This water conditioner’s control valve conforms to NSF/ANSI 44 for materials and
structural integrity only. Generic systems were tested and certified by WQA as
verified by the performance data sheet.
•Please review this entire Installation and Operation manual before installing
unit.
•As with all plumbing projects, we recommend that this Water Conditioning
Unit be installed by a trained professional water treatment dealer. Please
follow all local codes for plumbing this unit.
•Follow local electrical codes. Install a correctly sized electrical bonding jumper
between the inlet and outlet pipes when these devices are installed in metallic
plumbing systems.
•Inspect this unit carefully for carrier shortage or shipping damage before
beginning installation of unit.
•This system is not intended to be used for treating water that is
microbiologically unsafe or of unknown quality without adequate disinfection
before or after the system.
•This system is to be used only for potable water.
•Use only lead-free solder and flux, as required by federal and state codes,
when installing soldered copper plumbing.
•Use caution when sweat joining metal pipes near this water conditioning
system. Heat can adversely affect the plastic used in this system and bypass
valve.
•Use only silicone grease for lubrication of this unit.
•Use only the power transformers supplied with this conditioning systems
control valve unit.
•Do not allow this water conditioning unit to freeze. Damage from freezing will
void this water conditioning unit’s warranty.
•Do not store flammable or volatile chemicals near this water conditioning unit.
•For the purpose of plumbing system sizing, only the rated service (i.e.
"Normal") flow and corresponding pressure loss may be used. The rated
service flow rates are the flow rates at which the performance capabilities of
these devices were evaluated.
Contact your local Professional Water Dealer for system service, and to obtain
Autotrol brand replacement parts for this control valve unit.
3
Valve Illustration
Autotrol 255 Valve Control Module
400 Series Control
Standard L-Lid Cover
Var iabl e
Brine Control
Injector Access Plug
Tank Adapter Module
Brine Line Fitting Connection
1/4-inch NPT
Air Check
Air Check
Figure 1
Probe Connection Slot
Optional
Optional i-lid Cover
i-lid Cover
Optional Bypass
S
S
A
P
Y
B
S
S
A
P
Y
B
Inlet Connection 3/4-inch
or 1-inch NPT or BSPT
Drain Connection 3/8-inch
or 1/2-inch NPT or BSPT
Tank Thread 2-1/2-inch - 8 male
Outlet connection 3/4-inch
or 1-inch NPT or BSPT
Figure 2
4
Introduction
The 255 series control incorporates five cycles during operation, Figure 3 and is
responsible for directing the flow of water during all phases of regeneration. The
water conditioner consists of a control valve, mineral tank, resin and a salt storage
tank. During the service cycle, hardness contaminants are removed from the
water by the resin bed. The regeneration process consists of backwash, brine and
slow rinse, fast rinse and brine refill cycles. During the regeneration process the
hardness contaminants are removed from the resin bed and flushed to the drain,
while the resin bed is regenerated with brine. A description of each cycle and its
function is listed below:
1. Service (Downflow):
Untreated water is directed down through the resin bed and up through the
riser tube. The hardness ions attach themselves to the resin and are removed
from the water. The water is conditioned as it passes through the resin bed.
2. Backwash (Upflow):
The flow of water is reversed by the control valve and directed down the riser
tube and up through the resin bed. During the backwash cycle, the bed is
expanded and debris is flushed to the drain.
3. Brine/Slow Rinse (Downflow):
The control directs water through the brine injector and brine is drawn from
the salt tank. The brine is then directed down through the resin bed and up
through the riser tube to the drain. The hardness ions are displaced by
sodium ions and are sent to the drain. The resin is regenerated during the
brine cycle. Brine draw is completed when the air check closes.
4. Fast Rinse (Downflow):
The control directs water down through the resin bed and up through the riser
tube to the drain. Any remaining brine residual is rinsed from the resin bed.
5. Brine Refill (Downflow):
Brine refill occurs during a portion of the fast rinse cycle. Water is directed to
the salt tank at a controlled rate, to create brine for the next regeneration.
5
From Brine
Tank
To Brine
Tan k
SERVICEBACKWASHBRINE/SLOW RINSEFAST RINSE
BRINE REFILL
Figure 3
Installation
All plumbing must conform to local codes.
Inspect unit carefully for carrier shortage or shipping damage.
Location Selection
1. The distance between the unit and a drain should be as short as possible.
2. If it is likely that supplementary water treating equipment will be required, make
certain adequate additional space is available.
3. Since salt must be added periodically to the brine tank, the location should be
easily accessible.
4. Do not install any unit closer to a water heater than a total run of 10 feet (3 m)
of piping between the outlet of the conditioner and the inlet to the heater. Water
heaters can sometimes overheat to the extent they will transmit heat back
down the cold pipe into the unit control valve.
Hot water can severely damage the conditioner. A 10-foot (3-m) total pipe run,
including bends, elbows, etc., is a reasonable distance to help prevent this
possibility. A positive way to prevent hot water from flowing from heat source
to the conditioner, in the event of a negative pressure situation, is to install a
check valve in the soft water piping from the conditioner. If a check valve is
installed, make certain the water heating unit is equipped with a properly
6
rated temperature and pressure safety relief valve. Also, be certain that
local codes are not violated.
5. Do not locate unit where it or it’s connections (including the drain and overflow
lines) will ever be subjected to room temperatures under 34
o
120
F (49oC).
o
F (1oC) or over
6. Do not install unit near acid or acid fumes.
7. The use of resin cleaners in an unvented enclosure is not recommended.
Water Line Connection
The installation of a bypass valve system is recommended to provide for
occasions when the water conditioner must be bypassed for hard water or for
servicing.
The most common bypass systems are the Autotrol
(Figure 4) and plumbed-in globe valves (Figure 5). Though both are similar in
function, the 256 Autotrol bypass offers simplicity and ease of operation.
Not in BypassIn Bypass
B
Y
P
A
S
S
B
Y
P
A
S
S
®
Series 256 bypass valve
A
P
A
P
S
Y
S
B
S
Y
S
B
Figure 4 Autotrol Series 256 Bypass Valve
Not in Bypass
Water
Conditioner
In Bypass
Water
Conditioner
Figure 5 Typical Globe Valve Bypass System
7
Drain Line Connection
1. Ideally located, the unit will be above and not more than 20 feet (6.1 m) from the
drain. For such installations, use an appropriate adapter fitting (not supplied), to
connect 1/2-inch (1.3-cm) plastic tubing to the drain line connection of the control
valve.
2. If the unit is located more than 20 feet (6.1 m) from drain, use 3/4-inch (1.9-cm)
tubing for runs up to 40 feet (12.2 m). Also, purchase appropriate fitting to
connect the 3/4-inch tubing to the 1/2-inch NPT drain connection.
3. If the unit is located where the drain line must be elevated, you may elevate the
line up to 6 feet (1.8 m) providing the run does not exceed 15 feet (4.6 m) and
water pressure at conditioner is not less than 40 psi (2.76 bar). You may
elevate an additional 2 feet (61 cm) for each additional 10 psi (0.69 bar).
4. Where the drain line is elevated but empties into a drain below the level of the
control valve, form a 7-inch (18-cm) loop at the far end of the line so that the
bottom of the loop is level with the drain line connection. This will provide an
adequate siphon trap.
5. Where the drain empties into an overhead sewer line, a sink-type trap must be
used.
IMPORTANT: Never insert drain line into a drain, sewer line or trap. Always
allow an air gap between the drain line and the wastewater to prevent the
possibility of sewage being back-siphoned into conditioner.
Correct Way
Drain Line Tube
Right Way
Drain
Figure 6
Note: Standard commercial practices have been expressed here. Local codes
may require changes to these suggestions.
Brine Line Connection
It will be necessary to install the brine tube and line to a fitting installed on the air
check. Teflon
Be sure all fittings and connections are tight so that premature checking does not
take place. Premature checking is when the ball in the air check falls to the bottom
before all brine is drawn out of the brine tank. See Placing Conditioner into Operation section.
*Teflon is a registered trademark of E.I. DuPont de Nemours and Company, Inc.
*
tape all threaded connections.
8
Overflow Line Connection
In the absence of a safety overflow and in the event of a malfunction, the BRINE
TANK OVERFLOW will direct “overflow” to the drain instead of spilling on the floor
where it could cause considerable damage. This fitting should be on the side of
the cabinet or brine tank.
To connect overflow, locate hole on side of brine tank. Insert overflow fitting (not
supplied) into tank and tighten with plastic thumb nut and gasket as shown
(Figure 7). Attach length of 1/2-inch (1.3-cm) I.D. tubing (not supplied) to fitting
and run to drain. Do not elevate overflow line higher than 3 inches (7.6 cm) below
bottom of overflow fitting. Do not tie into drain line of control unit. Overflow line
must be a direct, separate line from overflow fitting to drain, sewer or tub. Allow an
air gap as per drain line instructions (Figure 6).
Overflow Fitting
Brine Tank
Installed
Connect 1/2-inch (1.3-cm)
Tubing or Hose and Run
to Drain
Figure 7
Low Voltage Transformer
Use only the included transformer for powering the 400 series timers. Connect the
plug of the transformer secondary cable to the mating socket on the control (see
Figure 8).
Be certain that the transformer is plugged into a correct voltage source that is not
controlled by a wall switch.
9
Increasing the Length of the Transformer Cord
If it is necessary to extend the length of the transformer cord, an optional 15-foot
(4.6-m) extension is available (see Figure 9).
Figure 8
Figure 9
Disinfection of Water Conditioners
The materials of construction of the modern water conditioner will not support
bacterial growth, nor will these materials contaminate a water supply. In addition,
during normal use, a conditioner may become fouled with organic matter, or in
some cases with bacteria from the water supply. This may result in an off-taste or
odor in the water.
Thus, your conditioner may need to be disinfected after installation. Some
conditioners will require periodic disinfection during their normal life. Consult your
installing dealer for more information on disinfecting your conditioner.
Depending upon the conditions of use, the style of conditioner, the type of ion
exchanger, and the disinfectant available, a choice can be made among the
following methods.
10
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.