. Carefully tuck all wires and connections back inside
the junction box. Be sure there are no loose
connections or stray uninsulated wires exposed.
2. Place the junction box cover in place. Replace the two
screws removed earlier and tighten securely.
RAK3153Tandem15-Amp Time-Delay Fuse or Breaker2.55/2.09 KW
RAK3203Perpendicular20-Amp Time-Delay Fuse or Breaker3.45/2.82 KW
RAK3303*Large Tandem30-Amp Time-Delay Fuse or Breaker5.00/4.10 KW
Direct Connections
230/208 VoltHeater Wattage
Power Supply KitsCircuit Protective Device@ 230/208 Volts
RAK415715-Amp Time-Delay Fuse or Breaker2.55 KW/2.09 KW
RAK420720-Amp Time-Delay Fuse or Breaker3.45 KW/2.82 KW
RAK4307*30-Amp Time-Delay Fuse or Breaker5.00 KW/4.10 KW
265 VoltHeater Wattage
Power Supply KitsCircuit Protective Device@ 265 Volts
RAK515715-Amp Time-Delay Fuse or Breaker2.55 KW
RAK520720-Amp Time-Delay Fuse or Breaker3.45 KW
RAK5307*30-Amp Time-Delay Fuse or Breaker5.00 KW
*Not approved for use on 7000 BTUH units.
16
Installation Instructions
INSTALLING THE ZONELINE
1
INSTALL THE WALL CASE AND
EXTERIOR GRILLE
The RAB71A series or RAB77A4 wall case must be
properly installed per instructions packed with the case.
• Remove the corrugated stiffener and the outdoor
protective panel. Use the slit in the outdoor panel
as a handhold and push out.
Protective
panel
Stiffener
• Install the exterior grille from the room side following
instructions packed with the grille.
Insulated Wall Case
This unit is designed to be installed in a GE plastic
or an insulated steel wall case. This minimizes
condensation from forming on the room side of
the case.
The RAB71A series wall cases are insulated. Insulation kit
RAK901L is available for use with RAB77A4 or existing
uninsulated wall cases when needed.
NOTE: For installation with a subbase or duct adapter,
see the instructions packed with those kits.
Slit
2
PREPARE THE UNIT
• Carefully remove shipping tape and foam shipping
blocks from the room cabinet, compressor and
vent door. There may be multiple blocks and pieces
of shipping tape that need to be removed.
Shipping tape
(Locations may vary)
• Remove the room cabinet by pulling it out at the
bottom to release it (1); then lift it up to clear the rail
along the unit top (2).
• If vent door is to be operational, remove shippingscrews
from the front side of the vent door, if present.
17
Remove two
shipping screws
(if operation is
desired)
Installation Instructions
INSTALLING THE ZONELINE (cont.)
3
INSTALL THE UNIT INTO THE
WALL CASE
lide the unit into the wall case and secure with four
S
screws through the unit flange holes.
NOTE: There are several extra holes in the unit side
flanges for installation in wall cases other than GE.
To avoid damaging the flange insulation, the installer
should use an awl or other sharp tool to puncture the
insulation in the appropriate holes before installing the
attachment screws.
4
REPLACE THE ROOM CABINET
einstall the room cabinet by hooking the top over
R
the rail along the unit top (1), then pushing it in at
the bottom (2).
18
Installation Instructions
OPTIONAL—DRAIN KIT INSTALLATION
Dry Air 25 Series models are designed to improve dehumidification by 25%. Since more moisture will be removed from
the air, there is a greater possibility that water will drip from the wall case than with a standard unit. To prevent this
water from dripping onto external building walls, we recommend the use of RAD10 Drain Kit .
External Drain
See the Installation Instructions
in the RAD10 kit.
See the Installation Instructions in
the RAD10 kit .
Type “A” screw for metal case or
Type “B” screw for molded case
(The drain is located
under the cabinet)
Square drain holes
Neoprene sponge gasket
Type “A” screw for metal case or
Type “B” screw for molded case
Steel mounting plate
19
Before you call for service…
Troubleshooting Tips
Save time and money! Review the charts on the
following pages first and you may not need to call for
service.
ProblemPossible CausesWhat To Do
Zoneline doesThe unit is• Make sure the Zoneline plug is pushed completely
not startunplugged.into the outlet.
The power cord is not• Remove the room cabinet and make sure that the
firmly attached.yellow connector on the end of the power cord is
firmly engaged.
The fuse is blown/circuit• Check the house fuse/circuit breaker box and replace
breaker is tripped.the fuse or reset the breaker.
The unit is waiting for• This is normal. The Zoneline will start again after
the compressor overloadit resets.
protector to reset.
Power failure.• If power failure occurs, set the mode control to STOP.
When power is restored, set the mode control to the
desired setting.
• There is a protective time delay (up to 3 minutes) to
prevent tripping of the compressor overload. For this
reason, the unit may not start normal heating or cooling
for 3 minutes after it is turned back on.
The current interrupter• Press the RESET button located on the power cord plug
device is tripped.or the box near the plug.
• If the RESET button will not stay engaged,discontinue use
of the Zoneline and contacta qualified service technician.
Zoneline does not coolIndoor airflow• Make sure there are no curtains, blinds or furniture
or heat as it shouldis restricted.blocking the front of the Zoneline.
Outdoor airflow is• Make sure the rear grille is not restricted. This can
restricted or recirculated.cause the unit to cycle off due to the compressor
overload protector.
• Outdoor grille must have a minimum of 65% free area.
Non-GE grilles may be too restrictive for proper
performance. Consult your salesperson for assistance.
The temp control may• Turn the control to a lower or higher setting.
not be set properly.NOTE: The temperature limiter may belimiting the
temperature range.
The air filter is dirty.• Clean the filter at least every 30 days.
See the Operating Instructions section.
The room may have• When the Zoneline is first turned on you need to
been hot or cold.allow time for the room to cool down or warm up.
Outdoor air is• Set the vent control to the closed position.
entering the room.
Burning odoratthe startDust is on the surface• This can cause a “burning” odor at the beginning of
of heating operationof the heating element .the heating operation. This odor should quickly fade.
Consumer SupportTroubleshooting TipsCare and CleaningOperating InstructionsSafety Instructions
20
GEAppliances.com
ProblemPossible CausesWhat To Do
The air is not alwaysThe heat pump is not• This is normal. The heat pump will produce warm air
cool or hot duringproducing hot air.but not as hot as air produced when the higher-cost
operationelectric heat is used.
The Smart Fan Auxiliary• This causes the fan to blow room temperature air
Controls may be set toeven when the compressor or heater cycles off.
continuous fan.The continuous air movement provides better
overall temperature control in the cool mode.
See Smart Fan – Cooling/Heating on page 5.
The air does not feelThe heat pump alone• Use the Electric Heat Option. This turns off the
warm enough duringproduces air that feelsheat pump and warms with electric heat only.
heating operationcooler than desired.NOTE: Use of this option will result in increased energy
consumption.
The unit is notThe Smart Fan Auxiliary• See Smart Fan – Cooling/Heating on page 5.
blowing out airControls may be set to cycle.
The electric heatingThe power cord is not• Remove the room cabinet and make sure that the
feature does not workfirmly attached.yellow connector on the end of the power cord is
firmly engaged.
Safety InstructionsOperating InstructionsCare and CleaningTroubleshooting TipsConsumer Support
Temperature displayThe compressor may• Set the operation control to STOP and then restart
flasheshave failed.the unit . If the flashing light reappears within
30 minutes, call for service.
21
Things that are normal.
Normal Operating Sounds
“CLICK”
You may hear a pinging noise caused by water being
picked up and thrown against the condenser on rainy
days or when the humidity is high. This design feature
helps remove moisture and improve efficiency.
You may hear relays click when the controls cycle
on and off or are adjusted to change the room
temperature.
Water will collect in the base pan during high humidity
or on rainy days. The water may overflow and drip
from the outdoor side of the unit.
The indoor fan runs continuously when the unit is
operating in the cooling mode, unless the Smart Fan
Auxiliary Control is set to cycle. This will cause the fan
to cycle on and off with the compressor. You may also
hear a fan noise stop and start.
3-Minute
Delay
SILENCE
COMPRESSOR
PROTECTION
You may notice a few minutes delay in starting if you
try to restart the Zoneline too soon after turning it
off or if you adjust the thermostat right after the
compressor has shut off. This is due to a built-in
restart protector for the compressor that causes
a 3-minute delay.
During the defrost cycle, both indoor and outdoor fans
stop and the compressor will operate in the cooling
mode to remove frost from the outdoor coil. After
defrost, the unit will restart in electric heat to quickly
warm the room to the desired comfort level.
To protect the compressor and prevent short cycling,
the unit is designed to run for a minimum of 3 minutes
after the compressor starts at any thermostat setting.
Consumer SupportTroubleshooting TipsCare and CleaningOperating InstructionsSafety Instructions
22
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.