Friedrich MR09C1F, MR12C1F, MW12C1F, MW09C1F User Manual

COOLING MODEL
Friedrich Air Conditioning Co.
4200 N. Pan Am
San Antonio, Texas 78218 USA
Tel. (210) 357-4400 Fax (210) 357-4490
Visit us at www. friedrich. com
ROOM AIR CONDITIONER
WALL MOUNTED TYPE
Indoor Unit
MW09C1F
OPERATING MANUAL
MODE D’EMPLOI
MANUAL DE FUNCIONAMIENTO
MW12C1F
Outdoor Unit
MR09C1F MR12C1F
English
Français
KEEP THIS OPERATION MANUAL FOR FUTURE REFERENCE
P/N9314787041
Ÿ
*
&
§
+
£
%
^
¡
º
ª
(
)
¢
_
5 6 4 7 8
OPERATION TIMER
SUPER QUIET
SWING
=
A
B
D
C
9
3
1
Fig. 1 Indoor Unit
Fig. 6 Remote Control Unit
1 Operating Control Panel (Fig. 2) 2 MANUAL AUTO button
3 Indicator Lamps (Fig. 3) 4 Remote Control Signal Receiver 5 OPERATION Indicator Lamp (red) 6 TIMER Indicator Lamp (green)
If the TIMER indicator lamp flashes when the timer is operating, it indicates that a fault has occurred with the timer setting (See Page 12 Auto Restart).
7 SUPER QUIET Indicator Lamp (green) 8 SWING Indicator Lamp (orange)
9 Intake Grille (Fig. 4) 0 Air Filter (left) A Air Flow Direction Louver B Right-Left Louver
(behind Air Flow Direction Louver)
C Drain Hose D Air Filter (right)
Fig. 5 Outdoor Unit
E Intake Port F Outlet Port G Pipe Unit
H MASTER CONTROL button I SET TEMP. / SET TIME buttons (+/-) J Signal Transmitter K TIMER button L FAN CONTROL button M START/STOP button N SLEEP button O SET button P SWING button Q ACL button R TIME ADJUST button
Rear side (Fig. 7) S TEST RUN
Touch the two metal contacts with a
metallic object to send the signal to perform a test run.
Perform a test run only when installing the air conditioner. If the signal to perform a test run is received during normal operation, the air conditioner’s thermostat will malfunction.
If the signal to perform a test run is re­ceived during normal operation, the unit will switch to the test operation mode and the indoor unit’s OPERATION and TIMER indicator lamps will flash simultaneously.
To stop the test operation mode, press the
START/STOP button to stop the air conditioner.
Refer to the folded out page on the cover.
T Remote Control Unit Display (Fig. 8) U Transmit Indicator V Clock Display W Operating Mode Display X Timer Mode Display Y Fan Speed Display Z Temperature Set Display [ Timer Set Indicator \ Temperature Set Indicator
En-2
FEATURES AND FUNCTIONS
SLEEP TIMER
When SLEEP is selected be pressing TIMER button during Heating mode, the air conditioner’s thermostat setting is gradually lowered during the period of operation; during Cooling or Dry mode, the thermostat setting is gradually raised during the period of operation. When the set time is reached, the unit automatically turns off.
SWING OPERATION
The Air Flow Direction Louvers swings automatically up and down so that the air speeds to every nook and corner of your room.
WIRELESS REMOTE CONTROL UNIT
The Wireless Remote Control Unit allows convenient con­trol of air conditioner operation.
MILDEW-RESISTANT FILTER
The AIR FILTER has been treated to resist mildew growth, thus allowing cleaner use and easier care.
SUPER QUIET OPERATION
When the FAN CONTROL button is used to select QUIET, the unit begins super-quiet operation; the indoor unit’s air­flow is reduced to produce quieter operation.
En-3
PREPARATION
Turn on the Power
In the case of a direct line connection, turn on the circuit breaker.
Load Batteries (R03 / LR03 × 2)
Press and slide the battery compartment lid on the re-
1
verse side to open it.
Slide in the direction of the arrow while pressing the mark.
Insert batteries.
2
Be sure to align the battery polarities ( ) correctly.
Close the battery compartment lid.
3
Set the Current time
Press the TIME ADJUST button (Fig. 6 R).
1
Use the tip of a ball-point pen or other small object to press the button.
CAUTION!
Take care to prevent infants from accidentally swallowing batteries.
When not using the remote control unit for an extended period, remove the batteries to avoid possible leakage and damage to the unit.
If leaking battery fluid comes in contact with your skin, eyes, or mouth, immedi­ately wash with copious amounts of water, and consult your physician.
Dead batteries should be removed immediately and disposed of properly, either in a battery collection receptacle or to the appropriate authority.
Do not attempt to recharge dry batteries.
Never mix new and used batteries, or batteries of different types. Batteries should last about one year under normal use. If the remote control unit’s operating range becomes appre­ciably reduced, replace the batteries and press the ACL button with the tip of a ballpoint pen or other small object.
Use the , / - SET TEMP. / SET TIME buttons (Fig. 6
2
I) to adjust the clock to the current time.
, button: Press to advance the time.
- button: Press to reverse the time.
(Each time the buttons are pressed, the time will be advanced/reversed in one-minute increments; hold the buttons depressed to change the time quickly in ten-minute increments.)
Press the TIME ADJUST button again.
3
This completes the time setting and starts the clock.
To Use the Remote Control Unit
The Remote Control Unit must be pointed at signal receiver (Fig. 1 4) to operate
correctly.
Operating Range: About 7 meters.
When a signal is properly received by the air conditioner, a beeping sound will
be heard.
If no beep is heard, press the Remote Control Unit button again.
Remote Control Unit Holder
Insert
Press in
Screws
Slide up
Pull out
1 Mount the Holder. 2 Set the Remote Control
Unit.
3 To remove the Remote
Control Unit (when use at hand).
En-4
OPERATION
To Select Mode Operation
Press the START / STOP button (Fig.6 M).
1
The indoor unit’s OPERATION indicator lamp (red) (Fig. 3 5) will light. The air conditioner will start operating.
Press the MASTER CONTROL button (Fig.6 H) to se-
2
lect the desired mode.
Each time the button is pressed, the mode will change in the following order.
s
AUTO COOL DRY
About three seconds later, the entire display will reappear.
To Set the Thermostat
Press the SET TEMP. / SET TIME buttons (Fig. 6 I).
, button: Press to raise the thermostat setting.
- button: Press to lower the thermostat setting.
Thermostat setting range:
AUTO .................................. 64 to 88 °F
Cooling/Dry ........................ 64 to 88 °F
The thermostat cannot be used to set room temperature during the FAN mode (the temperature will not appear on the remote control
About three seconds later, the entire display will reappear.
unit’s display).
s
FAN
s
t
Example: When set to COOL.
The thermostat setting should be considered a standard value, and may differ somewhat from the actual room temperature.
To Set the Fan Speed
Press the FAN CONTROL button (Fig. 6 L).
Each time the button is pressed, the fan speed changes in the following order:
AUTO HIGH MED LOW QUIET
About three seconds later, the entire display will reappear.
When set to AUTO:
Heating : Fan operates so as to optimally circulate warmed air.
However, the fan will operate at very low speed when the tempera­ture of the air issued from the indoor unit is low.
Cooling : As the room temperature approaches that of the thermostat setting,
the fan speed becomes slower.
Fan : The fan runs at the low fan speed.
The fan will operate at a very low setting during Monitor operation and at the start of the Heating mode.
When set to QUIET:
SUPER QUIET operation begins. The indoor unit’s airflow will be reduced for qui­eter operation.
SUPER QUIET operation cannot be used during Dry mode. (The same is true when dry mode is selected during AUTO mode operation.)
Cooling performance will be reduced somewhat during SUPER QUIET operation.
ssss
s
Example: When set to 86 °F.
Example: When set to AUTO.
To Stop Operation
Press the START/STOP button (Fig.6 M).
The OPERATION indicator lamp (red) (Fig. 3 5) will go out.
En-5
OPERATION
About Mode Operation
AUTO: Depending on the room temperature at the time operation begins, the
operating mode will be switched automatically as shown in the accompanying table. Also, depending on the operating mode, the room temperature set­ting will cause the “standard” temperature to be set as shown.
Actual Room Operating Mode Thermostat Setting Temperature (standard setting) 88 °F or above Cooling 82 °F 82 °F to 88 °F Cooling 80 °F 78 °F to 82 °F Dry 76 °F 74 °F to 78 °F Dry 72 °F Below 74 °F Dry 68 °F
The operating mode and standard thermostat settings are selected auto­matically when operation begins.
When automatic operation is initiated, the fan will run at very low speed for about one minute while the unit detects and selects the proper operating mode.
Once the operating mode has been set, the mode will not change even if the room temperature changes.
If the START/STOP button is pressed to recommence operation within two hours after stopping automatic operation, the unit will begin op­erating from the same mode as before.
Cooling: Use to cool your room. Dry: Use for gently cooling while dehumidifying your room.
You cannot heat the room during Dry mode.
During Dry mode, the unit will operate at low speed; in order to adjust
room humidity, the indoor unit’s fan may stop from time to time. Also, the fan may operate at very low speed when adjusting room humidity.
The fan speed cannot be changed manually when Dry mode has been
selected.
Fan: Use to circulate the air throughout your room.
During Cooling/Dry mode:
Set the thermostat to a temperature set­ting that is lower than the current room temperature. The Cooling and Dry modes will not operate if the thermostat is set higher than the actual room temperature (in Cooling mode, the fan alone will oper­ate).
During Fan mode:
You can not use the unit to heat and cool your room.
En-6
TIMER OPERATION
Before using the timer function, be sure that the Remote Control Unit is set to the correct current time, see page 4.
To Use the ON timer or OFF timer
Press the START / STOP button (Fig. 6 M).
1
(if the unit is already operating, proceed to step 2).
The indoor unit's OPERATION Indicator Lamp (red) (Fig. 3 5) will light.
Press the TIMER button (Fig. 6 K) to select the OFF
2
timer or ON timer operation.
Each time the button is pressed the timer function changes in the following order:
RESET OFF ON
PROGRAM (OFF ON, OFF ON)
The indoor unit's green TIMER lamp (Fig. 3 6) will light.
Use the SET TEMP. / SET TIME buttons (Fig. 6 I) to
3
adjust the desired OFF time or ON time.
Set the time while the time display is flashing (the flashing will continue for about five seconds).
, button: Press to advance the time.
- button: Press to reverse the time.
About five seconds later, the entire display will reappear.
To Cancel the Timer
Use the TIMER button to select “TIMER RESET.” The air conditioner will return to normal operation.
To Change the Timer Settings
Perform steps 2 and 3.
To Stop Air Conditioner Operation while the Timer is Operating
Press the START / STOP button.
To Change Operating Conditions
If you wish to change operating conditions (Mode, Fan Speed, Thermostat Setting, SUPER QUIET mode), after making the timer setting wait until the entire display reappears, then press the appropriate buttons to change the operating condition desired.
To Use the Program Timer
Press the START / STOP button (Fig. 6 M).
1
(if the unit is already operating, proceed to step 2).
The indoor unit's OPERATION Indicator Lamp (red) (Fig. 3 5) will light.
Set the desired times for OFF timer and ON timer.
2
See the section “To Use the ON Timer or OFF Timer” to set the desired mode and times. About three seconds later, the entire display will reappear. The indoor unit's TIMER Indicator Lamp (green) (Fig. 3 6) will light.
Press the TIMER button (Fig. 6 K) to select the
3
PROGRAM timer operation (OFF
ON or OFF ON
will display).
The display will alternately show “OFF timer” and “ON timer”, then change to show the time setting for the operation to occur first.
The program timer will begin operation. ( If the ON timer has been
selected to operate first, the unit will stop operating at this point).
About five seconds later, the entire display will reappear.
About the Program Timer
The program timer allows you to integrate OFF timer and ON timer operations in a single sequence. The sequence can involve one transition from OFF timer to ON timer, or from ON timer to OFF timer, within a twenty-four hour period.
The first timer function to operate will be the one set nearest to the current time. The order of operation is indicated by the arrow in the Remote Control Unit's Display (OFF
One example of Program timer use might be to have the air conditioner automatically stop ( OFF timer ) after you go to sleep, then start ( ON timer) automatically in the morning before you arise.
ON or OFF ON ).
To Cancel the Timer
Use the TIMER button to select “TIMER RESET.” The air conditioner will return to normal operation.
To Change the Timer Settings
1. Follow the instructions given in the section "To Use the ON Timer or OFF Timer" to select the timer setting you wish to change.
2. Press the TIMER button to select either OFF
ON or OFF ON.
To Stop Air Conditioner Operation while the Timer is Operating
Press the START / STOP button.
To Change Operating Conditions
If you wish to change operating conditions (Mode, Fan Speed, Thermostat Setting, SUPER QUIET mode), after making the timer setting wait until the entire display reappears, then press the appropriate buttons to change the operating condition desired.
En-7
SLEEP TIMER OPERATION
Unlike other timer functions, the SLEEP timer is used to set the length of time until air conditioner operate is stopped.
To Use the SLEEP Timer
While the air conditioner is operating or stopped, press the SLEEP button (Fig. 6 N).
The indoor units OPERATION Indicator Lamp (red) (Fig. 3 5) lights and the TIMER Indicator Lamp (green) (Fig. 3 6) light.
To Change the Timer Settings
Press the SLEEP button (Fig. 6 N) once again and set the time using the SET TEMP./SET TIME ( , / - ) buttons (Fig. 6 I).
Set the time while the Timer Mode Display is flashing (the flashing will continue about five seconds).
, button: Press to advance the time.
- button: Press to reverse the time.
About five seconds later, the entire display will reappear.
About the SLEEP Timer
To prevent excessive cooling during sleep, the SLEEP timer function automatically modifies the thermostat setting in accon­dance with the time setting. When the set time has elapsed, the air conditioner completely stops.
During Heating operation :
When the SLEEP timer is set, the thermostat setting is automatically lowered 2 °F every thirty minutes. When the thermostat has been lowered a total of 8 °F, the thermostat setting at that time is maintained until the set time has elapsed, at which time the air conditioner automatically turns off.
During Cooling/Dry operation:
When the SLEEP timer is set, the thermostat setting is auto­matically raised 2 °F every sixty minutes. When the thermo­stat has been raised a total of 4 °F, the thermostat setting at that time is maintained until the set time has elapsed, at which time the air conditioner automatically turns off.
To Cancel the Timer:
Use the TIMER button to select “TIMER RESET. The air conditioner will return to normal operation.
To Stop the Air Conditioner During Timer Operation:
Press the START/STOP button.
SLEEP timer setting
30 minutes
1 hour
2 °F
1 hour 30 minutes
4 °F
Set time
6 °F
8 °F
SLEEP timer setting
1 hour
Set time
2 °F
4 °F
En-8
ADJUSTING THE DIRECTION OF AIR CIRCULATION
Vertical (up-down) direction of airflow is adjusted by pressing the Remote Control Unit’s SET button. Horizontal (right-left) airflow direction is adjusted manually, by moving the Air Flow Direction Louvers. Whenever making horizontal airflow adjustments, start air conditioner operation and be sure that the vertical air direction louvers are stopped.
Vertical Air Direction Adjustment
Press the SET button (Fig. 6 O).
Each time the button is pressed, the air direction range will change as follows:
2 3 4 5 6 7
1
Types of Air flow Direction Setting:
1,2,3 : During Cooling / Dry modes 1,2,3,4,5,6,7 : During Fan mode
The remote Control Unit’s display does not change.
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with
the type of operation selected.
During Cooling / Dry / Fan mode : Horizontal flow 1
During AUTO mode operation, for the first minute after beginning operation,
airflow will be horizontal 1; the air direction cannot be adjusted during this period.
Right-Left Adjustment
Adjust the Right-Left louvers.
Move the Right-Left louvers to adjust air flow in the direction you prefer.
R
DANGER!
Never place fingers or foreign objects in­side the outlet ports, since the internal fan operates at high speed and could cause personal injury.
Always use the remote control unit’s SET button to adjust the vertical airflow louvers. Attempting to move them manually could result in improper operation; in this case, stop operation and restart. The louvers should begin to operate properly again.
During Cooling and Dry modes, do not move the vertical air direcion louvers outside their proper operating range for the mode (1 - 3) and into the fan region (4 - 7) ; using the louvers in the fan region will cause moisture to condense near the air outlet, and water may drop onto the floor. During the Cooling / Dry modes, if the louvers are operated outside the range 1 - 3 for more than 30 minutes, they will automatically return to position 3 range.
When used in a room with infants, chil­dren, elderly or sick persons, the air direction and room temperature should be considered carefully when making settings.
R
DANGER!
When adjusting the Right-Left Louvers, it is necessary to stop the Air-Conditioner first and make sure that it stops completely before adjusting the direction.
En-9
knob
knobs (three places)
SWING OPERATION
Begin air conditioner operation before performing this procedure.
To select SWING Operation
Press the SWING button (Fig. 6 P).
The SWING indicator lamp (orange) (Fig. 3 8) will light. In this mode, the Air Flow Direction Louvers will swing automatically to direct the air flow both up and down.
To Stop SWING Operation
Press the SWING button (Fig. 6 P) once again.
The SWING indicator lamp (orange) (Fig. 3 8) will go out. Airflow direction will return to the setting before swing was begun.
About Swing Operation
The range of swing is relative to the currently set airflow direction.
The SWING operation may stop temporarily when the air conditioners fan is not operating, or when operating at very low speeds.
If the Remote Control Unit’s SET button is pressed during swing, swing will be canceled, and the Air flow direction will return to the setting before swing was setted.
MANUAL AUTO OPERATION
Use the MANUAL AUTO operation in the event the Remote Control Unit is lost or otherwise unavailable.
How To Use the Main Unit Controls
Press the MANUAL AUTO button (Fig. 2 2) on the main unit control panel.
To stop operation, press the MANUAL AUTO button once again. (Controls are located inside the Intake Grille)
CAUTION!
Do not press the MANUAL AUTO button with wet hands or pointed objects, otherwise an electric shock or malfunction may occur.
When the air conditioner is operated with the controls on the Main Unit, it will operate under the same mode as the AUTO mode selected on the Re­mote Control Unit (see page 6).
The fan speed selected will be “AUTO and the thermostat setting will be standard.
En-10
CLEANING AND CARE
CAUTION!
Before cleaning the air conditioner, be sure to turn off the power supply to the air conditioner.
Make sure the plasma filter unit is properly mounted before cleaning or performing other tasks
on it. If the unit is not properly mounted, it could fall off and cause damage or injury.
You can be injured if you touch the heat exchanger when removing or installing the plasma filter unit. Do not insert your fingers between the plasma filter unit and the heat exchanger.
Cleaning the Intake Grille
1. Remove the Intake Grille.
1 Place your fingers at both lower ends of the grille
panel, and lift forward; if the grille seems to catch partway through its movement, continue lifting up­ward to remove.
2 Pull past the intermediate catch and open the Intake
Grill wide so that it become horizontal.
Intake Grille
Intake Grille
Mounting
shaft
Knob
2. Clean with water.
Remove dust with a vacuum cleaner; wipe the unit with warm water, then dry with a clean, soft cloth.
Cleaning the Air Filter
1. Open the Intake Grille, and remove the air filter.
Lift up the air filters handle, disconnect the two lower tabs, and pull out.
Air filter handle
2. Remove dust with a vacuum cleaner or by washing.
After washing, allow to dry thoroughly in a shaded place.
3. Replace the Air Filter and close the Intake Grille.
1 Align the sides of the Air Filter with the panel, and
push in fully, making sure the two lower tabs are re­turned properly to their holes in the panel.
3. Replace the Intake Grille.
1 Pull the knobs all the way. 2 Hold the grille horizontal and set the left and right
mounting shafts into the bearings at the top of the panel.
Intake Grille
Intake Grille
When used for extended periods, the unit may accumulate dirt inside, reducing its performance. We recommend that the unit be inspected regularly, in addition to your own cleaning and care. For more information, consult authorized service personnel.
When cleaning the unit’s body, do not use water hotter than 108 °F, harsh abrasive cleansers, or volatile agents like benzene or thinner.
Do not expose the unit body to liquid insecticides or hairsprays.
When shutting down the unit for one month or more, first allow the fan mode to operate continuously for about one-half
day to allow internal parts to dry thoroughly.
Mounting shaft
Bearing
Knob
Mounting
shaft
Knob
2 Close the Intake Grille.
(For purposes of example, the illustration shows the unit without Intake Grille installed.)
Dust can be cleaned from the Air Filter either with a vacuum cleaner, or by washing the filter in a solution of mild detergent and warm water. If you wash the filter, be sure to allow it to dry thoroughly in a shady place before reinstalling.
If dirt is allowed to accumulate on the Air Filter, air flow will be reduced, lowering operating efficiency and in­creasing noise.
During periods of normal use, the Air Filters should be cleaned every two weeks.
Air filter handle
En-11
TROUBLESHOOTING
WARNING!
Before requesting service, perform the following checks:
NORMAL
FUNCTION
Doesnt operate immediately:
Noise is heard:
Smells:
Mist is emitted:
Airflow is weak or stops:
In the event of a malfunction (burning smell, etc.), immediately stop operation, disconnect the Power Supply Plug, and consult authorized service personnel. Merely turning off the units power switch will not completely disconnect the unit from the power source. Always be sure to disconnect the Power Supply Plug or turn off your circuit breaker to ensure that power is completely off.
Symptom
If the unit is stopped and then immediately started again, the com­pressor will not operate for about 3 minutes, in order to prevent fuse blowouts. Whenever the Power Supply Plug is disconnected and then re-
connected to a power outlet, the protection circuit will operate for about 3 minutes, preventing unit operation during that period.
During operation and immediately after stopping the unit, the sound of water flowing in the air conditioners piping may be heard. Also, noise may be particularly noticeable for about 2 to 3 minutes after starting operation (sound of coolant flowing).
During operation, a slight squeaking sound may be heard. This is the result of minute expansion and contraction of the front cover due to temperature changes.
Some smell may be emitted from the indoor unit. This smell is the result of room smells (furniture, tobacco, etc.) which have been taken into the air conditioner.
During Cooling or Dry operation, a thin mist may be seen emitted from the indoor unit. This results from the sudden Cooling of room air by the air emitted from the air conditioner, resulting in condensation and misting.
The fan may operate at very low speed during Dry operation or when the unit is monitoring the rooms temperature.
During SUPER QUIET operation, the fan will operate at very low speed.
In the monitor AUTO operation, the fan will operate at very low speed.
Problem
See Page
5
5
5
En-12
TROUBLESHOOTING
Symptom
CHECK ONCE
MORE
If the problem persists after performing these checks, or if you notice burning smells, or the TIMER indicator lamp (Fig. 3 6) flashes, immediately stop operation, disconnect the Power Supply Plug, and consult authorized service personnel.
Doesnt operate at all:
Poor Cooling or Heating performance:
The unit operates differently from the Remote Control Units setting:
Is the Power Supply Plug disconnected its outlet?
Has there been a power failure?
Has a fuse blown out, or a circuit breaker been tripped?
Is the timer operating?
Is the air filter dirty?
Air the air conditioners intake grille or outlet port blocked?
Did you adjust the room temperature settings (thermostat)
correctly?
Is there a window or door open?
In the case of Cooling operation, is a window allowing bright sun-
light to enter? (Close the curtains.)
In the case of Cooling operation, are there heating apparatus and computers inside the room, or are there too many people in the room?
Is the unit set for SUPER QUIET operation?
Are the Remote Control Units batteries dead?
Are the Remote Control Units batteries loaded properly?
Items to check
See Page
7 - 8
5
4
OPERATING TIPS
AUTO Restart
In Event of Power Interruption
The air conditioner power has been interrupted by a power failure. The air conditioner will then restart automatically in its previous mode when the power is restored.
Operated by setting before the power failure.
If a power failure occurs during TIMER operation, the timer will be reset and the unit will begin (or stop) operation at the new time setting. In the event that this (kind of timer fault occurs the TIMER Indicator Lamp will flash (see Page. 3)).
Use of other electrical appliances (electric shaver, etc.) or nearby use of a wireless radio transmitter may cause the air conditioner to malfunction. In this event, temporarily disconnect the Power Supply Plug, reconnect it, and then use the Remote Control Unit to resume operation.
En-13
Loading...
+ 32 hidden pages