(1) subject to authorization by EX2
(2) provided the outdoor temperature is less than the setting on "2884 or 3700" (+2° from the beginning)
OFF
ON (1)
ON (2)
ON (2)
ON (2)
Load-shedding (EJP) Off-peak/peak
0 V 230 V 230 V 0 V230 V 0 V 230 V
ON ON OFF ONON ON OFF
ON OFF OFF ONOFF ON OFF
ON OFF OFF ONON ON OFF
ON OFF OFF ONON ON OFF
ON ON ON ONON ON OFF
1.2 Sensor and Input Test Mode
EX 1 EX 2 EX 3
hours
"released"
"locked"
External fault
(369)
LINESENSORINPUTOUTPUT WATERSTAGE
7700 QX Relay test
7710 UX1 Output test
7712 UX1 PWM-Signal
7722 DO2 Cooling mode
7723 D3 Heat pump
7724 UX3 Output test ("Inverter" command)
7725 UX3 Voltage signal (Ux3)
7820 BX1 Sensor temp (HP flow temperature)
7821 BX2 Sensor temp (HP return temperature)
7822 BX3 Sensor temp (DHW temperature)
7823 BX4 Sensor temp (Outside temperature)
7911 EX1 Input (Power shedding, EJP)
7912 EX2 Input (Tariffs day/night)
7913 EX3 Input (External fault)
7973 BX31 Sensor temp (Mixing circuit temp.)
7976 BX34 Sensor temp (Swimming pool exchanger temperature)
7996 H33 Contact state
Maintenance Document 1544-1 5
Split system (Single phase and 3-phase type)
2 Faults
2.1 Fault List
2.1.1 Hydraulic Unit Fault
Faults which occur on the Hydraulic Unit are shown
by the symbol
. Press the info key for details on the
cause of the fault. The following information is
displayed:
Description of the error
Location of the error (sensor or contact)
Reset. Depending on its type, the fault can be
manually or automatically deleted:
No.: Designation of error
10: Outdoor sensor X86 No No Yes
33: Flow sensor HP X70 No No Yes
44: Return sensor HP X70 No No Yes
50: DHW sensor 1 X84 No No Yes
60: Room sensor 1 No No Yes
65: Room sensor 2 No No Yes
105: Maintenance message No No Yes
121: Flow temp HC1 (too low) No No Yes
122: Flow temp HC2 (too low) No No Yes
127: Legionella temp No No Yes
369: External fault (safety component)
370: Thermodynamic source* No No No
No connection
* A fault in the outdoor unit is indicated by LED located on the Hydraulic Unit interface board.
LED display
LED 2 (green) LED 1(red)
1 Flash 1 Flash Communication error between Hydraulic Unit and Outdoor unit.
4 Flashes 1 Flash Heat pump capacity signal error (Open or short).
4 Flashes 2 Flashes Hydraulic Unit heat-exchange thermistor Error.
6 Flashes 3 Flashes Inverter error.
6 Flashes 4 Flashes Active filter error.
7 Flashes 1 Flash Discharge thermistor error.
7 Flashes 2 Flashes Compressor thermistor error.
7 Flashes 3 Flashes Heat-exchange thermistor (outlet) error.
9 Flashes 7 Flashes Outdoor unit fan motor error.
10 Flashes 1 Flash Discharge temperature protection.
10 Flashes 3 Flashes Compressor temperature protection.
10 Flashes 5 Flashes Low pressure abnormal.
Continuous flashing (1 sec ON / 1 sec OFF) Pump down operation.
Fault description
Heat-exchange thermistor (intermediate) error.
Compressor start up error.
Manual delete: the text displayed when pressing
the info key shows "reset ?". Press OK once, the
yes flashes; press again to confirm deletion of the
fault.
Faults whose deletion is automatic are
automatically reset.
Heat pump op: shows whether or not the heat pump
operates despite the fault.
Location
(connection)
Reset
Manual Auto
the polarity of the
room sensor is not
respected.
- - No
HP op
No
6 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
Faults external to the heat pump
Any safety device (e.g. thermostat pressure switch)
wired to input Ex3 (E20) allows external problems to
be reported and the heat pump to be immediately
stopped. For example, a safety thermostat on the
heating floor can be wired to input Ex3 (E20) to avoid
excessively high temperatures in the floor.
Figure 1: Typical Wiring of External Devices
Maintenance Document 1544-1 7
Split system (Single phase and 3-phase type)
2.1.2 Outdoor Unit Fault
When the system is switched back on after a power
outage, the Hydraulic Unit may display fault 370 for a
few tens of seconds. This is not a serious problem. It
simply means that the outdoor unit is running its
tests. Once the tests have been completed, the fault
should disappear.
On the outdoor unit
When an error occurs:
- The diode “ERROR” (2) blinks
Press once on the switch “ENTER” (SW4)
- The “ERROR” (2) diode blinks several times depending on the error’s type
If it doesn't, if a fault has occurred on the outdoor unit
as indicated by the Hydraulic Unit, you must remove
the front (right-hand) facing from the outdoor unit.
Faults are coded by LED flashes. Error messages are
listed in the table below:
LED display on the outdoor unit (single phase and 3-phase)
2. Check for external causes on the Hydraulic Unit and outdoor unit (noise or voltage drop) :
- Check for any other electrical device on the same electric circuit which might cause a drop in
voltage.
- Check for any current leaks.
- Check for any equipment generating electromagnetic waves which interfere with the
communication between the Hydraulic Unit and the outdoor unit.
OK
3. Check the electrical components:
- Check that a voltage between AC 198 and AC 264 V exists between terminals 1 and 2 on the
Hydraulic Unit terminal block.
YES
- Check Main PCB (power supply) for :
o either the fuse (F1, F3).
o or the varistor (VA1-VA5). Fault: overvoltage - external causes - power supply to be
checked).
- Replace the faulty component (if the varistor is blown, the PCB must be replaced).
OK
If all of these checks are unsuccessful, replace Main PCB.
NO
32 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
Clear 38: No heat
Probable causes:
Hydraulic Unit error.
Outdoor unit error.
Influence from the outdoor environment.
Misconnections of connectors and cables.
Refrigeration system fault (not enough gas, clogging, dirty filters).
Check:
1. The unit provides heating or cooling
No
2. Check the Hydraulic Unit :
- Is the pump operating?
- See if the exchanger is not clogged?
3. Check the outdoor unit:
- Is the fan rotating at high speed?
- Are there any objects blocking the air flow?
- Is the outdoor exchanger clogged?
- Are the valves open?
4. Check the configuration of the room:
- Is the heat pump power suited to the need?
5. Inspect the Hydraulic Unit and outdoor unit installation:
- Check the refrigeration connections (length, diameter)
6. Inspect the refrigeration circuit:
- See if the dehydrator is clogged (there should be no temperature variation
between the dehydrator input and output in normal operating conditions).
- Check the electronic expansion valve
- Check the compressor
Yes
Is the cooling kit
connected ?
Check the wiring of the cooling kit
control wire
Maintenance Document 1544-133
Split system (Single phase and 3-phase type)
Clear 39: Abnormal noise
Probable causes:
Abnormal installation (outdoor)
Fan failure
Compressor failure.
Temperature (°C) 0 5 10 15 20 30 40 50 60
Resistance value (k)
Temperature (°C) 70 80 90 100 120
Resistance value (k)
Outdoor Temperature
Temperature (°C) -20 -10 -5 0 5 10 15 20 30
Resistance value (k)
Temperature (°C) 40 50 60 70
Resistance value (k)
27,5
168
8,7
115
5,18
Heat sink
Temperature (°C) 0 5 10 15 20 30 40 50 60
Resistance value (k)
Temperature (°C) 70 80 90 100 110 120
Resistance value (k)
15,8
0,83
20,9 16,1 12,4 9,73 7,67 6,1 3,95
130 101 79 63 40 26,3 17,8 12,3
6,3 4,6 3,4 2
62,3 46,6 35,2 26,9 20,7 16,1 12,6 7,97
3,45 2,36 1,65
12,2 9,5 7,5 5,9 3,78 2,50 1,69 1,17
0,60 0,44 0,33
0,25
0,19
2.3.2 Hydraulic Unit Temperature Sensors
Heat Exchanger (Condensing sensor)
Temperature (°C) 0 5 10 15 20 25 30 35 40 45 50
134 103 80,362,949,739,631,7 25,6
Resistance value (k)
Outdoor sensor
Temperature (°C) -20 -15 -10 -5 0 5 10 15 20
Resistance value (k)
Temperature (°C) 25 30 35 40 45
Resistance value (k)
Heat pump flow and return sensor – DHW and heating zone 2 sensor – Swimming pool return sensor
Temperature (°C) -15 -10 -5 0 5 10 15 20 25
Resistance value (k)
Temperature (°C) 30 35 40 45 50 55 60 65 70
Resistance value (k)
176
7,60
1
72,5
8
5,85
0,83 0,70 0,58 0,48
55 42 32,5 25 20 15,7 12,5 10
6,5 5 4 3,5 3 2,5 2 1,7
4,60
3,60 2,85 2,30 1,85 1,50 1,20
20,8 17,1
Maintenance Document 1544-135
Split system (Single phase and 3-phase type)
2.4 Service parts information
2.4.1 Service parts information 1 : Compressor
Diagnosis method of compressor (if outdoor unit LED displays error, refer to Failures and clears)
Does not start up
Is there open or loose
connection cable?
Check connection of
compressor, and winding
resistance (Refer to the next
page).
If there is no failure, the
defected of compressor is
considered (locked
compressor due to clogged
dirt or less oil).
Replace compressor
Abnormal noise Stops soon after starting up
Is there open or loose
connection cable?
Is gas pipe valve open ?
(Low pressure is too low)
Check if refrigerant is leakin.
Recharge refrigerant.
Check if stainer is clogged
(Parts information 3)
Check inverter PCB, connection of compressor, and
winding resistance (refer to the next page).
If there is no failure, the defected of compressor is
considered (Compression part broken or valve
defective).
Check if vibration noise by
loose bolt or contact noise of
piping is happening.
Defective compressor can
be considered (due to inside
dirt clogging or broken
component).
Replace compressor
Replace compressor
36 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
2.4.2 Service parts information 2 : Inverter compressor
Check point 1 : Check connection
Check terminal connection of compressor
(Loose or incorrect wiring)
Only for 3-phase type :
Check connection of inverter PCB
(Loose or incorrect wiring)
(RED)
Main PCB
(WHITE)
(BLACK)
Check point 2 : check winding resistance
Check winding resistance on each terminal
If the resistance value is 0Ω or infinite, replace compressor.
Resistance value :
- 0.24 Ω (at 20°C) for single phase type
- 0.79 Ω (at 20°C) for 3-phase type
BLACK
WHITE
Compressor
Check point 3 : replace Main PCB
If check point 1 and 2 do not improve the symptom, replace Main PCB.
Maintenance Document 1544-137
Split system (Single phase and 3-phase type)
)
)
)
2.4.3 Service parts information 3 : Outdoor unit electronic expansion
valve (EEV, EEV(INJ))
Check point 1 : Check connection
Check connection of connector
(Loose connector or open cable)
Single phase :
EXPANSION VALVE
COIL
EXPANSION
VALVE COIL
(INJ)
3-phase :
EXPANSION VALVE COIL
Check point 2 : Check coil of EEV
Remove connector, check each winding resistance of
coil.
Read wire Resistance value
White-Red
Yellow-Red
Orange-Red
46Ω +/- 4Ω
at 20°C
Blue-Red
If resistance value is abnormal, replace EEV.
Check point 5 : Check opening and closing operation of valve
When valve is closed, it has a temp. (Add period)
difference between inlet and outlet.
CLOSE
Example : Hot gas
Pipe (In)
HI TEMP.
Check point 3 : Check voltage from main PCB
Remove connector and check voltage (DC12V)
If it does not appear, replace Main PCB.
Check point 4 : Check noise at start up
Turn on power and check operation noise.
If an abnormal noise does not show, replace Main
PCB.
If it is open, it has no temp. (Add period) difference
between inlet and outlet.
OPEN
Example : Hot gas
Pipe (In)
HI TEMP.
EXPANSION VALVE
COIL (INJ)
Pipe (Out)
Pipe (Out)
There is no refrigerant flow coming to EEV(INJ) while the liquid injection is inactive. Check whether the liquid
injection is active before executing check point 5 for EEV(INJ).
Check point 6 : Check stainer
Stainer normally does not have temperature difference between inlet and outlet as shown in 1, but if there is a
difference as shown in 2, there is a possibility of inside clogged. In this case, replace stainer.
Pipe (In)
Pipe (Out
Pipe (In
Pipe (Out
38 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
2.4.4 Service parts information 4 : Outdoor unit solenoid valve (SV)
Check point 1 : Check connections
Check connection of connector
(Loose connector or open cable)
CN501
1 2
1 2
SOLENOID
COIL (INJ)
SV
BLUE
BLUE
Check point 4 : check opening and closing operation valve
Depending on the injection activity, check if valve is operating normally.
(When valve opens, ther is no temperature difference between inlet and outlet)
Check point 2 : Check solenoid coil
Remove connector and check if coil is open
(normal resistance value of each coil : 1495+/7%)
If resistance value is abnormal, replace
solenoid coil.
Check point 3 : Check voltage from main
PCB
Remove connector and check the voltage
(AC230V).
If the voltage does not appear, replace Main
PCB.
Injection is inactive
Pipe (In) TEMP. HI.
Pipe (Out) TEMP. Normal
Pipe (In)
HI TEMP.
CLOSE
Pipe (Out)
Normal TEMP.
SOLENOIDE COIL
If the valve closes by removing the connector of the
valve which does not close, it is considered to be
Main PCB failure. Replace Main PCB.
If it does not closeby removing connector, there is a
possibility of (1) clogging by dirt, or (2) deformation
by the heat at the time of solenoid valve installation.
In this case, replace solenoid valve.
Injection is active
Pipe (In) TEMP.= Pipe (Out) TEMP.
Pipe (In)
HI TEMP.
SOLENOIDE COIL
OPEN
Pipe (Out)
HI TEMP.
Maintenance Document 1544-139
Split system (Single phase and 3-phase type)
2.5 Operating Limits
HEAT PUMP
Min/max OT in heat mode
(°C)***
Heating floor maximum
water temperature (°C)
LT radiator maximum
water temperature (°C)
Min/max OT in cooling
mode(°C)
Cooling floor minimum
water temperature (°C)
Fan coil minimum water
temperature (°C)
Water circuit max pressure
(Bar)
Maximum flow rate (l/h) 2340 2920 2340 2920 3290
Minimum flow rate (l/h) 1170 1460 1170 1460 1650
Refrigerant circ max
pressure (kPa)
Min delta T (°C) 4
Max delta T (°C) 8
Outdoor unit Noise level 1
(dBA)*
Outdoor unit Noise level 5
(dBA)**
Outdoor unit air flow rate
3
(m
/h)
* Acoustic pressure level reading at 1m, in open field, on a reflecting plane.
** Acoustic pressure level reading at 5m, in open field, on a reflecting plane.
*** When the outdoor temperature continuously exceeds 35°C, DHW heating is done b y the water heater
heating element.
Single phase 3-phase
112 140 112 140 160
-25/35
45
60
8/43
18
8
3
4,2
55 56 53 55 56
39 41 39 41 42
3100 x 2 3450 x 2
40 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
3 Failures
3.1 Hydraulic, Electric and Refrigeration Systems
3.1.1 Hydraulic System
If the installation is fitted with a heating floor, the most
common failures are those listed below:
FAILURE CASES CONSEQUENCES SOLUTIONS
1- Clogged filter*
or sludge in system
2- Pump out of order
3-Leak Low level in expansion vessel
4- Clogged heating
circuit (crushed pipe)
5- Misbalance
6- Floor undersized or
charge losses too high
* Not required and not shown on the device.
Flow pressure too high clean filter or desludge Installer
∆T too high (>7) clean filter or desludge Installer
Zero flow pressure
current too high (rotor locked)
zero current (winding cut off)
pump stuck release with a screwdriver
Very high difference between floor
flow/return temp
Very high difference between floor
flow/return temp
Very high difference between floor
flow/return temp
change pump with warranty if pump
is faulty
change pump with warranty if pump
is faulty
change pump with warranty if pump
is faulty
On collector,
isolate heating
circuits to
determine which
heating circuit is
perforated.
On collector,
check heating
circuit flow/return
temps (infrared
thermometer)
If no clogged
heating circuit,
check for
crushing with
infrared camera
Rebalance Installer
On collector,
check heating
circuit flow/return
temps (infrared
thermometer)
Pipe leak. Pipe
under warranty if
faulty
Leak in heating
circuit. Floor
again.
Clear with test
pump
Call the installer's
or floor coverer's
responsibility into
question
Call the installer's
responsibility into
question
APPLIED
BY
Service
station
Service
station
Service
station
Installer
Service
station
Installer
Service
station
Installer
or
Service
station
Maintenance Document 1544-141
Split system (Single phase and 3-phase type)
3.1.2 Electrical System
Outdoor Unit Overvoltage
Check for possible causes in the list below (this list is
not exhaustive):
Problem with the compressor
Main board
Faulty power relay
Inspection of the Power Transistor Module (Main board)
Disconnect the compressor relay and the condenser
connection. Measure the resistance value at the
points shown on the illustration, and then compare
the values observed with those in the table.
Steps to be followed before performing any work
on the Inverter module:
First switch off the system using the circuit
breaker at the head of the line.
Remove the unit cover and then remove the
Inverter module cover.
Measure the voltage at the condenser terminals.
You should find a value of 5 Vdc or less.
3-phase type Single phase type
Multimeter Resistor
Terminal block
N
W
1 MOhm
or more
V
U
Main PCB
P
42 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
3.1.3 Refrigeration System
Unit produces no heat
The unit remains in continuous scanning mode.
Initial checks:
Check the settings
Are the data sent by the user interface received by the heat pump?
Hydraulic unit
electronic circuit
sending data to
outdoor unit ?
Yes
Compressor
running ?
Yes
Operating pressure
OK ?
Yes
4-way valve
switching ?
Yes
Expansion correct ?
Yes
Inspect refrigeration
lines (clogging)
No
No
No
No
No
No
Change
expansion valve
Hydraulic unit electronic system faulty
Inspect PCB
Charge to balance
Problem solved?
Yes
Servicing complete
Valve coil faulty ?
Yes
Change coil
No
Change 4-way valve
after testing
Maintenance Document 1544-143
Split system (Single phase and 3-phase type)
)
Outdoor unit does not defrost
Is condensation drain properly discharged
(outdoor unit directly on the ground)?
Are the auxiliaries powered?
In boiler backup mode, is the boiler authorized?
In very cold areas, a fusing resistance value is
recommended.
Is the installation regularly subject to micro-
outages of power (frequent outages on the mains
power system may also cause defrosting
problems)?
Is there a peak day clearing (EJP) outage on the
installation?
Does the heat pump regularly switch to high
pressure safety mode?
If this occurs at low temperatures (< 5 °C), we
recommend checking that the water pump is
operating properly.
Note:
Outdoor unit defrosting is controlled by the exchanger sensor and the controller board. If no frosting is observed
and no anomaly is otherwise noted, the sensor and board must be inspected and the faulty part will have to be
replaced.
Defrosting
a. Defrost beginning conditions
Is the charge correct (refer to the
temperature/pressure curve)?
Insufficient charging will result in frequent icing.
Overcharging will result in frequently switching to
HP safety mode.
(If you still have doubts as to the charge, perform the
charging with an electronic scale).
Outdoor unit defrosting is controlled by the
exchanger sensor and the controller board.
If the defrost sensor is not iced up while the rest of
the exchanger is, then:
Move the sensor between the exchanger blades
to a place where the exchanger is iced up.
If all these points have been checked, replace the
outdoor controller board.
1st defrost Subsequent defrosts
62’ < t < 240’
O Exch T
≤ -9°C
OT – O Exch T >5°C
Start of heat mode
(Compressor ON)
(No defrost for 10 min
Cumulative compressor operating time
O Exch T
≤ -5°C
O Exch T
≤ -3°C
O Exch T
≤ -10°C
240’ < t 17’ < t < 62’ 240’ < t 35’ < t < 240’
O Exch T
≤ -3°C
Defrost
O Exch T : outdoor unit exchanger temperature
OT : outdoor temperature
t : Cumulative compressor operating time
44 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
b. Defrost ending conditions
With all models, defrosting stops if the exchanger
temperature is above 10 °C or if the defrosting time is
over 15 minutes).
Crankcase heater
When the outdoor exchanger temperature is below
-18°C and the heating mode has been stopped for
30 minutes, the compressor windings are powered
and maintain the compressor temperature.
3.2 Compressor Operating Checks
Using a multimeter set to mega ohm, check that the
resistance value across the windings is identical
irrespective of the phase (between U and V, V and
W, W and U). This value should be approx. 1 Ohm.
3.3 Refrigeration Circuit Leak Test
The new regulation requires annual leak testing of
installations with a refrigerant charge higher than 2kg.
When operation has started and the temperature
becomes higher than -16°C, heating stops.
Check that resistance between each phase and the
earth is infinite. The result should be clear (you
should not see the displayed value increasing slowly
up to a value greater than the multimeter maximum
rating).
Leak testing is to be performed with an approved
detector that has been appropriately calibrated.
3.4 Troubleshooting
The heat pump is not operating at all (no illuminated indicator):
Are the power supply voltage and frequency
normal?
Is the connection to mains correct?
Have all the connectors been properly inserted?
Are the fuses on the outdoor unit still operating?
If not, change the bad fuse(s).
Is the connection between the outdoor unit and
the Hydraulic Unit correct? Do you read 230V AC
between terminals 1 and 2 of the Hydraulic Unit
terminal block?
Do you read 230V AC at the transformer primary
on the Hydraulic Unit? If not, change the board.
Is there any voltage on the transformer
secondary on the Hydraulic Unit? If not, check
the thermal fuse. If the fuse is good, the error
comes from the board.
Maintenance Document 1544-145
Split system (Single phase and 3-phase type)
4 Control Settings
4.1 General
The settings described below are those which can be
modified by the user.
We wish to remind you that changing the settings
below may cause the heat pump to behave in an
undesirable way. A testing period should be
conducted before the permanent settings of the heat
pump are confirmed. This may require a number of
changes to be made by the installer.
1 U Hour/minutes 00:00…23:59
2 U Day/month 01.01…31.12
3 U Year 1900…2099
5 S Start of summertime 01.01…31.12 25.03
6 S End of summertime 01.01…31.12 25.10
Operator section
20 U Language English
22 S Info
Temporarily /
Permanent
Temporarily
26 S Operation lock Off/on Off
27 S Programming lock Off/on Off
28 S Direct adjustment... Auto/confirm Confirm
29 S
Temperature unit
Pressure unit
°C, °F
bar, psi
°C
bar
70 S Software version
Time prog heating circuit 1
500 U Preselection
Mon-Sun ¦ Mon-Fri ¦ Sat - Sun ¦
Mon ¦ Tue ¦ Wed ¦Thu ¦ Fri ¦ Sat
¦Sun
Mon-Sun
501 U 1st phase on 00:00…--:-- 6:00
502 U 1st phase off 00:00…--:-- 22:00
503 U 2nd phase on 00:00…--:-- --:-504 U 2nd phase off 00:00…--:-- --:-505 U 3rd phase on 00:00…--:-- --:-506 U 3rd phase off 00:00…--:-- --:-515 U Copy
516 U Default values, Circuit 1 No/yes No
Time prog heating circuit 2
520 UPreselection
Mon-Sun ¦ Mon-Fri ¦ Sat - Sun ¦
Mon ¦ Tue ¦ Wed ¦Thu ¦ Fri ¦ Sat
¦Sun
Mon-Sun
521 U1st phase on 00:00…--:-- 6:00
522 U1st phase off 00:00…--:-- 22:00
523 U2nd phase on 00:00…--:-- --:-524 U2nd phase off 00:00…--:-- --:-525 U3rd phase on 00:00…--:-- --:-526 U3rd phase off 00:00…--:-- --:-535 U Copy
536 UDefault values, Circuit 2 No/yes No
Time program 4 / DHW
560 U Preselection
Mon-Sun ¦ Mon-Fri ¦ Sat - Sun ¦
Mon ¦ Tue ¦ Wed ¦Thu ¦ Fri ¦ Sat
¦Sun
Mon-Sun
561 U 1st phase on 00:00…--:-- 00:00
562 U 1st phase off 00:00…--:-- 05:00
563 U 2nd phase on 00:00…--:-- 14:30
564 U 2nd phase off 00:00…--:-- 17:00
565 U 3rd phase on 00:00…--:-- --:-566 U 3rd phase off 00:00…--:-- --:-575 U Copy
576 U Default values No/yes No
Time program 5 / Cooling circuit
600 U Preselection
Mon-Sun ¦ Mon-Fri ¦ Sat - Sun ¦
Mon ¦ Tue ¦ Wed ¦Thu ¦ Fri ¦ Sat
¦Sun
Mon-Sun
601 U 1st phase on 00:00…--:-- 8:00
602 U 1st phase off 00:00…--:-- 20:00
Maintenance Document 1544-147
Split system (Single phase and 3-phase type)
COMMAND
LINE
ACCESS
LEVEL
FUNCTION SETTING RANGE
FACTORY
SETTING
603 U 2nd phase on 00:00…--:-- --:-604 U 2nd phase off 00:00…--:-- --:-605 U 3rd phase on 00:00…--:-- --:-606 U 3rd phase off 00:00…--:-- --:-615 U Copy
616 U Default values No/yes No
Holidays heating circuit 1
641 U Preselection Period 1…8 Period 1
642 UPeriod start (Day / Month) 01.01…31.12
643 UPeriod end (Day / Month) 01.01…31.12
648 UOperating level
Frost protection ¦ ReducedFrost protection
Holidays heating circuit 2
651 U Preselection Period 1…8 Period 1
652 UPeriod start (Day / Month) 01.01…31.12
653 UPeriod end (Day / Month) 01.01…31.12
658 UOperating level
716 S Comfort setpoint maximum 20°C…35°C 28°C
720 I Heating curve slope 0,1…4 0,5
721 I Heating curve displacement -4,5°C…4,5°C 0°C
726 I Heating curve adaption Off, on Off
730 I Summer/winter heating limit 8°C…30°C 18°C
732 S 24-hour heating limit -10°C…10°C -2°C
740 I
Flow temp setpoint min (for fan
convectors)
8°C… 95°C 8°C
741 I Flow temp setpoint max 8°C… 95°C 55°C
750 S Room influence 1%...100% 50%
780 S Quick setback
Off ¦ Down to reduced
setpoint ¦ Down to frost
prot setpoint
Down to reduced
setpoint
790 S Optimum start control max 0…360min 180 min
791 S Optimum stop control max 0…360min 60 min
800 S Reduced setpoint increase start -30°C…10°C --801 S Reduced setpoint increase end -30°C…10°C -5°C
830 S Mixer valve boost 0…50°C 0
834 S Actuator running time 30…873s 240s
850 I Floor curing function 0…5 Off
851 I Floor curing setpoint manually 0°C…95°C 25°C
856 IFloor curing day current 0…32
857 I Floor curing day completed 0…32
900 S Optg mode changeover
Protection mode
Cooling circuit 1
901 U Operating mode
Off ¦ Automatic
Automatic
902 U Comfort setpoint 15…40°C 24°C
24h/day ¦ Time
907 U Release
program HC ¦ Time
program 5
24h/day
908 I Flow temp setp at OT 25°C 6…35°C 20°C
909 I Flow temp setp at OT 35°C 6…35°C 16°C
912 I Cooling limit at OT ---/8…35°C 20°C
913 S Lock time at end of heating ---/8…100h 24h
918 S Summer comp start at OT 20…50°C 26°C
919 S Summer comp end at OT 20…50°C 35°C
48 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
COMMAND
LINE
ACCESS
LEVEL
FUNCTION SETTING RANGE
FACTORY
SETTING
920 S Summer comp setp increase ---/1…10°C 4°C
923 S Flow temp setp min OT 25°C 6…35°C 18°C
924 S Flow temp setp min OT 35°C 6…35°C 18°C
928 S Room influence ---/1…100% 80%
932 S Room temp limitation ---/0…4°C 0.5°C
938 S Mixing valve decrease 0…20°C 0°C
941 S Actuator running time 30…650s 120s
945 S Mixing valve in heating mode
963 S With prim contr/system pump
1016 S Comfort setpoint maximum 20…35°C 28°C
1020 I Heating curve slope 0,1…4 0,5
1021 I Heating curve displacement
-4,5°C…4,5°C
0°C
1026 S Heating curve adaption Off, on Off
1030 I Summer/winter heating limit 8°C…30°C 18°C
1032 S 24-hour heating limit -10°C…10°C -2°C
1040 S
Flow temp setpoint min (for fan
convectors)
8°C… 95°C 8°C
1041 I Flow temp setpoint max 8°C… 95°C 55°C
1050 I Room influence 1%...100% 50%
1080 S Quick setback
Off ¦ Down to reduced
setpoint ¦ Down to frost
prot setpoint
Down to reduced
setpoint
1090 S Optimum start control max 0…360min 180 min
1091 S Optimum stop control max 0…360min 60 min
1100 S Reduced setpoint increase start -30…10°C --1101 S Reduced setpoint increase end -30…10°C -5°C
1130 S Mixer valve boost 0…50°C 0°C
1134 S Actuator running time 30…873s 240s
1150 I Floor curing function Off
1151 I Floor curing setpoint manually 0°C…95°C 25°C
1156 IFloor curing day current 0…32
1157 I Floor curing day completed 0…32 0
1200 S Optg mode changeover
Protection mode
Domestic hot water
1610 U Nominal setpoint Thc…65°C 55°C
1612 U Reduced setpoint 8°C….Thc 40°C
24h/day
1620 I Release of DHW load
1640 I Legionella function
Heating circ time pgms
Time program 4/DHW
Off-peak rate
4: Time pgm 4/DHW or
Off-peak rate
Off
Periodically
Fixed weekday
Time program
4/DHW
Off
1641 I Legionella function periodically 1 to 7 7
1642 I Legionella function weekday Mon,…Sun Sunday
Swimming pool
2056 U Setpoint source heating 8…80 22
Heat pump
2803 S Overrun time cond pump 0…240s 240
2843 S Compressor off time min 0…120min 8min
2844 S Switch-off temp max 8°C… 100°C 75°C
2862 S Locking time stage 2 0…40min 5min
Maintenance Document 1544-149
Split system (Single phase and 3-phase type)
COMMAND
LINE
2873 S
ACCESS
LEVEL
FUNCTION SETTING RANGE
Compressor mod run time
FACTORY
SETTING
10…240s 240
2882 S Release integr electric flow 0… 500°Cmin 100°Cmin
2884 S Release el flow at OT -30°C…30°C 2°C
2886 S Compensation heat deficit
Off ¦ On ¦ Only with
floor curing fct
Off
2916 S Max setpoint HP DHW charg 8°C… 80°C 60°C
2920 S With electrical utility lock Lock/release Released
Supplementary source
3700 S Release below outside temp -50…50°C 2°C
3701 S Release above outside temp -50…50°C
3705 S Overrun time 0...120min 20min
3720 S Switching integral 0… 500°Cmin 100°Cmin
3723 S Locking time 0...120min 30min
DHW storage tank
5024 S Switching differential 0…20°C 7°C
5030 S Charging time limitation 10…600min 90 min
5055 S Recooling temp 8…95°C 65°C
5057 S Recooling collector
5061 S Electric immersion heater release
5093 S Not used
Off ¦ Summer ¦ Always
24h/day
DHW release
Time program 4/DHW
Summer
DHW release
Configuration
5700 I Pre-setting 1 to 12 1
5710 I Heating circuit 1
5711 I Cooling circuit 1
5715 I Heating circuit 2
5731 I DHW ctrl elem Q3
5806 I Type el imm heater flow
5981 S Cont type input EX1
5983 S Cont type input EX2
5985 S Cont type input EX3
NO
6098 S Not used -20…20°C 0°C
6100 S Readjustm outside sensor -3…3°C 0°C
6120 S Frost protection plant On/off On
6205 S Reset to default parameters No/yes No
6220 S Software version 0…99 --
6711 U Reset HP No/yes No
6800 S History 1 Date/time/code
6802 S History 2 Date/time/code
6804 S History 3 Date/time/code
6806 S History 4 Date/time/code
6808 S History 5 Date/time/code
6810 S History 6 Date/time/code
6812 S History 7 Date/time/code
50 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
COMMAND
LINE
ACCESS
LEVEL
FUNCTION SETTING RANGE
FACTORY
SETTING
6814 S History 8 Date/time/code
6816 S History 9 Date/time/code
6818 S History 10 Date/time/code
Service / special operation
7070 SHP interval 1..240 months --7071 SHP time since maint 0..240 months 0
7073 SCur starts compressor 1/hrs run 0…12 0
7141 U Emergency operation On/off Off
7142 S Emergency operating function type Manual/auto Manual
7150 I Simulation outside temp -50…50°C ---
Input / output test
No test
All OFF
Relay output QX1
Relay output QX2
Relay output QX3
Relay output QX4
Relay output QX5
Relay output QX6
Relay output QX31
7710 I Output test UX1 0…100% ---%
7712 I PWM-Signal UX1 0…100% 0
7716 I Output test UX2 0…100%-7719 I PWM-Signal UX2 0…100%0
7722 I Cooling mode DO2 On/off Off
7723 I Heat pump D3 On/off Off
7724 I Output test UX3 0…100%
7725 I Voltage value UX3 0…100% --
7820 I Sensor temp BX1 -28…350°C -7821 I Sensor temp BX2 -28…350°C -7822 I Sensor temp BX3 -28…350°C -7823 I Sensor temp BX4 -28…350°C -7824 I Sensor temp BX5 -28…350°C -7825 I Sensor temp BX6 -28…350°C -7830 I Sensor temp BX21 module 1 -28…350°C -7832 I Sensor temp BX21 module 2 -28…350°C -7849 I Contact status H2, module 2 Open, Closed Open
7911 I Input EX1
7912 I Input EX2
7913 I Input EX3
0V ¦ 230V
0V ¦ 230V
0V ¦ 230V
--
--
-7973 I Sensor temp BX31 -28…350°C -7974 I Sensor temp BX32 -28…350°C -7975 I Sensor temp BX33 -28…350°C -7976 I Sensor temp BX34 -28…350°C -7977 I Sensor temp BX35 -28…350°C -7978 I Sensor temp BX36 -28…350°C -7996 I Contact state H33 Open ¦ Closed Open
State of plant
8000 I State heating circuit 1 -8001 I State heating circuit 2 -8003 I State DHW -8004 I State cooling circuit 1 --
Maintenance Document 1544-151
Split system (Single phase and 3-phase type)
COMMAND
LINE
ACCESS
LEVEL
FUNCTION SETTING RANGE
FACTORY
SETTING
8006 I State heat pump -8007 I Not used -8010 I Not used -8011 I State swimming pool -8022 I State supplementary source --
Diagnostics heat source
8402 I El imm heater flow 1 Off/on Off
8403 I El imm heater flow 2 Off/on Off
8406 I Condenser pump Off/on Off
8410 U Return temp HP 0…140°C -8412 U Flow temp HP 0…140°C -8413 U Compressor modulation 0…100% -8414 I Modulation electric flow 0…100% -8425 I Temp diff condenser -50…140°C -8454 S Locking time HP 0…2730h -8455 S Counter number of locks HP 0…65535 -8456 S Hours run el flow 0…2730h -8457 S Start counter el flow 0…65535 --
Diagnostics consumers
8700 U Outside temperature -50…50°C -8701 U Outside temp min -50…50°C -8702 U Outside temp max -50…50°C -8703 I Outside temp attenuated -50…50°C -8704 I Outside temp composite -50…50°C -8730 I Heating circuit pump, circuit 1 Off/on Off
8731 I Mixer valve HC1 open Off/on Off
8732 I Mixer valve HC1 closed Off/on Off
8740 U Room temp 1 0…50°C -8743 U Flow temp 1 0…140°C -8756 U Flow temperature cooling 1 0…140°C -8760 I Heating circulation pump, circuit 2 Off/on Off
8770 URoom temp 2 0…50°C 20°C
8773 U Flow temp 2 0…140°C -8820 I DHW pump Off/on Off
8821 I Electric immersion heater DHW Off/on Off
8830 U
DHW (domestic hot water)
temperature
0…140°C 55°C
8840 S Hours run DHW pump 0…2730h -8841 S Start counter DHW pump 0…2730h -8842 S Hours run el DHW 0…2730h -8843 S Start counter el DHW 0…65535 -8900 U Swimming pool temp 0…140°C 22°C
8950 S Common flow temp 0…140°C -8957 S Common flow setp refrig 0…140°C -9031 I Relay output QX1 Off/on On
9032 I Relay output QX2 Off/on On
9033 I Relay output QX3 Off/on On
9034 I Relay output QX4 Off/on Off
9035 I Relay output QX5 Off/on Off
9050 I Relay output QX21 module 1 Off/on Off
9051 I Relay output QX22 module 1 Off/on Off
9052 I Relay output QX23 module 1 Off/on Off
9053 I Relay output QX21 module 2 Off/on Off
9054 I Relay output QX22 module 2 Off/on Off
9055 I Relay output QX23 module 2 Off/on Off
9071 U Relay output QX31 Off/on On
9072 U Relay output QX32 Off/on On
52 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
COMMAND
LINE
9073 U Relay output QX33 Off/on Off
9074 U Relay output QX34 Off/on Off
9075 U Relay output QX35 Off/on Off
ACCESS
LEVEL
FUNCTION SETTING RANGE
FACTORY
SETTING
4.3 Adjustment Function Details
4.3.1 Date and Time Functions
The controller has an annual clock which contains the time, the day of the week and the date.
In order for the function to operate, the time and date must be set properly on the clock.
LINE NO. PROGRAMMING LINE
1 Hour/minutes
2 Day/month
3 Year
5 Start of summertime
6 End of summertime
NOTE: Summer time/winter time change
Dates have been set for changing to summer time or to winter time. The time changes automatically from 2am
(winter time) to 3am (summer time) or from 3am (summer time) to 2am (winter time) on the first Sunday
following the respective date.
4.3.2 User Interface Functions
LINE NO. PROGRAMMING LINE
20 Language
22 Info
26 Operation lock
27 Programming lock
28 Direct adjustment...
29
Info (22):
Temporary:
After pressing the Info key, the information display
returns to the basic "predefined" display after 8
minutes or when pressing the operating mode key.
Permanent:
After pressing the Info key, the information display
returns to the "new" standard display after a
maximum of 8 minutes. The last selected information
value is shown in the new basic display.
Maintenance Document 1544-153
Temperature unit
Pressure unit
Operation lock (26):
If the operating lock is activated, the following control
elements can no longer be adjusted:
Heating circuit mode, DHW mode, room temp comfort
setpoint (knob), occupancy key.
Split system (Single phase and 3-phase type)
Programming lock (27):
If the programming lock is activated, the setting
values are displayed but may no longer be changed.
Temporary Suspension of Programming
The programming lock can be temporarily
deactivated at programming level. To do this,
simultaneously press the OK and ESC keys for at
least 3 seconds. The temporary suspension of the
programming lock remains in effect until you exit the
programming.
Heating Circuit Assignment
LINE NO. PROGRAMMING LINE
70 Software version
Software version
The indication shows the current version of the user
interface.
Permanent Suspension of Programming
First perform a temporary suspension, then cancel
"Programming lock" on line 27.
Direct adjustment... (28):
Automatic storage
Correction of the setpoint with the knob is adopted
without a particular confirmation (timeout) or by
pressing the OK key.
Storage with confirmation
Correction of the setpoint with the knob will be
adopted only after pressing the OK key.
4.3.3 Time Program Functions (heating circuit 1 & 2, DHW, cooling)
Several control programs are available for the heating
circuits and the production of DHW. They are initiated
in "Automatic" mode and control the change in
temperature levels (and therefore the associated
setpoints, reduced and comfort) via the adjusted
changeover times.
Changeover Points
Line no.
HC1 HC2 4/DHW 5
500 520 560 600 Preselection
501 521 561 601 1st phase On
502 522 562 602 1st phase Off
503 523 563 603 2nd phase On
504 524 564 604 2nd phase Off
505 525 565 605 3rd phase On
506 526 566 606 3rd phase Off
Standard Program
Line no. Programming line
516, 536, 576, 616 Default values
All time programs can be reset to factory settings.
Each time program has its own command line for this
reset action.
Programming line
(Mon-Sun / Mon-Fri / Sat – Sun / Mon...Sun)
(No /Yes)
Enter changeover times:
Changeover times can be adjusted in a combined
way, i.e., identical times for several days or distinct
times for certain days. Preselecting groups of days
(e.g., Mon...Fri and Sat...Sun) having the same
changeover times makes adjustment of the
changeover program considerably shorter.
In this case, individual settings will be lost!
54 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
Holidays:
Line no.
HC1 HC2
642 652 Period start (Day / Month)
643 653 Period end (Day / Month)
648 658 Operating level
The holiday program enables changing the heating
circuits over to a selected operating level according to
the date (calendar).
Programming line
4.3.4 Heating Circuit 1 & 2 Functions
Operating Mode
For heating circuits there are several functions
available which can be individually adjusted for each
heating circuit.
Room temperature can be set according to different
setpoint values. Depending on the selected mode,
these setpoints are activated and provide different
temperature levels in the rooms.
Programming line
Important !
The holiday program can be used only in the
automatic mode.
The programming lines for the 2nd heating circuit are
displayed only if an extension module has been
connected to the controller.
Operation of heating circuits 1 and 2 is directly
controlled via the operating mode key.
The ranges of configurable setpoints are defined by
their interdependencies, as shown in the graph
below.
Comfort setpoint
Reduced setpoint
Frost prot. setpoint
Frost protection:
The protection mode automatically prevents an
excessively sharp drop in room temperature.
Maintenance Document 1544-155
In this case the control adopts the frost protection
room setpoint.
Based on the heating characteristic, the controller
computes the flow temperature setpoint which will be
used for controlling the flow temperature in
consideration of atmospheric conditions. Different
settings can be used to adapt the heating
characteristic so that the heating capacity, and
therefore the room temperature, will match the
individual needs.
The colder the outdoor temperature, the greater the
extent to which the slope will modify the flow
temperature. In other words, the slope should be
corrected if the room temperature shows a difference
when the outdoor temperature is low, but not when it
is high.
oIncrease the setting:
The flow temperature is increased mainly when the
outdoor temperatures are low.
oDecrease the setting:
The flow temperature is lowered mainly when the
outdoor temperatures are low.
Warning:
The heating curve is adjusted in relation to a room
temperature setpoint of 20°C. If the room temperature
setpoint is modified, the flow temperature setpoint is
automatically recomputed. This will not modify the
setting and amounts to automatically adapting the
curve.
Heating Flow Temperature (°C)
70
60
50
40
30
20
Heating Curves
2
1,75
1,5
1,25
1
0,75
0,5
0,25
-20,0-15,0-10,0-5,00,05,010,015,020,0
Outdoor Temperature (°C)
56 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
Heating curve displacement
The curve shift (offset) modifies the flow
temperature in a general and even manner over the
full range of outdoor temperature. In other words,
the shift should be corrected when the room
temperature is generally too high or too low.
Heating curve adaption
Adaptation enables the controller to automatically
adapt the heating curve to the present conditions.
This correction may only be activated or
deactivated.
In the latter case, there is no need to correct the
slope and shift.
The summer/winter heating limit switches the heating
on or off through the year according to the
temperature ratio. Changeover is performed
automatically when in automatic mode and thus
avoids the user having to turn the heating on or off.
Changing the input value makes the respective
annual periods (summer/winter) shorter or longer.
- If the value is increased:
Changing to winter operating mode is advanced,
changing to summer mode is delayed
Example:
Programming line
Attenuated outdoor T
Information:
To ensure operation, the following requirements
must be met:
- A room sensor must be connected.
- The "room influence" parameter must be
set between 1 and 99.
- The reference room (where the room
sensor is installed) must not contain adjusted
thermostatic valves. If present in the room, these
valves must be fully open.
- Operation of this function requires an
adaptation period which can take more or less time
(approx. 1 week) depending on weather conditions
and on the stability of the room temperature
setpoint.
- If the value is decreased:
Changing to winter mode is delayed; changing to
summer mode is advanced.
Information:
This function does not work in "Continuous Comfort
temperature" mode. (Sunlight)
The controller displays "ECO".
The outdoor temperature is attenuated to take the
building's dynamics into account.
The 24-hour heating limit is used to switch the
heating on and of in the course of the day, depending
on the outside temperature.This function is used
mainly during intermediate seasons (spring and fall)
to react rapidly in case of fluctuating temperatures.
Thus, in the following example the changeover
temperature will be 18°C, computed as follows:
Maintenance Document 1544-157
Split system (Single phase and 3-phase type)
Comfort heating setpoint (710) 22°C
24-Hour heating limit (732) -3°C
Changeover temperature (710 – 732)
Heating off
Differential (Fixed) -1°C
Changeover temperature Heating on =18°C
Changing the input value makes the respective
heating periods shorter or longer.
- If the value is increased: changeover to
heating mode is advanced; changeover to ECO is
delayed.
- If the value is decreased: changeover to
heating mode is delayed; changeover to ECO is
advanced.
Flow temperature setpoint
=19°C
Information:
This function will not work in "Continuous Comfort
temperature" mode.
The display will show "ECO".
The outdoor temperature is attenuated to take the
building's thermal dynamics into account.
Line no.
HC1 HC2
740 1040 Flow temp setpoint min (for fan convectors)
741 1041 Flow temp setpoint max
Programming line
This limitation allows to define a range for the orders
to start. When instructed to start the heating circuit
reaches the threshold, this record remains
permanently at the maximum or minimum, even if the
heat demand continues to increase or decrease.
Room Influence
Line no.
HC1 HC2
750 1050 Room influence
Control types:
When using a room temperature sensor there are 3
different types of control to choose from.
SETTING CONTROL TYPE
- - - % Simple control according to outdoor conditions *
1...99 % Control according to outdoor conditions with room influence *
100 % Control according to room temperature only
* Requires the connection of an outdoor sensor
Simple control according to outdoor conditions
The flow temperature is computed via the heating
curve according to the averaged outdoor
temperature.
This type of control requires proper adjustment of the
heating curve, as the control does not take the room
temperature into account for this adjustment.
Control according to outdoor conditions with
room influence
The difference between the room temperature and
the setpoint value is measured and taken into
account for temperature control. This enables taking
Programming line
into account possible heat inputs and ensures a more
even room temperature.
The influence of the difference is defined as a
percentage. The better the installation in the
reference room (accurate room temperature, correct
installation location, etc.) the higher will be the value
that can be set.
Example:
Approx 60%: the reference room is appropriate
Approx 20 %: the reference room is inappropriate
Information:
Activation of the function requires taking into account
the following requirements:
58 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
- A room sensor must be connected.
- The "room influence" parameter must be set
between 1 and 99.
- The reference room (where the room sensor
is installed) must not contain adjusted thermostatic
valves. If present in the room, these valves must be
fully open.
Control according to room temperature only
The flow temperature is adjusted according to the
room temperature setpoint, the current room
temperature and its evolution. A slight increase in
Quick setback
Line no.
HC1 HC2
780 1080 Quick setback
During quick setback, the heating circuit pump is
deactivated and, in the case of mixing circuits, the
mixing valve is fully closed.
When using a room sensor, the function keeps the
heating off until the room temperature drops to the
level of the "Reduced" or "Frost protection" setpoint.
If the room temperature falls to the reduced or frost
level, the heating circuit pump is activated and the
mixing valve released.
Building time constant [h]
Composite outside 5
temperature
15°C 7.7
10°C 3.3
5°C 2.1
0°C 1.6
-5°C 1.3
-10°C 1.0
-15°C 0.9
-20°C 0.8
Programming line
Duration of quick setback [h]
room temperature, for example, causes an immediate
drop in the flow temperature.
Information:
Activation of the function requires taking into account
the following requirements:
- A room sensor must be connected.
- The "room influence" parameter must be set
to 100%.
The reference room (where the room sensor is
installed) must not contain adjusted thermostatic
valves. If present in the room, these valves must be
fully open.
Quick setback switches the heating off for a certain
period of time, depending on the outside temperature
and the building time constant.
Duration of quick setback when "Comfort" setpoint
minus "Reduced" setpoint = 2 K (e.g. "Comfort"
setpoint = 20 °C and "Reduced" setpoint = 18 °C)
Optimisation at switch-on and switch-off
Line no.
HC1 HC2
790 1090 Optimum start control max
791 1091 Optimum stop control max
Optimum start control max
The change in temperature levels is optimised in
such a way as to reach the comfort setpoint during
changeover times.
Maintenance Document 1544-159
Programming line
Optimum stop control max
The change in temperature levels is optimised in
such a way as to reach the comfort setpoint -1/4 °C
during changeover times.
This function is used mainly in heating installations
that do not have high supplies of power (e.g. low
energy homes). In that case, when outdoor
temperatures are low, adjusting the temperature
Increasing the reduced setpoint prevents excessive
cooling of the rooms in order to shorten the
temperature adjustment period when changing over
to the comfort setpoint.
would be too long.
End increase
801
Comfort
oint(710)
set
Reduced
oint(712)
set
Begin
increase
800
Mixing Valve Control
Averaged OT
Line no.
Programming line
HC1 HC2
830 1130 Mixer valve boost
834 1134 Actuator running time
Mixer valve boost
The controller adds the increase set here to the
current flow setpoint and uses the result as the
temperature setpoint for the heat generator.
Actuator running time
For 3-position control the valve Actuator running time
can be adjusted. With a 2-position servomotor, the
adjusted travel time is inoperative.
Controlled floor drying function
Line no.
HC1 HC2
850 1150 Floor curing function
851 1151 Floor curing setpoint manually
856 1156 Floor curing day current
857 1157 Floor curing day completed
This function is used in the controlled drying of floors.
It adjusts the flow temperature to a temperature
profile. Drying is performed by floor heating via the
heating circuit with a mixing valve or with a pump.
Floor curing function
Off:
The function is deactivated.
Heating operational (Fh):
The first part of the temperature profile is
automatically completed.
Heating "ready for occupancy" (Bh)
Programming line
The second part of the temperature profile is handled
automatically..
Heating "ready for occupancy" / Heating
operational
The full temperature profile (1st and 2nd part) is
performed automatically.
Manual
No temperature profile is performed, but the control is
performed according to the "manual controlled drying
setpoint". The function is automatically terminated
after 25 days
60 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
p
Important
oThe standards and directions of the building
contractor must be followed!
oThis function will not work properly unless the
installation has been adequately made (hydraulics,
Heat pump
flow tem
X : Starting day
Fh
Fh + Bh
Floor curing setpoint manually
The flow temperature setpoint for the "Manual"
controlled floor drying function can be adjusted
separately for each heating circuit.
Floor curing day current
Displays the current flow temperature setpoint for the
controlled floor drying function
electricity, settings). Otherwise, the floors to be dried
may be damaged!
oThe function may be prematurely interrupted
by setting it to Off.
oThe maximum flow temperature limitation
remains active.
Days
Bh
Floor curing day completed
Displays the current day of the controlled floor drying
function
Important:
After a power outage, the installation resumes the
controlled drying function as it was when the outage
occurred.
Operating Mode Changeover
Line no.
HC1 HC2
900 1200 Optg mode changeover
In case of an external changeover via input H2 (on the extension module only) the operating mode to which the
changeover will be performed must be previously defined.
The heating circuit frost protection is continuously
activated (protection mode
Heating circuit frost protection in heating mode
) and is not adjustable.
If the flow temperature is below 5°C, the controller
initiates the production of heat and starts the heating
pumps, regardless of the current heating mode.
If the flow temperature rises again above 7°C, the
controller waits another 5 minutes, and then stops the
production of heat and the heating pumps.
Heating circuit frost protection in cooling mode
See Cooling mode
Maintenance Document 1544-161
Split system (Single phase and 3-phase type)
4.3.5 Cooling Circuit 1 Functions
The cooling sequence is automatically started when
the room temperature is higher than the comfort
setpoint in cooling mode (line 902). The cooling
function must be activated (command line 901 =
Auto) and is triggered by the programming clock
(Command line 907).
The cooling sequence is interrupted as soon as
heating circuit 1 indicates a need for heat or in the
presence of a heat demand signal from a DHW circuit
or other heating circuit (only if cooling is active).
The controller measures the current room
temperature and compares it with the room
temperature setpoint to compute the flow temperature
setpoint. If the temperature is not low enough the
heat pump is started to provide cooling (reversed
control of the mixing valve).
Operating Mode
Line no. Programming line
901 Operating mode
(Off / Automatic)
The cooling key on the user interface enables
switching between operating modes.
Off:
The cooling function is deactivated.
The following settings apply to the hydraulic circuit in
zone 1 (HC1).
If there is a second zone, this zone can be cooled
with the setting 963 which will connect the pump
directly to zone 2. This will require setting the "Mixing
valve sub-cooling" parameter (938) to a suitable
value in order for both zones to be adequately cooled
according to the available emitters.
WARNING:
Cooling mode is prohibited on all radiators, heatingonly floors, or any emitters not intended for this
purpose.
Automatic:
The cooling function is automatically activated by the
time program (command line 907), the holiday
program, the occupancy key, or according to the
need.
Comfort cooling setpoint
Line no. Programming line
902 Comfort cooling setpoint
In cooling mode the room temperature control follows
the comfort setpoint adjusted under this setting. The
cooling comfort setpoint can be displayed with a knob
on the room unit.
Release:
Line no. Programming line
907 Release
(24h/day / heating circuit time pgm / Time program 5)
The "Release" setting determines the time program
according to which cooling is released.
24h/day:
Cooling is continuously activated (24h/day).
In summer the comfort setpoint is gradually increased
in relation to the outdoor temperature (see lines 918-
920).
heating circuit time program:
Cooling is activated according to the heating circuit
time program.
Time program 5:
Cooling is released according to time program 5.
62 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
A
p
Cooling Characteristic
Line no. Programming line
908 Flow temp setp at OT 25°C
909 Flow temp setp at OT 35°C
The controller computes the flow temperature
required for a given averaged outdoor temperature
based on the cooling characteristic. This is defined by
two reference points (flow setpoint at 25°C and at
35°C).
Flow temp setp at OT 35°C
This is the cooling flow temperature required when
the averaged outdoor temperature is 35°C, without
summer compensation.
Flow temp setp at OT 25°C
This is the cooling flow temperature required when
the averaged outdoor temperature is 25°C, without
summer compensation.
Flow temp
oint
set
908
909
25°C 35°C
The cooling characteristic is adjusted for a 25°C room
temperature setpoint. If the room temperature
veraged
OT
setpoint is changed the curve will automatically
adapt.
Eco
Line no. Programming line
912 Cooling limit at OT
913 Lock time after end of heating
Cooling limit at OT
If the composite outdoor temperature is higher than
the cooling limit, cooling is released. If the composite
outdoor temperature falls at least 0.5°C below the
cooling limit, cooling is locked.
Maintenance Document 1544-163
Lock time after end of heating
To avoid a quick start of cooling after termination of
heating, the cooling function is locked for a time
period which can be adjusted with this setting. The
lock time starts when there is no valid heating
demand from heating circuit 1. Heating demands
from heating circuits 2 or P are ignored.
Information:
Switching off and switching on again the mode
selection key causes the lock time to be interrupted
Split system (Single phase and 3-phase type)
p
Summer Compensation
Line no. Programming line
918 Summer comp start at OT
919 Summer comp end at OT
920 Summer comp setp increase
In summer the "cooling comfort setpoint" (902) is
gradually increased according to the outdoor
temperature. This saves on cooling power and
prevents the differences between the ambient
temperature of the room and the outdoor temperature
being too high.
The resulting "room temperature setpoint" (cooling)
can be viewed in the Info section.
Summer compensation start at OT
Summer compensation starts to be active from the
outdoor temperature defined here. If the outdoor
temperature continues to rise, the comfort setpoint
will be gradually increased.
Comfort
set
oint
Summer compensation end at OT
At this outdoor temperature the summer
compensation reaches its peak efficiency (920). If the
outdoor temperature continues to rise, it will no longer
influence the comfort setpoint.
Summer compensation setpoint increase
This setting defines the highest value to which the
comfort setpoint can be increased.
902
918
919
920
OT
64 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
A
p
p
Flow Setpoint Limitation
Line no. Programming line
923 Flow temp setp min at OT 25°C
924 Flow temp setp min at OT 35°C
It is possible to assign a lower limit to the cooling flow
temperature.
The limitation line will be defined by two reference
points.
In addition the resulting flow setpoint will have a lower
limit and may not be less than 5 °C.
Flow temp setp min at OT 25°C
Determines the lowest flow temperature for a
composite outdoor temperature of 25°C.
Flow temp
set
oint
Flow temp setp min at OT 35°C
Determines the lowest flow temperature for a
composite outdoor temperature of 35°C.
Warning:
If no outdoor temperature is available, the controller
will use the "Min. flow setpoint at OT= 35°C"
parameter.
923
924
25°C 35°C
Room Influence
Line no. Programming line
928 Room influence
When using a room temperature sensor there are 3
different types of control to choose from.
SETTING CONTROL TYPE
- - - % Simple control according to outdoor conditions *
1...99 % Control according to outdoor conditions with room influence *
100 % Control according to room temperature only
* Requires the connection of an outdoor sensor
Simple control according to outdoor conditions
The flow temperature is obtained from the composite
outdoor temperature on the basis of the cooling
characteristic.
Flow temp
oint
set
veraged
OT
This type of control requires the cooling curve to be
properly adjusted, as the control does not take the
room temperature into account for this adjustment.
Maintenance Document 1544-165
Split system (Single phase and 3-phase type)
Control according to outdoor conditions with
room influence
The difference between the room temperature and
the setpoint value is measured and taken into
account for temperature control. This enables taking
into account possible heat inputs and ensures a more
even room temperature. Thus the differences with the
room temperature are taken into account and the
room temperature becomes more stable. The
influence of the difference is defined as a percentage.
The better the installation in the reference room
(accurate room temperature, correct installation
location, etc.) the higher will be the value that can be
set.
Example:
Approx 60%: the reference room is
appropriate
Approx 20 %: the reference room is
inappropriate
Activation of the function requires taking into account
the following requirements:
A room sensor must imperatively be
connected.
The "room influence" parameter must be set
between 1 and 99.
The reference room (where the room sensor
is installed) must not contain adjusted thermostatic
valves. Any thermostatic valves present in the rooms
must be fully open.
Control according to room temperature only
The flow temperature is adjusted according to the
room temperature setpoint, the current room
temperature and its evolution. A slight increase in
room temperature, for example, causes an immediate
drop in the flow temperature.
Activation of the function requires taking into account
the following requirements:
A room sensor must imperatively be
connected.
The "room influence" parameter must be set
to 100%.
The reference room (where the room sensor
is installed) must not contain adjusted thermostatic
valves. Any thermostatic valves present in the rooms
must be fully open.
Room Temperature Limitation
Line no. Programming line
932 Room temperature limitation
The "room temperature limitation" function enables
shutting off the cooling circuit pump if the room
temperature falls below the adjusted room
temperature setpoint (with summer compensation line
920) by more than the adjusted differential.
The cooling circuit pump is reinitiated as soon as the
room temperature rises again above the current room
temperature setpoint.
If the room temperature limitation function is active,
no cooling demand will be transmitted to production.
The function is deactivated if:
no room temperature sensor is available
"Room influence limit." = -- "Room influence" (928) = --- (simple control
according to outdoor conditions)
66 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
Mixing Valve Control
Line no. Programming line
938 Mixing valve cooling offset
941 Actuator running time
945 Mixing valve in heating mode
Mixing valve cooling offset
The cooling demand issued by cooling circuit 1 to
production is reduced by the adjusted value.
Example:
Configuration How the configuration affects control
Zone 1: Heating/cooling
floor
Zone 2: Fan coils
Zone 1: Heating/cooling
floor
Zone 2: HCF
WARNING:
If these settings are not chosen properly the heat
pump may stop automatically due to the flow
temperature being too low. A safety mechanism is
triggered at 6°C to protect the exchanger from
freezing.
Actuator running time
For the 3-position servomotor used, it is possible to
adjust the travel time. With a 2-position servomotor,
the adjusted travel time is inoperative.
938 = 10°C,
with 924 = 18°C
963 = yes
938 = 0°C,
with 924 = 18°C
963 = yes
If there is a second zone, this reduction should
enable the second zone to be cooled. To achieve this
result, the sub-cooling must be determined in
accordance with the type of emitter and the
parameter 963 "With prim control/prim pump" must
be set to "yes" to switch on the pump for the second
zone.
with a 35°C outdoor temperature the flow
setpoint will be 18°C – 10°C i.e. 8°C
while in the first zone (HCF) it will be 18°C
through action of the mixing valve
with a 35°C outdoor temperature the flow
setpoint will be 18°C in both zones
This parameter is inoperative in installations where
heating and cooling circuits are hydraulically
separate.
Control:
mode.
Open:
in heating mode.
the valve controls in heating and cooling
the valve controls in cooling mode, and is open
Mixing valve in heating mode
Determines the position of mixing valve 1 (Y1 / Y2)
during heating operation is activated.
With prim controller/system pump
Line no. Programming line
963 With prim contr/system pump
This setting specifies whether the cooling circuit is
supplied from the primary controller or from the
primary pump (depending on the installation). It can
also be used to provide cooling to the second zone.
(no / yes)
Warning:
In the case of a radiator or any other emitter which
does not support the cooling mode in zone 2, this
setting must remain on "No".
Maintenance Document 1544-167
Split system (Single phase and 3-phase type)
4.3.6 DHW Functions
The control sets the DHW temperature, according to
the time program or continuously, to the desired
setpoint. The priority of DHW charging over room
heating is adjustable in this case.
Setpoint value
Line no. Programming line
1610 Nominal setpoint
1612 Reduced setpoint
The DHW is heated to various setpoint values. These
setpoints are active according to the selected
DHW reduced setpoint
The controller has a configurable legionella function
designed for protection against legionella in the
storage tank and the pipes. The circulation pump is
controlled according to the current time program and
operating mode.
operating mode and allow the desired temperatures
to be reached in the DHW storage tank.
Comfort setting DHW max setpoint
Important:
For optimal operation we recommend reducing the
setpoints to the lowest value.
Setpoints which are too high may interfere with
heating and cause some discomfort. In this case
DHW/Heating changeover cycles may successively
occur.
Release
Line no. Programming line
1620 Release of DHW load
(24h/day / Heating circ time pgm / Time program 4/DHW / Low-tariff/ Time pgm 4/DHW or Low-tariff)
24h/day
(Not recommended)
Regardless of the time programs, the temperature of
the domestic hot water is continuously maintained at
the DHW nominal setpoint temperature.
Example:
If DHW charge boosting is not desired during the day,
we recommend adjusting the reduced temperature
setpoint to 15°C. Full charging will occur during the
night at the nominal temperature.
Heating circuit time programs:
(Not recommended)
68 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
Depending on the heating circuit time programs, the
DHW setpoint is changed between the DHW
temperature nominal setpoint and the DHW
Example:
Time program 4 / DHW:
(Recommended)
Time program 4 of the local controller is taken into
account for the DHW mode. The changeover
between DHW nominal setpoint and DHW reduced
temperature reduced setpoint. The first switch-on
point of each phase is advanced by one hour each
time.
setpoint occurs on the changeover times of this
program. Thus, domestic hot water charging takes
place independently from the heating circuits.
Low tariff
Released when the low tariff input is active (Input
Ex2)
Time pgm 4/DHW or low tariff
Released when DHW program 4 is set to "Nominal"
or if the low tariff input is active.
Maintenance Document 1544-169
Split system (Single phase and 3-phase type)
DHW mode Holiday
status
Off x x x x Frost protection
On Yes x x x Frost protection
On No … … x …
On No Low tariff (OPK) x Inactive Reduced
On No Low tariff (OPK) x Active Nominal
On No Time pgm 4 or OPK Nominal Inactive Nominal
On No Time pgm 4 or OPK Reduced Inactive Reduced
On No Time pgm 4 or OPK Nominal Active Nominal
On No Time pgm 4 or OPK Reduced Active Nominal
x = indifferent
Information:
Release by low tariff input always triggers forced
DHW charging
Release
(settings 1620)
Time pgm
status (Pgm 4)
If the low tariff input EX2 has not been configured and
release via OPK has nevertheless been set, the DHW
level will either continuously remain on reduced or will
follow time program 4.
Low tariff
status
(Ex2)
DHW mode level
Legionella Function
Line no. Programming line
1640 Legionella function
1641 Legionella function periodically
1642 Legionella function weekday
Legionella function
Periodically
The legionella function occurs repeatedly according
to the adjusted periodicity (command line 1641).
Fixed weekday
The legionella function can be activated on a fixed
day of the week (command line 1642). With this
setting, heating up to the legionella setpoint occurs
on the scheduled day of the week, regardless of the
storage tank temperatures during the previous period.
70 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
4.3.7 Swimming Pool Functions
Line no. Programming line
2056 Setpoint source heating
The controller enables a swimming pool to be heated
by the heat pump. An individual setpoint can be set
by means of parameter 2056, which appears when
the swimming pool function is activated by parameter
6046 being set to "Swimming pool release".
4.3.8 Heat Pump Functions
Line no. Programming line
2803 Overrun time cond pump
2843 Compressor off time min
2844 Switch-off temp max
2862 Locking time stage 2
2873
2882 Release integr electric flow
2884 Release el flow at OT
2886 Compensation heat deficit
2916 Max setpoint HP DHW charg
2920 With electrical utility lock
Compressor mod run time
Use of input H33 requires an extension to be
connected to the control.
Overrun time cond pump
When the compressor is switched off, the condenser
pump continues to run for the set overrun time.
Compressor off time min
For the same reason, the compressor remains
switched off for the minimum period of time set here.
Switch-off temperature maximum if the flow or the
return temperature exceeds the maximum switch-off
temperature, the compressor will be switched off.The
heat pump is switched on again when the
temperature at both sensors has dropped by the
"Switching diff return temp" below the maximum
switch-off temperature and the minimum off time has
elapsed.
Switch-off temp max
If the flow or the return temperature exceeds the
maximum switch off temperature, the compressor will
be switched off.
Locking time stage 2
When compressor is restarted, the time which keeps
minimum capacity can be adjusted. Efficiency
becomes better; however, the time of rising capacity
becomes long.
Compressor mod run time
Compressor mod run time means the time of
compressor frequency indication changed from
minimum to maximum. If this setting value changes to
small, compressor frequency changes more quickly.
Warning :
This setting value is too small, the efficiency is
decreased due to the compressor frequency changes
frequently.
Release integr electric flow
After the release of the 1st stage (heater 1:on, heater
2:off), the controller compares the temperature
measured with the point of engagement and forms an
integral and includes a possible deficit of heat. Once
the value of the integral reaches the maximum value
(2882), the 2nd stage is engaged (heater 1:off, heater
2:control). The controller continuously compares the
temperature measured at the point of engagement
and new features to the deficit of heat in the full
release. When the full release reaches the value set
(2882), the 3rd stage of the heater is triggered
(heater 1:fixed on, heater 2:control).
Maintenance Document 1544-171
Split system (Single phase and 3-phase type)
Flow elec. release at OT
The heater will be activated only if the attenuated
outdoor temperature is below the temperature set
here.
Warning:
If this setting is too low, there may be a feeling of
discomfort due to the fact that the heat pump is
unable to meet the heating requirements alone at low
outdoor temperatures, and heaters are not switched
on.
Compensation heat deficit
This function compensates for excess heat and heat
deficits. These can occur in the following situations:
Minimum compressor on and off times
In the case of low temperature requests, the flow
temperature can lie below the required setpoint, but
the return temperature may not drop below the
switch-on point for a longer period of time. In this
situation, the heat pump must be switched on to
prevent heat deficits
The controller compares continuously the flow
temperature setpoint with the actual value and
integrates the surplus heat and heat deficits.
Differences are compensated for by extending the
compressor on and off times.
If the compressor is not switched on or off due to
surplus heat/heat deficits, the controller displays an
appropriate status message.
This function is not active during the time the DHW
storage tank is charged.
The function is not active either in the case of plants
with buffer/(combi) storage tanks.
"Compensation heat deficit" only acts in heating
mode. The parameter is inactive in cooling mode.
The maximum switch-off temperature is given priority
over the "Compensation" function.
In the case of sudden setpoint changes, both
integrals are cleared.
Behavior in connection with the "Floor curing"
function
When activating the "Floor curing" function, the
integral is set to a level representing 1.5 times the
predefined value (factory setting). If the current
temperature lies at least 2 K below the required
setpoint, the heat pump is immediately switched on.
If compensation of surplus heat/heat deficits shall act
"Only with floor curing fct", the respective setting
must be selected. This means that the parameter is
deactivated in normal heating mode.
Calculation of integral
If a flow temperature sensor (BX1) is connected
and the heating curve is set to the flow temperature
setpoint, the controller uses the flow temperature
and the flow temperature setpoint for computing the
integrals
In the following situations, the integral is set to "0":
No valid temperature request delivered
Setpoint change >2 K
Frost protection for the heat pump is active
The heat pump has gone to lockout or cannot
deliver any heat for a longer period of time
The heat pump is in active cooling mode
A buffer storage tank is being charged
The function is deactivated
With active DHW charging, the integral value is
frozen.
With electrical utility lock
This setting relates to input Ex1 (load-shedding or
peak day clearing) and allows the electric heaters to
be locked as follows:
Locked:
The heat pump and all electric heaters are locked,
both heat pump stages and the DHW tank electric
auxiliary.
Only the boiler backup, if installed, continues to
operate
Released
The heat pump operates and all electric heaters are
locked, both heat pump stages and the DHW tank
electric auxiliary.
The boiler backup, if installed, continues to operate.
72 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
4.3.9 Supplementary source
A supplementary producer can be operated in
addition to the main producer (heat pump).
Release of the supplementary producer depends on
a number of parameters a detailed description of
which is given on the following pages.
Line no. Programming line
3700 Release below outside temperature
3701 Release under outside temperature
Operation of the supplementary source is released
only when the composite outside temperature lies
above or below the set temperature limit.
This enables the supplementary source to lock in a
selected outside temperature range to ensure
bivalent operation of supplementary source and heat
pump.
Overtemperature protection
Line no. Programming line
3705 Overrun time
Overrun time of release for the external source: If the
integral indicates another heat deficit before the
overrun time has elapsed, the release remains
activated.
Release is effected via release relay QX2
2-position control is effected via control relay QX3
Ux can be used to transmit the supplementary
source a DC 0...10 V signal for the required
temperature/output setpoint
To ensure continuous release of the supplementary
source, setting "---" must be selected on the
respective operating lines.
If both release values are enabled, the outside
temperature must satisfy both criteria, thus ensuring
release of the supplementary source .
If the set overrun time elapses before the common
flow temperature drops below the common flow
temperature setpoint, the release is deactivated also.
Flow control
Line no. Programming line
3720 Switching integral
3723 Locking time
Switching integral
The temperature-time integral is a continuous
summation of the temperature differential over time.
In this case, the decisive criterion is the difference by
which the temperature lies above or below the
common flow temperature setpoint.
The temperature-time integral gives consideration not
only to the period of time, but also to the extent of
over-/undershoot. This means that when the crossing
is significant, the supplementary source is released
earlier, or locked earlier, than with minor crossings.
QX2
QX3
TVx Actual value of flow temperature
TVw Flow temperature setpoint
+ Int Surplus integral
- Int Deficit integral
t1 Overrun time (not completed)
t2 Overrun time (fully completed)
QX2 Release output QX2
QX3 Control QX3
Locking time
The locking time enables the heat pump to reach a
stable operating state before the supplementary
source is allowed to switch on.
The supplementary source is released only when the
locking time has elapsed.
The locking time starts as soon as a valid flow
temperature setpoint is available.
Calculation of the release integral starts only when
the locking time has elapsed.
QX2
TVxSch Actual value of common flow temperature
TVwSch Setpoint of common flow temperature
A Request
QX2 Release output QX2
T Locking time
Maintenance Document 1544-173
Split system (Single phase and 3-phase type)
No consideration is given to the locking time, if the
heat pump malfunctions or is locked, or if the
4.3.10 DHW Tank Functions
DHW charging at the nominal setpoint temperature
(1610) always takes place in two stages. In the first
stage, only the heating pump heats the DHW tank.
The power supplied during this time is at its peak.
Then, when the heat pump is no longer able to supply
Charging Control
Line no. Programming line
5024 Switching differential
5030 Charging time limitation
Switching differential :
If the DHW temperature is lower than the current
setpoint minus the differential set here, the DHW
charging process is launched.
It ends when the temperature reaches the current
setpoint.
Information:
Forced charging is triggered on the first DHW
release of the day.
Charging is also launched when the DHW
temperature is within the differential, and as long as
it is not less than 1K above the setpoint.
Charging time limitation
During charging, the room heating may be stopped
or insufficient. Therefore it is often advisable to limit
the charging process timewise to enable heating.
If "- - -" has been selected the charging time
limitation will be deactivated. The DHW will be
heated to the nominal setpoint, even if the room
supplementary source must end DHW charging.
Setting "- - -" can be used to deactivate the function.
enough heat to reach the setpoint value, it switches
on the DHW tank auxiliary if authorised. The auxiliary
will be cut off when charging is complete.
While the DHW tank charging process via the electric
auxiliary is finishing, the heat pump resumes heating.
heating has not received enough power in the
meantime.
If a value between 10 and 600 is selected, charging
will be suspended after the time period set in
minutes, and will remain suspended over that time
before resuming. The generator power remains
available in the meantime to heat the room. This
cycle is repeated until the DHW nominal setpoint
has been reached.
Information:
When the room heating is stopped (summer mode,
economy function, etc.), DHW charging remains
active, regardless of the setting.
Recooling
Line no. Programming line
5055 Recooling temp
5057 Recooling collector
Recooling temp :
An activated "Recooling" function remains active until
the set recooling temperature in the DHW storage
tank is reached.
Recooling collector :
When the collector is cold, surplus energy can be
emitted to the environment via the collector’s
surfaces.
74 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
Heater
Line no. Programming line
5061 Electric immersion heater release
Electric immersion heater release
24h/day
The heater is continuously active regardless of time
programs.
DHW release
The heater is controlled according to "DHW release".
Time program 4/DHW
Time program 4/DHW of the local controller is taken
into account for the heater.
Information:
Switch-on will actually be in effect only if the heater is
able to operate according to the "heater operating
mode" setting.
Maintenance Document 1544-175
Split system (Single phase and 3-phase type)
4.3.11 Configuration Functions
When an installation is started up, the hydraulic
diagram presetting for that installation must be
entered.
Presettings
Line no. Programming line
5700 Pre-setting
Only Pre-setting 1 to 4 are used among 9 availables.
Using this setting, heating circuit 1 can be switched
on and off.
Cooling circuit 1
Off: The cooling circuit is deactivated.
4-pipe system: Not compatible with the Waterstage
heat pump. This setting relates to passive cooling.
2-pipe system:
Activates the heat pump cooling mode. However, the
cooling kit must have been previously connected.
Warning:
If the cooling kit has not been connected and the
cooling mode is activated the heat pump will behave
abnormally and might cause some unwanted
discomfort.
Information:
Switching on the cooling mode causes the menu
'"Cooling circuit 1" to appear.
Heating circuit 2
Using this setting, heating circuit 2 can be switched
on and off.
DHW
Line no. Programming line
5731 DHW ctrl elem Q3
No charging request
No DHW charging via Q3.
Charging pump
DHW charging is effected with a pump connected to
terminal Q3.
Electric backup
Line no. Programming line
5806 Type el imm heater flow
Within the type of electric backup, 4 settings are
possible :
3-stage
Not used
2-stage excuding
Not used
Diverting valve
DHW charging is effected with a diverting valve
connected to terminal Q3.
2-stage complementary
The backup 1 starts alone, then the backup 2 starts
alone, then the two backups start simultaneously.
Exemple for a 3kw backup and a 6kw backup, 1
stage : 3kw, 2
Modulating Ux
The backup 1 is regulated as required.
nd
stage : 6kw, 3rd stage : 3+6=9kw.
st
76 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
Basic unit EX/E
Line no. Programming line
5981
Cont type input EX1, EX2, EX3
5983
5985
The type of contact can be selected:
NC
The input’s function is active when voltage is not
present.
Sensor Corrections
Line no. Programming line
6098 Not used
6100 Readjustm outside sensor
The outdoor temperature measuring value can be
corrected within a range of +/- 3 K.
Installation Frost Protection
NO
The input’s function is active when voltage is present.
The descriptions relating to the functions of the EX
contact apply when an NO contact is selected.
Line no. Programming line
6120 Frost protection plant
According to the outdoor temperature, the heating
circuit pump and the condenser pump are switched
on although there is no demand for heat
Outdoor
temperature
Pump Diagram
Continuously ON
Set to ON for 10 min, approx. every
6 hours.
Continuously off
Miscellaneous
Line no. Programming line
6205 Reset to default parameters
6220 Software version
ON
Periodically ON
OFF
Reset to default parameters :
All parameters can be reset to factory settings,
except when it comes to the following pages: Time
and date, User interface and all time programs, as
well as the operating hours and the various counters.
Software version:
The software version represents the controller
software status at the time the unit is being produced.
It is printed on the back of the unit.
The first two digits represent the software version,
and the third is the revision number (e.g. 01.0)
Maintenance Document 1544-177
Split system (Single phase and 3-phase type)
4.3.12 Error Functions
When a fault occurs, the symbol appears and it is
possible to display an error message in the Info
section by pressing the Info key.
Reset (unlock) Heat Pump
Line no. Programming line
6711 Reset HP
This line is used to clear the heat pump error
messages. The predetermined switch-on delay in
case of a failure is therefore ignored, which avoids
waiting periods during servicing / troubleshooting.
Fault History
Line no. Programming line
6800 to 6818 Time stamp and history of faults 1 -10
The controller saves the last 10 faults which have
occurred to a non volatile memory. Any new entry will
delete the oldest entry from the memory.
A fault code and a time are saved for each fault.
Error Code List
Designation of error
The error designations in the table below are
displayed in plain text on the user interface.
Location
The sensor or contact associated to the error
message.
Reset
Reset is either automatic or manual, depending on
the type of error (see table below with error
messages).
Manual reset
Errors which are displayed in the Info section and
accompanied by the "Reset?" question can be
manually reset.
Press the "OK" key once, "yes" flashes on the
display. Press the "OK" key again to confirm the "yes"
and the error will be reset.
Automatic reset
Automatic clearing occurs after a previously set time
(OEM setting) has elapsed. After this timeout (6
hours by default) has elapsed, the controller will
attempt to reset the error.
If "Number" appears in the table, it is possible to
define how many times the fault can be reset before
the heat pump is declared out of order.
The display shows what caused the fault.
This option should not be used in normal operating
conditions.
Heat pump operation
Shows whether or not the heat pump can continue to
operate when the error occurs.
Yes
The heat pump continues to operate despite the error
message.
No
The error interrupts operation of the heat pump.
No with glycol water
This error stops glycol water heat pumps, but does
not prevent operation of water or air heat pumps.
No with water
This error stops water heat pumps, but does not
prevent operation of glycol water heat pumps
No with air
This error stops air heat pumps, but does not prevent
operation of water heat pumps or glycol water heat
pumps.
Per diagram
The heat pump will be stopped according to the
current installation diagram.
Alarm messages
Errors are ranked by priority. From priority 5 onward
(i.e. priority levels 5 - 9) the alarm messages used in
remote control (OCI) are sent. In addition, the alarm
relay is switched on.
78 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
Table of error messages which can be displayed:
No. Designation of error Location
0: No fault
10: Outdoor sensor BX4 (X84) No No Yes
30: Flow sensor 1 BX1 (X80) No No Yes
31: Cooling flow sensor 1 BX1 (X80) No No Yes
32: Flow sensor 2 BX31 (X153) No No Yes
33: Heat pump flow temp sensor
error
44: Heat pump return temp sensor
error
50: DHW temp sensor 1 BX3 (X84) No No Yes
60: Room sensor 1 No No Yes
65: Room sensor 2 No No Yes
76: Special sensor 1 Bx No No Yes
83: BSB wire short-circuit No No Yes
84: BSB, address collision No No Yes
85: Radio communication error No No Yes
98: Extension module 1 No No Yes
99: Extension module 2 No No Yes
100: 2 master clocks on bus No No Yes
102: Clock without running supply No No Yes
105: Maintenance message No No Yes
121: HC1 flow temp too low No No Yes
122: HC2 flow temp too low No No Yes
126: DHW charge monitoring No No Yes
127: Anti-legionella temperature No No Yes
134: Heat pump alarm summary E20 Yes Number * No
138: No heat pump control sensor No Yes No
146: Sensor / control device
configuration
171: Alarm contact 1 activated H1/H31 No No Yes
172: Alarm contact 2 activated H21/H22/H32 No No Yes
174:Alarm contact 4 active H3 No No Yes
178: HC1 safety thermostat No No Yes
179: HC2 safety thermostat No No Yes
201: Frost alarm BX1 (X80) Yes No No
243: Swimming pool sensor BX34 (X154) No No Yes
325: BX/ext unit: same sensors No No Yes
327: Ext modules: same functions No No Yes
329: Ext modules/mixing grp: same
functions
330: BX1 no function No No Yes
331: BX2 no function No No Yes
332: BX3 no function No No Yes
333: BX4 no function No No Yes
334: BX5 no function No No Yes
335: BX21 no function No No Yes
336: BX22 no function No No Yes
357: cooling circuit flow temp not
reached
359: no cooling valve Y21 No No Yes
360: no process reversing valve
Y22
364: Heat pump cooling system
error
369: External fault No
370: Outdoor unit fault No
Number* If such statuses or events occur for the first
time, they will not directly generate a fault message,
but only a status message.
BX1 (X80) No No Yes
BX2 (X80) No No per diagram
No No Yes
No No Yes
No No Yes
No No Yes
No No Yes
Reset
Manual Automatic
HP oper.
Only if the anomaly occurs repeatedly over a
predefined time period and at a given frequency
(number) will an error message be generated.
Maintenance Document 1544-179
Split system (Single phase and 3-phase type)
4.3.13 Maintenance / Special Operating Mode Functions
Maintenance
Maintenance functions can be used as a preventive
step for periodically monitoring the installation. All
maintenance functions can be individually
activated / deactivated.
Line no. Programming line
7070 HP interval
7071 HP time since maint
7073 Cur starts compressor 1/hrs run
The controller automatically generates maintenance
messages if the settings defined are either exceeded
or fail to be reached.
HP interval :
Defines the maintenance frequency (in months) for
the heat pump.
HP time since maint :
Displays the time (months) elapsed since the last
maintenance. If the value exceeds the "heat pump
interval" setting (Line 7070), the symbol
displayed and a maintenance message will appear in
the Info section:
17: Heat pump maintenance Interval (Priority 6)
This setting can be reset with the associated rights of
access.
will be
Emergency mode
If the heat pump is not operating properly, a
emergency service can be maintained. The
emergency mode enables the installation to be run
Line no. Programming line
7141 Emergency operation
7142 Emergency operating function type
Cur starts compressor 1/hrs run :
The average number of compressor startups per hour
of operation, obtained over a period of 6 weeks.
If the value exceeds the "Comp1 max startups/hr op"
adjusted setting, the symbol
a maintenance message will appear in the Info
section:
8: Too many compressor 1 startups (Priority 9)
This setting can be reset with the associated rights of
access.
with the available heaters (flow, storage tank, DHW
tank). In this case the compressor will remain off.
will be displayed and
Emergency operation (7141):
Emergency operation can be activated and
deactivated manually.
Off:
Emergency operation is deactivated.
On:
Emergency operation is activated.
Emergency operating function type (7142):
Manual:
Emergency operation can be activated/deactivated
only through the Emergency operation setting on line
7141.
Automatic:
As soon as a fault occurs on the heat pump,
emergency operation is automatically switched on. It
stops when the fault is removed and, if necessary,
cleared (reset). Emergency mode may however be
activated / deactivated manually via the "Emergency
operation" setting on line 7141.
80 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
Simulation
Line no. Programming line
7150 Simulation outside temp
Simulation outside temp (7150):
To make the starting-up and troubleshooting
processes easier, it is possible to simulate an outdoor
temperature in the range of -50...+50°C. During
simulation, the current, composite and attenuated
outdoor temperatures are ignored and substituted
with the adjusted simulation temperature.
Computation of the three outdoor temperatures
based on the actual outdoor temperature continues to
be performed during the simulation, and these
temperatures are available again when the simulation
is over.
This function can be deactivated by selecting -.- on
this line or automatically, after a 5 hour waiting
period.
Maintenance Document 1544-181
Split system (Single phase and 3-phase type)
4.3.14 Input / Output Testing Functions
Input/output testing is used to ensure that the
connected components are in working order.
Relay Output Testing
Selection of a setting from relay testing closes the
corresponding relay and therefore switches on the
connected component. This makes it possible to
Line no. Programming line
7700 Relay test
Warning:
During testing of an output, the heat pump is stopped,
all outputs are "off" and only the controlled output is
on.
This consists of instructing the regulator's relays one by one and checking their outputs. This enables you
to check that the relays are working and that the cabling is correct. Check that each appliance in the
installation is operating correctly.
(0) No test, (1) Everything is on STOP, (2) Relay output QX1 : heat pump CC1 (Main regulation board), (3)
Relay output QX2 : Electrical back-up (1st stage) or Boiler connection distribution valve, (4) Relay output
QX3 : Electrical back-up (2nd stage) or Boiler connection contact, (5) Relay output QX4 : DHW distribution
valve, (6) Relay output QX5 : DHW Electrical back-up, (7) Relay output QX6 , (8) Relay output QX31 :
Heat circ mix valve open Y1, (9) Relay output QX32 : Heat circ mix valve close Y2, (10) Relay output
QX33 : heat pump CC2, (11) Relay output QX34, (12) Relay output QX35 : Swimming pool distribution
valve, (13) Relay output QX21 module 1, (14) Relay output QX22 module 1, (15) Relay output QX23
module 1, (16) Relay output QX21 module 2, (17) Relay output QX22 module 2, (18) Relay output QX23
module 2, (19) Not used, (20) Not used, (21) Not used.
The display shows the “Key” symbol. Pressing the Info button displays "Error 368".
Warning: The component being tested is receiving electrical power throughout the test.
check that the relays are in working order and that
the wiring has been performed correctly.
Analog Input/Output Testing
Line no. Programming line
7710 Output test UX1
7712 PWM signal UX1
7722 Cooling mode DO2
7723 Heat pump D3
7724 Output test UX3
7725 Voltage value UX3
The sensor test operate the same as for BX1-4 on
the basic unit
4.3.15 Status Functions
The current operating status of the installation can be
viewed by means of status displays.
Display of 0 V means that there is no voltage and the
respective input is currently inactive. Display of 230 V
means that voltage is present at the respective input
so that it is activated.
Messages
Line no. Programming line
8000 State heating circuit 1
8001 State heating circuit 2
8003 State DHW
8004 State cooling circuit 1
8006 State heat pump
8007 Not used
8010 Not used
8011 State swimming pool
8022 State supplementary source
Maintenance Document 1544-183
Split system (Single phase and 3-phase type)
State heating circuit
End user (Info level) Startup, heating engineer
Thermostat response Thermostat response
Manual action active Manual action active
Controlled drying active Controlled drying active
Heating mode restriction Overeating protection active
Forced draft Forced draft, storage tank
Comfort heating mode Optimis. at switch-on + accelerated
Reduced heating mode Optimisation at switch-off
Frost protection active Room frost protection
Summer mode Summer mode
Off Eco day active
Restriction, Boiler protection
Restriction, DHW priority
Restriction, storage tank
heating
Optimisation at switch-on
Accelerated heating
Comfort heating mode
Reduced heating mode
Flow frost protection active
Install. frost protection active
Reduced decrease
Frost protection decrease
Room temperature limitation
Off
84 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
State DHW (8003):
End user (Info level) Startup, heating engineer
Thermostat response Thermostat response
Manual action active Manual action active
Draw-off mode Draw-off mode
Adiabatic cooling active Adiabatic cooling by collector
Charging lock active Discharge protection active
Forced charging active Forcing, DHW tank max temp
Charging by heater Charging by heater, anti-legion. setpoint
Accelerated charging active Flow active
Charging active Charging, anti-legion. setpoint
Frost protection active Frost protection active
Switch-off delay active Switch-off delay active
Charging on standby Charging on standby
Charged Charged, max tank temp
Off Off
Ready Ready
adiabatic cooling via gen/HC
Charging duration limit. active
Charging locked
Forcing, max charging temp
Forcing, anti-legion. setpoint
Forcing, comfort setpoint
Charging by heater, Comfort setpoint
Charging by heater, Reduced setpoint
Charging by heater, frost protection setpoint
Heater released
Dewpoint sensor activated Dewpoint sensor activated
Manual action active Manual action active
Fault Fault
Frost protection active Flow frost protection active
Cooling mode locked Locked, heating mode
Cooling mode restricted Flow temp setpoint increase by hygrostat
Comfort cooling mode Comfort cooling mode
Cooling protection mode Cooling protection mode
Frost protection active Frost protection active
OT cooling limit activated OT cooling limit activated
Off Off
Cooling mode off Cooling mode off
Lock time after heating
Locked, generator
Locked, storage tank
Dewpoint flow min limit
Outdoor temp flow min limit
Switch-off delay active
Room temperature limitation
Flow limit reached
86 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
State heat pump (8006):
End user (Info level) Startup, heating engineer
Emergency mode Emergency mode
Fault Fault
Locked Locked, outdoor temperature
Lim. time active Consumer flow rate controller
Frost protection active Heat pump frost protection
Defrosting activated Defrosting activated
Cooling mode active Comp min ON time active
Heating Comp min ON time active
Frost protection active Install. frost protection active
Off Flow active
Locked, external
Locked, economy mode
Min outdoor temp use limit
Max outdoor temp use limit
Max switchoff temp lim
Max OT limit cooling
Min switchoff temp limit
Comp min switchoff time active
Excess heat compensation
Comp 1 ON
Heat deficiency compensation
Max cond diff limit
Min cond diff limit
Comp.1 and heater ON
Comp 1 ON
Heater ON
Switch-off delay active
No demand
State swimming pool (8011):
End user (Info level) Startup, heating engineer
Manual action active Manual action active
Fault Fault
Heating mode restriction Heating mode restriction
Forced draft Forced draft
Heating Generator heating mode
Heated, max pool temp
Heated
Heating off
Cooling Cooling
Heated, max pool temp
Heated, generator setpoint
Solar heating mode OFF
Generator heating mode OFF
Maintenance Document 1544-187
Split system (Single phase and 3-phase type)
State supplementary source (8022):
End user (Info level) Startup, heating engineer
Locked Locked, solid fuel boiler
In operation for HC, DHW In operation for HC, DHW
Released for HC, DHW Released for HC, DHW
In operation for DHW In operation for DHW
Released for DHW Released for DHW
In operation for heating circuit In operation for heating circuit
In operation for HC, DHW In operation for HC, DHW
Released for HC, DHW Released for HC, DHW
In operation for DHW In operation for DHW
Released for DHW Released for DHW
In operation for heating circuit In operation for heating circuit
Released for HC Released for HC
Overrun active Overrun active
Off. Off.
Locked, outside temperature
Locked, economy mode
4.3.16 Generator Diagnosis Functions
Various setpoints and actual values, relay switch
status data can be displayed for purposes of
diagnosis.
Heat Pump:
Line no. Programming line
8402 El imm heater flow 1
8403 El imm heater flow 2
8406 Condenser pump
These command lines are used to check the
operating mode of the components controlled by the
heat pump relays. The display "0" means that the
associated components are currently disconnected.
The display "1" means that the associated
components are currently switched on.
Information
This information applies to relays defined as normally
open contacts. For normally closed contacts, the
action is reversed.
88 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
Setpoints and Measured Values
Line no. Programming line
8410 Return temp HP
8412 Flow temp HP
8413 Compressor modulation
8414 Modulation electric flow
8425 Temp diff condenser
These lines allow the various setpoints and measured
values for the heat pump to be viewed.
Hour / Startup Counter
Line no. Programming line
8454 Locking time HP
8455 Counter number of locks HP
8456 Hours run el flow
8457 Start counter el flow
Locking time HP
Displays the cumulative locking time since start-up by
the electrical services (via external locking signal).
Counter number of locks HP
Displays the cumulative locks since start-up by the
electrical services (via external locking signal).
4.3.17 Consumer Diagnosis Functions
Various setpoints and actual values, relay switch
status and timing status data can be displayed for
purposes of diagnosis.
Outdoor Temperatures
Line no. Programming line
8700 Outside temperature
8701 Outside temp min
8702 Outside temp max
8703 Outside temp attenuated
8704 Outside temp composite
The current, minimum, maximum, attenuated and
composite outdoor temperatures are displayed.
Hours run el flow, Start counter el flow
These lines are used to view the hours of operation
and the number of startups of electric heater.
Heating Circuits
Line no. Programming line
8730 and 8760 Heating circuit pump, circuit 1
8731 and 8761 Mixer valve HC1 open
8732 and 8762 Mixer valve HC1 closed
8740 and 8770 Room temp
8743 and 8773 Flow temp
The display "Off" means that the associated
components are currently disconnected. The display
Maintenance Document 1544-189
"On" means that the associated components are
currently switched on.
Split system (Single phase and 3-phase type)
Cooling Circuit
Line no. Programming line
8756 Flow temperature cooling 1
8757 Flow temperature setpoint cooling 1
The actual values of the cooling mode are displayed. The cooling mode room setpoint is displayed on
programming line 8741.
Domestic Hot Water
Line no. Programming line
8820 DHW pump
8821 Electric immersion heater DHW
8830 DHW (domestic hot water) temperature
8840 Hours run DHW pump
8841 Start counter DHW pump
8842 Hours run el DHW
8843 Start counter el DHW
The measured values, the DHW circulation pump and
charging temperature, operating hour and startup
counters are displayed, as well as temperatures of
the primary controllers and DHW heater.
Swimming Pool
Line no. Programming line
8900 Swimming pool temp
The current and setpoint temperature of the
swimming pool are displayed.
The switching status of multifunction relays 1 - 5 can
be viewed individually on these lines. The display
"Off" means that the components assigned to this
output are currently disconnected. The display "On"
means that the associated components are currently
switched on.
The switching status of the relays connected to
extension modules 1 and 2 can be viewed on these
programming lines.
The display "Off" means that the components
assigned to this output are currently disconnected.
The display "On" means that the associated
components are currently switched on.
clean heat exchanger
clean refrigeration and ventilation compartment
check for correct condensation drain
conduct refrigeration circuit leak test (required if
charged > 2 kg)
5.3 Electrical
Inspect connections and tighten where
appropriate
Check condition of wires and boards
5.4 Operating checks
conduct refrigeration readings at temperatures
in case of malfunction, install pressure gauges
for refrigeration diagnosis
check voltage, current and control
92 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
(
6 Disassembly Process of Outdoor Unit
> Warning ! <
Before servicing the unit, turn the power supply
switch OFF, then, do not touch electric parts for
10 minutes due to the risk of electric shock.
6.1 Single phase type
6.1.1 Appearance
6.1.2 Service panel removal
Screw
serrated)
Remove the mounting screws.
6.1.3 Top panel removal
Screw
(with washer)
Hook (3 places)
Remove the SERVICE PANEL
by sliding downward.
Screw
(with washer)
Screw
(serrated)
Single Phase type
Remove the mounting screws
Remove the TOP PANEL
Maintenance Document 1544-193
Split system (Single phase and 3-phase type)
6.1.4 MAIN PCB, FILTER PCB, and INDICATOR PCB removal
screws
Hook (2 places)
Remove the 1 mounting screw
DIODE BRIDGE
ACTPM
Single Phase type
Remove the INVERTER BOX COVER
by sliding upward.
MAIN PCB
FILTER PCB
INDICATOR PCB
94 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
MAIN PCB removal
Screw of IPM (2 places)
screw
Remove the connectors
and screws
For screws of IPM.
Note the tightening torque at the
installation.
Tightening torque is 1.2=-0.2N.M
FILTER PCB removal
Screw
Holder
screw
Holder
Filter PCB
IPM
Remove the MAIN PCB
Spread the heat dissipation
compound on the other side of
IPM when you exchange
INVERTER PCB by the repair.
Remove the connectors
and screws
INDICATOR PCB removal
Remove the connectors and
locking spacers.
Screw
Earth screw
Remove the earth screw.
Locking
spacers
Remove the INDICATOR PCB.
Remove the FILTER PCB.
Single Phase type
Maintenance Document 1544-195
Split system (Single phase and 3-phase type)
6.1.5 FAN MOTOR removal
Remove the 4 mounting screws.
Cut the binder. (2 places)
Single Phase type
Remove the FAN GUARD by
sliding upward.
Loose the clamp. (2 places) and
remove the lead wires.
Remove the Hex Socket Screw. And
remove the PROPELLER FAN.
Note at the installation.
Insert propeller Fan and Moter shalf
reference D cutting position.
And the tightening torque at the
installation.
Tightening torque is from 10 to 15 N.M.
Remove the 4 mounting screws.
Remove the FAN MOTOR.
6.1.6 VALVE COVER removal
Hook (4 places)
Remove the mounting screws
96 Maintenance Document 1544-1
screw
Remove the VALVE COVER.
Split system (Single phase and 3-phase type)
(
6.1.7 RIGHT PANEL removal
screw
Screw
serrated)
Remove the 12 mounting screws.
Remove the RIGHT PANEL by
sliding upward.
Screw
(with washer)
6.1.8 THERMISTOR removal
HEAT EXCHANGER (MID) THERMISTOR
screw
Remove the THERMISTOR SPRING.
Remove the THERMISTOR.
HEAT EXCHANGER (OUT) THERMISTOR
Remove the THERMISTOR SPRING.
Remove the THERMISTOR.
Single Phase type
Maintenance Document 1544-197
Split system (Single phase and 3-phase type)
EEV THERMISTOR
Remove the THERMISTOR SPRING.
OUTDOOR THERMISTOR
Remove the THERMOR HOLDER.
6.1.9 SOLENOID COIL removal
4WAY VALVE
Remove the THERMISTOR.
hook
Open the THERMO HOLDER and
remove the THERMISTOR.
Single Phase type
Remove the mounting screw.
INJECTION
Remove the mounting screw.
Remove the SOLENOID COIL.
Remove the SOLENOID COIL.
98 Maintenance Document 1544-1
Split system (Single phase and 3-phase type)
6.1.10 EEV COIL removal
MAIN
Remove the EEV coil by hand.
6.1.11 PRESSURE SENSOR removal
Remove the PRESSURE SENSOR
with wrench.
Note the tightening at the installation.
Tightening torque is 12+-1.5N.m.
INJECTION
Remove the EEV coil by hand.
> Warning ! <
Wear gloves to prevent the frostbite, because a
small amount of refrigerant leaks during work.
Single Phase type
Maintenance Document 1544-199
Split system (Single phase and 3-phase type)
6.1.12 COMPRESSOR removal
Precautions for exchange of compressor.
Do not allow moisture or debris to get inside refrigerant pipes during work.
Procedure for compressor removal.
1 Turn off the power
2 Remove the service panel and right panel
3 Fully close the 3Way valve (gas) and 3Way valve (liquid)
4 Collect the refrigerant from the 3Way valve.
Start the following work after completely collecting the refrigerant.
Do not reuse the refrigerant that has been collected.