Fluke 80i-110s User Manual

The ideal current probe for
Fluke ScopeMeter®Test Tools
80i-110s AC/DC
Current Probe
Technical Data
The specially designed built­in safety features such as the 600 V rms rating at the input jaws, output cable, and BNC connector enhance work safety in industrial and commercial power distribution systems.
The probe is shielded for high noise immunity, to prevent unwanted noise when trou­bleshooting around noise gen­erating devices like adjustable speed motor drives and ignition systems.
The 80i-110s accurately reproduces current waveforms as they occur. Connect the clamp to a Fluke ScopeMeter Test Tool or other waveform recording device like a Fluke Power Harmonics Analyzer, to clearly see distorted waveforms that result from non-linear loads such as computers, adjustable speed motor drives, and elec­tronic ballasts for fluorescent lighting.
Current clamps, not specifi­cally designed for oscilloscopes, may add distortion to the actual signal present in the system
under test. This makes it diffi­cult to get an accurate wave­form measurement.
The wide measurement range from 50 milliamps to 100 Amps with a high fidelity milli­volt output gives you full advantage of the high resolu­tion oscilloscope displays. This gives you the true picture of your current situation, and allows useful measurements as low as 10 milliamps.
The broad band frequency response of the Fluke 80i-110s AC/DC Current Probe from dc to 100 kHz supports a wide range of applications where the probe can be used. The probe can be used to track down leakage currents discharging car batter­ies or to measure dc currents in an Uninterruptible Power
Supply (UPS), that uses a battery backup system.
With its narrow jaw design, the Fluke 80i-110s makes it easy to take measurements in tight spots.
Specifications
Electrical specifications
Current ranges:
0 to 10 A dc or ac peak 0 to 100 A dc or ac peak
Output signals:
10 A range: 100 mV/A 100 A range: 10 mV/A
Working voltage (clamp jaws to ground):
600 V ac rms on Installation Category II per IEC 1010-1 circuits. 300 V ac rms on Installation Category III per IEC 1010-1 circuits.
Page 1 of 2, Document #2228 80i-110s AC/DC Current Probe ©2002 Fluke Corporation Rev. A-9/2002
Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or Fax (425) 446-5116 In Europe/M-East/Africa (31 40) 2 675 200 or Fax (31 40) 2 675 222 In Canada (800)-36-FLUKE or Fax (905) 890-6866 From other countries +1 (425) 446-5500 or Fax +1 (425) 446-5116 Web access: http://www.fluke.com/
Fluke. Keeping your world
up and running.
Floating voltage (output cable and connector to ground):
600 V ac rms on Installation Category II per IEC 1010-1 circuits. 300 V ac rms on Installation Category III per IEC 1010-1 circuits.
Basic accuracy (dc to 1 kHz)
Extended accuracy:
For other frequencies, refer to the appropriate input current range and add the error listed below to the “Basic Accuracy.”
Phase shift, dc to 65 Hz:
10 A range < 1.5 degree 100 A range < 1 degree
Input load impedance (of host instrument):
> 1 Min parallel with up to 100 pF
Useful bandwidth (-3 dB):
0 to 100 kHz
Rise or fall time: < 4 msec Output noise level:
10 mV/A typ. 480 mV pk-pk 100 mV/A typ. 3 mV pk-pk
Maximum non-destructive current:
0 to 2 kHz 140 A peak 2 to 10 kHz 110 A peak 10 to 20 kHz 70 A peak 20 to 50 kHz 30 A peak 50 to 100 kHz 20 A peak
Temperature coefficient:
2000 ppm/°C max. for tempera­ture from 0 °C to 50 °C (32 °F to 132 °F)
All Electrical Specifications are valid at a temperature of 3 °C to 23 °C (5 °F to 73 °F)
General specifications
Dimensions:
67 x 231 x 36 mm (2.6 x 9.1 x 1.4 inches) Wei ght: 330 g (11.6 oz), battery included
Output cable:
1.6 meters (63 inches)
Maximum conductor size:
11. 8 mm (.46 inch)
Maximum jaw opening:
12.5 mm (.49 inch)
Temperature:
Operating: 0 °C to 50 °C (32 °F to 122 °F) Non-operating: -30 °C to 70 °C (-22 °F to 158 °F)
Relative humidity (operating):
0 to 85 % (0 °C to 35 °C; 32 °F to 95 °F) 0 to 45 % (35 °C to 50 °C; 95 °F to 122 °F)
Altitude:
Operating: 0 to 2,000 meters (0 to 6,560 feet) Non-operating: 0 to 12,000 meters (0 to 40,000 feet)
Safety specification
Designed to meet the require­ments of IEC 1010 and CSA­C22.2 No. 1010.1: Installation Category II, Working Voltage 600V, Pollution Degree 2. Installation Category III, Working Voltage 300V, Pollution Degree 2.
Installation (Overvoltage) Category II refers to local level, appliances, and portable equipment.
Installation (Overvoltage) Category III refers to distribu­tion level and fixed installation circuits inside a building electrical service entrance.
Designed to meet the requirements of UL1244, Protection Class II Double Insulation.
Battery information
Battery: 9 volt, IEC 6LR61 Consumption: 8.6 mA typical;
12 mA maximum
Service life:
55 hours typical, when Alkaline IEC 6LR61 is used 40 hours minimum, when Alkaline IEC 6LR61 is used
Battery indicator (ON):
Green LED dims when battery voltage is below 6.5V
Overload indicator (OL):
Red LED indicates that wave­form or impulse is out of range
Instrument compatibility
The 80i-110s is compatible with any Fluke ScopeMeter Test Tool, Power Harmonics Analyzer, Oscilloscope, Multimeter, or other voltage measurement device that has the following features:
BNC input connector. A BNC-to-banana adapter (order PM 9081/001 from Fluke) can also be used with standard inputs on a digital multimeter (DMM).
Input accuracy of 2 % or better to take full advantage of the accuracy of the probe.
Input impedance of greater than or equal to 1 Min parallel with a maximum of 100 pF.
A passband of more than four times the frequency of the waveform to be measured.
Warranty
One-year warranty
Input current
Error (after zero check)
dc or ac peak
100 mV/A 10 mV/A
50 mA to 10 A < 3 % of reading —
+ 50 mA
50 mA to 40 A < 4 % of reading
+ 50 mA
40 to 80 A < 12 % of reading
+ 50 mA
80 to 100 A < 15 % of reading
Additional error Frequency 100 mV/A 10 mV/A 1 to 5 kHz 3 % 3 % 5 to 20 kHz 12 % 12 % > 20 kHz Not specified Not specified
Ordering information
Model
80i-110s AC/DC Current Probe
Page 2 of 2, Document #2228 80i-110s AC/DC Current Probe ©2002 Fluke Corporation Rev. A-9/2002