Troubleshooting
power harmonics
Basic troubleshooting using
multimeters and current clamps
A mystery is occurring in today’s office buildings and
manufacturing plants. Transformers supplying seemingly
average loads are overheating. Neutral conductors in
balanced circuits are overheating from excessive loads.
Circuit breakers are tripping for no apparent reason.
Yet the standard troubleshooting procedures show
everything to be normal. So what’s the problem?
In one word—harmonics.
New technology,
new challenges
Harmonics are the byproducts
of modern electronics. They
are especially prevalent wherever there are large numbers of
personal computers, adjustable
speed drives, and other types of
equipment that draw current in
short pulses.
This equipment is designed
to draw current only during a
controlled portion of the incoming voltage waveform. While
this dramatically improves
efficiency, it causes harmonics in the load current. And that
causes overheated transformers
and neutrals, as well as tripped
circuit breakers.
If you were to listen to an ordinary 60-cycle power line, you’d
hear a monotone hum. When
harmonics are present, you hear
a different tune, rich with high
notes. The problem is even more
evident when you look at the
waveform. A normal 60-cycle
power line voltage appears on
the oscilloscope as a near sine
wave (Figure 1). When harmonics are present, the waveform
is distorted (Figure 2A and 2B).
These waves are described as
non-sinusoidal. The voltage and
current waveforms are no longer
simply related-hence the term
“non-linear.”
Getting to the root of the
problem
Finding the problem is relatively
easy once you know what to look
for and where to look. Harmonics
symptoms are usually anything
but subtle. This application note
provides some basic pointers on
how to find harmonics and some
suggestions of ways to address
the problems they create.
Application Note
Figure 1. Near sine wave.
Figure 2A. Distorted current waveform.
Figure 2B. Distorted voltage waveform.
From the Fluke Digital Library @ www.fluke.com/library
Sources of harmonics
Defining the problem
Harmonics are currents or voltages with frequencies that are
integer multiples of the fundamental power frequency. For
example, if the fundamental frequency is 60 Hz, then the second
harmonic is 120 Hz, the third is
180 Hz, etc.
Harmonics are created by nonlinear loads that draw current
in abrupt pulses rather than in
a smooth sinusoidal manner.
These pulses cause distorted
current wave shapes which in
turn cause harmonic currents to
flow back into other parts of the
power system.
Figure 3A. Single-phase, non-linear load
current waveform.
The inside story
This phenomenon is especially
prevalent with equipment that
has diode-capacitor input power
supplies; i.e., personal computers, printers and medical test
equipment.
Electrically what happens is
the incoming ac voltage is diode
rectified and is then used to
charge a large capacitor. After
a few cycles, the capacitor is
charged to the peak voltage of
the sine wave (e.g., 170 V for a
120 V ac line). The electronic
equipment then draws current
from this high dc voltage to
power the rest of the circuit.
The equipment can draw the
current down to a regulated
lower limit. Typically, before
reaching that limit, the capacitor
is recharged to the peak in the
next half cycle of the sine wave.
This process is repeated over
and over. The capacitor basically
draws a pulse of current only
during the peak of the wave.
During the rest of the wave,
when the voltage is below the
capacitor residual, the capacitor
draws no current.
The diode/capacitor power
supplies found in office equipment are typically single-phase,
non-linear loads (Figure 3A).
In industrial plants, the most
common causes of harmonic currents are three-phase, non-linear
loads which include electronic
motor drives, and uninterruptible
power supplies (UPS) (Figure 3B).
Figure 3B. Three-phase, non-linear load
current waveform.
Voltage harmonics
The power line itself can be an indirect
source of voltage harmonics.
The harmonic current drawn by non-linear
loads acts in an Ohm’s law relationship
with the source impedance of the supplying
transformer to produce voltage harmonics.
Source impedance includes the supplying
transformer and branch circuit components.
For example, a 10 A harmonic current being
drawn from a source impedance of 0.1 W will
generate a harmonic voltage of 1.0 V.
Any loads sharing a transformer or a
branch circuit with a heavy harmonic load
can be affected by the voltage harmonics
generated.
The personal computer can be affected by
voltage harmonics. The performance of the
diode/capacitor power supply is critically
dependent on the magnitude of the peak
voltage. Voltage harmonics can cause “flat
topping” of the voltage waveform lowering
the peak voltage (see Figure 2B). In severe
cases, the computer may reset due to insufficient peak voltage.
In the industrial environment, the induction motor and power factor correction
capacitors can also be seriously affected by
voltage harmonics.
Power correction capacitors can form a
resonant circuit with the inductive parts
of a power distribution system. If the resonant frequency is near that of the harmonic
voltage, the resultant harmonic current
can increase substantially, overloading the
capacitors and blowing the capacitor fuses.
Fortunately, the capacitor failure detunes the
circuit and the resonance disappears.
2 Fluke Corporation Troubleshooting power harmonics
Effects of harmonic currents
01
02
03
120 V Branch Circuits
208/480 Volt Transformer
Secondary
Primary
Neutral
A
B
C
Symptoms of harmonics usually
show up in the power distribution equipment that supports the
non-linear loads. There are two
basic types of non-linear loads:
single-phase and three-phase.
Single-phase, non-linear loads
are prevalent in offices, while
three-phase loads are widespread in industrial plants.
Each component of the power
distribution system manifests
the effects of harmonics a little
differently, yet all are subject to
damage and inefficient performance if not designed to handle
electronic loads.
Neutral conductors
In a three-phase, four-wire
system, neutral conductors can
be severely affected by nonlinear loads connected to the 120
V branch circuits. Under normal
conditions for a balanced linear
load, the fundamental 60 Hz
portion of the phase currents will
cancel in the neutral conductor.
In a four-wire system with
single-phase, non-linear loads,
certain odd-numbered harmonics called triplens—odd multiples
of the third harmonic: 3rd, 9th,
15th, etc—do not cancel, but
rather add together in the neutral
conductor. In systems with many
single-phase, non-linear loads,
the neutral current can actually
exceed the phase current. The
danger here is excessive overheating because, unlike phase
conductors, there are no circuit
breakers in the neutral conductor
to limit the current.
Excessive current in the neutral conductor can also cause
higher-than-normal voltage
drops between the neutral conductor and ground at the 120 V
outlet.
Circuit breakers
Common thermal-magnetic
circuit breakers use a bi-metallic
trip mechanism that responds to
the heating effect of the circuit
current. They are designed to
respond to the true-rms value of
the current waveform and will
trip when the trip mechanism
gets too hot. This type of breaker
has a good chance of protecting against harmonic current
overloads.
A peak-sensing, electronic trip
circuit breaker responds to the
peak of current waveform. As a
result, it won’t always respond
properly to harmonic currents.
Since the peak of the harmonic
current is usually higher than
normal, this type of circuit
breaker may trip prematurely at a
low current. If the peak is lower
than normal, the breaker may
fail to trip when it should.
Bus bars and
connecting lugs
Neutral bus bars and connecting
lugs are sized to carry the full
value of the rated phase current.
They can become overloaded
when the neutral conductors are
overloaded with the additional
sum of the triplen harmonics.
Electrical panels
Panels that are designed to carry
60 Hz currents can become
mechanically resonant to the
magnetic fields generated by
higher frequency harmonic
currents. When this happens,
the panel vibrates and emits a
buzzing sound at the harmonic
frequencies.
Telecommunications
Telecommunications systems
often give you the first clue to
a harmonics problem because
the cable can be run right next
to power cables. To minimize
the inductive interference from
phase currents, telecommunications cables are run closer to the
neutral wire.
Triplens in the neutral conductor commonly cause inductive
interference, which can be heard
on a phone line. This is often the
first indication of a harmonics
problem and gives you a head
start in detecting the problem
before it causes major damage.
Transformer
Commercial buildings commonly
have a 208/120 V transformer
in a delta-wye configuration.
These transformers commonly
feed receptacles in a commercial building. Single-phase,
non-linear loads connected to
the receptacles produce triplen
harmonics, which add up in the
neutral. When this neutral current reaches the transformer, it is
reflected into the delta primary
winding where it causes overheating and transformer failures.
Another transformer problem
results from core loss and copper
loss. Transformers are normally
rated for a 60 Hz phase current
load only. Higher frequency harmonic currents cause increased
core loss due to eddy currents
and hysteresis, resulting in more
heating than would occur at the
same 60 Hz current.
These heating effects demand
that transformers be derated for
harmonic loads or replaced with
specially designed transformers.
3 Fluke Corporation Troubleshooting power harmonics