Frymaster H17 Installation Manual

Installation Instructions H17 Issue Date August 20, 2008
H17 Series BASO® Automatic Pilot Valve
The H17 Series pilot valves provide complete shutoff in the event that the flame heating the thermocouple is extinguished. Applications include room heaters, infrared heaters, salamanders, and refrigerators.
H17 models are also available with a higher ambient temperature, up to a maximum of 300°F (149°C), for use on commercial ovens, broilers, and other applications.
IMPORTANT: Verify that the valve is installed only in applications where the specified maximum ambient (surface) temperature and maximum operating pressures do not exceed the limits in the Technical Specifications section.
To install the H17 valve:
IMPORTANT: Only qualified personnel should install or service BASO® Gas Products. These instructions are a guide for such personnel. Carefully follow all instructions in this document and all instructions for the appliance.
IMPORTANT: Make all gas installations in accordance with applicable local, national, and regional regulations.
!
CAUTION: Risk of Electric Shock.
Disconnect power supply before making electrical connections to avoid electric shock.
Note: In applications that do not require electrical power, disregard the above caution.
!
WARNING: Risk of Explosion or Fire.
Shut off the gas supply at the main manual shutoff valve before installing or servicing the H17. Failure to shut off the gas supply can result in the release of gas during installation or servicing, which can lead to an explosion or fire, and may result in severe personal injury or death.
1. Shut off power to the appliance (if applicable).
2. Shut off the gas at the main manual shutoff valve.
3. Ensure that the gas flows through the valve body in the direction indicated by the arrow on the valve body. If the valve is installed with the gas flow in the opposite direction of the arrow, leakage can occur.
IMPORTANT: Do not use a wrench on any surface other than the casting flats provided at the inlet and outlet ends of the valve body. The H17 may be damaged in the mounting process if a wrench is used on any other surface. Using a wrench incorrectly may void the warranty.
4. Mount the valve to the pipework. The H17 valve may be mounted in any convenient position. Use an approved pipe joint sealing compound on the male threads before assembly. Remove excess compound after mounting the valve to the pipework. Threads of the pipe and nipples must be smooth and free of tears and burrs. Steam clean all piping to remove foreign substances such as cutting oil or thread chips. A sediment trap should also be installed in accordance with the National Fuel Gas Code (ANSI Z223.1). See Figure 1.
5. Attach the thermocouple securely to the pilot burner, and screw the terminal end to the BASO® power unit terminal on the valve. Make sure this connection is clean. Tighten the thermocouple lead nut finger tight plus a maximum of 1/8 turn. Do not overtighten.
© 2008 BASO Gas Products 1 Part No. BASO-INS-H17, Rev. A www.baso.com
6. Attach the pilot gas line to the pilot burner fitting and to the pilot gas outlet of the H17 valve. In applications that light the main burner directly, the pilot tap should be fit with a suitable plug.
!
WARNING: Risk of Explosion or Fire.
Verify that there are no gas leaks by testing with appropriate equipment. Never use a match or lighter to test for the presence of gas. Failure to test properly can lead to an explosion or fire and may result in severe personal injury or death.
Shutoff Valve
7. Check for leakage. a. Shut off the gas at the main manual shutoff
valve, and open the pressure connection between the manual shutoff valve and the H17 valve.
b. Connect air tubing with a maximum pressure
of 1-1/2 times the valve’s maximum operating pressure (as indicated on the valve) to the opened pressure connection.
c. Paint all pipe and pilot tube connections with a
rich soap and water solution. If bubbles occur, this is an indication of a leak.
To stop a leak, tighten joints and connections. Replace the part if the leak cannot be stopped.
If bubbles do not occur, remove the air tubing and close the pressure connection.
8. Perform the Checkout section before leaving the installation.
3 in. (76.2 mm)
Sediment Tarp
X
Reset Button
X
Thermocouple
Lead
Pilot Burner
Gas Line
Figure 1: Typical H17 Installation
X
indicates possible
locations f or other contr ol s.
fig1
2 H17 Series BASO Automatic Pilot Valve Installation Instructions